ELECTRICAL SPECIFICATIONS ( ANY REFEENCES IN THE MEP DOCUMENT TOLI EMUSPPROVID MENT D BY 0 HERS SHALL BE IGNORAND MATERIALS SHALL BEIEDDUNLEDSS THIS REF INSTLLEDB ENCOE IS ON R. HE A CHITECTURAL RESPONSIBILITIES SCHEDULE.T )
<br />16010 WORK INCLUDED:
<br />1.1 CONTRACTOR SHALL PROVIDE THE FOLLOWING;
<br />a. LABOR
<br />b. SUPPLIES
<br />c. MATERIALS
<br />d. SHOP DRAWINGS
<br />e. PERMITS AND INSPECTION FEES
<br />f. CERTIFICATION OF FINAL INSPECTION AND APPROVAL
<br />g, ONE YEAR GUARANTEE
<br />1.2 CONTRACTOR SHALL PERFORM THE FOLLOWING;
<br />a. INSTALLATION OF ALL ELECTRICAL EQUIPMENT.
<br />b. COORDINATE WITH OTHER TRADES OF ELECTRICAL EQUIPMENT INSTALLATION
<br />c. MATERIAL PROTECTION DURING CONSTRUCTION.
<br />d. TEST OF ENTIRE SYSTEM IN PRESENCE OF OWNER OR HIS REPRESENTATIVE
<br />AND CORRECT ANY DEFICIENCIES DISCOVERED.
<br />e. COORDINATION OF ELECTRICAL SERVICE AND METERING WITH LOCAL POWER
<br />COMPANY.
<br />f. COORDINATION OF TELEPHONE SERVICE WITH LOCAL TELEPHONE COMPANY.
<br />1.3 GOVERNING CODES SHALL BE THE FOLLOWING;
<br />a. LOCAL MUNICIPALITY ELECTRICAL CODE.
<br />b. PER LATEST NATIONAL ELECTRICAL CODE (NEC)
<br />c. UTILITY COMPANY REGULATIONS
<br />d. AMERICANS WITH DISABILITY ACT
<br />e. CURRENT APPLICABLE BUILDING CODES
<br />f. LOCAL BUILDING CODES AND ORDINANCES
<br />g. THE NATIONAL MANUFACTURER'S ASSOCIATION STANDARDS (NEMA)
<br />h. UNDERWRITER LABORATORIES INCORPORATED STANDARD(S)
<br />i. AMERICAN NATIONAL STANDARD INSTITUTE (ANSI)
<br />j. THE MANUFACTURER'S RECOMMENDATION
<br />1.4 MATERIAL WILL BE;
<br />a. NEW
<br />b. UL LISTED
<br />16110 RACEWAYS
<br />1.1 USED AND TYPES
<br />a. SERVICE ENTRANCE - RIGID STEEL
<br />b. FEEDERS - RIGID STEEL EXCEPT ABOVE 8'-0" AND INDOOR
<br />THEN EMT
<br />c. BRANCH CIRCUIT, TELEPHONE OR COMMUNICATIONS -
<br />EMT
<br />d. IN EARTH OR CONCRETE - SCHEDULE 40 PVC
<br />e. RECESSED LIGHTING FIXTURES - FLEXIBLE STEEL CONDUIT (SHORT BUT
<br />MAXIMUM 72")
<br />f. OUTDOOR FINAL CONNECTION TO EQUIPMENT OR IN WET LOCATIONS - LIQUID
<br />TIGHT FLEXIBLE STEEL CONDUIT (MAXIMUM 36")
<br />g. ALL RACEWAYS, UNLESS SPECIFICALLY INDICATED TO
<br />BE EXPOSED, SHALL
<br />BE CONCEALED IN WALLS, CEILING OR FLOORS.
<br />h. PAINT ALL EXPOSED RACEWAYS COLOR AS DIRECTED
<br />BY ARCHITECT.
<br />1.2 CONDUIT BUSHING,
<br />a. PROVIDE INSULATED CONDUIT BUSHING AT EACH END
<br />OF EVERY CONDUIT
<br />RUN.
<br />16120 WIRES AND CABLES 600 VOLTS
<br />1.1 COLOR CODING 208Y/120V 240-DELTA/120V
<br />480Y/277V
<br />PHASE A BLACK BLACK
<br />BROWN
<br />PHASE B BLUE ORANGE
<br />YELLOW
<br />PHASE C RED RED
<br />ORANGE
<br />NEUTRAL WHITE WHITE
<br />WHITE
<br />GROUND GREEN GREEN
<br />GREEN
<br />1.2 INSULATED, THHN, THWN, XHHW 75 DEGREE C.
<br />1.3 PROVIDE COPPER WIRING UNLESS ALUMINUM IS SPECIFICALLY SHOWN ON THE
<br />DRAWINGS. WHEN ALUMINUM CONDUCTORS ARE UTILIZED - PROVIDE COMPRESSION
<br />LUG FITTINGS.
<br />1.4 FIXTURE WIRE, 600 VOLTS, 200 DEGREE C. #14 AWG MINIMUM STRANDED,
<br />TINNED COPPER NH SILICONE RUBBER INSULATION AND AN OVERALL JACKET OF
<br />GLASS BRAID, AND RATED AS NEC TYPE 'SF-2'
<br />16130 BOXES
<br />1.1 ATTACHED SECURELY TO BUILDING CONSTRUCTION OR SUPPORT FROM SAME
<br />1.2 MASONRY BOXES SHALL BE RACO OR STEEL CITY
<br />1.3 EXPOSED BOXES SHALL BE CAST TYPE SIMILAR TO CROUSE HINDS TYPE FS
<br />1.4 ALL OTHERS SHALL BE STAMPED STEEL
<br />16140 WIRING DEVICES
<br />1.1 RECEPTACLES
<br />a. DUPLEX - 20 AMPS, 125V. AC GROUNDED UNO
<br />b. SINGLE - 20 AMPS, 125V. AC GROUNDED UNO
<br />c. COORDINATE COLOR OF DEVICE WITH ARCHITECT
<br />d. COORDINATE FINISH AND COLOR OF COVERPLATE WITH ARCHITECT
<br />1.2 WALL SWITCHES
<br />a. SINGLE POLE - 20 AMPS, SINGLE THROW, QUIET TYPE, GROUNDED
<br />b. COORDINATE COLOR OF DEVICE WITH ARCHITECT
<br />c. COORDINATE FINISH AND COLOR OF COVERPLATE WITH ARCHITECT
<br />1.3 TIME CLOCK
<br />a. FURNISH AND INSTALL A TWENTY FOUR (24), SEVEN (7) DAY TIME CLOCK
<br />INCLUDING ALL INTEGRAL WIRING AND LOAD BALANCING (PANEL) FOR CONTROLLING
<br />THE STOREFRONT SIGN AND SHOW WINDOW LIGHTING, WHETHER SUCH WORK IS OR
<br />IS NOT SHOWN ON PLANS OR SPECIFICATIONS
<br />16170 PANELBOARDS
<br />1.1 PANELBOARDS SHALL HAVE, BUT NOT BE LIMITED TO THE FOLLOWING;
<br />a. THREE PHASE, 4 WIRE, COPPER BUSING, NEMA 1 ENCLOSURE FOR INDOOR,
<br />NEMA 3R FOR OUTDOOR.
<br />b. GROUND BUS WITH SET SCREW CONNECTIONS
<br />c. SOLID NEUTRAL, 100% RATED WITH SET SCREW CONNECTION
<br />d. SWITCH RATED BOLT -ON BREAKERS
<br />e. TYPE WRITTEN DIRECTORY
<br />f. PLAQUE, BLACK WITH 1" HIGH WHITE LETTERS TO INDICATE PANEL NAME
<br />g. SQUARE D, EATON, GENERAL ELECTRIC OR SIEMENS
<br />16190 GROUNDING
<br />1.1 FEEDERS AND BRANCH CIRCUITS
<br />a. PROVIDE A GREEN INSULATED GROUND CONDUCTOR, SIZED PER THE NEC IN
<br />EACH RACEWAY
<br />16200 LIGHTING FIXTURES
<br />1.1 COORDINATE FIXTURE TRIMS WITH CEILING IN/ON WHICH IT IS BEING INSULATED.
<br />1.2 MATCH VOLTAGE OF FIXTURE TO CIRCUIT TO WHICH FIXTURE IS SHOWN
<br />CONNECTED
<br />1.3 PROVIDE LOW TEMPERATURE HIGH EFFICIENCY ELECTRONIC BALLASTS IN
<br />FLUORESCENT FIXTURES
<br />1.4 PROVIDE THERMAL OVERLOAD PROTECTION IN BOTH FLUORESCENT AND
<br />INCANDESCENT FIXTURES
<br />1.5 NARRATIVE DESCRIPTION IN LIGHTING FIXTURE SCHEDULE TAKES PRECEDENCE
<br />OVER CATALOG NUMBER
<br />1.6 PROVIDE INTEGRAL DISCONNECTING MEANS FOR ALL FLUORESCENT FIXTURES
<br />PER THE NEC
<br />16210 EXISTING CONDITION
<br />1.1 VISIT SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS IN AND AROUND
<br />THE BUILDINGS
<br />16220 TELEPHONE SERVI
<br />1.1 SAFETY SWITCHES SHALL BE HEAVY DUTY TYPE, 600 OR 250 VOLT, WITH
<br />NUMBER OF POLES REQUIRED. FUSED SAFETY SWITCHES SHALL BE QUICK -MAKE,
<br />QUICK -BREAK MECHANISM, VISIBLE BLADES WITH REJECTION TYPE FUSE CLIPS AND
<br />NEMA CLASS "LPJ" FUSES, THE SWITCHES SHALL BE NEMA 313 FOR OUTDOOR. ALL
<br />SWITCHES SHALL BE LOCKABLE.
<br />16270 FIRE ALARM SYSTEM - AS APPLICABLE, CHECK REQUIREMENTS AGAINST
<br />ARCHITECTURAL DRAWINGS.
<br />'FIRE ALARMZSPRINKLER DRAWINGS, WHERE NECESSARY, WILL BE SUBMITTED
<br />SEPARATELY UNDER A SEPARATE PERMIT BY A LICENSED FIRE PROTECTION
<br />'ONTRACTOR - DESIGN BUILD).
<br />1.1 FURNISH AND INSTALL FIRE ALARM POWER BOOSTER TO EXISTING BUILDING
<br />FIRE ALARM PANEL AS INDICATED ON DRAWINGS. THE FIRE ALARM SYSTEM NEW
<br />DEVICES SHALL BE FORMALLY PLANNED BY A LICENSED FIRE ALARM CONTRACTOR
<br />WHO SHALL SUBMIT SIGNED AND SEALED DRAWINGS, IF REQUIRED FOR PERMIT, AND
<br />SHALL SUPERVISE AND CERTIFY THE INSTALLATION. FIRE ALARM SYSTEM
<br />CONTRACTOR SHALL REVIEW THE MECHANICAL DRAWINGS AND PROVIDE AND
<br />INSTALL DUCT SMOKE DETECTORS AS REQUIRED IN THE STANDARD MECHANICAL
<br />CODE AND BY THE LOCAL FIRE MARSHALL. DESIGN SHALL COMPLY WITH NFPA 72.
<br />PROVIDE VOCE EVACUATION MODULES WITH ALL NECESSARY APPURTENANCES.
<br />1.2 REMOTE ANNUNCIATOR
<br />PROVIDE AN ALPHANUMERIC ANNUNCIATOR WITH INTEGRAL ALPHANUMERIC
<br />DISPLAY, SYSTEM CONTROL/TEST SWITCHES, KEY OPERATED ENABLED SWITCH AND
<br />BACK BOX. COORDINATE LOCATION WITH AUTHORITY HAVING JURISDICTION PRIOR
<br />TO ROUGH -IN.
<br />1.3 MANUAL STATIONS
<br />PROVIDE ANALOG ADDRESSABLE MANUAL STATIONS WITH PROTECTIVE COVERS
<br />(WITH INTEGRAL HORN AND 9V BATTERY) AS SHOWN ON THE PLANS.
<br />1.4 SYSTEM SMOKE DETECTORS
<br />PROVIDE ANALOG ADDRESSABLE PHOTOELECTRIC SMOKE DETECTORS WITH
<br />BASES AS SHOWN, SUPPLEMENT AS DIRECTED BY BUILDING OFFICIAL.
<br />1.5 DUCT MOUNTED SMOKE DETECTORS
<br />PROVIDE DUCT MOUNTED ANALOG ADDRESSABLE PHOTOELECTRIC SMOKE
<br />DETECTORS WITH SAMPLING TUBES AND ADDRESSABLE CONTROL RELAYS AS SHOWN
<br />ON THE PLANS AND AS REQUIRED TO COMPLY WITH THE MECHANICAL CODE.
<br />WHERE IN -DUCT SMOKE DETECTORS ARE INSTALLED IN CONCEALED LOCATIONS
<br />MORE THEN 10 FEET ABOVE THE FINISHED FLOOR OR N ARRANGEMENT WHERE THE
<br />DETECTORS ALARM OR SUPERVISORY INDICATOR IS NOT VISIBLE TO RESPONDING
<br />PERSONNEL, THE DETECTOR SHALL BE PROVIDED WITH REMOTE ALARM OR
<br />SUPERVISORY INDICATION IN A LOCATION ACCEPTABLE TO THE AUTHORITY HAVING
<br />JURISDICTION. ADDITIONALLY, LABEL REMOTE ALARMS TO INDICATE BOTH THEIR
<br />FUNCTION AND THE AIR HANDLING UNIT(S) ASSOCIATED WITH EACH DETECTOR.
<br />1.6 ADDRESSABLE MONITOR MODULES
<br />PROVIDE ADDRESSABLE MONITOR MODULES AS SHOWN ON THE PLANS TO
<br />MONITOR SPRINKLER FLOW SWITCHES, SPRINKLER VALVES, SUPERVISORY SWITCHES
<br />AND SPRINKLER FIRE PUMP (AS REQUIRED)
<br />1.7 ADDRESSABLE CONTROL MODULES
<br />PROVIDE ADDRESSABLE CONTROL MODULES AS REQUIRED FOR INTERFACE WITH
<br />THE ELEVATOR CONTROLS, ELEVATOR POWER CONTROLS AND HVAC CONTROLS (AS
<br />REQUIRED)
<br />1.8 ALARM SIGNALS
<br />PROVIDE 15/75-WW SPEAKER/STROBE ALARM SIGNALS AS SHOWN ON THE
<br />PLANS FOR ALL PUBLIC AREAS. PROVIDE 15/75-WW STROBE VISUAL ALARM
<br />SIGNALS FOR ALL STROBE ONLY LOCATIONS AS SHOWN ON THE PLANS, 110
<br />CANDELA.
<br />1.9 WIRING
<br />WIRING SHALL BE CONCEALED IN CONDUIT. PROVIDE WIRING AND CONDUIT AS
<br />DIRECTED BY THE MANUFACTURER'S AUTHORIZED DISTRIBUTOR.
<br />1.10 APPLICABLE CODES AND STANDARDS
<br />ALL EQUIPMENT SHALL BE UL LISTED FOR ITS INTENDED USE.
<br />ALL RACEWAYS AND WIRING SHALL BE INSTALLED IN COMPLIANCE WITH NFPA
<br />STANDARD 70 (NATIONAL ELECTRIC CODE)
<br />NFPA STANDS 71 AND 72
<br />NFPA 101 (LIFE SAFETY CODE)
<br />AMERICANS WITH DISABILITIES ACT (ADA)
<br />STANDARD BUILDING CODE (SBC)
<br />APPLICABLE LOCAL AND NATIONAL CODES AND AUTHORITIES HAVING
<br />JURISDICTION
<br />1.11 SYSTEM OPERATION
<br />ACTUATION OF ANY FIRE ALARM INITIATING DEVICE SHALL IMMEDIATELY CAUSE
<br />THE FOLLOWING ACTIONS TO BE INITIATED
<br />a. IDENTIFY THE TYPE OF ALARM, SPECIFIC DEVICE AND LOCATION ON THE
<br />BACK LIT LCD DISPLAY AT THE BUILDING FIRE ALARM CONTROL PANEL AND AT THE
<br />REMOTE ANNUNCIATORS
<br />b. CAUSE THE SYSTEM ALARM LED TO FLASH AT THE FIRE ALARM CONTROL
<br />PANEL
<br />c. CAUSE ALL SYSTEM HORNS TO SOUND
<br />d. CAUSE ALL VISUAL ALARMS SIGNALS TO FLASH
<br />e. ACTIVATE THE DIGITAL COMMUNICATOR TO REPORT THE TYPE OF ALARM
<br />AND LOCATION TO THE REMOTE CENTRAL MONITORING STATION. COORDINATE
<br />CONNECTIONS WITH OWNER'S REPRESENTATIVE.
<br />f. ACTIVATE SIGNALS TO THE BUILDING DOOR LOCK CONTROLS TO DEACTIVATE
<br />LOCKS
<br />g. ACTIVATE SIGNALS TO THE HVAC CONTROLS TO INITIATE SHUT DOWN OR
<br />REROUTING OF AIR HANDLING SYSTEMS
<br />1.12 ACTIVATION OF ANY SPRINKLER VALVE SUPERVISORY SWITCH SHALL
<br />AUTOMATICALLY
<br />a. CAUSE THE SYSTEM SUPERVISORY LED TO FLASH AND AN AUDIBLE
<br />INDICATOR TO SOUND AT THE CONTROL PANEL AND REMOTE ANNUNCIATOR
<br />b. IDENTIFY THE SUPERVISORY CONDITION, SPECIFIC DEVICE AND LOCATION ON
<br />THE BACK LIT LCD DISPLAY AT THE SYSTEM CONTROL PANEL AND THE REMOTE
<br />ANNUNCIATOR.
<br />1. LIGHTING LAYOUTS SHOWN ARE INTENDED TO INDICATE DESIRED FIXTURE
<br />LOCATIONS AND SWITCHING.
<br />2. COMPLY WITH THE LATEST VERSIONS OF ALL APPLICABLE NATIONAL, STATE AND
<br />LOCAL CODES.
<br />3. THE DIRECTIVE, IF ANY, OF THE BUILDING OFFICIAL SHALL TAKE PRECEDENCE
<br />OVER THIS DRAWING REGARDING LOCATION AND NUMBER OF EXIT AND EMERGENCY
<br />EGRESS LIGHTS.
<br />4. ALL FIXTURES TO BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS.
<br />5. ALL PENDANT HUNG FIXTURES SHALL BE SUPPORTED DIRECTLY FROM
<br />STRUCTURE ABOVE WITH NO. 9 GAGE WIRE OR APPROVED ALTERNATE SUPPORT
<br />WITHOUT USING CEILING SUSPENSION SYSTEM FOR DIRECT SUPPORT.
<br />6. ALL LIGHTING FIXTURES MUST BE SUPPORTED BY #12 GAUGE WIRE ATTACHED TO
<br />THE GRID MEMBERS WITHIN 3" OF EACH CORNER OF EACH FIXTURE.
<br />7. REFER TO DRAWING LIGHTING LEGEND FOR DETAIL INFORMATION ON LIGHTING.
<br />8. REFER TO DRAWING E3.0 FOR POWER AND PANEL SCHEDULE.
<br />9. GENERAL CONTRACTOR TO PROVIDE AND INSTALL ALL FIXTURES AND LAMPS,
<br />EXCEPT FOR THOSE LISTED AS EXISTING, IN THE LIGHT FIXTURE SCHEDULE.
<br />10. WHEN DIRECTED BY OWNER, GENERAL CONTRACTOR TO SALVAGE ALL 2'X4'
<br />LIGHT FIXTURES IN KITCHEN. RELAMP FIXTURES, CLEAN AND REINSTALL PER
<br />REFLECTED CEILING PLAN.
<br />11. ALL RACEWAYS IN MILLWORK SHALL BE RUN CONCEALED FROM VIEW.
<br />12. ROUTE CIRCUIT THROUGH SWITCH ON SWITCH BANK. COORDINATE LOCATION
<br />OF SWITCH BANK WITH OWNER.
<br />13. ELECTRICAL CONTRACTOR TO VERIFY LIGHTING FOR WALK IN COOLER &
<br />FREEZER. PROVIDE FIXTURE IF COOLER DOES NOT HAVE BUILT-IN LIGHT, OR
<br />COOLER LIGHTING IS NOT EXISTING. COORDINATE INSTALLED LOCATION WITH
<br />SUPPLIER.
<br />14. ALL DEDICATED CIRCUIT OUTLETS SHALL BE ORANGE.
<br />15. ALL 20 AMP 125 VOLT RECEPTACLES IN THE KITCHEN AREAS SHALL BE GFCI
<br />PROTECTED AND ACCESSIBLE.
<br />16. EXIT FIXTURES TO BE CIRCUITED BY UNSWITCHED LEG AND TO PROVIDE
<br />CONTINUOUS ILLUMINATION PER NEC 700-12(A) AND NFPA 101, LIFE SAFETY CODE
<br />17. PROVIDE DUAL LEVEL SWITCHING IN KITCHEN IN ACCORDANCE WITH IECC
<br />REQUIREMENTS. PROVIDE ALL LIGHTING WITH DUAL BALLAST FOR SEPARATE
<br />CONTROL OF INBOARD & OUTBOARD LAMPS.
<br />18. HOOD EQUIPMENT FROM VENDOR; ELECTRICAL PANELS ASSOCIATED WITH HOOD
<br />EQUIPMENT. COORDINATE WIRING & INSTALLATION OF EQUIPMENT WITH HOOD
<br />CONTRACTOR. ROUE CIRCUITS FOR EQUIPMENT UNDER HOODS THROUGH SHUNT
<br />TRIP. E.C. TO INTEGRATE HOOD ELECTRICAL SYSTEMS. SEE DETAIL ON HOOD
<br />DRAWINGS
<br />19. T.G.C. SHALL INSTALL A MINIMUM OF 3 OUTLETS IN THE DINING ROOM.
<br />LOCATION SHALL BE DETERMINED BY TENANT.
<br />20. FOR ADDITIONAL INSTALLATION INSTRUCTIONS SEE ARCHITECTURAL SHEETS.
<br />21. THE SCOPE OF THE ELECTRICAL WORK SHALL INCLUDE FURNISHING, INSTALLING
<br />AND TESTING ALL ELECTRICAL SYSTEMS FOR A COMPLETE AND FULLY OPERABLE
<br />INSTALLATION. COMPLY WITH THE LATEST VERSIONS OF ALL APPLICABLE NATIONAL,
<br />STATE AND LOCAL CODES.
<br />22. LOCATIONS OF EXISTING ELECTRICAL SYSTEMS, EQUIPMENT AND DEVICES SHALL
<br />BE VERIFIED IN THE FIELD BY THE TGC.
<br />23. POWER LAYOUTS SHOWN ARE INTENDED TO INDICATE DESIRED LOCATIONS.
<br />24. VERIFY ELECTRICAL REQUIREMENTS FOR ALL SPECIAL EQUIPMENT PRIOR TO ANY
<br />WORK BEING PERFORMED. PROVIDE ISOLATED GROUND WIRE PER EQUIP.
<br />MANUFACTURER'S INSTALLATION REQUIREMENTS. PROVIDE CONDUIT FOR MECHANICAL
<br />CONTROLS AS MAY BE REQUIRED BY CODE. ELECTRICAL CONTRACTOR SHALL
<br />COORDINATE WITH MECHANICAL CONTRACTOR AS TO LOCATION OF A/C UNITS AND
<br />EXHAUST FANS.
<br />25. ALL POWER CIRCUITS SHALL BE INSTALLED BY AN ELECTRICIAN LICENSED IN
<br />THE JURISDICTION OF THE PROJECT.
<br />26. ALL BUSSING AND WIRING SHALL BE COPPER, UNLESS EXPLICITLY NOTED
<br />ELSEWHERE IN THIS DOCUMENT SET.
<br />27. ELECTRICAL CONTRACTOR SHALL PROVIDE LEGIBLE LABELING OF ALL BREAKERS
<br />ON PANELBOARDS.
<br />28. ELECTRICAL CONTRACTOR TO SIZE AND PROVIDE ALL ELECTRICAL JUNCTION
<br />BOXES, PULL BOXES, AND CONVENIENCE OUTLETS.
<br />29. ELECTRICAL CONTRACTOR SHALL DETERMINE, ARRANGE FOR PROPER SERVICE
<br />AND METERS, FEES PAID BY E.C..
<br />30. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY POWER TO ROOF AND
<br />CONNECT ALL ROOF -MOUNTED EQUIPMENT.
<br />31. ELECTRICAL CONTRACTOR TO PROVIDE SERVICE DISCONNECTS.
<br />32. ELECTRICAL CONTRACTOR SHALL PROVIDE, AT EACH TELEPHONE JACK
<br />INDICATED, AN OUTLET BOX, CONDUIT AND TRIM. THE CONDUIT SHALL EXTEND
<br />ABOVE SUSPENDED CEILING. PROVIDE CONDUCTOR TELEPHONE WIRE AS REQUIRED
<br />TO EACH BOX. REMOTE UNITS & INSTALL DISCONNECTS CAD ALL A/C UNITS.
<br />33. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY POWER AND
<br />PERFORM FINAL CONNECTIONS TO EXTERIOR SIGNAGE.
<br />34. ELECTRICAL CONTRACTOR SHALL INSTALL & CONNECT THE ICE MACHINES.
<br />NEITHER THE TENANT'S GENERAL CONTRACTOR NOR ANY SUBCONTRACTOR IS TO
<br />START THE ICE MACHINE. A MANUFACTURER'S REPRESENTATIVE WILL INITIATE THE
<br />START UP OF ICE MACHINE.
<br />35. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO FURNISH & INSTALL
<br />CORDS & PLUGS AS REQUIRED FOR THE DISHWASHER, & ICE MACHINE.
<br />36. WHEN MAIN ELECTRICAL SERVICE IS PROVIDED BY THE LANDLORD, HIS
<br />OBLIGATIONS TERMINATE AT THE DISCONNECT. ALL PANELS, FEEDERS, ETC.
<br />REQUIRED FOR THE CONSTRUCTION OF THIS PROJECT SHALL BE FURNISHED &
<br />INSTALLED BY THE E.C.
<br />37. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH ALL
<br />TRADES AND VERIFY THAT ALL EQUIPMENT SHIPPED TO THE SITE IS COMPATIBLE
<br />WITH MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS PRIOR TO INSTALLATION OF
<br />SAID EQUIPMENT. IN THE EVENT OF ANY DISCREPANCIES, IMMEDIATELY CONTACT
<br />DESIGNER BEFORE PROCEEDING.
<br />38. ELECTRICAL CONTRACTOR TO INTERLOCK GREASE EXHAUST FANS, MAKE-UP AIR
<br />SUPPLY FANS AND ROOF -TOP UNITS, AS DESCRIBED ON SHEET MEP1.0.
<br />39. ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL LOCAL DISCONNECT
<br />SWITCH, MOUNTED INSIDE BUILDING FOR EXTERIOR SIGNAGE. PROVIDE TIME CLOCK
<br />FOR CONTROL OF EXTERIOR SIGN. JUNCTION BOX FOR EXTERIOR SIGNAGE SHALL BE
<br />MOUNTED ON THE EXTERIOR SPACE/FRAME. COORDINATE EXACT LOCATION AND
<br />REQUIREMENTS WITH SIGN VENDOR AND OWNER.
<br />40. STARERS & RELATED WIRING SHALL BE FURN'D & INSTD BY E.C. OVERLOAD
<br />LIMITS SHALL BE INSTALLED PER GIVEN NAMEPLATE DATA ON EQUIPMENT.
<br />STARTERS SHALL BE INSTALLED AS PER MANUFACTURER'S RECOMMENDATIONS.
<br />41. DISCONNECT SWITCHES SHALL BE FURN'D & INSTD BY E.C.
<br />42. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL UTILITY COMPANY FOR
<br />SERVICE AND TRANSFORMER REQUIREMENTS AND SHALL INCLUDE ALL WORK IN
<br />HIS/HER BID.
<br />43. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL UTILITY COMPANY & VERIFY
<br />SERVICE VOLTAGE AND SHALL REVISE & BALANCE PANELS AS REQUIRED.
<br />44. ELECTRICAL CONTRACTOR TO PROVIDE ELECTRICAL OUTLET FIRE PROTECTION
<br />PAD FOR ALL RECEPTACLES IN RATED WALLS AS MANUFACTURED BY PFP
<br />PARTNERS. APPLY TO BOXES AS INSTRUCTED BY MFR. TO PROVIDE RATING TO
<br />MEET RATING OF CORRESPONDING WALL.
<br />45. MOUNT RECEPTACLE ABOVE WINDOW FOR USE AT STOREFRONT.
<br />46. PROVIDE POWER TO JUNCTION BOX & CONNECT WIRE CORD DROP HEAT LAMPS
<br />THROUGH JUNCTION BOX.
<br />47. ELECTRICAL CONTRACTOR TO PROVIDE POWER FOR THE DISHWASHER ON A GFI
<br />BREAKER. COORDINATE LOCATION OF RECEPTACLE NH EQUIPMENT SUPPLIER.
<br />48. ELECTRICAL CONTRACTOR TO PROVIDE REMOTE RESET FOR RTU SMOKE
<br />DETECTORS.
<br />49. EMERGENCY PULL STATION SWITCH FOR HOOD, FURNISHED AND INSTALLED BY
<br />ANSUL CONTRACTOR.
<br />50. ELECTRICAL CONTRACTOR TO PROVIDE AND WIRE DISCONNECT & RECEPTACLE
<br />FOR RTUs/AHUs &CUs.
<br />51. ELECTRICAL CONTRACTOR SHALL WIRE THE DOOR HEAT 'TRACE' FROM ONE OF
<br />THE LEGS OF THE ELECTRICAL SERVICE FROM THE PANEL TO THE COOLER OR
<br />FREEZER.
<br />52. WHERE PORTIONS OF A CABLE RACEWAY OR SLEEVE ARE KNOWN TO BE
<br />SUBJECTED TO DIFFERENT TEMPERATURES AND WHERE CONDENSATION IS KNOWN TO
<br />BE AN ISSUE, AS IN COLD STORAGE AREAS OF BUILDINGS OR WHERE PASSING
<br />FROM THE INTERIOR TO THE EXTERIOR OF A BUILDING, THE RACEWAY OR SLEEVE
<br />SHALL BE FILLED WITH AN APPROVED MATERIAL TO PREVENT THE CIRCULATION OF
<br />WARM AIR TO COLDER SECTION OF THE RACEWAY OR SLEEVE PER NEC 300.7 (A).
<br />53. CONTRACTOR SHALL VERIFY AVAILABLE FAULT CURRENT WITH UTILITY COMPANY
<br />AND PROVIDE GEAR WITH A SCCR GREATER THAN AVAILABLE FAULT.
<br />DATA CABLE TERMINATION:
<br />ALL CABLE RUNS SHALL BE TERMINATED WITH A PUNCH -DOWN, OR "KEYSTONE"
<br />CAT-5E RJ45 JACK (PANDUIT P/N MUJC588BEI OR EQUIVO WITH FACEPLATE
<br />INSTALLED & LABELED. THE WIRING OF THIS JACK SHALL BE TO EIA/TIA 568E
<br />STANDARD (PAIR 1=BLUE, PAIR 2=ORANGE, PAIR 3=GREEN, & PAIR 4=BROWN) ON
<br />BOTH ENDS OF THE RUN (STRAIGHT THROUGH, NOT CROSS OVER). THE FACEPLATE
<br />& ELECTRICAL BOX IN BACK OF IT SHALL ONLY HAVE THE DATA CABLE RUNS
<br />ASSOCIATED WITH POS SYSTEM GOING TO IT (NO TELEPHONE, COAX AC LINES, ETC).
<br />IF MORE THAN ONE DATA CABLE IS GOING TO A LOCATION, THE FACEPLATE CAN
<br />BE SHARED WITH OTHER POS SYSTEM RUNS. TERMINATION MUST BE WITHIN 5 FEET
<br />OF WHERE EACH WORKSTATION WILL BE LOCATED. AT THE BACK OFFICE/NETWORK
<br />HUB LOCATION, A CAT-5E PATCH PANEL (110 STYLE WITH RJ45's ON FRONT) CAN
<br />BE EMPLOYED TO MINIMIZE THE NUMBER OF INDIVIDUAL RJ45 JACKS REQUIRED. THIS
<br />PANEL OR SET OF JACKS MUST BE LOCATED WITHIN 5 FEET OF THE BACK OFFICE
<br />COMPUTER/NETWORK HUB, & MUST BE LABELED. LABELING OF JACKS SHOULD BE
<br />IN A LOGICAL SEQUENCE (e.g. POS1, POS2, KP1, KP2, ETC).
<br />USE OF "PATCH CABLES"
<br />PATCH CABLES MAY BE USED TO CONNECT TERMINALS/WORKSTATIONS TO WALL
<br />JACKS, TERMINALS/WORKSTATIONS TO RECEIPT PRINTERS, HUBS/SWITCHES TO WALL
<br />JACKS/PATCH PANELS, REMOTE PRINTERS TO WALL JACKS, ETC. THE MAXIMUM
<br />LENGTH OF THESE PATCH CABLES IS 2 METERS, OR 7 FEET. THE MINIMUM
<br />SPECIFICATION OF THESE CABLES IS CAT-5E, WITH STRANDED WIRE BEING USED.
<br />IF THESE PATCH CABLES NEED TO BE "WIRE -TIED" TO FACILITATE A CLEANER
<br />INSTALLATION, THIS MUST BE DONE SO THAT THE MINIMUM DIAMETER OF THE
<br />BUNDLE IS 4". IN NO EVENT SHALL THIS BUNDLE BE "SMASHED TOGETHER" AND
<br />CINCHED SO TIGHT THE JACKET OF THE CABLE IS DEPRESSED. THE USE OF PATCH
<br />CABLES LONGER THAN 2 METERS IS HIGHLY DISCOURAGED, AS THIS INTRODUCES
<br />TOO MANY CHANCES FOR COMPROMISING THE INTEGRITY OF THE DATA NETWORK.
<br />CARE SHOULD ALSO BE TAKEN NOT TO INTRODUCE SUB-CAT-5E (I.E. CAT-5,
<br />CAT-3) PATCH CABLES INTO A SYSTEM.
<br />120VAC DUPLEX OUTLET:
<br />THE PREFERRED TYPE WOULD BE AN ISOLATED GROUND OUTLET (INDUSTRY
<br />STANDARD ORANGE IN COLOR). IF THIS IS NOT AVAILABLE, A "REGULAR" OUTLET IS
<br />SUITABLE, AS LONG AS THERE IS NOTHING ELSE ON THE SAME CIRCUIT BESIDES
<br />THE POS EQUIPMENT, & IT IS WIRED CORRECTLY (INCLUDING GROUND). THIS MEANS
<br />NO COFFEE MAKERS, SODA MACHINES, SIGNAGE, REFRIGERATION EQUIPMENT, ETC. IN
<br />ADDITION, WHETHER THE OUTLETS ARE ISOLATED GROUND OR "CONVENTIONAL",
<br />THEY ALL NEED TO SHARE A SINGLE DISTRIBUTION PANEL.
<br />POS SYSTEM MINIMUM SPECIFICATIONS AND REQUIREMENTS:
<br />AC POWER
<br />AC POWER REQUIREMENTS:
<br />EACH WORKSTATION LOCATION, KITCHEN/REMOTE PRINTER LOCATION, AND BACK
<br />OFFICE/NETWORK HUB LOCATION SHALL HAVE A 120VAC DUPLEX OUTLET (INDUSTRY
<br />STANDARD NEMA 5-20R OR EQUIV.) WITHIN 5 FEET OF THE LOCATION. THE
<br />PREFERRED TYPE WOULD BE A DEDICATED, ISOLATED GROUND OUTLET (INDUSTRY
<br />STANDARD ORANGE IN COLOR). IF THIS IS NOT AVAILABLE, A "REGULAR" DUPLEX
<br />RECEPTACLE IS ACCEPTABLE, AS LONG AS THERE IS NOTHING ELSE ON THE SAME
<br />CIRCUIT BESIDES THE POS EQUIPMENT, AND IT IS WIRED CORRECTLY (INCLUDING
<br />GROUND). THIS MEANS NO COFFEE MAKERS, SODA MACHINES, SIGNAGE,
<br />REFRIGERATION EQUIPMENT, ETC. IN ADDITION, WHETHER THE OUTLETS ARE
<br />DEDICATED, ISOLATED GROUND OR "CONVENTIONAL", THEY ALL NEED TO SHARE A
<br />SINGLE DISTRIBUTION PANEL.
<br />IN A TYPICAL SYSTEM, EACH WORKSTATION/RECEIPT PRINTER COMBINATION WOULD
<br />DRAW A MAXIMUM OF ABOUT 2 AMPS OF POWER. THIS MEANS THAT IN A 3 OR
<br />4-TERMINAL ALOHA SYSTEM, FOR EXAMPLE, THE ENTIRE SYSTEM (INCLUDING
<br />FILESERVER) MAY BE ON ONE SEPERATE CIRCUIT. IN FACT, THIS IS THE
<br />PREFERABLE METHOD AS ALL DEVICES WOULD BE ON THE SAME "GROUND -PLANE"
<br />(COMMON PANEL/SUBPANEL), AND NOTHING ELSE WOULD BE ON THAT CIRCUIT TO
<br />INTRODUCE UNWANTED ELECTRICAL INTERFERENCE.
<br />THE COMCHECK REPORT IS CONSIDERED PART OF THE MEP DOCUMENT
<br />SET. CONTRACTOR SHALL COMPLY WITH ALL ENERGY CODE
<br />REQUIREMENTS.
<br />Peter A. Leptuch, P.E.
<br />300 N. Carroll Blvd. #20C
<br />Denton, TX 76201
<br />(940) 735-5127
<br />Stud i o RG.,...,
<br />MAIN OFFICE:
<br />1 HUNTINGTON QUADRANGLE
<br />SUITE 2CO3
<br />MELVILLE, NY 11747
<br />P: 631.226-7700 F: 631.226.7175
<br />©Copyright 2018: RGBK, INC.
<br />Seal:
<br />Landry
<br />GREG LAN DRY
<br />AROVEOURE nAWING IN'r Eit _O Dt S*N
<br />1202 �ichardsen Dr. #106 Tel; =214 631.6941
<br />Rchardson, Texas 75080 Fax::214.634.1814
<br />No 72679 •, �.
<br />•:
<br />STATE- 0
<br />c �
<br />(1j✓s
<br />��V
<br />Owner:
<br />George Morkos
<br />2520 Colony Reed Lane
<br />Clearwater, FL33763
<br />It is the responsibility of the Construction
<br />Manager/General Contractor and all
<br />Sub -Contractors to verify all dimensions and
<br />accept conditions of prior work by related
<br />trades before proceeding with any work.
<br />Date
<br />07-22-2020
<br />Drawn By
<br />Check By
<br />MRP
<br />TN
<br />Scale
<br />AS SHOWN
<br />Issued:
<br />Rev.
<br />No.
<br />Description
<br />Issued for Review
<br />Project Title
<br />Charleys
<br />Zephyrhills
<br />WM706
<br />Project Address
<br />7631 Gall Blvd,
<br />Zephyrhills, FL 33541
<br />Project Number
<br />WM706
<br />Drawing Title and Number
<br />ELECTRICAL
<br />SPECIFICATIONS
<br />E4.0