1/4' 5GREW5 (TYP)
<br />1/4' 5GREW5 C"J
<br />II , II
<br />WIND RESTRAINT BRACKETS
<br />SCALE: NONE
<br />NOTE: ATTACH ALL HANGERS FROM
<br />GER STRAPS TOP CHORD OF JOISTS.
<br />STRAP OR ANGLE
<br />60' MAX
<br />UWLE55 FOOT OF STRAP
<br />15 PLACED UNDER A
<br />BOTTOM REINFORGEMENT
<br />M1 I 5GREW5 MAY BE OMITTED
<br />IN IF HANGER LOOPS SIZE BOLT(5) FOR LOAD
<br />HANGER LOAD RATED
<br />FASTENERS
<br />STRAP
<br />SECURE
<br />WIRE
<br />10" VIA MAX 24" DIA MAX
<br />50' DIA MAX
<br />BAND OF SAME 517E
<br />AS HANGER STRAP
<br />HANGER RODS, WIRES,
<br />OR STRAPS REINFORGEMENT MAY BE
<br />U5ED FOR ATTACHMENT
<br />IF IT QUALIFIES FOR
<br />BOTH DUTIES
<br />DO NOT EXCEED
<br />ALLOWABLE LOAD
<br />LIMITS
<br />HA OR5 MUST NOT
<br />DEFORM DUGT SHAPE
<br />BAND ONE HALF-ROUW MAY BE
<br />USED IF DUCT SHAPE 15 MAINTAINED
<br />STRAP HAN6ER5
<br />DUCT HANGER DETAIL
<br />SCALE: NONE
<br />LOGKNUTS
<br />(TYPIGAU
<br />MECHANICAL GENERAL NOTES
<br />A. SPRINKLER CONTRACTOR 15 RESPONSIBLE FOR COORDINATION WITH MECHANICAL AND ELECTRICAL
<br />TRADE5.5PRINKLER CONTRACTOR SHALL OBTAIN SHEET METAL SHOP DRAWINGS AND DE516N SPRINKLER
<br />SYSTEM (INCLUDING MODIFICATION OF EXISTING BRANCH PIPING AND MAINS) TO AVOID DUGTWORK
<br />CONFLICTS.
<br />B. MECHANICAL CONTRACTOR SHALL VISIT 51TE PRIOR TO BIDDING PROGE55 AND FIELD VERIFY EXISTING
<br />CONDITIONS. CONTRACTOR SHALL TAKE ALL INTERFERENCES INTO CONSIDERATION. PROVIDE ALL
<br />NEGE95ARY OFFSETS OR TRANSITIONS WITH EQUIVALENT AREAS TO MATCH DUCT SIZES AS INDICATED ON
<br />0RAWING5.
<br />C. ROOF C IRB5 SHALL BE GOMPATIBLE WITH ROOFING SYSTEM AND 54ALL MATCH ROOF SLOPE IN ORDER
<br />THAT EQUIPMENT SITS DEAD LEVEL.
<br />D. PATCHING OF ROOF SHALL BE BY OWNER'S ROOFING CONTRACTOR AND PAID FOR BY THIS GONTRACTOR.
<br />E. CONTRACTOR SHALL BE FAMILIAR WITH OWNER'S STANDARDS, RULES AND RE6ULATION5. ALL OWNER'S
<br />CRITERIA SHALL BE COMPLIED KITH AND INCLUDED IN THIS BID.
<br />F. MAINTAIN ALL MANUFACTURER'S RECOMMENDED SERVICE CLEARANCES FOR ALL EQUIPMENT.
<br />G. ALL CEILING DIFFUSERS SHALL HAVE MANUAL VOLUME DAMPERS IN 0ORRE5PONDIN6 SUPPLY AIR RUJOUT5.
<br />H. COORDINATE LOCATION OF ENERGY MANAGEMENT SYSTEM EQUIPMENT WITH OWNER PRIOR TO ROUGH -IN.
<br />I. MECHANICAL CONTRACTOR TO PROVIDE 12' HIGH NUMBER PLATES WITH THE SPECIFIC RTU # ON THE
<br />CENTRAL PANEL DOOR AND SIDE WITH THE 015GONNEGT 5WITCH IN A V15115LE LOCATION PER R055 PROTO
<br />SHEET AI.I.
<br />J. ALL DUGTWORK SHALL BE INSTALLED TIGHT TO UNDERSIDE OF ROOF STRUCTURE OR A5 HIGH A5
<br />POSSIBLE TO AVOID 0136TRUGTION5.
<br />K. WAG DUGTWORK SHALL BE FA13RIGATED AND ERECTED IN AC.CORDANGE KITH ASHRAE AND LATEST
<br />5MAGNA STANDARDS. PROVIDE TURNING VANES AND ALL ELBOW5.
<br />L. ALL SUPPLY, RETURN AND EXHAUST BRANCH DUCTWORK SHALL. HAVE MANUAL VOLUME DAMPERS IN
<br />GORRE5PONDIN6 RUNOUTS NEAR GONNEGTION TO MAIN DUCT.
<br />M. NO THERM05TATS ARE TO BE LOGATED OVER HEAT PRODUCING EQUIPMENT.
<br />N. SPRINKLER CONTRACTOR SHALL MODIFY EXISTING SPRINKLER SYSTEM TO AGGOMMIMATE NEW
<br />DUGTWORK, LIGHTING AND PARTITION LAYOUTS. REFER TO SPECIFICATIONS FOR DETAILS.
<br />O. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, LICENSES, DOCUMENTS AND SERVICES
<br />RELATED TO INSTALLATION OF THE WORK.
<br />P. CONTRACTOR SHALL PAINT INTERIOR OF ALL DUCTS V151BLE FROM FLOOR FLAT BLACK.
<br />Q. CONTRACTOR SHALL OBTAIN, BECOME FAMILIAR WITH AND COMPLY TO ALL ROSS DRE55 FOR LE55
<br />PROTOTYPE CRITERIA DOCUMENTS AND DRAWINGS.
<br />R. CONTRACTOR SHALL GOMPLETE AIR BALANCE OF SYSTEM AND LOCK AND 5GREW SHEET METAL
<br />BALANGING DAMPERS IN P051TION PRIOR TO INSTALLATION OF HARD GEILINGS.
<br />S. ALL SUPPLY AND RETURN AIR DLIGTWORK SHALL BE INSTALLED A5 HIGH AS POSSIBLE.
<br />ROD REMOVABLE MOTOR COVER:
<br />ALUMINUM
<br />N. F. DISCONNECT SWITGH
<br />r�
<br />Li
<br />PER
<br />II L J
<br />FAN: BI, ALUMINUM WIND
<br />D RESISTANT CURB _
<br />ANCHORED TO STRUCTURE - --,
<br />FACTORY RECOMMENDATIONS
<br />FOR 150 MPH WINDS.
<br />ROOF
<br />ANA , \
<br />ALTERNATE LOCATION
<br />(VERIFY UPPER TRAPEZE
<br />LOAD GAPAGITY)
<br />TRAPEZE HANGERS
<br />ELBOW WITH
<br />AGOU5TIG
<br />AIRFOIL
<br />LINED DUCT
<br />TURNING VANES
<br />(5EE NOTE #1)
<br />BRANGH
<br />TAKE -OFF
<br />BRANCH
<br />TAKE -OFF
<br />REGTAN6ULARWMvV
<br />REGTAN6U..AR
<br />MVTO5'TO
<br />ROUND
<br />45.
<br />REGTANGULAR
<br />BRANCH
<br />TAKE -OFF
<br />SQUARE TO
<br />ROUND
<br />El""
<br />ROUND TO
<br />TRANSITION
<br />ROUND
<br />MYD
<br />FITTIN G
<br />30"
<br />PORPORT10NAL
<br />FLEXIBLE
<br />BRANCH TO
<br />DUCT DIFFU5�7
<br />SPLIT
<br />DUCT
<br />llllll
<br />MAX LENGTH = 48'
<br />MANUAL
<br />VOLUME
<br />NOTE:
<br />DASHED LINE INDICATES 1" INTERIOR
<br />DAMPER
<br />El
<br />ACOUSTIC LINING UNLESS OTHERWISE
<br />()
<br />NOTED. DUGT 51ZE 15 EXTERIOR
<br />AND INGUUDE5 LINING.
<br />TYPICAL DUCT TAKE -OFF DETAIL
<br />NE SCALE: NO
<br />MECHANICAL VENTILATION (OUTSIDE AIR) SCHEDULE
<br />DASHED LINE -
<br />INDIGATE5 1/2"
<br />ACOUSTIC LINING
<br />MOTOR: INTERNALLY
<br />PROTECTED.
<br />WIND COWLINS: ALUMINUM
<br />HURRIGANE TIE-DOV�pd STRAPS -
<br />ANCHORED TO CURB PER
<br />FACTORY RECOMMENDATIONS
<br />F 150 MPH WINDS.
<br />BACKMAFT DAMPER
<br />4 BUR6L.AR BARS
<br />EXHAUST AIR DUCT: METAL,
<br />NO INSULATION. SEAL
<br />AIR -TIGHT
<br />EXHAUST FAN DETAIL
<br />SCALE: NONE
<br />GRILLE WALL
<br />TYPE 6-2
<br />6RILLE WALL
<br />TYPE 6-1 �-
<br />ATD-1 SECTION VIEW
<br />NOTES FOR ALL AIR TRANSFER DUCTS:
<br />A. SEAL VOID BETWEEN WALL AND ALL DUCTHT PENETRATIONS AIRTIG.
<br />B. ACOUSTIC, LINE AIR TRANSFER DUCTS WITH 1/2'
<br />ACOUSTIC LINING. DUCT DIMENSIONS ARE EXTERIOR
<br />AND INCLUDE LINING.
<br />G. ALL GRILLES SHALL BE FL RN15HED WITH FRAMES
<br />GOMPATIBLE WITH WALL OR GEILING CONSTRUCTION.
<br />D. REFER TO PLANS FOR GRILLE AND DUCT SIZES.
<br />G-2, WALL
<br />GRILLE
<br />ATD-I
<br />C' 1,
<br />24x24
<br />ATDA PLAN VIEW
<br />AIR TRANSFER DUCT DETAILS
<br />SCALE: NONE
<br />APPROPRIATE CODE: 2010 FLORIDA MECHANICAL CODE
<br />EXHAUST AND VENTILATION FANS
<br />MARK
<br />SERVICE
<br />MAKE
<br />MODEL
<br />TYPE
<br />WHEEL
<br />DRIVE
<br />CFM
<br />EXT.
<br />RPM
<br />HP
<br />ELECTRICAL
<br />SONES
<br />CONTROLS
<br />ACCESSORIES
<br />WEIGHT
<br />ROOF
<br />STAT
<br />OPENING
<br />EF / 1
<br />RESTROOMS,
<br />ACME
<br />PV-120
<br />PRV
<br />CENT
<br />BELT
<br />800
<br />.375"
<br />1080
<br />1 / 4
<br />120 / 1 / 60
<br />6.1
<br />A
<br />1
<br />100 LBS
<br />13-1/2" X
<br />FITTING
<br />13-1 /2"
<br />EF / 2
<br />LOCKER RM,
<br />ACME
<br />PV-120
<br />PRV
<br />CENT
<br />BELT
<br />680
<br />.375"
<br />1080
<br />1 / 4
<br />120 / 1 / 60
<br />6.1
<br />A, B
<br />2
<br />100 LBS
<br />13-1/2" X
<br />EQUIPMENT
<br />13-1 /2"
<br />EF / 3
<br />ELECTRICAL
<br />ACME
<br />PV-120
<br />PRV
<br />CENT
<br />BELT
<br />800
<br />.375"
<br />1080
<br />1 / 4
<br />120 / 1 / 60
<br />6.1
<br />B
<br />1
<br />100 LBS
<br />13-1/2" X
<br />13-1/2"
<br />EF / 4
<br />JANITOR
<br />ACME
<br />VQ150
<br />CEILING FAN
<br />CENT
<br />--
<br />100
<br />.375"
<br />750
<br />--
<br />120 / 1 / 60
<br />1.8
<br />JA
<br />2
<br />130 LBS
<br />--
<br />EQUIVALENT BY GREENHECK, COOK, OR PENN.
<br />ACCESSORIES:
<br />1. N.F. DISCONNECT SWITCH, INSULATED ROOF CURB, BIRDSCREEN, LOW LEAKAGE GRAVITY
<br />BACKDRAFT DAMPER, FLEXIBLE DUCT COLLAR CONNECTION.
<br />2. N.F DISCONNECT SWITCH, MOTOR & BELT GUARD, FLEXIBLE INLET AND OUTLET DUCT
<br />CONNECTIONS, VIBRATION ISOLATION HANGERS, GRAVITY BACKDRAFT DAMPER.
<br />NOTES:
<br />WIND DATA
<br />DESIGN OF MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT RESTRAINT
<br />SYSTEMS FOR WIND FORCES SPECIFIC FOR THIS PROJECT LOCATION SHALL BE BY
<br />MASON INDUSTRIES, INC. OR EQUAL MANUFACTURER AND AS REQUIRED FOR ALL
<br />APPLICABLE CODES.
<br />WIND BASE SPEED = 130 MPH
<br />CONTROLS:
<br />A. CONTROLLED VIA EMS (REFER TO ELECTRICAL DRAWINGS FOR WIRING DIAGRAM).
<br />B. CONTROLLED VIA LINE VOLTAGE THERMOSTAT (REFER TO ELECTRICAL DRAWINGS
<br />FOR WIRING DIAGRAM).
<br />PACKAGED GAS / ELECTRIC HIGH EFFICIENCY AIR CONDITIONING UNITS - PROVIDED BY LANDLORD
<br />MARK
<br />SERVICE
<br />MAKE
<br />MODEL
<br />S.A.
<br />MIN.
<br />EXT.
<br />FAN
<br />HP
<br />HEATING
<br />COOLING CAPACITY
<br />REFRIG.
<br />SEER /
<br />FLA/MCA
<br />ELECTRICAL
<br />WEIGHT
<br />ACCESSORIES
<br />CFM
<br />O.A.
<br />STATIC
<br />RPM
<br />FUEL
<br />INPUT
<br />TOTAL / SENS
<br />EAT
<br />AMBIENT
<br />EER
<br />MOCP
<br />CFM
<br />MBH/STAGES
<br />MBH
<br />DB / WB
<br />DB
<br />AC / 1
<br />STOCK
<br />LENNOX
<br />LGHO6OH4E
<br />2000
<br />210
<br />1.0
<br />1110
<br />1
<br />GAS
<br />65 / 1
<br />57.5 / 47.0
<br />77 / 64
<br />105
<br />R-410A
<br />17.0 /
<br />14.8 / 18
<br />480 / 3 / 60
<br />1100 LBS
<br />1 - 2
<br />12.7
<br />25
<br />AC / 2
<br />OFFICE AREA
<br />LENNOX
<br />LGH048H4E
<br />1600
<br />175
<br />1.0
<br />1195
<br />3/4
<br />GAS
<br />65 / 1
<br />45.4 / 37.7
<br />77 / 64
<br />105
<br />R-410A
<br />17.0 /
<br />11.6 / 14
<br />480 / 3 / 60
<br />1000 LBS
<br />1 - 2
<br />12.8
<br />15
<br />AC / 3
<br />SALES
<br />LENNOX
<br />LGH156H4B
<br />5200
<br />1270
<br />1.0
<br />945
<br />5
<br />GAS
<br />169 / 1
<br />148.3 / 114.2
<br />80 / 67
<br />105
<br />R-41OA
<br />-- /
<br />30.4 / 35
<br />480 / 3 / 60
<br />2400 LBS
<br />1 - 2
<br />12.0
<br />40
<br />AC / 4
<br />FITTING/
<br />LENNOX
<br />LGH036H4E
<br />1200
<br />165
<br />1.0
<br />1110
<br />1/2
<br />GAS
<br />65 / 1
<br />33.2 / 27.4
<br />78 / 65
<br />105
<br />R-41OA
<br />17.0 /
<br />8.8 / 10
<br />480 / 3 / 60
<br />1000 LBS
<br />1 - 2
<br />TOILETS
<br />12.5
<br />15
<br />AC / 5
<br />SALES
<br />LENNOX
<br />LGH156H4B
<br />5200
<br />1270
<br />1.0
<br />945
<br />5
<br />GAS
<br />169 / 1
<br />148.3 / 114.2
<br />80 / 67
<br />105
<br />R-410A
<br />-- /
<br />30.4 / 35
<br />480 / 3 / 60
<br />2400 LBS
<br />1 - 2
<br />12.0
<br />40
<br />AC / 6
<br />SALES
<br />LENNOX
<br />LGH156H4B
<br />5200
<br />1270
<br />1.0
<br />945
<br />5
<br />GAS
<br />169 / 1
<br />148.3 / 114.2
<br />80 / 67
<br />105
<br />R-41OA
<br />-- /
<br />30.4 / 35
<br />480 / 3 / 60
<br />2400 LBS
<br />1 - 2
<br />12.0
<br />40
<br />AC / 7
<br />SALES
<br />LENNOX
<br />LGH18OH4B
<br />6000
<br />1460
<br />1.0
<br />970
<br />5
<br />GAS
<br />169 / 1
<br />176.0 / 167.8
<br />77 / 65
<br />105
<br />R-410A
<br />-- /
<br />36.8 / 42
<br />480 / 3 / 60
<br />2700 LBS
<br />1 - 2
<br />12.0
<br />45
<br />ACCESSORIES:
<br />1. EXISTING UNITS PROVIDED BY LANDLORD. COORDINATE CONTROL REQUIREMENTS WITH C&C AUTOMATION.
<br />2. AIR BALANCE CONTRACTOR TO BALANCE UNITS TO AIR QUANTITY LISTED ON PLAN.
<br />I. ALL WIRING TO BE PER MANUFACTURER'S
<br />FACTORY INSTALLED E WIRED
<br />WIRING DIAGRAM5.
<br />PHOTO-ELEGTRIG DUCT DETECTOR IN
<br />2. LOCATION OF DUCT DETECTOR TO BE
<br />SUPPLY AND RETURN AIR 5EGTION5 OF
<br />VERIFIED WITH LOCAL FIRE MARSHALL.
<br />UNIT TO SHUT DOWN UNIT ON ALARM.
<br />DETECTOR 15 TO BE INSTALLED IN AN
<br />SYSTEM 5EN50R #DHIOOAGDGLP
<br />ACGE55ABLE LOCATION.
<br />3. PROVIDE AUXILLARY CONTACTS FOR
<br />FIRE ALARM SYSTEM BY E.G.
<br />#18
<br />PROVIDE LABEL INDIGATING AG-X
<br />A550GIATED AG UNIT SERVED.
<br />INSTALL ADJACENT T-STAT OR o SYSTEM SENSOR #55K451
<br />IN LOCATION APPROVED BY COMBINATION COMBINATION ALARM, TROUBLE,
<br />FIRE MAR5HALL HORN d KEY TEST STATION SHIPPED
<br />L005E A5 ACCESSORY TO AG UNIT
<br />DUCT SMOKE DETECTOR WIRING DIAGRAM
<br />SCALE: NONE
<br />DRAW BAND
<br />WITH SEALAW
<br />STORM GOLD
<br />ROOF GONE -
<br />4 FLA5HIN6
<br />FLUE THRU ROOF DETAIL
<br />SCALE: NOW
<br />RIEDERT VENT GAP.
<br />AINTAIN A MINIMUM OF 3'-0"
<br />BOVE ROOF AND 2'-0' ABO
<br />LL ELSE WITHIN 10'-O"
<br />REFER TO PLANS
<br />FOR CONTINUATION
<br />AND 51ZE
<br />NOTE:
<br />ROUTE FLUE TO
<br />AVOID ROOF JOISTS
<br />GRILLES AND DIFFUSERS
<br />MARK
<br />MAKE
<br />MODEL
<br />DESCRIPTION
<br />FINISH
<br />MATERIAL
<br />FRAME
<br />DAMPER
<br />REMARKS
<br />CD / 1
<br />TITUS
<br />PCs
<br />PERF. DIFFUSER WITH
<br />WHITE
<br />STEEL
<br />24" x 24"
<br />YES
<br />ROUND NECK
<br />PATTERN CONTROL
<br />LAY -IN
<br />CD / 2
<br />TITUS
<br />TDC
<br />4 WAY THROW FIXED BLADE
<br />WHITE
<br />STEEL
<br />SURFACE
<br />YES
<br />ROUND NECK, 1BX18
<br />SUPPLY DIFFUSER
<br />FULL FACE DIFFUSER
<br />CD / 3
<br />ACCUTHERM
<br />TF-HC
<br />SELF-CONTAINED VAV TERMINAL
<br />WHITE
<br />STEEL
<br />TO MATCH CLG
<br />YES
<br />ROUND NECK. ROOMS: FITTING ROOM FOYER, MEN'S
<br />AND TERMOSTAT DIFFUSER
<br />CONSTRUCTION
<br />FITTING ROOM, LOCKER ROOM, CASH OFFICE.
<br />CD / 4
<br />TITUS
<br />TMRA
<br />ROUND SUPPLY DIFFUSER
<br />WHITE
<br />STEEL
<br />SURFACE
<br />YES
<br />ROUND NECK
<br />W/ ADJUSTABLE INNER CONES
<br />SR / 1
<br />TITUS
<br />30ORL
<br />DOUBLE DEFLECTION LONG FRONT
<br />WHITE
<br />STEEL
<br />SURFACE
<br />YES
<br />AG-15
<br />BLADE WALL REGISTER
<br />G / 1
<br />TITUS
<br />PAR
<br />PERFORATED RETURN
<br />WHITE
<br />STEEL
<br />LAY -IN
<br />NO
<br />GRILLE
<br />G / 2
<br />TITUS
<br />30RL
<br />HEAVY DUTY
<br />WHITE
<br />STEEL
<br />TO MATCH CLG OR
<br />NO
<br />BAR GRILLE
<br />WALL CONSTRUCTION
<br />ER / 1
<br />TITUS
<br />30RL
<br />HEAVY DUTY
<br />WHITE
<br />STEEL
<br />SURFACE
<br />NO
<br />BAR GRILLE
<br />SR / 1
<br />TITUS
<br />30ORS
<br />DOUBLE DEFLECTION
<br />WHITE
<br />STEEL
<br />SURFACE
<br />YES
<br />WALL REGISTER
<br />NOTE: NO SUBSTITUTIONS PERMITTED FOR GRILLES AND DIFFUSERS.
<br />REMARKS: APPLY TO ALL DEVICES UNLESS SPECIFICALLY NOTED OTHERWISE.
<br />A. SUBMITTALS MUST IDENTIFY DIFFUSER LOCATION BY ROOM NUMBER, TYPE, AND CEILING CONSTRUCTION.
<br />B. ALL FRAME TYPES SHALL BE COMPATIBLE WITH ADJACENT CONSTRUCTION. REFER TO ARCHITECTURAL PLANS FOR CONSTRUCTION DETAILS.
<br />MANUAL VOLUME DAMPERS
<br />MARK
<br />MAKE
<br />MODEL
<br />DESCRIPTION
<br />MATERIAL
<br />REMARKS
<br />MVD / 1
<br />METROPOLITAN
<br />RECT.-
<br />CABLE OPERATED
<br />GALV. STEEL
<br />OUTSIDE THE AIR STREAM INSTALLATION
<br />AIR TECHNOLOGY
<br />RT-200
<br />REMOTE CONTROL
<br />FOR SQUARE CEILING DIFFUSERS OR GRILLES WITH
<br />ROUND -
<br />MANUAL BALANCING
<br />BALANCING DAMPER INSTALLED AT AN
<br />RT-250
<br />DAMPER
<br />INACCESSIBLE CONCEALED LOCATION, NOTE 1
<br />NOTES:
<br />1. LOCATE DAMPER REMOTE ADJUSTMENT TIP IN CEILING ADJACENT TO CORRESPONDING DIFFUSER OR GRILLE WITH 1" MINI CEILING CUP.
<br />MECHANICAL VENTILATION (OUTSIDE AIR) SCHEDULE
<br />Room Name
<br />ROOM AREA (ft2)
<br />CLASSIFICATION
<br />CFM / FIXTURE
<br />(2009 IMC TABLE 403.3)
<br />NO. OF FIXTURES
<br />REQUIRED
<br />EXHAUST
<br />DESIGN
<br />EXHAUST
<br />MEN
<br />115
<br />TOILET
<br />70 CFM/FIXTURE
<br />2
<br />140
<br />200
<br />WOMEN
<br />125
<br />TOILET
<br />71 CFM/FIXTURE
<br />2
<br />140
<br />200
<br />MEN FITTING
<br />150
<br />FIT nNG ROOM
<br />0.25 CFM/SQ FT
<br />38
<br />200
<br />WOMEN FITTING
<br />345
<br />FITTING ROOM
<br />0.25 CFM SQ FT
<br />86
<br />200
<br />ROOM NAME
<br />ROOM AREA (ft2)
<br />CLASSIFICATION
<br />OUTDOOR AIR
<br />PRIMARY
<br />AIRFLOW
<br />(Vpz)
<br />Multiple Zone System
<br />REQUIRED
<br />DESIGN
<br />CALCULATED
<br /># OF PEOPLE
<br />IN AREA
<br />(Ps)
<br />CFM/PERSON
<br />PER TABLE
<br />(Table 403.3)
<br />(R)
<br />CFM/ft2
<br />(Ra)
<br />(Table 403.3)
<br />Net Area)
<br />CFM1
<br />(Rp*Pz)
<br />CFM2
<br />(Ra*Az)
<br />REQUIRED
<br />O.A.
<br />(Vbz=
<br />R Pz+RaAz
<br />ZONE AIR DIST.
<br />EFFECTIVENESS
<br />Ez
<br />(Table 403.3.1.2)
<br />ZONE O.A.
<br />RATE
<br />(Voz=
<br />Vbz Ez)
<br />PRIMARY O.A.
<br />FRACTION
<br />(Voz/Vpz)
<br />SYSTEM
<br />VENTILATION
<br />EFFICIENCY (Ev)
<br />(Table 403.3.2.3.2)
<br />OCCUPANT
<br />DIVERSITY
<br />(D=Ps/Pz)
<br />UNCORRECTED
<br />O.A. INTAKE
<br />(Vou=D(RpPz)
<br />+RaAz
<br />O.A.
<br />FLOW RATE
<br />(Vot=Vou/Ev)
<br />CFM
<br />O.A.
<br />FLOW RATE
<br />(CFM)
<br />SYSTEM
<br />GROSS
<br />NET (Az)
<br />PEOPLE PER
<br />1000 ft2
<br />Net Area)
<br />NO.
<br />OF OCCUR
<br />(Pz
<br />RECEIVING
<br />1400
<br />1400
<br />Storage rooms
<br />0
<br />0
<br />0
<br />0
<br />0.12
<br />0
<br />168
<br />168
<br />0.8
<br />210
<br />210
<br />210
<br />AC-1
<br />MANAGER
<br />100
<br />100
<br />Offices ace
<br />5
<br />1
<br />1
<br />5
<br />0.06
<br />5
<br />6
<br />11
<br />0.8
<br />14
<br />330
<br />0.04
<br />CASH
<br />60
<br />60
<br />Office space
<br />5
<br />1
<br />1
<br />5
<br />0.06
<br />5
<br />4
<br />9
<br />0.8
<br />12
<br />190
<br />0.06
<br />EQUIP
<br />45
<br />45
<br />Storage rooms
<br />0
<br />0
<br />0
<br />0
<br />0.12
<br />0
<br />5
<br />6
<br />0.8
<br />8
<br />25
<br />0.32
<br />BREAKROOM
<br />280
<br />280
<br />Conference/meeting
<br />50
<br />14
<br />14
<br />5
<br />0.06
<br />70
<br />17
<br />87
<br />0.8
<br />109
<br />580
<br />0.19
<br />OFFICE HALL
<br />65
<br />65
<br />Corridors
<br />0
<br />0
<br />0
<br />0
<br />0.06
<br />0
<br />4
<br />4
<br />0.8
<br />5
<br />100
<br />0.05
<br />BATH HALL
<br />145
<br />145
<br />Corridors
<br />0
<br />0
<br />0
<br />0
<br />0.06
<br />0
<br />9
<br />9
<br />0.8
<br />12
<br />100
<br />0.12
<br />Totals
<br />80
<br />45
<br />Max Z 1
<br />0.32
<br />0.8
<br />1
<br />125
<br />157
<br />175
<br />AC-2
<br />SALES 4
<br />520
<br />520
<br />Sales
<br />15
<br />8
<br />8
<br />7.5
<br />0.12
<br />60
<br />62
<br />123
<br />0.8
<br />154
<br />450
<br />0.34
<br />FITTING FOYER
<br />108
<br />108
<br />Corridors
<br />0
<br />0
<br />0
<br />0
<br />0.06
<br />0
<br />6
<br />7
<br />0.8
<br />9
<br />140
<br />0.06
<br />Total,
<br />60
<br />69
<br />Max Z 1
<br />0.34
<br />0.8
<br />1
<br />129
<br />162
<br />165
<br />AC-4
<br />SALES 3,5,6,7 18025 18025 Sales 15 271 271 7.5 0.12 2033 2163 4196 0.8 5245 5245 5270 AC-3, 5, 6, 7
<br />GONTRAGTOR MU5T \/ERIFY
<br />ALL GLEARANGE5 AND
<br />DIMEN51ON5 IN FIELD
<br />mcg architecture
<br />® 216. M1551 p 216.520.107
<br />7100 E Pbmi Vft N, &ft 3M i28rda A OH 44131
<br />Seal:
<br />®®®,rrrl11/11/��I
<br />s ®
<br />U_ v' g'�13+ ® Q
<br />OD
<br />"
<br />0 p®�� �
<br />C)
<br />X-3
<br />I- 0 o
<br />a
<br />�%
<br />gA " �� °
<br />�
<br />• e e e ® �yy��ai®
<br />v �
<br />A Project for:
<br />Client:
<br />W
<br />H
<br />Z
<br />W
<br />U
<br />Z
<br />U a Ln c,
<br />co
<br />CD O J J
<br />m �
<br />Z � J J
<br />ILw W a J
<br />A CCc�=
<br />o 00
<br />aco Cn CO
<br />I in N.
<br />-� w
<br />Z
<br />3:
<br />ROSS STORES, INC.
<br />4440 ROSEWOOD DRIVE
<br />PLEASANTON, CA 94588
<br />Revisions:
<br />BID/PERMIT
<br />02-14-13
<br />No. Description
<br />Date
<br />Project No.:
<br />11.594.01
<br />Drawn By:
<br />J P U
<br />Reviewed By:
<br />MAB
<br />Scale:
<br />AS NOTED
<br />Date:
<br />01-28-2013
<br />Filename:
<br />Sheet Title:
<br />MECHANICAL
<br />SCHEDULES AND
<br />DETAILS
<br />MECHANICAL SCHEDULES AND DETAILS
<br />i..l h. i -.! t.�'i 1,u 1 4 11b.;.l 1 11 1, ,.
<br />McHENRY & ASSOCIATES, INC.
<br />CONSULTING ENGINEERS
<br />25001 EMERY ROAD, SUITE #200
<br />WARRENSVILLE HEIGHTS, OHIO 44128
<br />PHONE: 216-292-4696
<br />FAX: 216-292-5874
<br />SCALE Email: MAIL®MCHENRYASSOCIATES.COM
<br />1/8" = 1' 0" FLORIDA BUSINESS #0005282
<br />Sheet #:
<br />M2
<br />O MCG ARCHITECTS 2013 ALL RIGHTS RESERVED
<br />
|