ELECTRICAL ONE -LINE RISER DIAGRAM NOTES
<br />1. INSPECT AND REUSE DISCONNECT AND OVERCURRENT PROTECTION MEANS, FEEDERS AND WHERE
<br />POSSIBLE ELECTRICAL PANELS. BRANCH CIRCUIT WIRING SHALL BE ALL COPPER CONDUCTORS.
<br />2. PROVIDE FEEDER FOR TENANT SERVICE. VERIFY LOCATION OF WALMART XFMR. IN FIELD.
<br />3. E.C. SHALL VERIFY LENGTH OF FEEDERS PRIOR TO (AND INCLUDE PRICING IN) BID.
<br />4. ALL PANELS AND SUB -PANELS SHALL HAVE LOCKS. ALL PANELS SHALL BE SQUARE D / EATON /
<br />CUTLER -HAMMER & SUB -PANELS AND PANELS 600A OR LESS SHALL FIT INTO A 6" STUD WALL
<br />WITH LOCKING FLUSH MOUNT COVERS.
<br />5. G.C. SHALL CONFIRM VOLTAGE AVAILABLE ON SITE PRIOR TO ORDERING ANY NEW HVAC EQUIPMENT
<br />OR ELECTRICAL GEAR. NOTIFY ENGINEER IF VOLTAGE IS DIFFERENT THAN AS SHOWN.
<br />6. HVAC BREAKER SIZES SHALL BE CONFIRMED WITH UNITS AND/OR EQUIPMENT THAT ARRIVE ON SITE.
<br />BREAKER SIZES AND WIRE SIZES SHALL BE ADJUSTED AS NECESSARY.
<br />7. PROVIDE LOCK -ON BREAKERS FOR ALL NL/EM AND SECURITY/PHONE CIRCUITS, REFRIGERATION
<br />EQUIPMENT, DUCT DETECTORS, AND TIME CLOCK OR OTHER EQUIPMENT REQUIRED TO HAVE POWER
<br />24/7 WITHOUT INTERRUPTION.
<br />8. ON 480V JOBS, AS NEEDED, PROVIDE SECONDARY DISCONNECT (FUSED) WITHIN 10' OF THE STEP
<br />DOWN TRANSFORMER WHERE SECONDARY CONDUCTOR DISTANCE IS >25' OR AS REQUIRED
<br />ELSEWHERE BY THE TAP RULE.
<br />9. ELECTRICAL PANELS SHALL BE SERIES RATED WITH COORDINATED BREAKERS. WHERE POSSIBLE,
<br />ORDER ALL PANELS FROM ONE MANUFACTURER FOR A COMPLETE COORDINATED PACKAGE.
<br />10. PROVIDE ANCILLAR POWER AS NEEDED FOR ITEMS SUCH AS FLUSH SENSORS, DUCT DETECTORS,
<br />CAMERA/MUSIC SYSTEMS, ETC. COORDINATE REQUIREMENTS WITH OWNER'S REP.
<br />11. ALL ELECTRICAL CIRCUITS UNDER TYPE 1 HOODS SHALL BE EQUIPPED WITH SHUNT TRIP BREAKERS
<br />FOR AUTOMATIC SHUTDOWN OF COOKING ENERGY SOURCE UPON RECEIPT OF A SIGNAL FROM THE
<br />HOOD CONTROLLER, OR EQUAL.
<br />12. AREA SMOKE DETECTORS AND DUCT SMOKE DETECTORS SHALL BE INSTALLED AND CIRCUITED TO AN
<br />OPEN 20/1 CIRCUIT.
<br />13. VERIFY FAULT DUTY (SCCR) OF EX. PANEL, SUB -PANEL TO MATCH OR SHALL HAVE SERIES RATED
<br />BREAKER FROM SAME MANUFACTURER AS MAIN PANEL.
<br />14. ELECTRICAL CONTRACTOR SHALL VERIFY AVAILABLE FAULT WITH UTILITY CO. PRIOR TO ENERGIZING
<br />SERVICE.
<br />15. DISCONNECTS SHALL BE RATED FOR VOLTAGE OF EQUIPMENT SERVED.
<br />16. ALL WIRING IS COPPER, SIZED FOR 75' C THWN.
<br />17. FEEDER CONDUIT SHALL BE RIGID METALLIC CONDUIT, OR PVC SUITABLE (RATED) FOR ELECTRICAL
<br />USE.
<br />18. DISCONNECTS SHALL BE PROVIDED WHERE REQUIRED BY CODE AND ORDERED AT THE VOLTAGE OF
<br />THE EQUIPMENT SERVED.
<br />MECHANICAL EQUIPMENT POWER SCHEDULE NOTES
<br />1. ELECTRICAL CONTRACTOR SHALL REFER TO ALL MECHANICAL, PLUMBING AND ARCHITECTURAL
<br />DRAWINGS FOR EXACT LOCATIONS AND CHARACTERISTICS OF ALL EQUIPMENT LISTED BELOW. ANY
<br />MODIFICATION AND/OR ADDITIONAL WORK NECESSARY SHALL BE INCLUDED IN THE BASE BID.
<br />2. ELECTRICAL CONTRACTOR SHALL CHECK THE ROTATION OF ALL THREE PHASE MOTORS AND
<br />CORRECT THE ROTATION IF REVERSED.
<br />3. ALL TEMPERATURE CONTROL AND INTERLOCK WIRING SHALL BE BY HVAC CONTRACTOR UNLESS
<br />NOTED OTHERWISE.
<br />4. ELECTRICAL CONTRACTOR SHALL SUBMIT FOUR (4) SETS OF CATALOG CUTS FOR ALL SCHEDULED
<br />EQUIPMENT FURNISHED BY THIS CONTRACTOR FOR ARCHITECT/ENGINEER REVIEW.
<br />5. ELECTRICAL CONTRACTOR SHALL COORDINATE THE ROUTING OF POWER WIRING TO ROOF -MOUNTED
<br />EQUIPMENT WITH MECHANICAL PIPE CURB ASSEMBLY. NO SEPARATE ROOF PENETRATIONS WILL BE
<br />PERMITTED UNLESS OTHERWISE SPECIFIED BY LANDLORD'S NEW ROOFING WARRANTY.
<br />6. ELECTRICAL CONTRACTOR SHALL FURNISH AND WIRE DUCT SMOKE DETECTORS IN THE RETURN AND
<br />SUPPLY AIR PLENUM AND A FAN SHUT DOWN RELAY FOR ALL AIR SUPPLY UNITS. DETECTORS TO
<br />BE INSTALLED BY MECHANICAL CONTRACTOR.
<br />7. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL A WEATHER PROOF, GROUND FAULT
<br />INTERRUPTER TYPE RECEPTACLE, AT AN ACCESSIBLE LOCATION FOR SERVICING ON
<br />8. ROOFTOP HEATING AND AIR CONDITIONING EQUIPMENT. THIS RECEPTACLE SHALL BE LOCATED WITHIN
<br />25 FEET AND AT THE SAME LEVEL OF THIS EQUIPMENT.
<br />FIXTURE SCHEDULE NOTES
<br />1. 1. VERIFY ALL LUMINARIES COLORS, TRIMS, LENGTHS, ETC. WITH THE ARCHITECT PRIOR TO PLACING
<br />FINAL PURCHASE ORDERS. SUBMISSION OF SHOP DRAWINGS WILL BE INTERPRETED AS HAVING BEEN
<br />COORDINATED WITH THE ARCHITECTURAL DRAWINGS.
<br />2. PROVIDE LENGTHS, FEEDS, ACCESSORIES, CONNECTORS, WIRING, POWER SUPPLIES, DRIVERS, ETC. FOR
<br />COMPLETE INSTALLATION. THE E.C. SHALL VERIFY THE COMPLETE BILL OF MATERIAL WITH
<br />MANUFACTURER'S REPRESENTATIVE AND ENSURE ALL EQUIPMENT IS INCLUDED IN BID PRICE.
<br />COORDINATE INSTALLATION WITH ARCHITECTURAL DETAILS.
<br />3. VERIFY LUMINAIRE LOCATIONS WITH OTHER CEILING MOUNTED EQUIPMENT SUCH DIFFUSERS, FIRE
<br />SPRINKLER & ALARMS DEVICES, SPEAKERS, ETC. WITH ARCHITECTURAL REFLECTED CEILING PLANS
<br />AND IN FIELD.
<br />4. VERIFY EXACT MOUNTING HEIGHT AND LOCATIONS OF ALL WALL MOUNTED AND PENDANT MOUNTED
<br />LUMINAIRES WITH ARCHITECTURAL PLANS AND ELEVATIONS PRIOR TO ROUGH -IN.
<br />5. ANY PROPOSED ALTERNATE LUMINAIRES SHALL BE APPROVED BY THE ARCHITECT PRIOR TO FINAL
<br />BID PRICING. SHOULD THE CONTRACTOR PROPOSE TO FURNISH MATERIALS, EQUIPMENT, AND
<br />DEVICES OTHER THAN THOSE SPECIFIED AND LISTED, THE CONTRACTOR SHALL SUBMIT A WRITTEN
<br />REQUEST FOR SUBSTITUTIONS, TO THE ENGINEER AT LEAST TEN (10) BUSINESS DAYS PRIOR TO BID
<br />OPENING. THE REQUEST SHALL BE AN ALTERNATE TO THE ORIGINAL BID AND SHALL INCLUDE A
<br />COMPLETE SPECIFICATION CUT SHEET SUBMITTAL AS OUTLINED IN THE SPECIFICATIONS, COMPLETE
<br />WITH DESCRIPTIVE (MANUFACTURER, BRAND NAME, CATALOG NUMBER, ETC.) AND TECHNICAL DATA
<br />(VOLTAGE, INPUT WATTS, ETC.) FOR ALL ITEMS. INDICATE ANY ADDITIONS OR DEDUCTIONS TO THE
<br />CONTRACT PRICE WITH THE SUBSTITUTION SUBMITTAL AND ON THE BID FORM.
<br />6. ALL EXIT SIGNS AND EMERGENCY LIGHT FIXTURES ARE TO BE STRICT ACCORDANCE WITH THE LOCAL
<br />FIRE PREVENTION CODE AUTHORITY. ANY MODIFICATIONS TO UPGRADE SYSTEM SHALL BE INCLUDED
<br />IN THE BASE BID. ALL EXIT SIGNS ARE TO BE INSTALLED IN A VISIBLE LOCATION. ELECTRICAL
<br />CONTRACTOR SHALL FURNISH AND INSTALL WHERE NECESSARY TO DROP A SIGN BELOW AN
<br />OBSTRUCTION.
<br />7. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL THE NECESSARY CLIPS, SCREWS, RIVETS,
<br />TIES/BRACING ETC., TO SECURELY FASTEN RECESSED LAY -IN LIGHTING FIXTURES TO CEILING
<br />FRAMING GRID WORK.
<br />8. ALL LIGHTING FIXTURES SHALL BEAR THE APPROPRIATE UL LABEL FOR THE APPLICATION AND UNION
<br />LABEL WHERE REQUIRED.
<br />9. ALL LIGHTING FIXTURES SHALL BE SHATTER PROOF OR COMPLETELY SHIELDED/COVERED.
<br />10. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS, EQUIPMENT, S.E.S., AND EXTENT OF ELECTRICAL
<br />ITEMS. PROVIDE AND INCLUDE IN BID ALL REQUIRED ITEMS TO ENSURE PROPER SCOPE OF WORK.
<br />UPGRADE METERING EQUIPMENT AS NEEDED.
<br />11. ALL LIGHTING FIXTURES SHALL BEAR THE APPROPRIATE UL LABEL FOR THE APPLICATION AND UNION
<br />LABEL WHERE REQUIRED.
<br />REFLECTED CEILING NOTES
<br />1. REFER TO MECHANICAL FOR EXACT NUMBER, TYPE AND LOCATION OF SUPPLY, RETURN AND
<br />EXHAUST FIXTURES.
<br />2. REFER TO ELECTRICAL FOR EXACT NUMBER, TYPE AND LOCATION OF OUTLETS.
<br />3. G.C. WILL COORDINATE THE WORK OF ALL TRADES INVOLVED IN THE CEILING WORK TO ENSURE
<br />CLEARANCES FOR FIXTURES, DUCTS, PIPING, CEILING SUSPENSION SYSTEMS, ETC., NECESSARY TO
<br />MAINTAIN THE FINISHED CEILING HEIGHTS INDICATED ON ARCHITECTURAL DRAWINGS.
<br />4. PROVIDE CEILING ACCESS AS REQUIRED FOR EQUIPMENT AND SYSTEM MAINTENANCE VERIFY
<br />MANUFACTURER RECOMMENDATIONS.
<br />5. ALL SWITCHES AND DIMMERS SHALL BE LOCATED 46" ABOVE FINISHED FLOOR, TO CENTER OF
<br />SWITCHES AND 6" FROM DOOR FRAME U.O.N. MULTIPLE SWITCHES AT ONE LOCATION SHALL BE
<br />GANGED TOGETHER AND FINISHED WITH ONE COVER PLATE.
<br />6. CONTRACTOR TO NOTIFY ARCHITECT OF ANY CONFLICT OF LIGHT FIXTURE LOCATIONS WITH MAIN
<br />RUNNERS, DUCTS, ETC., PRIOR TO INSTALLATION.
<br />7. FURNISH AND INSTALL UNDERWRITERS LABORATORY, INC (UL) LABELED DEVICES THROUGHOUT
<br />PANELBOARD SCHEDULE - 'A' EX.
<br />MAIN:
<br />400A MCB
<br />VOLTAGE: 208/120
<br />PHASE:3
<br />1 WIRE: 4
<br />MOUNTING: SURFACE AIC: EX
<br />CKT
<br />#
<br />TRIP
<br />POLE
<br />DESCRIPTION
<br />LOAD (KVA)
<br />S4 LOAD (KVA)
<br />DESCRIPTION
<br />TRIP
<br />POLE
<br />CKT
<br />#
<br />LTG
<br />RECIM111
<br />A/C
<br />HTC
<br />KIT
<br />MIS
<br />B LTG
<br />REC
<br />MTR
<br />A/C
<br />HTG1
<br />KiTIMR
<br />1
<br />20/1
<br />U/C FRZR (K17)
<br />0.3
<br />1.4
<br />1.0
<br />1.2
<br />0.8
<br />0.0
<br />0.0
<br />5.4
<br />3.6
<br />PANEL S'
<br />-
<br />2
<br />3
<br />20/1
<br />U/C FRIDGE (K16)
<br />0.3
<br />1.3
<br />0.8
<br />0.0
<br />0.0
<br />6.2
<br />3.6
<br />VIA FEED THRU LUGS
<br />-
<br />4
<br />5
<br />20/1
<br />MONITOR (E3)
<br />0.4
<br />0.5
<br />0.0
<br />0.8
<br />0.0
<br />0.0
<br />4.4
<br />3.9
<br />-
<br />-
<br />6
<br />7
<br />20/1
<br />WARMING DRAWER (K18)
<br />0.9
<br />0.2
<br />GAME RECEPTS
<br />20/1
<br />8
<br />9
<br />20/1
<br />GRID. CONTR.(K1.1)MON.(E3
<br />0.9
<br />0.2
<br />0.4
<br />GAME RECEPTS
<br />20/1
<br />10
<br />11
<br />-
<br />SHUNT TRIP
<br />1.9
<br />SOFT SERVE (K21)
<br />3013
<br />12
<br />13
<br />20/1
<br />FRY CONTROLS (K2.1)
<br />1.4
<br />1.9
<br />-
<br />-
<br />14
<br />15
<br />-
<br />SHUNT TRIP
<br />1.9
<br />-
<br />-
<br />1 16
<br />17
<br />20/1
<br />INSECT CONTROL / T.C.
<br />0.4
<br />1.0
<br />WARMER (K6)
<br />20/1
<br />18
<br />19
<br />20/1
<br />FRY CONTROLS (K2.2)
<br />1.4
<br />SHUNT TRIP
<br />-
<br />20
<br />21
<br />20/1
<br />SHUNT TRIP
<br />0.5
<br />PHONE BOARD / MGR (E4)
<br />20/1
<br />22
<br />23
<br />20/1
<br />SPARE
<br />1.0
<br />DUMP STATION (K3)
<br />2011
<br />24
<br />25
<br />20/1
<br />FILT./CARB. AREA (P2.1,1013)
<br />1
<br />10.5
<br />ISHUNTTRIP
<br />-
<br />26
<br />27
<br />20/1
<br />MONITOR (E3) / DINING TV
<br />0.9
<br />1
<br />1
<br />1.5
<br />OIL STORAGE TANK (K20)
<br />20/1
<br />28
<br />29
<br />20/1
<br />SHAKE (K23)
<br />1
<br />1.0
<br />1.5
<br />OIL CADDY (P3)
<br />20/1
<br />30
<br />31
<br />20/1
<br />DINING T.V.
<br />0.2
<br />SPARE
<br />20/1
<br />32
<br />33
<br />20/1
<br />U/C FRZR (K13)
<br />0.2
<br />SPARE
<br />20/1
<br />34
<br />35
<br />-
<br />SHUNT TRIP
<br />SPARE
<br />20/1
<br />36
<br />37
<br />20/1
<br />SPARE
<br />SPARE
<br />20/1
<br />38
<br />39
<br />20/1
<br />SPARE
<br />SPARE
<br />1 20/1
<br />40
<br />41
<br />20/1
<br />SPARE
<br />SPARE
<br />2011
<br />42
<br />LIGHTING
<br />(KVA):
<br />2.9
<br />0.0
<br />2.7
<br />0.0
<br />10.0
<br />10.0
<br />62
<br />0.0
<br />2.9
<br />4.6
<br />2.4
<br />0.0 10.0
<br />25.8
<br />11.2
<br />CONNECTED LOAD (KVA):
<br />55.7
<br />RECEPTACLES (KVA): 7.3
<br />DEMAND LOAD (KVA):
<br />44.5
<br />MOTORS (KVA):
<br />2.4
<br />PHASE A
<br />19
<br />160.5
<br />A/C (KVA):
<br />0.0
<br />PHASE B
<br />20
<br />164.0
<br />CONNECTED LOAD (AMPS):
<br />154.7
<br />HEATING (KVA):
<br />0.0
<br />PHASE C
<br />17
<br />139.9
<br />DEMAND LOAD (AMPS):
<br />123.6
<br />KITCHEN (KVA):
<br />32.0
<br />KVA
<br />AMPS
<br />MISCELLANEOUS (KVA): 11.2
<br />1AMPACITY REQUIRED:
<br />125.6
<br />NOTES: BREAKERS PROTECTING MULTI -WIRE BRANCH CIRCUITS SHALL BE EQUIPPED WITH A PAD -LOCK DEVICE SO THAT CIRCUITS CAN BE DISCONNECTED SIMULTANEOUSLY.
<br />(a) - PROVIDE'IIACR' TYPE CIRCUIT BREAKER
<br />AMPACITY READ CALCS
<br />LIGHTING 2.92 KVA X 125 % = 3.7 KVA
<br />RECEPTACTOTAL 7.26 KVA
<br />1ST 10.00 KVA X 100 % = 7.3 KVA
<br />REMAIN 0.00 KVA X 50 % = 0.0 KVA
<br />MOTORS TOTAL 2.38 KVA X 100 %
<br />LARGEST KVAX 125 % = 0.0 KVA
<br />REMAIN 2.38 KVAX 100 % = 2.4 KVA
<br />A/C 0.00 KVAX 100 % = 0.0 KVA
<br />HEATING 0.00 KVAX 100 % = 0.0 KVA
<br />LOCKED -OJT LOAD KVA X 100 % = 0.0 KVA
<br />KITCHEN 32.00 KVA X 65 % = 20.8 KVA
<br />MISCELLANEOUS 11.18 KVAX 100 % = 11.2 KVA
<br />TOTAL = 45.3 KVA
<br />DETAIL NOTES:
<br />1. ALL GROUNDING SHALL BE
<br />INSTALLED IN ACCORDANCE
<br />WITH ARTICLE 250-50 OF
<br />THE NATIONAL ELECTRICAL
<br />CODE.
<br />2. ALL GROUNDING CABLES
<br />SHALL BE #3/0 UNLESS
<br />OTHERWISE SPECIFIED
<br />SIZE PER TABLE 250-66
<br />MINIMUM OF 20'-0" OF
<br />1/2" REBAR IN BUILDING
<br />WALL FOOTING,
<br />(NEC 250-50c) -�
<br />CADWELD
<br />3/4" X 10' GROUND ROD
<br />(NEC 250-52)
<br />MAIN SERVICE GROUNDING
<br />I� NEUTRAL BUS
<br />GROUND BUS
<br />Q
<br />U
<br />Peter A. Leptuch, P.E.
<br />300 N. Carroll Blvd. #200
<br />Denton, TX 76201
<br />(940) 735-5127
<br />PANELBOARD SCHEDULE -
<br />'B' EX.
<br />MAIN:
<br />400A MLO
<br />VOLTAGE: 2081120 PHASE: 3
<br />WIRE:4 MOUNTING: SURFACE AIC: EX.
<br />CKT
<br />#
<br />TRIP
<br />POLE
<br />DESCRIPTION
<br />LOAD (KVA)
<br />LOAD (KVA)
<br />DESCRIPTION
<br />TRIP
<br />POLE
<br />CKT
<br />#
<br />LTG
<br />REC;
<br />MTR
<br />AIC
<br />HTC
<br />KrrMISCIAB
<br />LTG
<br />REC
<br />M
<br />A/C
<br />HT
<br />KITIMISC
<br />1
<br />20/1
<br />HOOD CONTROLS (1-11) + LTS
<br />0.5
<br />0.8
<br />1.0
<br />LIGHTING
<br />20/1
<br />2
<br />3
<br />20/1
<br />HVAC RECEPTS
<br />0.5
<br />LIGHTING
<br />20/1
<br />4
<br />5
<br />20/1
<br />U/C FREEZER (K10)
<br />1
<br />1
<br />0.5
<br />0.2
<br />SIGN (LED)
<br />20/1
<br />6
<br />7
<br />50/2
<br />CONV OVEN (K5)
<br />3.0
<br />0.4
<br />WIC LTS & DEFROST
<br />20/1
<br />8
<br />9
<br />-
<br />-
<br />3.0
<br />3.6
<br />MAC UNIT (EXISTING)
<br />40/3
<br />10
<br />11
<br />-
<br />SHUNT TRIP
<br />3.6
<br />-
<br />-
<br />12
<br />13
<br />20/1
<br />SAND PREP(K9)
<br />0.5
<br />3.6
<br />-
<br />-
<br />14
<br />15
<br />-
<br />SHUNT TRIP
<br />SPARE
<br />20/1
<br />16
<br />17
<br />20/1
<br />REFRIG (K15)
<br />0.6
<br />SPARE
<br />20/1
<br />18
<br />19
<br />20/1
<br />MENU BOARD / TV
<br />0.7
<br />0.8
<br />EF-1
<br />20/3
<br />20
<br />21
<br />20/1
<br />POS (E1, E2)
<br />0.7
<br />0.8
<br />-
<br />-
<br />22
<br />23
<br />20/1
<br />BEV DISP (K11)
<br />0.4
<br />0.8
<br />-
<br />-
<br />24
<br />25
<br />20/1
<br />BEV DISP (K11)
<br />0.4
<br />1
<br />1
<br />1.5
<br />1 FROZ. CARB. BEV. (K19)
<br />3012
<br />26
<br />27
<br />20/1
<br />TEA BREWER (K12.1)
<br />1.7
<br />1.5
<br />-
<br />-
<br />28
<br />29
<br />20/1
<br />SODA DISP (P1.1)
<br />0.7
<br />2.2
<br />ICEMAKER(PIA)
<br />25/1
<br />30
<br />31
<br />20/1
<br />SPARE
<br />0.2
<br />SIGN (LED)
<br />2011
<br />32
<br />33
<br />20/1
<br />SPARE
<br />SPARE
<br />20/1
<br />34
<br />35
<br />20/1
<br />INTERIOR NEON SIGN
<br />0.3
<br />0.3
<br />1
<br />1
<br />1
<br />INTERIOR NEON SIGN
<br />20/1
<br />36
<br />37
<br />20/1
<br />SPARE
<br />SPARE
<br />20/1
<br />38
<br />39
<br />20/1
<br />SPARE
<br />SPARE
<br />20/1
<br />40
<br />41
<br />2011
<br />SPARE
<br />SPARE
<br />20/1
<br />42
<br />LIGHTING
<br />(KVA):
<br />2.9
<br />0.0
<br />2.5
<br />0.0
<br />0.0
<br />0.0
<br />10.9
<br />0.3
<br />2.9
<br />0.0
<br />2.4
<br />0.0
<br />10.0
<br />5.2
<br />10.9
<br />CONNECTED LOAD (KVA):
<br />35.0
<br />RECEPTACLES (KVA): 2.5
<br />DEMAND LOAD (KVA):
<br />29.4
<br />MOTORS (KVA):
<br />2.4
<br />PHASE A
<br />12
<br />104.1
<br />C (KVA):
<br />0.0
<br />PHASE B
<br />13
<br />107.4
<br />CONNECTED LOAD (AMPS):
<br />97.2
<br />HEATING (KVA):
<br />0.0
<br />PHASE C
<br />10
<br />80.4
<br />DEMAND LOAD (AMPS):
<br />81.6
<br />KITCHEN (KVA):
<br />16.1
<br />KVA
<br />AMPS
<br />MISCELLANEOUS (KVA): 11.2
<br />AMPACITY REQUIRED:
<br />83.6
<br />NOTES: BREAKERS PROTECTING MULTI -WIRE BRANCH CIRCUITS SHALL BE EQUIPPED WTH A PAD -LOCK DEVICE SO THAT CIRCUITS CAN BE DISCONNECTED SIMULTANEOUSLY.
<br />(a) - PROVIDE'HACR' TYPE CIRCUIT BREAKER
<br />AMPACITY READ CALCS
<br />LIGHTING 2.92 KVA X 125 % = 3.7 KVA
<br />RECEPTAC TOTAL 2.48 KVA
<br />1ST 10.00 KVA X 100 % = 2.5 KVA
<br />REMAIN 0.00 KVAX 50 % = 0.0 KVA
<br />MOTORS TOTAL 2.38 KVA X 100 %
<br />LARGEST KVAX 125 % = 0.0 KVA
<br />REMAIN 2.38 KVAX 100 % = 2.4 KVA
<br />A/C 0.00 KVA X 100 % = 0.0 KVA
<br />HEATING 0.00 KVA X 100 % = 0.0 KVA
<br />LOCKED -OUT LOAD KVAX 100 % = 0.0 KVA
<br />KITCHEN 16.07 KVAX 65 % = 10.4 KVA
<br />MISCELLANEOUS 11.18 KVAX 100 % = 11.2 KVA
<br />TOTAL = 30.1 KVA
<br />PANEL SCHEDULES Q zwo R U-)1 RTU>2
<br />1 EXISTING CONDUIT AND
<br />CONDUCTOR RUNS, NO < J�
<br /><<< Ll� Q
<br />SCALE: NOT TO SCALE CHANGES.N
<br />1-#6 TO
<br />TELEPHONE BOARD
<br />BARE COPPER
<br />GROUNDING ELECTRODE
<br />CONDUCTOR
<br />(NEC 250-66)
<br />TO PANELBOARD
<br />ENCLOSURE SIZE PER
<br />NEC 250-122
<br />VALVE,NA;
<br />METER
<br />SUPPLY
<br />BUILDING STRUCTURAL
<br />TCADWELD
<br />r UNIO
<br />SIDE
<br />STEEL (NEC 250-50b)
<br />COLD WATER (METALLIC) SERVICE
<br />ENTRANCE (PROVIDE SIMILAR
<br />CONNECTION
<br />CADWELD
<br />TO FIRE PROTECTION WATER
<br />SERVICE
<br />JUMPER
<br />ENTRANCE), (NEC 250-50a)
<br />o 1
<br />ELECTRICAL
<br />GROUNDING
<br />DETAIL
<br />SCALE: NOT TO SCALE
<br />REUSE EXISTING
<br />PANELS THAT WERE
<br />SERVING THE PREVIOUS
<br />TENANT AS -IS.
<br />ELECTRICAL WORK IS
<br />EXPECTED TO BE
<br />LIMITED TO BRANCH
<br />CIRCUIT WIRING ONLY.
<br />I --
<br />I I Ir
<br />I I I
<br />I I I
<br />I I I
<br />I I
<br />I I I
<br />I
<br />(EX) I�t (EX) C
<br />I
<br />I
<br />iL
<br />EXISTING 277/480V EXISTING 120/208V
<br />3-PH 4-WIRE VOLTAGE 3-PH 4-WIRE VOLTAGE
<br />SOURCE (WALMART SOURCE (WALMART
<br />ELECTRICAL ROOM) ELECTRICAL ROOM)
<br />--> NO CHANGES <-- --> NO CHANGES <--
<br />I (EX)
<br />EQ. TO:
<br />2 SETS OF
<br />(1)#1 /0 G
<br />IN 2"C.
<br />_ _ _
<br />r (EX) , r (EX)
<br />-� PANEL I I PANEL
<br />'A' I I 'B'
<br />A.K.A. A.K.A.
<br />LFS1 I I LFS2
<br />400A I I 400A I
<br />L MCB J L MLO- J
<br />(EX) SUB
<br />T.V.S.S. FEED
<br />LUGS
<br />annr
<br />CEILING
<br />PROVIDE TIME
<br />CLOCK FOR
<br />INTERIOR/
<br />EXTERIOR
<br />SIGNAGE.
<br />ELECTRICAL RISER DIAGRAM
<br />SCALE: NOT TO SCALE
<br />FLOOR
<br />StudioRGII...._
<br />MAIN OFFICE:
<br />1 HUNTINGTON QUADRANGLE
<br />SUITE 2CO3
<br />MELVILLE, NY 11747
<br />P: 631.226-7700 F: 631.226.7175
<br />©Copyright 2018: RGBK, INC.
<br />n rYGREG LANDRY
<br />AlGifTEMRE PLAN
<br />NING INTHtt01t DESIGN
<br />LLa
<br />1202 Pidrardsm Dr. #106 Tel: 214,631.6941
<br />Rchardsm, Texas 75080 fax 214.634.1814
<br />Seal:
<br />t Ygu
<br />v(//?� . B E N S ,6, o
<br />. rlj•
<br />No 72679
<br />f STAYz_ 7F
<br />` h=>
<br />Owner:
<br />George Morkos
<br />2520 Colony Reed Lane
<br />Clearwater, FL33763
<br />It is the responsibility of the Construction
<br />Manager/General Contractor and all
<br />Sub -Contractors to verify all dimensions and
<br />accept conditions of prior work by related
<br />trades before proceeding with any work.
<br />Date
<br />07-22-2020
<br />Drawn By Check By
<br />MRP TN
<br />Scale
<br />AS SHOWN
<br />Issued:
<br />Project Title
<br />Charleys
<br />Zephyrhills
<br />WM706
<br />Project Address
<br />7631 Gall Blvd,
<br />Zephyrhills, FL 33541
<br />Project Number
<br />WM706
<br />Drawing Title and Number
<br />POWER RISER &
<br />PANEL SCHEDULES
<br />E3.0