<br />BING PUMPS
<br />[PP-
<br />VING
<br />E1HW-
<br />MAKE
<br />MODEL
<br />LOCATION
<br />HEAD
<br />GPM
<br />RPM
<br />H.P.
<br />ELECTRIC
<br />REMARKS
<br />SIZE
<br />1
<br />TACO
<br />006
<br />REFER TO
<br />5 TDH
<br />5
<br />3250
<br />1/40
<br />120/1/60
<br />ALL BRONZE RECIRCULATION PUMP. PROVIDE SPARE REPLACEABLE CARTRIDGE.
<br />PLANS
<br />WATER HEATER (EQUAL SUBSTITUTIONS WITH ROSS CONSTRUCTION REPRESENTATIVE APPROVAL)
<br />MARK
<br />LOCATION
<br />MAKE
<br />MODEL
<br />TANK
<br />FUEL
<br />INPUT
<br />RECOVERY
<br />OPERATING
<br />ELECTRIC
<br />REMARKS
<br />SIZE
<br />TEMPERATURE
<br />HW-1
<br />SHELF
<br />STATE
<br />PCE 10
<br />10 GAL
<br />ELECT.
<br />4.0 KW
<br />16 GPH
<br />120 F
<br />208/1/60
<br />QUICK RECOVERY WATER HEATER - COORDINATE ELECTRICAL WITH E.C. T&P RELIEF
<br />MOUNTED
<br />10MSA
<br />0 100 F
<br />VALVE WATTS NO. 100XL-4-125 ACCEPTABLE ALTERNATES: A.O. SMITH, RHEEM OR
<br />EQUAL. A SCEOND WATER HEATER WILL BE REQUIED WHEN LOCKER ROOM SINK OR
<br />RESTROOM LAVATORIES ARE MORE THAN 60 FEET FROM THE WATER HEATER
<br />LOCATED IN THE JANITORIAL CLOSET.
<br />KING FOUNTAIN (NO SUBSTITUTIONS - NO EXCEPTIONS)
<br />r!WC1'
<br />IT
<br />MAKE
<br />MODEL
<br />TYPE
<br />NAME
<br />CAPACITY
<br />COMPRESS.
<br />CONDENSER
<br />HORSE
<br />ELECTRIC
<br />REMARKS
<br />POWER
<br />TER
<br />HALSEY
<br />HACBLSS-
<br />WALL
<br />BI-LEVEL
<br />8.0 GPH
<br />NONE
<br />NONE
<br />NONE
<br />NONE
<br />BARRIER FREE WITH WALL HANGER PLATE - NO SUBSTITUTION
<br />OLER
<br />TAYLOR
<br />LR
<br />MOUNTED
<br />INSTALLED WITH ORIFICE AT +34" LOW AND +41" (HIGH).
<br />CLEANOUTS & MISC. ITEMS(EQUAL SUBSTITUTIONS WITH ROSS CONST. REP. APPROVAL).
<br />MAKE
<br />MODEL
<br />LOCATION
<br />SIZE
<br />BODY
<br />TOP
<br />REMARKS
<br />FRATS,
<br />OR
<br />IN
<br />J.R.
<br />SMITH
<br />2005
<br />SERIES
<br />SEE PLANS
<br />AS NOTED
<br />CAST IRON
<br />STAINLESS
<br />STEEL
<br />SQUARE TOP - FLAT STRAINER WITH P050 1/2" TRAP PRIMER
<br />ANOUT
<br />J.R.
<br />SMITH
<br />4402
<br />SERIES
<br />WALL TYPE
<br />AS NOTED
<br />CAST IRON
<br />STAINLESS
<br />STEEL
<br />IF CLEANOUTS ARE INSTALLED ON THE SALES FLOOR, INSTALL AT MAX. DISTANCE OF
<br />100 FT. OR LESS AS MAY BE REQUIRED BY GOVERNING AUTHORITY.
<br />P
<br />ER
<br />PRECISION
<br />PLUMBING
<br />OREGON1
<br />SEE PLANS
<br />1/2"
<br />-
<br />-
<br />OR EQUAL
<br />PLUMBING FIXTURES (NO SUBSTITUTIONS - NO EXCEPTIONS)
<br />MARK
<br />ITEM
<br />MAKE
<br />NAME
<br />MODEL
<br />TRIM
<br />TRAP
<br />STOPS
<br />CONNECTIONS
<br />REMARKS
<br />WASTE
<br />VENT
<br />HW
<br />CW
<br />P-1
<br />WATER
<br />KOHLER
<br />WELCOMME
<br />K-4406
<br />SLOAN
<br />INTEGRAL
<br />INTEGRAL
<br />4"
<br />2"
<br />-
<br />1"
<br />FLOOR MOUNTED, FLUSH VALVE, WITH K-4670-C SEAT
<br />CLOSET
<br />1.28 GPF
<br />111-1.28
<br />P-11-1
<br />WATER
<br />KOHLER
<br />HIGHLINE
<br />K-4405
<br />SLOAN
<br />INTEGRAL
<br />INTEGRAL
<br />4"
<br />2"
<br />-
<br />1"
<br />FLOOR MOUNTED, FLUSH VALVE, WITH K-4670-C SEAT
<br />CLOSET
<br />1.28 GPF
<br />111-1.28
<br />REFER TO NOTES #8, #9 AND 10.
<br />P-21-1
<br />URINAL
<br />AMERICAN
<br />ALLBROOK
<br />6541.132
<br />SLOAN
<br />INTEGRAL
<br />INTEGRAL
<br />2"
<br />1-1/2"
<br />-
<br />3/4"
<br />WITH WALL CARRIER, MOUNTED AT ADA HEIGHT, 17" MAX.
<br />STANDARD
<br />186-.5
<br />1
<br />1
<br />REFER TO NOTE #8.
<br />P-31-1
<br />LAVATORY
<br />AMERICAN
<br />LUCERNE
<br />0355.012
<br />HERITAGE
<br />NOTE #3
<br />NOTE #4
<br />1-1/2"
<br />1-1/2"
<br />1/2"
<br />1/2"
<br />WITH FLOOR MOUNTED CONCEALED ARM WALL CARRIER, FAUCET TO BE
<br />STANDARD
<br />4" CENTERS
<br />(0.5 GPM)
<br />5402.172V.002 WITH WRIST HANDLES, REFER TO NOTE #7.
<br />MOUNTED AT ADA HEIGHT, 2'-9" A.F.F. TO TOP OF RIM
<br />P-4H
<br />LOCKER
<br />ELKAY
<br />CELEBRITY
<br />GECR2521
<br />AMER. STD.
<br />NOTE #3
<br />NOTE #4
<br />1-1/2"
<br />1-1/2"
<br />1/2"
<br />1/2"
<br />DRAIN - JUST NO. J-35, CRUMB CUP. FAUCET TO BE #7400.172H.002,
<br />ROOM SINK
<br />HERITAGE
<br />GOOSE NECK WITH WRIST BLADE HANDLES.
<br />P-5
<br />JANITOR'S
<br />FLORESTONE
<br />TERRAllO
<br />MODEL
<br />CENTRAL
<br />3"
<br />1/2"
<br />3"
<br />1-1/2"
<br />3/4"
<br />3/4"
<br />SERVICE SINK FAUCET TO BE CENTRAL BRASS #0054-YELSRC-Q
<br />SINK
<br />36x24x12
<br />191
<br />BRASS
<br />VALVES i
<br />I
<br />REFER TO NOTE #6
<br />NInTP-c-
<br />1. INSTALL SERVICE, SHUTOFF & CHECK VALVES, COCKS, STOPS, AIR CUSHIONS, VACUUM BREAKERS, AND SAFETY DEVICES WHERE REQUIRED BY CODE, SPECIFICATIONS, OR DRAWINGS.
<br />2. ALL CATALOG NOS. REFER TO AMERICAN STANDARD UNLESS NOTED AND ALL FIXTURES IN WHITE UNLESS NOTED.
<br />3. EXPOSED P-TRAPS TO BE 17 GA. CHROME PLATE WITH CLEANOUT AND ESCUTCHEON PLATE.
<br />4. STOPS TO BE CHROME PLATED 1/2" ANGLE VALVE WITH CHROME PLATED 12" LONG, 1/2" O.D. FLEXIBLE RISER AND ESCUTCHEON PLATE.
<br />5. ALL DRAINS AND WATER SUPPLY PIPING TO LAVATORIES TO BE INSULATED WITH 'HANDI LAV-GUARD' INSULATION KIT BY TRUEBRO.
<br />6. WITH FLORESTONE 24" HOSE AND BRACKET, MOP HOOK, AND 12" HIGH STAINLESS STEEL WALL GUARD.
<br />7. SINK TO BE MOUNTED FLUSH WITH WALLS AND SILICONE SEALANT APPLIED WHERE SINK MEETS WALL
<br />8. AN 'H' AT THE FIXTURE DESIGNATION INDICATES A ADA FIXTURE.
<br />9. FLUSH VALVE HANDLES FOR ADA FIXTURES SHALL BE MOUNTED ON WIDE SIDE OF TOILET AREA.
<br />10. PROVIDE SLOAN VBF-72-A FLUSH TRAP PRIMER WITH FLUSH VALVE. DRAIN PIPES FROM TRAP PRIMER VALVES TO BE PITCHED 1/2% MIN. FROM VALVE TO FLOOR DRAIN.
<br />r • W •- r : •
<br />WATER SUPPLY FIXTURE UNITS
<br />MARK
<br />DE5GRIPTION
<br />FIXITURE
<br />QUANTITY
<br />F.U.TAL
<br />P-1
<br />WATER CLOSET
<br />IOD
<br />I
<br />IOA
<br />P-IH
<br />HANDICAPPED
<br />10.0
<br />2
<br />20D
<br />KA
<br />P-2H
<br />HI �
<br />5.0
<br />1
<br />5.0
<br />URIP-3
<br />LAVATORY
<br />2D
<br />2
<br />4D
<br />HANDICAPPEDP-
<br />2.0
<br />2
<br />4.0
<br />LAVATORY
<br />P-414
<br />LOCKER RM SINK
<br />1.4
<br />1
<br />1.4
<br />P-5
<br />SERVICE SINK
<br />3.0
<br />1
<br />3D
<br />OF-IH
<br />WATER COOLER
<br />0.25
<br />2
<br />0.5
<br />TOTAL 47.q
<br />NOTE:
<br />2" GA REQUIRED, MAXIMUM WSFU ON 2' = 140 WSFU
<br />SANITARY FIXTURE UNITS
<br />MARK
<br />DESCRIPTION
<br />FIXTURE
<br />QUANTITY
<br />UNITS
<br />F.U.
<br />P-1
<br />WATER CLOSET
<br />4
<br />1
<br />4
<br />P-IH
<br />HANDICAPPED
<br />4
<br />2
<br />8
<br />WATER GL05ET
<br />P-21-1
<br />H DIIINAL
<br />2
<br />1
<br />2
<br />P-3
<br />LAVATORY
<br />1
<br />2
<br />2
<br />P_3H
<br />HANDICAPPED
<br />1
<br />2
<br />2
<br />LAVATORY
<br />P-414
<br />LOCKER RM SINK
<br />2
<br />1
<br />2
<br />P-5
<br />SERVICE SINK
<br />3
<br />1
<br />3
<br />DF-IH
<br />WATER COOLER
<br />05
<br />2
<br />1
<br />FD-I
<br />I FLOOR DRAIN
<br />1 2
<br />3
<br />b
<br />TOTAL 30
<br />NOTE:
<br />4" SANITARY REQUIRED, MAXIMUM DR ON 4" = 180 DFU
<br />PLUMBING CODED NOTES O
<br />I. CONNECT TO EXI5TIN65 SANITARY, VERIFY EXACT LOCATION, DEPTH,
<br />SIZE, AND FLOW DIRECTION IN THE FIELD PRIOR TO THE START OF
<br />WORK. VERIFY WASTE PIPING 15 ACTIVE PRIOR TO GONNEGTIN6.
<br />2. BEFORE ANY SANITARY 5EWER 15 REUSED THE 6L. CONTRACTOR
<br />SHALL:
<br />- VERIFY LOGATION, DEPTH, SIZE, AND FLOW DIRECTION PRIOR TO
<br />THE 5TART OF WORK
<br />- SCOPE ALL EXI5TIN67 UNDERGROUND SANITARY LINES WITH
<br />CAMERA AND VERIFY EXISTING SANITARY 15 IN PROPER
<br />OPERATING CONDITION UPON TURNOVER TO ROSS. PLUS ALL
<br />UNUSED GONNEGTION5 AND PATGH FLOOR
<br />- JET GLEAN Fag5TING SEWER IN51DE BUILDING
<br />- PRIOR TO MAKING NEW GONNEGTION5, CONTRAGTOR SHALL TEST
<br />5EhER BY FLU5HIN6 WITH WATER, A MINIMUM OF FIVE (5) 6ALLON5
<br />PER MINUTE FOR FOUR (4) HOURS PRIOR TO START OF WORK.
<br />3. CONNECT TO EXISTING GOLD WATER PIPING, VERIFY EXACT
<br />LOCATION AND SIZE IN THE FIELD PRIOR TO THE START OF WORK.
<br />4. SAW GUT FLOOR AND TRENCH TO INSTALL PIPING, BAGKFILL,
<br />COMPACT AND PATGH FLOOR TO MATCH EXISTING.
<br />5. THERMOSTATIC MIXING VALVE UNDER LAVATORY / LOCKER ROOM
<br />SINK, REFER TO DETAIL ON DRAWIN6 P3.
<br />6. FLOOR DRAIN WITH TRAP PRIMER VALVE.
<br />1. COORDINATE VERTICAL P05T AT TOILET PARTITIONS WITH FLOOR
<br />DRAIN LOCATIONS.
<br />8. WATER HEATER. REFER TO ARGHITEGTURAL DRAWING A4D FOR
<br />SHELF SUPPORT DETAIL AND PLUMBING DETAILS FOR PIPING
<br />DIAGRAM.
<br />q. ROUTE VENTS AND WATER PIPING IN J015T / CEILING SPACE AS HIGH
<br />AS POSSIBLE. ROUTE TO SUIT FIELD GONDITION5 AND COORDINATE
<br />WITH ALL OTHER TRADES. PROVIDE ADDITIONAL HANGERS, ELBOW5,
<br />PIPE, ETC. AS REQUIRED. ALL HOT WATER LINES MUST BE INSULATED.
<br />ALL INTERIOR HOT AND GOLD WATER PIPING 15 TO BE COPPER (NO
<br />E)CEPTION) WITH CAPPER OR BRA55 FITTII95 AND LEAD-FREE
<br />SOLDER A WATER FILTRATION SYSTEM 15 REQUIRED MERE HARD
<br />WATER CONDITIONS EXIST.
<br />10. EXI5TIN6 SPRINKLER RISER TO REMAIN. REFER TO SPEVFIGATION
<br />FOR ADDITIONAL INFORMATION.
<br />11. R FER TO DRAWING PI FOR CONTINUATION.
<br />'X' - 4"-J
<br />WIND DATA
<br />DESIGN OF MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT RESTRAINT
<br />SYSTEMS FOR WIND FORCES SPECIFIC FOR THIS PROJECT LOCATION SHALL BE BY
<br />MASON INDUSTRIES, INC. OR EQUAL MANUFACTURER AND AS REQUIRED FOR ALL
<br />APPLICABLE CODES.
<br />WIND BASE SPEED = 130 MPH
<br />GONTRAGTOR MU5T VERIFY
<br />ALL GLEARANGE5 AND
<br />DIMEN51ON5 IN FIELD
<br />McHENRY & ASSOCIATES, INC.
<br />CONSULTING ENGINEERS
<br />25001 EMERY ROAD, SUITE #200
<br />WARRENSVILLE HEIGHTS, OHIO 44128
<br />PHONE: 216-292-4696
<br />FAX: 216-292-5874
<br />Email: MAILOMCHENRYASSOCIATES.COM
<br />FLORIDA BUSINESS #0005282
<br />mcg architecture
<br />218.520.1551 p 216.5MIN7
<br />71M E Plowd Ney Rd, Sub 32% ge ebb ON 44131
<br />Seal:
<br />A Project for:
<br />Client:
<br />ROSS STORES, INC.
<br />4440 ROSEWOOD DRIVE
<br />PLEASANTON, CA 94588
<br />Revisions:
<br />BID/PERMIT
<br />02-14-13
<br />No. Description
<br />Date
<br />Project No.:
<br />11.594.01
<br />Drawn By:
<br />SLH
<br />Reviewed By:
<br />MAB
<br />Scale:
<br />AS NOTED
<br />Date:
<br />01-28-2013
<br />Filename:
<br />Sheet Title:
<br />PARTIAL PLUMBING
<br />PLAN, NOTES AND
<br />SCHEDULES
<br />Sheet #:
<br />PARTIAL PLUMBING PLAN, NOTES AND SCHEDULES I SCALE
<br />1/4" = 1' 0"
<br />id
<br />Q MCG ARCHITECTS 2013 ALL RIGHTS RESERVED