I ELECTRICAL POWER NOTES I
<br />A. ALL ELECTRICAL OUTLETS SHOWN ON THIS PLAN ARE FOR FIXTURES AND EQUIPMENT SPECIFIED AS
<br />FURNISHED BY THE KITCHEN EQUIPMENT CONTRACTOR, UNLESS OTHERWISE NOTED. FOR ANY
<br />ADDITIONAL CONVENIENCE OUTLETS, COORDINATE LOCATION(S) WITH OWNER'S REP.
<br />B. ALL DIMENSIONS, WHERE GIVEN, ARE FROM COLUMN CENTERLINE AND/OR ROUGH WALLS. ELEVATIONS
<br />GIVEN ARE FROM FINISHED FLOOR TO CENTERLINE OF OUTLET. ALL OUTLETS ARE TO BE SET
<br />VERTICALLY UNLESS OTHERWISE REQUIRED BY A.H.J.. ALL 120V OUTLETS NOT DESIGNATED WITH
<br />SPECIFIC LOADS, TO BE RATED AT 15 AMPS MINIMUM.
<br />C. ALL ROUGH —INS SHOWN ARE TO BE RUN INSIDE WALLS, (EXCEPT STUB —UPS). LOCATIONS INDICATED
<br />POINT OF EXIT FROM WALLS, CEILING OR FLOOR. REFER TO KITCHEN EQUIP. DRAWINGS FOR
<br />REQUIREMENTS AND MOUNTING HEIGHTS USE FORE PUTTY TO MAINTAIN FIRE RATINGS.
<br />D. ELECTRICIAN TO BRANCH TO CONNECTION WHERE REQUIRED AND TO CONNECT ALL ELECTRICAL
<br />EQUIPMENT AND FIXTURES AND INSTALL ANY INTERNAL WIRING REQUIRED IN THE FIXTURES
<br />INCLUDING INTERWIRING TO APPLIANCES, APPLIANCE POWER SUPPLIES, ETC. AS REQUIRED BY THE
<br />SPECIFICATIONS AND/OR EQUIPMENT DRAWINGS.
<br />E. ELECTRICAL CONTRACTOR TO VERIFY ELECTRICAL REQUIREMENTS OF ALL OWNER FURNISHED
<br />EQUIPMENT AND MAKE ADJUSTMENTS AS REQUIRED BEFORE ELECTRICAL ROUGH —INS.
<br />F. ALL KITCHEN AND FOOD PREP. ELECTRICAL OUTLET COVER PLATES ARE TO BE STAINLESS STEEL.
<br />THOSE REQUIRED IN BUILDING STRUCTURE ARE TO BE FURNISHED BY THE ELECTRICIAN, WITH
<br />RECEPTACLE. ALL MAIN BREAKER PANELS AND DISCONNECT SWITCHES REQUIRED TO BE FURNISHED
<br />AND INSTALLED BY THE ELECTRICAL CONTRACTOR AT TIME OF INSTALLATION.
<br />G. UNLESS OTHERWISE INDICATED THE ELECTRICAL LOADS SPECIFIED ARE THE CONNECTED LOADS, FUSE
<br />OR CIRCUIT BREAKER SIZE TO BE DETERMINED ACCORDINGLY, BASED UPON APPLICABLE CODE
<br />REQUIREMENTS. OMISSIONS OR ERRORS IN THE SCHEDULE DO NOT RELIEVE ELECTRICAL CONTRACTOR
<br />FROM COMPLETE AND CORRECT FINAL CONNECTION RESPONSIBILITY. REVIEW OF EQUIPMENT
<br />BROCHURE BOOK AND SHOP DRAWINGS WILL ASSURE CORRECTNESS OF THIS WORK.
<br />H. ELECTRICAL CONTRACTOR TO PROVIDE AND INSTALL ALL SWITCHES, STARTERS, DISCONNECTS, ETC.
<br />FOR ALL EQUIPMENT UNLESS NOTED OTHERWISE. ALL DISCONNECTS OR LOCK —OUT DEVICES,
<br />STARTERS, ETC. TO MEET N.E.C. AND O.S.H.A. STANDARDS.
<br />I. RECEPTACLES SHALL BE GROUNDED PER N.E.C. AND O.S.H.A. AND TO HAVE NO GROUND FAULT
<br />PROTECTION, EXCEPT WHEN OUTLET OCCURS WITHIN 6'-0" OF A SINK. RECEPTACLES WITHIN
<br />KITCHEN, AND PREP. AREAS SHALL HAVE GROUND FAULT PROTECTION (GFCI).
<br />J. ELECTRICAL CONTRACTOR TO PROVIDE CONTROL WIRING AND ELECTRICAL SERVICE FOR REMOTE
<br />REFRIGERATION SYSTEMS FOR WALK—IN BOXES, ALSO COORDINATE LOCATION FOR SERVICE WITH THE
<br />ELECTRICAL ENGINEER. INSPECT EXISTING SYSTEM COMPONENTS AND REPAIR/REPLACE AS NEEEDED,
<br />AS APPLICABLE.
<br />K. ELECTRICAL CONTRACTOR TO PROVIDE WRAP AROUND HEATER CABLE (HEAT TRACE) ON ALL
<br />EVAPORATOR DRAIN LINES IN WALK—IN FREEZERS.
<br />L. ELECTRICAL CONTRACTOR TO INSTALL ALL LIGHTS IN WALK—IN COOLER/FREEZER AS REQUIRED, THRU
<br />DOOR SWITCH.
<br />M. ALL THREE (3) PHASE POWER CONNECTIONS TO BE ON A FOUR (4) WIRE SYSTEM, AND ALL SINGLE
<br />(1) PHASE POWER CONNECTIONS TO BE ON A THREE (3) WIRE SYSTEM, UNLESS SPECIFIED
<br />OTHERWISE.
<br />N. ALL WORK, RELATING TO THE INSTALLATION & HOOKUP OF THE SPECIFIED EQUIPMENT, IS TO BE
<br />MEET WITH ALL OTHER GOVERNMENTAL REGULATORY REQUIREMENTS.
<br />0. ELECTRICAL CONTRACTOR IS REQUIRED TO FURNISH AND INSTALL ALL ELECTRICAL COMPONENTS
<br />NECESSARY TO PROVIDE SERVICE TO LOCATIONS & EQUIPMENT SHOWN ON THE DRAWINGS UNLESS
<br />NOTED OTHERWISE. E.C. IS ALSO RESPONSIBLE FOR MAKING FINAL CONNECTIONS TO EQUIPMENT
<br />SUPPLIED AND INSTALLED BY K.E.C.
<br />P. PROVIDE A 4"x4" OUTLET BOX AND OUTLETS WITH 3/4" CONDUIT STUBBED INTO ACCESSIBLE CEILING
<br />WITH PULL CORD FOR EACH TELEPHONE/DATA OUTLET. ALL OUTLETS SHALL BE FULLY INSTALLED
<br />TESTED FOR POLARITY AND IN WORKING ORDER AS PART OF FINISHOUT ELECTRICIAN'S SCOPE.
<br />Q. REFER TO ELECTRICAL RISER DIAGRAM, SHEET E3.0 FOR GROUNDING.
<br />R. ELECTRICAL CONTRACTOR SHALL VERIFY WITH OWNER / SECURITY VENDOR WHETHER SECURITY
<br />J—BOXES REQUIRE HARDWIRING OF CEILING MOUNTED CAMERAS OR RECEPTACLES FOR THE CAMERAS
<br />TO PLUG INTO. SECURITY J—BOXES SHALL BE FLUSH MOUNTED TO CEILING. J—BOX/RECEPTACLE
<br />FACE PLATES IN CEILING SHALL BE WHITE, UNLESS DIRECTED OTHERWISE ON ARCHITECTURAL PLANS.
<br />S. FURROUT WALLS FOR ELECTRICAL AND PLUMBING AS NEEDED, OR WHERE REQUIRED BY LANDLORD
<br />FOR ELECTRICAL AND PLUMBING CONNECTIONS.
<br />T. CONFIRM FINISH OF ELECTRICAL COVERPLATES FOR OUTLETS & SWITCHES WITH ARCHITECTURAL
<br />FINISH SCHEDULES
<br />U. THE ELECTRICIAN SHALL PULL THE LOW VOLTAGE PERMIT IF REQUIRED BY THIS A.H.J.
<br />V. REFER TO SHEET MEP1.0 FOR POWER FOR ROOF —MOUNTED EQUIPMENT.
<br />W. FIRE ALARM DESIGN IS NOT PART OF THE MEP ENGINEER'S SCOPE. THE FIRE ALARM CONTRACTOR
<br />SHALL BE RESPONSIBLE FOR MAKING MODIFICATIONS TO EXISTING FIRE ALARM SYSTEM, INCLUDING
<br />TESTING AND INSPECTING SYSTEM COMPONENTS WITHIN LEASE SPACE SUCH AS DUCT SMOKE
<br />DETECTORS, ETC.
<br />X. THE GENERAL CONTRACTOR SHALL COORDINATE WITH THE KITCHEN APPLIANCE CONTRACTOR AND
<br />SHALL PROVIDE ALL HARDWARE AND CONNECTIONS AS REQUIRED.
<br />Y. ALL ELECTRICAL OUTLETS UNDER HOOD SHALL BE EQUIPPED WITH A SHUNT TRIP BREAKER, OR
<br />EQUAL. INTERLOCK SHUNT WITH ANSUL SYSTEM.
<br />Z. ALL CONDUIT PENETRATIONS THROUGH CASEWORK SHALL BE CLEAN, TIGHT AND SEALED WITH WHITE
<br />SILICONE CAULKING.
<br />AA. TO PROVIDE HANDLE TIE ON ALL MULTIWIRE BRANCH CIRCUITS PER NEC 210.4 (B).
<br />AB. ALL SPARE CIRCUIT BREAKERS AND DISCONNECT SWITCHES SHALL BE LEFT IN THE OFF POSITION.
<br />AC. E.C. SHALL VERIFY THE VOLTAGE AND AMPERAGE REQUIREMENTS OF ALL EQUIPMENT DELIVERED TO
<br />THE SITE PRIOR TO CONNECTION. E.0 SHALL NOTIFY OWNER OF ANY DISCREPANCIES.
<br />AD. PROVIDE (2) PULL STRINGS IN EACH EMPTY CONDUIT FOR DATA/PHONE LINES.
<br />AE. ALL CONDUITS MUST NOT BE MOUNTED ON WALL SURFACES ANYWHERE IN EXPOSED AREAS. ALL
<br />CONDUITS SERVING DEVICES IN EXTERIOR WALLS MUST BE CONCEALED WITHIN WALLS.
<br />AF. COORDINATE ALL LINES TO RUN CONCEALED. PUNCH DOWN BLOCK SHOULD BE ABOVE DROP CEILING.
<br />AG. ALL DATA CABLES TO TERMINATE ON RJ45 CATEGORY 5e JACKS AND WIRE TO EIA/TIA 568—B.1
<br />STANDARDS.
<br />AH. ALL DATA CABLES TO HOMERUN AND TERMINATE ON CATEGORY 5e EIA/TIA 568—B RJ45 PATCH
<br />PANELS THE NETWORK CABINET.
<br />Al. ALL CABLES TO BE CONTINUITY TESTED FOR POLARITY AND CORRECT PIN CONFIGURATION AND
<br />MACHINE LABELED.
<br />AJ. ALL WIRING IN EXPOSED AREAS MUST BE IN RIGID CONDUIT AND SPACED NO LOWER THAN 1 1/2-
<br />BELOW THE DECK. IF TRUSSES, JOISTS, OR BEAMS ARE PRESENT WHICH PROHIBIT CONDUIT RUNNING
<br />TIGHT TO DECK THAN THE CONDUIT MUST BE RAN TIGHT TO THE BOTTOM OF THE TOP CHORD OF
<br />THE STRUCTURAL MEMBER.
<br />AK. ANY PRE—EXISTING MC CABLE EXPOSED MUST BE REPLACED WITH RIGID CONDUIT. CONDUIT AND
<br />J—BOXES MUST NOT BE MOUNTED ON WALL SURFACES ANYWHERE IN EXPOSED AREAS. ALL CONDUIT
<br />SERVING DEVICES IN EXTERIOR WALLS MUST BE CONCEALED WITHIN WALLS.
<br />AL. EXACT LOCATION OF MECHANICAL, PLUMBING, KITCHEN, FURNITURE SYSTEMS, OWNER FURNISHED
<br />EQUIPMENT, ETC THAT REQUIRE ELECTRICAL CONNECTIONS ARE SHOWN ON THE MECHANICAL,
<br />PLUMBING AND/OR ARCHITECTURAL DRAWINGS. COORDINATE EXACT LOCATIONS WITH RESPECTIVE
<br />CONTRACTORS AND/OR VENDORS PRIOR TO ANY ROUGH —INS.
<br />AM. REVIEW AND COORDINATE WITH ALL TRADES CONTRACT DOCUMENTS TO DETERMINE SPECIFIC
<br />MOUNTING LOCATIONS FOR EQUIPMENT WITH ELECTRICAL CONNECTIONS. COORDINATE EXACT
<br />MOUNTING LOCATIONS WITH THE SPECIFIC TRADE AND ARCHITECT.
<br />WIRE SIZING
<br />SCHEDULE
<br />CIRCUIT
<br />BREAKER
<br />COPPER WIRE SIZE
<br />(INCLUDES NEUTRAL)
<br />20
<br />AMP
<br />4#12, #12GR., Y2"C.
<br />25
<br />AMP
<br />4#12, #12GR., Y2"C.
<br />30
<br />AMP
<br />4#10, #1 OGR., 3/4 "C.
<br />35
<br />AMP
<br />4#8, #1 OGR., -Y4"C.
<br />40
<br />AMP
<br />4#8, #1 OGR., 3/4"C.
<br />45
<br />AMP
<br />4#6, #1 OGR., 1 "C.
<br />50
<br />AMP
<br />4#6, #1 OGR., 1 "C.
<br />55
<br />AMP
<br />4#6, #1 OGR., 1 "C.
<br />60
<br />AMP
<br />4#4, #1 OGR., 1Y4"C.
<br />65
<br />AMP
<br />4#4, #8GR., 1Y4"C.
<br />70
<br />AMP
<br />4#4, #8GR., 1Y4"C.
<br />80
<br />AMP
<br />4#3, #8GR., 1Y4"C.
<br />90
<br />AMP
<br />4#2, #8GR., 1 X "C.
<br />100
<br />AMP
<br />4#2, #8GR., 1Y4"C.
<br />125
<br />AMP
<br />4#1, #8GR., 1Y2"C.
<br />150
<br />AMP
<br />4#1 /0, #6GR., 2"C.
<br />200
<br />AMP
<br />4#3/0, #6GR., 2"C.
<br />225
<br />AMP
<br />4#4 0, #4GR., 2 C.
<br />250
<br />AMP
<br />4#250KCM, #4GR., 2 C.
<br />400
<br />AMP
<br />4#600KCM, #3GR., 3Yz"C.
<br />NOTE:
<br />CONTRACTOR TO INCREASE WIRE SIZING FOR
<br />LONG RUNS OF WIRING FOR VOLTAGE DROP
<br />ALLOWANCE. VOLTAGE DROP SHALL NOT
<br />EXCEED 3 PERCENT.
<br />POWER REOUIREMENTS FOR WALK-IN COOLER AND FREEZER:
<br />INSTALL WALK—IN COOLER AND CHILLER (FREEZER) PER MANUFACTURER'S INSTALLATION
<br />INSTRUCTIONS. ADJUST NUMBER AND SIZE OF BREAKERS AS NEEDED. VERIFY BREAKER AND
<br />DISCONNECT PER MANUFACTURER'S NAMEPLATE INFORMATION. PROVIDE ALL NECESSARY AND
<br />REQUIRED CABLES AND CONNECTIONS.
<br />G.C. TO VERIFY ALL SPECIFICATION INSTALLATION REQUIREMENTS FOR WALK—IN COOLER /
<br />FREEZER WITH OWNER. LOCATION AND INSTALLATION OF CONDENSER UNITS VARY PER
<br />WALK—IN UNIT SIZE AND WITH BUILDING STRUCTURAL CAPACITY.
<br />WHERE EXISTING WALK—INS ARE BEING REUSED, VERIFY NAMEPLATE DATA AND INSPECT POWER
<br />SUPPLY. UPGRADE/REPAIR AS NECESSARY. A W.I.0 CONSULTANT SHALL BE HIRED TO FULLY
<br />SERVICE WALK INS AND BRING TO FULL —WORKING ORDER.
<br />POWER LEGEND
<br />MARK
<br />DESCRIPTION
<br />DUPLEX OUTLET AT 18" A.F.F.
<br />(U.N.O.)
<br />SPECIALTY PLUG — OTHER
<br />-e
<br />THAN 11OV. REFER TO PANEL
<br />SCHEDULE.
<br />QUAD OUTLET AT 18" A.F.F.
<br />(U.N.O.)
<br />J—BOX
<br />E::1
<br />ELECTRICAL DISCONNECT
<br />PHONE
<br />D
<br />DATA
<br />NOTES BY SYMBOL:
<br />OPANELS 'A', 'B' ARE EXISTING AND OPEN INTO ROOM. REUSE
<br />IN PLACE.
<br />O24"x24"0/4" PLYWOOD SHELF AT HEIGHT INDICATED PER
<br />PLANS WITH DUPLEX RECEPTACLE FOR TELEPHONE SYSTEM.
<br />ELECTRICAL CONTRACTOR TO PROVIDE TELEPHONE CONDUIT
<br />FROM LANDLORD'S DEMARC AS NEEDED.
<br />OALL 15A AND 20A 120V OUTLETS IN KITCHEN AND PREP
<br />AREA AND ALL OUTLETS WITHIN 6 FEET OF THE OUTSIDE
<br />EDGE OF A SINK TO BE GFCI PROTECTED, PER NEC 210.8(B).
<br />O4 CONTRACTOR SHALL INTERLOCK EF-1 AND RTU(S) (FANS),
<br />SO THAT FANS (AND O.A. SUPPLY) RUN CONTINUOUSLY
<br />WHEN EF-1 IS OPERATING. THE RTU COMPRESSORS SHALL
<br />CYCLE AS NEEDED.
<br />OEF-1 SHALL BE ROOF —MOUNTED TYPE. REFER TO M1.0,
<br />MEP1.0 FOR ADDITIONAL INFORMATION.
<br />O6 ISOLATED GROUND RECEPTACLE.
<br />OWALK—IN COOLERS ARE EXISTING TO REMAIN. ELECTRICAL
<br />CONTRACTOR MAY REUSE EXISTING BREAKERS WHERE
<br />POSSIBLE.
<br />O8 PROVIDE INSECT CONTROL (FLY LIGHT) RECEPTACLE AT 84"
<br />AFF.
<br />Og FURROUT WALLS FOR POWER AS NECESSARY.
<br />10 POWER FOR EXISTING WALK—INS IS ESTIMATED. CONFIRM
<br />AND REUSE EXISTING POWER SUPPLY, EXCEPT UPGRADE IF
<br />FOUND TO NOT CONFORM TO EQUIPMENT NAMEPLATE DATA.
<br />11 POWER FOR EXISTING EVAPORATOR COILS DERIVED FROM
<br />MAC UNIT. REFER TO SHEET MEP 1.0 FOR CIRCUITS AND
<br />ADDITIONAL DETAILS. NO CHANGES EXPECTED TO THIS
<br />EXISTING EQUIPMENT.
<br />ELECTRICAL POWER NOTES (CONTINUED)
<br />AN. MINIMUM CONTRACTOR SIZE FOR 120V BRANCH CIRCUITS SHALL BE
<br />12—AWG. FOR 120V BRANCH CIRCUITS WITH HOMERUNS OVER 100
<br />LINEAR FEET, A MINIMUM WIRE SIZE OF 10—AWG SHALL BE
<br />PROVIDED FROM FIRST JUNCTION/OUTLET BOX TO BRANCH CIRCUIT
<br />PANELBOARD.
<br />AO. ALL WIRING SHALL BE IDENTIFIED BY PANELBOARD AND CIRCUIT
<br />NUMBER(S) IN ALL CABINETS,
<br />JUNCTION BOXES, WIRING TROUGHS, ENCLOSURES, SPLICE OR
<br />TERMINATION POINTS, ETC.
<br />AP. TYPED PANELBOARD DIRECTORY CARD SHALL BE PROVIDED FOR ALL
<br />PANELS INSTALLED UNDER
<br />THIS CONTRACT. NEW DIRECTORY CARDS SHALL BE LOCATED ON THE
<br />INSIDE DOOR OF ASSOCIATED
<br />PANELS.
<br />AQ. IN THE EVENT THAT EXTRA BREAKER SPACES ARE NEEDED, THE E.C.
<br />SHALL USE CONTACTOR(S) IN
<br />LEIU OF SHUNT TRIP BREAKERS TO DISCONNECT POWER FOR
<br />EQUIPMENT BENEATH THE HOOD.
<br />AR. PROVIDE POWER FOR SPEAKERS BASED ON OWNER'S FINAL A/V
<br />PACKAGE. A/V RECEIVER TO BE AT MANAGER'S DESK.
<br />AS. CONTRACTOR SHALL COORDINATE ALL ELECTRICAL CONNECTIONS AND
<br />ENSURE ALL OUTLETS ARE INSTALLED WITHIN REACH OF THE
<br />CORD/PLUG OF THE EQUIPMENT INTENDED TO SERVE.
<br />r/
<br />a
<br />J
<br />3
<br />HOMERUNS AND
<br />BRANCH
<br />WIRING
<br />FOR 20 AMP CIRCUITS
<br />SHALL
<br />BE
<br />AS FOLLOWS:
<br />LENGTH CIRCUIT
<br />WIRE
<br />SIZE
<br />HOMERUN
<br />WIRE SIZE
<br />1FT
<br />TO
<br />50FT
<br />NO.12
<br />AWG
<br />NO.12
<br />AWG
<br />51 FT
<br />TO
<br />75FT
<br />NO.12
<br />AWG
<br />NO.10
<br />AWG
<br />76FT
<br />TO
<br />120FT
<br />NO.10
<br />AWG
<br />NO.8
<br />AWG
<br />121 FT
<br />TO
<br />19OFT
<br />NO.10
<br />AWG
<br />NO.6
<br />AWG
<br />191FT
<br />TO
<br />30OFT
<br />NO.10
<br />AWG
<br />NO.4
<br />AWG
<br />WALMART STORE
<br />PLAN
<br />NORTH
<br />1 POWER PLAN
<br />SCALE: 1/4" = 1'-0"
<br />:5
<br />Peter A. Leptuch, P.E.
<br />300 N. Carroll Blvd. #200
<br />Denton, TX 76201
<br />(940) 735-5127
<br />r/
<br />w
<br />0
<br />Q
<br />J
<br />3
<br />!HEAD SOFFIT
<br />TYP. FOR ALL
<br />MONITOR/ TVS.
<br />StudioRG,._
<br />MAIN OFFICE:
<br />1 HUNTINGTON QUADRANGLE
<br />SUITE 2CO3
<br />MELVILLE, NY 11747
<br />P: 631.226-7700 F: 631.226.7175
<br />© Copyright 2018: RGBK, INC.
<br />Lan,dry
<br />ARCHfTECfURE PLANNING INFO" DESIGN
<br />1202 Richardson Dr. #106 Tel: 214.631.6941
<br />Richardson, Texas 75080 Fax: 214.634-1814
<br />Seal:
<br />Owner:
<br />George Morkos
<br />2520 Colony Reed Lane
<br />Clearwater, FL33763
<br />It is the responsibility of the Construction
<br />Manager/General Contractor and all
<br />Sub -Contractors to verify all dimensions and
<br />accept conditions of prior work by related
<br />trades before proceeding with any work.
<br />Date
<br />07-22-2020
<br />Drawn By Check By
<br />MRP TN
<br />Scale
<br />AS SHOWN
<br />Issued:
<br />Project Title
<br />Charleys
<br />Zephyrhills
<br />WM706
<br />Project Address
<br />7631 Gall Blvd,
<br />Zephyrhills, FL 33541
<br />Project Number
<br />WM706
<br />Drawing Title and Number
<br />POWER PLAN
<br />E1.0
<br />
|