1.0 GENERAL <br />1.1 BIDDERS QUALIFICATIONS AND INSTRUCTIONS: <br />1.1.1 QUALIFICATIONS: <br />THE BIDDERS SHALL BE QUALIFIED, EXPERIENCED, AND LICENSED ELECTRICAL <br />CONTRACTORS. THEY MUST BE FAMILIAR WITH ALL FEDERAL, STATE, AND LOCAL <br />LAWS, ORDINANCES, RULES, AND REGULATIONS THAT MAY, IN ANY MANNER, <br />AFFECT THE TASK. <br />1.1.2 BIDDING INSTRUCTIONS: <br />BEFORE SUBMITTING THE BID, THE BIDDERS MUST REVIEW THE LANDLORD'S <br />DESIGN CRITERIA AND INFORMATION MANUAL, SPECIFICATIONS, PLANS, DRAWINGS, <br />AND ALL OTHER CONDITIONS AND REQUIREMENTS THAT MAY, IN ANY MANNER <br />AFFECT THE WORK UNDER CONTRACT. THEY MUST VISIT THE SITE OF <br />THE PROPOSED PROJECT TO FAMILIARIZE THEMSELVES WITH THE LOCAL <br />CONDITIONS, FIRE RATING REQUIREMENTS, AND THE NATURE OF THE PROJECT. THE <br />PRICING SHALL BE BASED ON THESE SPECIFICATIONS AND THE MATERIALS SHOWN <br />ON THE DRAWINGS. SUBMISSION OF THE BIDS SHALL BE CONSIDERED AS THE <br />EVIDENCE THAT THE BIDDER IS FAMILIARIZED TO ALL THE FACETS OF THE <br />SPECIFIED PROJECT. <br />1.1.3 EXC EPTIONS: <br />ANY EXCEPTIONS, OMISSIONS, DISCREPANCIES, AND DOUBTS REGARDING PLANS, <br />DRAWINGS, AND SPECIFICATIONS, IF ANY, SHALL BE COMMUNICATED PROMPTLY IN <br />WRITING TO THE ARCHITECT OR TO THE ENGINEER FOR THEIR REVIEW AND RESPONSE <br />BACK BEFORE THE BID SUBMISSION DATE. NO ORAL COMMUNICATION REGARDING <br />THE EXCEPTIONS OR CHANGES SHALL BE ACCEPTED. BIDDERS SHALL BE NOTIFIED <br />OF ANY CHANGES, IF MADE, DUE TO THE ACCEPTANCE OF EXCEPTIONS BEFORE THE <br />BID SUBMITTAL DATE. <br />1.1.4 MATERIAL TAKE OFF: <br />ALL MATERIAL TAKE OFFS, OTHER THAN THE EXISTING DEVICES, SHALL BE MADE <br />USING THE LIGHT & POWER WIRING AND CONDUIT DRAWINGS AND THEIR <br />ASSOCIATED REFERENCES INCLUDING THE SPECIFICATIONS OF THIS PROJECT ON <br />THIS DRAWING. <br />1.1.5 BID PRICE: <br />THE BID PRICE SHALL INCLUDE LABOR AND MATERIAL COSTS, NECESSARY <br />INSURANCE COSTS AND PERMIT FEES AS REQUIRED TO INSTALL THE COMPLETE <br />ELECTRICAL SYSTEM IN COMPLIANCE WITH THE DESIGN REQUIREMENTS OF THIS <br />PROJEC T. <br />1.1.6 SUCCESSFUL BIDDER: <br />THE SUCCESSFUL BIDDER WILL BE REFERENCED AS THE CONTRACTOR FTOM THIS <br />POINT ONWARDS THROUGHOUT THE REST OF THE SPECIFICATION. <br />1.2 THE ELECTRICAL CONTRACTOR REQUIREMENTS AND INSTRUCTIONS: <br />1.2.1 THE CONTRACTOR SHALL USE EXPERIENCED AND SKILLED PERSONS TO PERFORM <br />ALL THE ELECTRICAL INSTALLATION WORK UNDER THE CONSTANT <br />SUPERVISION OF LICENSED ELECTRICIANS AND/OR LICENSED JOURNEYMAN <br />ELECTRICIANS. <br />1.2.2 THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL REQUIRED PERMITS, <br />PAYING ALL FEES, AND PROVIDING ALL NECESSARY INSPECTIONS INCIDENTAL TO <br />THE ELECTRICAL PORTION OF THE WORK. <br />1.2.3 THE CONTRACTOR SHALL BE RESPONSIBLE FOR CARRYING NECESSARY INSURANCE <br />AS REQUIRED BY LAW TO PROTECT EMPLOYEES, OTHER PERSONS, EQUIPMENT, AND <br />MATERIAL. <br />1.2.4 THE INSTALLATION WORK SHALL COMPLY WITH ALL APPLICABLE STATE, COUNTY, <br />AND LOCAL BUILDING CODES. APPLICABLE CODES, AS A MINIMUM, WILL INCLUDE <br />THE LATEST EDITION OF THE FOLLOWING. THESE WILL BE CONSIDERED PART OF THE <br />SPECIFICATION OF THIS PROJECT. <br />A UNIFORM BUILDING CODE OF THE APPLICABLE CITY AND COUNTY. <br />B NATIONAL ELECTRIC CODE NFPA 70, 2005 <br />C LIFE SAFETY CODE NFPA 101 <br />1.2.5 IN CASE OF SUBSTITUTIONS THE CONTRACTOR SHALL PROVIDE A WRITTEN REQUEST <br />TO THE ARCHITECT FOR HIS REVIEW . THE CONTRACTOR SHALL IDENTIFY CLEARLY <br />THE DIFFERENCE BETWEEN THE SPECIFIED ITEMS AND THE SUBSTITUTE ITEMS, <br />INCLUDING THE ECONOMIC IMPACT ON THE PROJECT. THE SUBSTITUTE ITEM <br />SHALL NOT BE ORDERED OR USED UNLESS APPROVED BY THE ARCHITECT AND/OR <br />BY THE OWNER IN WRITING. <br />1.2.6 THE CONTRACTOR SHALL SUBMIT FIVE SETS OF SHOP DRAWINGS FOR SPECIFIED <br />PRODUCTS AT ONE TIME WITHIN THIRTY (30) DAYS FROM THE OFFICIAL NOTICE TO <br />PROCEED. SHOP DRAWING SUBMITTAL SHALL INCLUDE THE FOLLOWING MATERIALS <br />AND SYSTEMS: <br />A) LIGHTING FIXTURES, DIMMERS, LAMPS, AND SAFETY SWITCHES. <br />B) TRANSFORMERS, SWITCH BOARDS, DISTRIBUTION PANELS , DISCONNECTS, AND <br />WIREWAYS IF PURCHASED NEW. <br />C) METER CENTERS, CIRCUIT BREAKERS, FUSES, MOTOR STARTERS IF PURCHASED <br />FOR THIS PROJECT. <br />D) TIME CLOCK AND OTHER DEVICES, <br />E) SCHEMATIC DIAGRAMS FOR THE ABOVE ITEMS. <br />1.2.7 THE CONTRACTOR SHALL PROVIDE THE FOLLOWING DOCUMENTS BEFORE THE CLOSING <br />OF THE PROJECT AND PRIOR TO THE FINAL PAYMENT: <br />A) ONE YEAR WRITTEN WARRANTY FOR ANY DEFECT IN WORKMANSHIP, <br />MATERIAL, AND EQUIPMENT. <br />B) TWO SETS OF MANUFACTURER'S OPERATIONAL AND MAINTENANCE MANUALS IF <br />APPLIC AB LE. <br />C) MANUFACTURER'S WARRANTIES AND WARRANTY CERTIFICATES. <br />D) TWO SETS OF REPRODUCIBLE OR RED MARKED UP PRINTS OF "AS -BUILT" <br />DRAWINGS, ONE FOR THE ARCHITECT AND ONE FOR THE OWNER OF THE PROJECT. <br />1.2.8 THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE THE NECESSARY <br />TEMPORARY ELECTRICAL POWER, AT HIS EXPENSE, AS REQUIRED BY HIS <br />TRADE AND BY THE GENERAL CONTRACTOR. <br />1.2.9 THE CONTRACTOR SHALL MAKE SURE ON A DAILY BASIS THAT ALL <br />UNNECESSARY MATERIAL AND TRASH CONTRIBUTED BY HIS TRADE ARE <br />REMOVED. <br />1.2.10 THE CONTRACTOR SHALL CONCEALED ALL THE CONDUIT IN THE FINISHED <br />AREAS. <br />2.0 PRODUCTS: <br />2.1 GENERAL: <br />THE ELECTRICAL CONTRACTOR SHALL PURCHASE AND USE ALL "NEW" MATERIAL AS <br />SPECIFIED AND SHOWN ON THE ELECTRICAL PLAN OF THIS PROJECT. ALL THE MATERIAL <br />SHALL BE FREE FROM DEFECTS AND SHALL CARRY A "UL" LABEL. <br />2.2 C ONDUC TORS: <br />ALL INSULATED CONDUCTORS SHALL BE UNCOATED COPPER OF 98% <br />CONDUCTIVITY, 600 VOLT AC, DUAL RATED, TYPE THHN/THWN AS NECESSARY TO <br />MEET THE DESIGN REQUIREMENTS AND THE APPLICABLE CODES. THW (FOR # 4 AWG <br />AND LARGER) AND THERMO PLASTIC WIRES RATED FOR 75 DEGREES CENTIGRADE <br />OPERATIONS IN WET AND DRY LOCATIONS AND 90 DEGREES CENTIGRADE WITHIN <br />ELECTRIC DISCHARGE LIGHTING EQUIPMENT MAY BE USED. ALL CONDUCTORS SHALL BE <br />STRANDED COPPER. THE MINIMUM SIZE OF WIRE SHALL BE # 12 AWG FOR 20 AMP <br />BREAKER, # 10 AWG FOR 30 AMP BREAKER, # 8 AWG FOR 40 AMP BREAKER. <br />2.3 C AB LE: <br />SIGNAL CABLES, IF USED, SHALL BE COPPER AND SHALL MEET ALL UL AND N.E.0 <br />CODE REQUIREMENTS. ARMORED (TYPE AC) AND NON- <br />METALLIC (NM) CABLES SHALL NOT BE USED. ALL CABLE ASSEMBLIES SHALL <br />CONTAIN COPPER GROUND CONDUCTOR. <br />2.4 CONDUITS: <br />THE CONDUITS SHALL BE ELECTRICAL METALLIC TUBING (EMT) AND HOT DIPPED <br />GALVANIZED STANDARD STEEL AS MANUFACTURED BY WHEATLAND TUBE <br />COMPANY OR EQUIVALENT. UNDERSLAB CONDUITS CAN BE PVC SCHEDULE 40 CONDUIT, <br />OR EMT. IF EMT IS USED ALL ELBOWS TURNING UP FROM SLAB SHALL BE GALVANIZED <br />WITH B ITUMASTIC OR ASPHALTUM. PVC CONDUIT SHALL BE MANUFACTURED BY CARLON <br />OR EQUIVALENT. MINIMUM SIZE OF CONDUIT SHALL BE 1/2" INSIDE DIAMETER. <br />2.5 OUTLET BOXES AND FITTINGS: <br />OUTLET BOXES, FITTING CLAMPS AND HANGERS ETC. SHALL BE GALVANIZED STEEL, <br />RUST RESISTANT AND COMPATIBLE WITH THE RACEWAY. OUTLET BOXES FOR <br />FIXTURES, SWITCHES, AND RECEPTACLES SHALL HAVE SMOOTH ROUND EDGES AND <br />SHALL BE WITH COVER PLATES. BOXES SHALL BE "STEEL CITY" OR EQUIVALENT. <br />FITTINGS FOR EMT CONDUITS SHALL BE COMPRESSION TYPE. NO SET SCREW FITTINGS <br />WILL BE USED. <br />UNUSED HOLES SHALL BE COVERED WITH APPROVED INSERT CAPS <br />2.6 SWITCHES AND DIMMERS: <br />SWITCHES AND DIMMERS SHALL BE TOTALLY ENCLOSED, RATED AT 120/277 VOLTS <br />AC, 20 AMPS, 2000 WATTS WITH GRAY TOGGLE AND DEVICE PLATE. THESE SHALL BE <br />QUIET OPERATION, COMMERCIAL GRADE AS MANUFACTURED BY LEVITON, LUTRON <br />OR EQUIVALENT. PLATES SHALL MATCH THE SWITCHES. FURNISH IN GANGS AS <br />NECESSARY. <br />2.7 REC EPTAC LES: <br />RECEPTACLE SHALL BE COMMERCIAL GRADE, 125 VOLTS AC, 15 AND 20 AMPERE <br />RATING WITH GROUNDED POLE AND TWO CIRCUIT OPTION, AS MANUFACTURED BY <br />LEVITON OR EQUIVALENT. PLATES SHALL MATCH THE RECEPTACLES. FURNISH IN <br />GANGS AS NECESSARY. <br />2.8 DEVICE PLATES: <br />PROVIDE DEVICE PLATE FOR EACH AND EVERY OUTLET BOX. FURNISH IN GANGS AS <br />NECESSARY. IN KITCHEN AREA THE COVER PLATES SHALL BE STAINLESS STEEL. <br />IN AREAS OTHER THAN KITCHEN AREA COORDINATE WITH TENANT FOR COLORS. <br />2.13 GUARANTEE: <br />ALL ELECTRICAL EQUIPMENT, MATERIAL AND WORKMANSHIP SHALL BE <br />GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF ACCEPTANCE. <br />3.0 INSTALLATION INSTRUCTIONS: <br />3.1 GENERAL: <br />THE PLAN LOCATION OF LIGHTING FIXTURES, JUNCTION BOXES, CONVENIENCE <br />OUTLETS AND PANEL BOARDS ARE APPROXIMATE UNLESS DIMENSIONED <br />AND ARE <br />TO BE ADJUSTED BY THE CONTRACTOR AS REQUIRED IN THE AREAS WHERE CEILING <br />GRID AND OTHER OBSTRUCTIONS DETERMINE FIXTURE LOCATIONS. THE CONTRACTOR <br />SHALL COORDINATE WITH OTHER ARCHITECTURAL, MECHANICAL AN <br />D OTHER SYSTEMS <br />TO AVOID INTERFERENCE. ALL CUTTING AND CONSEQUENT REPAIRS IN CONJUNCTION <br />WITH THE WORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. <br />BEAMS OR OTHER STRUCTURAL COMPONENT SHALL NOT BE CUT WITHOUT THE <br />KNOWLEDGE AND WRITTEN CONSENT OF THE ARCHITECT. <br />3.2 THE CONTRACTOR SHALL PROVIDE ALL NECESSARY MATERIALS, LABOR, <br />TRANSPORTATION, RIGGING & HOISTING, TOOLS, AND STORAGE, ETC. FOR ALL WORK <br />INDICATED AND REQUIRED FOR COMPLETE INSTALLATION. <br />3.3 THE ELECTRICAL WORK SHALL BE EXECUTED IN ACCORDANCE WITH ALL APPLICABLE <br />CODES AND SHALL INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING. <br />WORKMANSHIP SHALL BE THE HIGHEST QUALITY AS ESTABLISHED BY TRADE STANDARD. <br />3.4 THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING NECESSARY PERMITS <br />AND COMMUNICATIONS WITH THE LOCAL BUILDING DEPARTMENT AND INSPECTION <br />PERSONNEL TO REVIEW CONTRACT DOCUMENTS PRIOR TO INSTALLATION. <br />3.5 OWNER WILL NOT BE HELD RESPONSIBLE FOR FIELD CHANGES THAT ARISE FROM <br />CONTRACTOR'S ERROR OR OMISSION OF MATERIALS OR WORKMANSHIP IN WORK <br />3.6 THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL UTILITIES <br />PLACEMENT, AS IDENTIFIED ON THE RISER DIAGRAM, AND LOCATION OF THE <br />ELECTRICAL SERVICE EQUIPMENT. THE CONTRACTOR SHALL PAY ALL NECESSARY <br />CHARGES ASSOCIATED WITH INSTALLATION OF ALL UTILITIES TO THE POWER <br />COMPANY PRIOR TO THE CONSTRUCTION. A LETTER SHALL BE PROVIDED FROM THE <br />POWER COMPANY THAT ALL THE CHARGES HAVE BEEN PAID IN FULL. <br />3.7 NECESSARY AND OBVIOUSLY REQUIRED, ELECTRICAL ITEMS THAT ARE NOT SHOWN <br />ON THE DRAWINGS, SHALL NOT RELIEVE THE CONTRACTOR OF HIS <br />RESPONSIBILITIES TO INSTALL A COMPLETE AND SAFE ELECTRICAL SYSTEM. <br />3.8 THE ELECTRICAL CONTRACTOR SHALL FOLLOW THE SAME COLOR CODE <br />IDENTIFICATION FOR EACH PHASE THROUGHOUT THE SYSTEM FROM SERVICE <br />SWITCH OR TRANSFORMER THROUGH ALL BRANCH CIRCUITS. <br />3.9 ALL SLAB OR ROOF PENETRATIONS SHALL BE MADE WITH APPROVED FIRE RATED <br />SMOKE BARRIER FITTINGS. PROVIDE ACCESSORIES (PITCH POCKETS, SLEEVES, ETC.) <br />AS REQUIRED. <br />3.10 JUNCTION BOXES FOR NEON SIGN LIGHTS, SWITCHES, LIGHTING FIXTURES, <br />RECEPTACLES AND FOR PULLING WIRES SHALL BE APPROXIMATELY AS SHOWN ON <br />THE PLANS BUT EXACT LOCATIONS SHALL BE GOVERNED BY THE ARCHITECTURAL <br />PLANS. <br />3.11 ALL OUTLET BOXES SHALL HAVE SQUARE CUT CORNERS. AIR SPACE GREATER THAN <br />1/8" AROUND OUTLET BOXES, AND ADJACENT DRYWALL WILL NOT BE PERMITTED. <br />THE CONTRACTOR SHALL COORDINATE WITH DRYWALL INSTALLER PRIOR TO <br />INSTALLATION. <br />3.12 LIGHTING SWITCHES AND CONVENIENCE RECEPTACLES SHALL BE FLUSH MOUNTED <br />IN SECTIONAL SWITCH BOXES WITH MATCHING COVER PLATES UNLESS NOTED <br />OTHERWISE. <br />3.13 THE MOUNTING ARRANGEMENT OF EACH FIXTURE WILL BE DETERMINED BY THE <br />CONTRACTOR EXCEPT WHERE THE MANUFACTURER HAS GIVEN SPECIFIC MOUNTING <br />INSTRUCTIONS. <br />3.14 THE CONTRACTOR SHALL FURNISH AND INSTALL ALL LUMINARIES, DEVICES, AND <br />EQUIPMENT AS SPECIFIED AND SHOWN ON THE PLAN DIAGRAMS. PROVIDE ALL <br />CABLES, CONDUCTORS, CONDUITS, AND CONNECTIONS AS REQUIRED TO PROVIDE <br />COMPLETE AND OPERATIONAL ELECTRICAL AND MECHANICAL SYSTEMS. ALL <br />CONDUITS SHALL BE RUN CONCEALED IN FINISHED AREAS. <br />3.15 INDIVIDUAL BREAKERS WILL SUPPLY ELECTRICAL POWER TO INDIVIDUAL SIGN OR <br />NEON LIGHT CIRCUITS. NEON TRANSFORMER EQUIPMENT IS TO BE CONCEALED <br />ABOVE ADJACENT COLUMN ENCLOSURE OR TO BE INSTALLED AS SHOWN ON <br />ARCHITECTURAL DRAWINGS. <br />3.16 ALL JOINTS IN CONDUIT AND RACEWAY SHALL BE MADE TIGHT AND BENDS SHALL <br />BE MADE OVER LONG RADIUS WHERE ENTERING A CABINET AND JUNCTION BOX. <br />THE CONTRACTOR SHALL SUPPORT ALL CONDUIT AND RACEWAYS SECURELY FROM <br />JOISTS AND/OR BEAMS (TIE WIRES ARE NOT ACCEPTABLE), THE CONTRACTOR SHALL <br />VERIFY ALL RACEWAY SIZES IN ACCORDANCE WITH THE N.E.C. CODE. NO CONDUIT <br />SHALL CARRY MORE THAN THREE(3) CURRENT CARRYING CONDUCTORS. <br />NOTE: ALL JOB CUT THREADS SHALL BE COATED WITH RUST RESISTANT ZINC <br />CHROMATE FOR THIN WALL EMT.' <br />3.17 LIGHTING CONDUITS SHALL BE SUPPORTED AT EVERY 8 FEET. <br />3A8 MOUNTING HEIGHT OF LIGHTING EQUIPMENT, UNLESS NOTED OTHERWISE ON <br />ARCHITECTURAL PLANS SHALL BE BY ARCHITECT AND OWNER IN FIELD. <br />3.19 AN EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED IN ALL <br />ELECTRICAL RACEWAYS AND SHALL BE SIZED IN ACCORDANCE WITH <br />NATIONAL ELECTRIC CODE (N.E.C) ARTICLE 250. ALL BRANCH CIRCUITS SHALL <br />HAVE A SEPARATE GREEN INSULATED GROUND WIRE IN EACH CONDUIT RUN. <br />ISOLATED GROUND CONDUCTORS SHALL BE ROUTED TO THOSE CIRCUITS WHICH <br />NEED ISOLATED GROUND ESPECIALLY FOR COMPUTERS AND CASH REGISTERS. <br />3.20 THE CONTRACTOR SHALL PROVIDE LIGHTNING PROTECTION VOLTAGE SURGE <br />PROTECTOR FOR ALL SERVICE PHASE CONDUCTORS TO GROUND (IF IT IS NOT <br />ALREADY THERE IN CASE OF RENOVATIONS). DEVICE SHALL BE APT TE 400 OR <br />APPROVED EQUIVALENT. <br />3.21 LUMINARIES SHALL BE AS SPECIFIED IN THE "LIGHTING FIXTURE SCHEDULE". ALL <br />RECESSED AND LAY -IN FIXTURES SHALL BE SUPPORTED FROM THE FOUR CORNERS <br />WITH SUPPORTS CAPABLE OF CARRYING TWICE THE WEIGHT OF THE FIXTURE. ALL <br />SUPPORTS SHALL BE ATTACHED TO THE JOISTS AND/OR BEAMS. <br />NO LIGHTING FIXTURE SHALL BE INSTALLED WITHIN 2 FEET OF ANY SPRINKLER <br />HEAD. <br />3.22 THE CONTRACTOR SHALL INSTALL ALL TELEPHONE JACKS AND WIRING FROM THE <br />MAIN TELEPHONE TERMINAL BOARD TO THE FINAL TELEPHONE OUTLETS. WIRING <br />SHALL BE INSTALLED IN A MINIMUM 1/2 INCH CONDUIT. <br />3.23 THE CONTRACTOR SHALL COORDINATE WITH THE FIRE PROTECTION CONTRACTOR <br />AND SHALL MAKE ALL NECESSARY CONNECTIONS BETWEEN DUCT SMOKE <br />DETECTORS AND HVAC UNITS. <br />3.24 ALL JUNCTION BOXES SHALL BE ACCESSIBLE FROM BELOW. OTHERWISE, <br />CONTRACTOR SHALL PROVIDE ACCESS PANEL AT ALL JUNCTION BOX LOCATIONS <br />AND SMOKE DETECTORS. <br />3.25 IF NOT ALREADY EXISTING, THE CONTRACTOR SHALL FURNISH ALL THE NECESSARY <br />DISCONNECT SWITCHES, RELAY BOXES, AND CONTROL BOXES AS REQUIRED AND <br />RECOMMENDED BY THE HVAC MANUFACTURER FOR THE HVAC UNIT AND WATER <br />HEATER. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE <br />MECHANICAL CONTRACTOR AND MAKE ALL NECESSARY CONNECTIONS TO MAKE <br />THE HVAC SYSTEM FUNCTIONAL. <br />3.26 A PLASTIC COVERED TYPE WRITTEN IDENTIFICATION CARD FOR ALL MAIN AND <br />BRANCH CIRCUITS INCLUDING SPARES SHALL BE POSTED AT THE INSIDE OF THE <br />PANEL DOOR. <br />3.27 LOCK -ON DEVICES ON PANEL CIRCUIT BREAKERS FOR NIGHT, EXIT AND EMERGENCY <br />LIGHTING CIRCUITS SHALL BE PROVIDED AND INSTALLED ON CORRESPONDING <br />CIRCUITS. <br />4.0 TRANSFORMER AND PANEL BOARD SPECIFICATIONS : <br />THIS SECTION SHALL APPLY TO THE NEW TRANSFORMER, PANEL BOARDS, <br />CIRCUIT BREAKERS, PANEL BOXES & TRIMS, DISCONNECT SWITCHES, AND <br />FUSES. <br />4.1 LOAD CENTERS & PANEL BOARDS: <br />LOAD CENTERS AND PANEL BOARDS SHALL BE GENERAL PURPOSE N.E.M.A. TYPE 1 <br />OR TYPE 3R ENCLOSURES SUITABLE FOR SPECIFIED INDOOR OR OUTDOOR <br />LOCATIONS AND FLUSH OR SURFACE MOUNTING APPLICATIONS AS INDICATED ON <br />THE PANEL SCHEDULE. PANEL BOARDS AND THE INTERNAL COMPONENTS SHALL BE <br />RATED TO PERFORM THEIR FUNCTIONS CONTINUOUSLY AT 40' C AMBIENT AND <br />50% RELATIVE HUMIDITY. BUSSES, TERMINALS, AND LUGS SHALL BE RATED AND <br />CAPABLE TO FUNCTION CONTINUOUSLY AT 75 DEGREES CENTIGRADE. <br />PANEL BOARDS SHALL BE AS MANUFACTURED BY CUTLER HAMMER, <br />GENERAL ELECTRIC, SQUARE 'D', CHALLENGER, OR APPROVED EQUAL. <br />A NAMEPLATE LISTING PANEL NUMBER, TYPE, MANUFACTURER'S NAME, NUMBER OF <br />PROTECTIVE AND SWITCHING DEVICES, VOLTAGE; CURRENT, PHASE AND AIC <br />RATINGS SHALL BE PROVIDED. <br />BRANCH CIRCUITS SHALL BE ARRANGED USING DOUBLE ROW CONSTRUCTION. <br />ALL INTERIORS SHALL BE COMPLETELY FACTORY ASSEMBLED WITH SWITCHING <br />AND PROTECTIVE DEVICES, WIRE CONNECTORS, ETC. ALL WIRE CONNECTORS, <br />EXCEPT SCREW TERMINALS, SHALL BE OF THE ANTI -TURN SOLDERLESS TYPE AND <br />ALL SHALL BE SUITABLE FOR COPPER WIRE OF THE SIZES INDICATED ON DRAWINGS <br />OR IN THE PANEL SCHEDULES AND CONTINUOUSLY FUNCTIONING AT 75 DEGREE <br />CENTIGRADE. <br />INTERIORS SHALL BE SO DESIGNED THAT SWITCHING AND PROTECTIVE DEVICES <br />CAN BE REPLACED WITHOUT DISTURBING ADJACENT UNITS AND WITHOUT <br />REMOVING THE MAIN BUS CONNECTORS AND SHALL BE SO DESIGNED THAT <br />CIRCUITS MAY BE CHANGED WITHOUT MACHINING, DRILLING, OR TAPPING. <br />BUS BARS FOR THE MAINS SHALL BE OF COPPER AND SIZED IN ACCORDANCE WITH <br />UNDERWRITERS' LABORATORIES STANDARDS. UNLESS NOTED OTHERWISE, FULL SIZE <br />NEUTRAL BARS SHALL BE INCLUDED. BUS BAR TAPS FOR PANELS WITH SINGLE POLE <br />BRANCHES SHALL BE ARRANGED FOR SEQUENCE PHASING OF THE BRANCH CIRCUIT <br />DEVIC ES. <br />THE SHORT CIRCUIT RATING OF THE ASSEMBLED PANEL BOARD SHALL BE IN <br />ACCORDANCE WITH UL. INC. STANDARDS AND THEIR TEST VERIFICATION. <br />PHASE BUSSING SHALL BE FULL HEIGHT WITHOUT REDUCTION. CROSS AND CENTER <br />CONNECTORS SHALL BE COPPER. <br />NEUTRAL AND GROUND BUSSING SHALL HAVE SUITABLE LUGS FOR OUTGOING <br />FEEDERS REQUIRING A NEUTRAL AND GROUND CONNECTIONS. <br />SPACES FOR FUTURE SWITCHING AND PROTECTIVE DEVICES ON LIGHTING AND <br />APPLIANCE DISTRIBUTION PANELS SHALL BE BUSSED FOR THE MAXIMUM DEVICE <br />THAT CAN BE FITTED INTO THEM. <br />PROVIDE BLANK FILLER PLATES IN THE EMPTY SPACES. <br />4.2 CIRCUIT BREAKER: <br />THE CIRCUIT BREAKERS ARE TO BE INDUSTRIAL MOLDED CASE BOLT ON TYPE, <br />STANDARD THERMAL, MAGNETIC, WITH TRIP FREE MECHANISM, THREE POSITION <br />HANDLES INDICATING "ON" "OFF" AND "TRIPPED" CONDITION. <br />EACH POLE SHALL PROVIDE INVERSE TIME DELAY AND INSTANTANEOUS CIRCUIT <br />PROTECTION. THE BREAKER RATING AND CONFIGURATION SHALL BE AS INDICATED <br />ON THE PANEL BOARD SCHEDULE. ALL MULTIPOLE BREAKERS SHALL HAVE AN <br />INTERNAL COMMON TRIP. <br />ALL BREAKER LUGS SHALL BE SUITABLE TO WITHSTAND 75 DEGREE CENTIGRADE <br />WITHOUT MALFUNCTIONING. <br />!�fi�1�VLf�1.iWE <br />HINGED DOORS IN PANEL TRIMS SHALL COVER ALL SWITCHING DEVICE HANDLES <br />AND SHALL CONFORM TO THE FOLLOWING REQUIREMENTS: <br />1. DOORS SHALL NOT UNCOVER ANY LIVE PARTS WHILE MAKING SWITCHING DEVICE <br />HANDLES ACCESSIBLE. <br />2. DOORS SHALL HAVE FLUSH -TYPE CYLINDER LOCK AND CATCH, EXCEPT THAT <br />DOORS OVER 48" IN HEIGHT SHALL HAVE AUXILIARY FASTENERS AT TOP AND <br />BOTTOM OF DOOR IN ADDITION TO FLUSH -TYPE CYLINDER LOCK AND CATCH. <br />DOOR HINGES SHALL BE CONCEALED. ALL LOCKS SHALL BE KEYED ALIKE. <br />DIRECTORY FRAME AND CARD HAVING A TRANSPARENT COVER SHALL BE FURNISHED <br />ON EACH DOOR. <br />THE TRIMS SHALL BE FABRICATED FROM CODE GAUGE SHEET STEEL. ALL EXTERIOR <br />AND INTERIOR STEEL SURFACES OF THE PANEL BOARDS SHALL BE PROPERLY <br />CLEANED PRIMED AND PAINTED IN ACCORDANCE WITH THE MANUFACTURER'S <br />STANDARD SPECIFICATIONS AND COLOR. <br />TRIMS FOR FLUSH MOUNT PANELS SHALL OVERLAP THE BOX BY AT LEAST 3/4" ALL <br />AROUND. SURFACE MOUNT PANELS TRIMS SHALL HAVE THE SAME WIDTH AND <br />HEIGHT AS OF THE BOX. TRIMS SHALL BE MOUNTABLE BY A SCREW DRIVER <br />WITHOUT THE NEED FOR SPECIAL TOOLS. <br />4.4 PANEL BOXES: <br />BOXES SHALL BE MADE FROM UNPAINTED GALVANIZED CODE GAUGE STEEL HAVING <br />MULTIPLE KNOCKOUTS ON THE TOP AND THE BOTTOM EXCEPT WHERE NOTED <br />OTHERWISE. BOXES SHALL BE OF SUFFICIENT SIZE TO PROVIDE A MINIMUM GUTTER <br />SPACE OF 4" ON ALL SIDES. <br />WHERE FEEDER CABLES SUPPLYING THE MAINS OF A PANEL ARE CARRIED THROUGH <br />ITS BOX TO SUPPLY OTHER ELECTRICAL EQUIPMENT, THE BOX SHALL BE SO SIZED <br />AS TO INCLUDE THIS WIRING SPACE. THIS WIRING SPACE SHALL BE IN ADDITION TO <br />THE MINIMUM GUTTER SPACE SPECIFIED ABOVE AND THE LIMITING WIDTH MAY BE <br />INCREASED ACCORDINGLY. AT LEAST FOUR (4) INTERIOR MOUNTING STUDS SHALL <br />BE PROVIDED. <br />ALL UNUSED HOLES IN THE BOXES SHALL BE PLUGGED WITH APPROVED INSERT <br />CAPS. BOXES SHALL BE "STEEL CITY" OR EQUAL. <br />4.5 DISCONNECT SWITCHES: <br />THE CONTRACTOR SHALL INSTALL N.E.M.A. TYPE 1 ENCLOSURES FOR INDOOR <br />APPLICATIONS AND TYPE 3R ENCLOSURES FOR OUT DOOR APPLICATIONS. <br />DISCONNECT SWITCHES FOR MOTOR CIRCUIT AND FIXED LOAD (SUCH AS HVAC <br />EQUIPMENT, AND WATER HEATER ETC.) CIRCUITS SHALL BE FUSIBLE OR <br />NON FUSIBLE AS SHOWN ON THE DRAWINGS OR REQUIRED BY THE MANUFACTURER. <br />CONSULTING <br />ENGINEERING <br />ASSOCIATES <br />8365 GUNN HIGHWAY <br />TAMPA, FL 33626 <br />FAX13) 1(844 48225 <br />0226 <br />EB - 0003962 <br />Mechanical Plumbing <br />Fire Protection <br />SEAL : <br />Nk.haF <br />a PE#�challa <br />3 P.E <br />Fla CO" 3967 <br />z <br />O <br />CV <br />d. <br />LO <br />co <br />CO <br />co <br />Q <br />0 <br />W <br />cc <br />U <br />O <br />J <br />J <br />LL <br />0 <br />- <br />co <br />Z <br />_I <br />z <br />W <br />W <br />N <br />W <br />M <br />w <br />u <br />0.W <br />Q <br />W <br />w <br />J <br />N <br />LL <br />W <br />0 <br />M <br />M <br />� <br />00 <br />z <br />U <br />U <br />LdU <br />MM <br />T <br />LLJ <br />> <br />REVISIONS <br />Z\ <br />delta <br />date <br />revision <br />SHEET TITLE : <br />ELECTRICAL <br />SPECIFICATION <br />DRAWN BY: MPS <br />DATE: 02/1 2/1 9 <br />PROD. NO. 18010 <br />2/13/2019 2:06:55 PME:\2180\218014 - Zephyrhills Police Station HVAC\Drawings\E4 Spe-Agn <br />I <br />SHEET NO. <br />E-004 <br />