<br />ELECTRICAL POWER NOTES
<br />A. JURISDICTIONS VARY AS TO WHO CAN MAKE FINAL CONNECTION OF SIGN TO BUILDING POWER.
<br />SOME JURISDICTIONS REQUIRE SPECIAL SIGN PERMITS. THE ELECTRICAL CONTRACTOR SHALL
<br />PROVIDE AN ACCESSIBLE J-BOX AT BUILDING PERIMETER FOR EACH SIGN LOCATION ON ALL JOBS
<br />WITH MEANS OF DISCONNECT AND CONDUCTOR BACK TO THE PANEL, PER NEC. THE SIGN
<br />CONTRACTOR SHALL PROVIDE ALL SIGNS WITH A SINGLE WHIP POKING THROUGH THE BACK OF THE
<br />SIGN OR SIGN RACEWAY FOR EACH SIGN LOCATION. FINAL CONNECTION (INCLUDING ANY CONDUIT
<br />ABOVE METAL AWNING/ STRUCTURE OR OTHER SPECIAL 'GAP' SITE CONDITIONS) SHALL BE BY
<br />ELECTRICAL CONTRACTOR UNLESS THE A.H.J. REQUIRES THIS CONNECTION TO BE BY THE SIGN
<br />CONTRACTOR.
<br />B. AT TIME OF ORDER OF LIGHT FIXTURES, CONFIRM ALL NEW FIXTURES ARE DIMMABLE.
<br />C. BACK OF HOUSE SWITCHES SHALL BE DUAL TECHNOLOGY VACANCY SENSOR TYPE.
<br />D. E.C. SHALL COORDINATE FULLY WITH OTHER CONTRACTORS ASSOCIATED WITH THIS PROJECT TO
<br />VERIFY ALL EQUIPMENT LOCATIONS, CONNECTION REQUIREMENTS, ELEVATIONS AND LOCATIONS OF
<br />PIPES, CONDUITS AND DUCTS TO PREVENT CONFLICTS DURING CONSTRUCTION. ANY RELOCATION OR
<br />REROUTING OF EQUIPMENT, PIPES, CONDUITS, DUCTS OR MATERIALS RESULTING FROM A LACK OF
<br />COORDINATION BETWEEN CONTRACTORS WILL BE AT THE CONTRACTORS EXPENSE.
<br />E. EQUIPMENT ROUGH -INS SHOWN ARE ACCURATE TO THE BEST OF DESIGNER'S KNOWLEDGE. HOWEVER,
<br />IN SOME INSTANCES, THE OWNER OR SUPPLIER MAY SUBSTITUTE OR THE EQUIPMENT ITEM MAY
<br />VARY FROM WHAT IS SHOWN. THEREFORE,THE CONTRACTOR SHALL VERIFY ALL CRITICAL DIMENSIONS
<br />WITH THE OWNER PRIOR TO CONSTRUCTION. FAILURE OF THE E.C. TO VERIFY THESE DIMENSIONS
<br />SHALL PLACE THE RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION DIRECTLY UPON THE
<br />CONTRACTOR.
<br />F. E.C. SHALL FURNISH AND INSTALL ALL REQUIRED DISCONNECT SWITCHES AND MOTOR STARTERS TO
<br />ALL EQUIPMENT.
<br />G. E.C. SHALL REVIEW WITH OWNER AND SIGNAGE MANUFACTURER, REQUIREMENTS AND LOCATION OF
<br />BUILDING SIGNAGE PRIOR TO CONSTRUCTION AND PROVIDE 120VAC CONNECTION AS REQUIRED.
<br />H. E.C. SHALL PROVIDE AS -BUILT DRAWINGS AT JOB COMPLETION TO ARCHITECT.
<br />I. ALL WORK SHALL BE INSTALLED PER ALL GOVERNING CODES.
<br />J. SUBCONTRACTOR IS TO SUPPLY AND INSTALL ALL BLOCKING REQUIRED TO HANG/MOUNT LIGHTS
<br />INCLUDING RESTROOM FIXTURES. BLOCKING IS TO BE FIRE RATED IF REQUIRED BY LOCAL CODES.
<br />K. SUBCONTRACTOR IS TO SUPPLY AND INSTALL UNISTRUT AND 3/8" THREADED ROD TO
<br />HANG/SUPPORT LIGHTING.
<br />L. RACEWAY SYSTEMS: ALL BRANCH CIRCUIT WIRING SHALL BE ROUTED IN EMT, RIGID OR ELECTRICAL
<br />METALLIC TUBING. USE STEEL SET SCREW TYPE FITTINGS ON ALL EMT.
<br />M. CONDUIT SHALL BE SUPPORTED AT INTERVALS PER NEC REQUIREMENTS AND SHALL BE SECURELY
<br />FASTENED TO BUILDING WITH AN APPROVED FASTENING SYSTEM.
<br />N. ALL NEW CONDUIT TO BE CONCEALED IN WALLS. PATCH/PAINT IF NECESSARY. WIRING, WIRING
<br />DEVICES, PLATES AND GROUNDING
<br />0. ALL WIRING SHALL CONSIST OF COPPER CONDUCTORS WITH THERMOPLASTIC INSULATION RATED FOR
<br />SIX HUNDRED (600) VOLTS. ALL WIRING INSULATION SHALL BE HEAT AND MOISTURE RESISTANT
<br />TYPES THW, THWN, OR THHN FOR INTERNAL AND DRIVE LOCATIONS. WIRE COLOR SHALL FOLLOW NEC
<br />STANDARDS, PER VOLTAGE.
<br />P. MINIMUM CONDUCTOR SIZE SHALL BE NO. 12 AWG FOR ALL BRANCH CIRCUITS (I.E. RECEPTACLES,
<br />LIGHTING, EQUIPMENT POWER, ETC.). MINIMUM CONDUCTOR SIZE SHALL BE NO. 10 AWG FOR ALL
<br />FEEDER CIRCUITS TO MECHANICAL EQUIPMENT (LE U-1, CONDENSERS, ETC.)
<br />Q. ALL SPLICED OR CONNECTIONS SHALL BE MADE IN OUTLET BOXES, JUNCTION BOXES OR EQUIPMENT
<br />WHERE ACCESSIBLE, AND NOT BELOW GRADE.
<br />R. CONDUCTORS SHALL BE PULLED WITHOUT THE USE OF OIL OR GREASE. WIRE PULLING LUBRICANTS
<br />WHICH ARE APPROVED FOR USE WITH CONDUCTOR INSULATION MAY BE USED. CARE SHALL BE
<br />TAKEN IN PULLING WIRE TO ASSURE THAT MAXIMUM ALLOWABLE PULLING TENSION OF WIRE IS NOT
<br />EXCEEDED. WIRING WITH DAMAGED CONDUCTORS OR INSULATION WILL NOT BE ACCEPTED.
<br />U. SWITCHES FOR LIGHTING CONTROL SHALL BE INDUSTRIAL GRADE. DEVICES AND PLATES
<br />TO MATCH WALLS IN THE DINING ROOM, WHITE DEVICES WITH STAINLESS PLATES IN THE
<br />KITCHEN AND RESTROOMS. UNLESS NOTED AS OTHERWISE, REFER TO ARCHITECTURAL FINISH
<br />SHEETS. SIDE WIRED ONLY, TWENTY (20) AMP, ONE HUNDRED
<br />TWENTY/TWO HUNDRED SEVENTY-SEVEN (120/277) VOLT.
<br />V. DUPLEX RECEPTACLES SHALL BE INDUSTRIAL GRADE, THREE (3) WIRE GROUNDING, WHITE
<br />COLOR, FINDER GROOVE, TWENTY (20) AMP, NEMA 5-20R 125 VAC.
<br />W. PLATES SHALL BE FURNISHED AND INSTALLED FOR ALL WIRING DEVICES, TELEPHONE
<br />OUTLETS, JUNCTION BOXES, ETC. MATCH SWITCHPLATE COVERS AS LAID OUT ABOVE.
<br />X. E.C. SHALL BE RESPONSIBLE FOR PROPERLY BALANCING ALL BRANCH CIRCUITS
<br />BETWEEN THE PHASES OF THE SYSTEM; REGARDLESS OF CIRCUITING INDICATED.
<br />ELECTRICAL POWER NOTES (CONTINUED)
<br />Y. ALL DUPLEX RECEPTACLES INSTALLED IN KITCHEN, BEVERAGE, AND
<br />PREPARATION AREA ARE TO BE
<br />GFCI RATED, WHERE NOT PROTECTED BY A GFCI CIRCUIT BREAKER.
<br />Z. THERE WILL BE NO MC RUNNING HORIZONTALLY OVER 12" IN LENGTH
<br />IN ANY EXPOSED
<br />AREA OR AREAS VISIBLE TO THE CUSTOMER. ANY HORIZONTAL
<br />CONDUIT MUST BE LEVEL.
<br />NOTES BY SYMBOL:
<br />OJ-BOX FOR SIGN(S), VERIFY EXACT LOCATION AND HEIGHT WITH
<br />SIGN VENDOR. SIGN CONTROLLED BY 7 DAY PROGRAMMABLE
<br />TIME CLOCK. REUSE EXISTING CONDUIT/CIRCUIT FROM PREVIOUS
<br />TENANT'S SIGN LOCATION FOR NEW TENANT'S SIGN.
<br />OEMERGENCY LIGHTS, NIGHT LIGHTS, AND EXIT SIGNS SHALL BE
<br />WIRED AHEAD OF SWITCHING (NOT SWITCHED) TO NEAREST
<br />LIGHTING CIRCUIT.
<br />OSWITCH BANK CONSISTING OF SWITCHES UNDER COMMON
<br />FACEPLATES FOR CONTROL OF LIGHTING, MOUNTED AT A
<br />MAXIMUM OF 48" AFF. LABEL EACH SWITCH PER AREA SERVED
<br />WITH STATUS INDICATOR, PER ENERGY CODE. REFER TO
<br />ARCHITECTURAL ELEVATIONS FOR ADDITIONAL INFORMATION.
<br />O REUSE EXISTING WALK-IN FREEZER/COOLER LIGHTS.
<br />O INSTALL HOOD LIGHTS THAT ARE SHIPPED LOOSE. VERIFY
<br />CONFIGURATION WITH VENDOR.
<br />FIXTURE MOUNTED ON EXTERIOR WALL ABOVE DOOR. IF NOT
<br />CD
<br />PRESENT, FOR EXTERIOR EGRESS LIGHTING. ASSUMED TO BE
<br />EXISTING. PROVIDE IF NOT PRESENT.
<br />THERE IS NO EXTERIOR DAYLIGHTING ZONE. DAYUGHTING IS NOT
<br />REQUIRED.
<br />THIS PROJECT IS AN INTERIOR REMODEL OF AN EXISTING WALMART STORE
<br />LEASE SPACE. THE SPACE IS BEING DELIVERED TO CONTRACTOR IN AS -IS
<br />CONDITION. ALL WORK TO COMPLETE AND DELIVER A FULLY OPERATIONAL
<br />SPACE IS BY THE G.C. THE G.C. SHALL VISIT THE JOB SITE PRIOR TO BID
<br />AND SHALL SUPPLEMENT WHAT IS SHOWN IN THIS DOCUMENT SET WITH
<br />FIELD OBSERVATIONS TO ENSURE AN ACCURATE BID.
<br />*ALL FIXTURES
<br />SHALL BE
<br />DIMMABLE AND
<br />ALL SHALL BE
<br />PROVIDED WITH
<br />A WALL DIMMER
<br />SWITCH.
<br />TYPICAL
<br />SWITCH
<br />INDICATES (5)
<br />CIRCUIT NUMBER
<br />(�J
<br />FIN. FLOOR
<br />B-2
<br />B-2
<br />B-4
<br />B-4
<br />SPARE
<br />a
<br />a
<br />a
<br />a
<br />a
<br />a
<br />b
<br />C
<br />d
<br />—
<br />LIGHTS � LIGHTS J
<br />(2X4) ACCENT
<br />2 SWITCH BANK O
<br />SCALE: NOT TO SCALE
<br />Q
<br />J
<br />3r
<br />B•
<br />VIA
<br />/ 4"C.
<br />OUTDOORS
<br />U—ti
<br />VI A T/C
<br />�WALMART STORE
<br />LIGHTING PLAN
<br />SCALE: 1 /4" = 1'-0"
<br />Peter A. Leptuch, P.E.
<br />300 N. Carroll Blvd. #20
<br />Denton, TX 76201
<br />(940) 735-5127
<br />w
<br />0
<br />N
<br />StudioRG_
<br />MAIN OFFICE:
<br />1 HUNTINGTON QUADRANGLE
<br />SUITE 2CO3
<br />MELVILLE, NY 11747
<br />P: 631.226-7700 F:631.226.7175
<br />© Copyright 2018: RGBK, INC.
<br />Seal:
<br />Landry
<br />_ GREG LANDRY
<br />AKWEMURE MANNING INTO" DESIGN
<br />1202 Richardson Dr. #'106 Tel. 214.631.6941
<br />Rchardsan, Texas 75080 Fax: 214.634.1814
<br />v��¢,.•�EN3 •fir
<br />No 72679
<br />..a;'. S;pT JF .'441;'
<br />V�
<br />I'�•
<br />Owner:
<br />George Morkos
<br />2520 Colony Reed Lane
<br />Clearwater, FL33763
<br />It is the responsibility of the Construction
<br />Manager/General Contractor and all
<br />Sub -Contractors to verify all dimensions and
<br />accept conditions of prior work by related
<br />trades before proceeding with any work.
<br />Date
<br />07-22-2020
<br />Drawn By Check By
<br />MRP TN
<br />Scale
<br />AS SHOWN
<br />Issued:
<br />Project Title
<br />Charleys
<br />Zephyrhills
<br />WM706
<br />Project Address
<br />7631 Gall Blvd,
<br />Zephyrhills, FL 33541
<br />Project Number
<br />WM706
<br />Drawing Title and Number
<br />LIGHTING PLAN
<br />E2.0