1" TEE WITH PLUG
<br />FIRE PROTECTION CONTRACTOR
<br />SHALL INSTALL PIPE THROUGH
<br />HOLE RESERVED FOR
<br />SPRINKLER INSTALLATION.
<br />NOTE TO CONTRACTOR:
<br />PROVIDE A SIGN WITH THE
<br />FOLLOWING STATEMENT AND
<br />ATTACH TO THE TOP OF THE
<br />AUTOMATED EQUIPMENT.
<br />"FLEXIBLE DROP IS
<br />PRESSURIZED. PRIOR TO
<br />REMOVING FIRE SPRINKLER
<br />DRAIN FIRE PROTECTION
<br />SYSTEM AND 1" DROP"
<br />L L = W/4, 4" MIN
<br />NOTES:
<br />1. SPIN -IN FITTINGS W/ SCOOPS ARE NOT
<br />ACCEPTABLE.
<br />2. REF PLANS FOR RUNOUT SIZES.
<br />3. 450 LEAD IN.
<br />SELF TAPPING
<br />SCREWS
<br />BRANCH DUCT FITTING
<br />12" = 1'-0"
<br />SUPPLY FROM WET
<br />PIPE SPRINKLER SYSTEM INSTITUTIONAL MODEL
<br />FLEXIBLE SPRINKLER DROP
<br />CORRUGATED STAINLESS
<br />STEEL HOSE WITH STAINLESS
<br />STEEL BRAID 4' LENGTH.
<br />WALL PLATE
<br />DO NOT ATTACH TO UNIT
<br />ADJUSTABLE HUB MULTI -PORT BRACKET INSTALL AS LOW AS
<br />POSSIBLE INSTALL AS LOW AS POSSIBLE
<br />METAL STUD E). APPROPRIATE
<br />RIGID SURFACE).
<br />I
<br />IS
<br />1"
<br />PENDENT SPRINKLER
<br />NO ESCUTHEON
<br />REQUIRED
<br />PHARMACY CEILING
<br />3"
<br />LOADS MUST BE HUNG
<br />WITHIN 3" OF PANEL
<br />POINTS OF EXISTING
<br />STRUCTURAL JOISTS -
<br />TOP BEAM
<br />CLAMP TYP
<br />TOP CHORD OF JOIST
<br />ROOF
<br />THREADED ROD
<br />TYP
<br />RECTANGULAR DUCT -J �-2"x2"x1/4" ANGLE
<br />BOTTOM OF OR 1 5/8"x1 5/8"
<br />STRUCTURE RECTANGULAR DUCT UNISTRUT
<br />PERPENDICULAR TO STRUCTURE
<br />OPTIONAL ROUTING IN
<br />CONCEALED AREAS -1
<br />HEALTH SERVICES
<br />CEILING DIFFUSER --
<br />SUPPLIED AND INSTALLED
<br />BY PANEL MANUFACTURER
<br />12"x12" FACE SIZE
<br />8" ROUND NECK
<br />SIMILAR TO TITUS TDC
<br />150 CFM
<br />FINAL DUCTWORK CONNECTION
<br />TO PRE -INSTALLED DIFFUSER
<br />BY GENERAL CONTRACTOR
<br />SPRINKLER HEAD SUPPLIED
<br />AND INSTALLED BY PANEL
<br />MANUFACTURER
<br />CEILING RETURN GRILLE -
<br />SUPPLIED AND INSTALLED
<br />BY PANEL MANUFACTURER
<br />12"x12" FACE SIZE
<br />8" ROUND NECK
<br />SIMILAR TO TITUS 50F
<br />150 CFM
<br />BOTTOM OF
<br />STRUCTURE
<br />TWIST STRAP
<br />16 GAUGE GALV STEEL
<br />BAND (2" WIDE)
<br />ROUND DUCT
<br />3"
<br />LOADS MUST BE HUN
<br />WITHIN 3" OF PANEL
<br />POINTS OF EXISTING
<br />STRUCTURAL JOISTS
<br />ROUND SUPPLY
<br />AIR DUCT
<br />450 LOAD RATED
<br />FASTENERS
<br />ROOF
<br />2"x7x1/4" ANGLE
<br />OR 1 5/8"x1 5/8"
<br />6" UNISTRUT
<br />lo
<br />HANGER STRAP -
<br />1" MIN.
<br />60" MAX.
<br />L•J
<br />SHEET METAL
<br />SCREWS TYP
<br />RECTANGULAR DUCT
<br />PARALLEL TO STRUCTURE
<br />LOAD RATED
<br />FASTENERS
<br />ROOF
<br />L-9
<br />ANGLE OR
<br />1 5/8"x1 5/8" UNISTRUT
<br />DUCT SUPPORT BAND
<br />SAME SIZE AS STRAP
<br />a2"x2"x1/4"
<br />010
<br />0�
<br />�6°
<br />45°
<br />SUPPLY REGISTER, REF FLOOR PLAN FOR SIZE AND
<br />LOCATION, MOUNT REGISTERS @ 30 DEGREE ANGLE
<br />DOWN FROM HORIZONTAL IN STOCKROOM AREA AND
<br />@ 15 DEGREE ANGLE DOWN FROM HORIZONTAL IN
<br />SALES AREA, EXCEPT THOSE SHOWN ON BOTTOM OF
<br />DUCT ON THE PLAN
<br />PERPENDICULAR TO JOIST
<br />PARALLEL TO JOIST
<br />DUCT SUPPORT AND GRILLE
<br />12" = V-0"
<br />INSTALL DAMPER IN VERTICAL
<br />AT 24" MAX ABOVE CEILING
<br />BALANCE TO 930 CFM _
<br />REMOVE DIFFUSER
<br />AND PORTION OF
<br />EXISTING DUCTWORK
<br />SHOWN DASHED
<br />RTU
<br />ETR
<br />GENERAL NOTES
<br />1. THE DESIGN SHOWN ON THESE CONTRACT
<br />DOCUMENTS HAS BEEN PREPARED FOR APPROVAL
<br />BY THE AUTHORITY HAVING JURISDICTION AND TO
<br />PROVIDE GUIDANCE FOR BIDDING. SUBMIT
<br />COMPLETE FIRE SPRINKLER SHOP DRAWINGS AS
<br />REQUIRED BY CONTRACT DOCUMENTS TO THE
<br />OWNERS DESIGNATED REVIEWERS. BASE
<br />SPRINKLER DESIGN UPON THESE DRAWINGS AND
<br />AS REQUIRED BY THE SPECIFICATIONS. SHOP
<br />DRAWINGS MUST INCLUDE ELEVATIONS, HANGER
<br />LOCATIONS, PIPE LENGTHS, DIMENSIONS,
<br />FABRICATIONS METHODS, MATERIAL DATA, AND
<br />ADDITIONAL INFORMATION NECESSARY TO CLARIFY
<br />THE INTENT OF INSTALLATION. CONTRACTOR SHALL
<br />PROVIDE PIPE SIZE, SPRINKLER SPACING, AND
<br />SYSTEM CONFIGURATION AS SHOWN. ALTERNATE
<br />MATERIALS MUST BE SENT TO THE FIRE
<br />PROTECTION ENGINEER OF RECORD OR VIA THE RFI
<br />PROCESS AND MUST BE APPROVED IN RECORD
<br />DOCUMENTS PRIOR TO BID.
<br />2. COORDINATE LOCATIONS OF FIRE PROTECTION
<br />COMPONENTS, INCLUDING PIPING, ALARMS, DRAINS,
<br />TEST POINTS, ETC. WITH ARCHITECTURAL,
<br />STRUCTURAL, MECHANICAL, AND ELECTRICAL
<br />COMPONENTS. OBSTRUCTION TO SPRINKLER
<br />DISCHARGE MUST BE CONSIDERED DURING SHOP
<br />DRAWING PRODUCTION AND INSTALLATION;
<br />ADDITIONAL SPRINKLERS MAY BE REQUIRED AT NO
<br />ADDITIONAL COST TO OWNER. REFER TO
<br />SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
<br />3. CONTRACTOR MUST VISIT THE BUILDING SITE TO
<br />DETERMINE THE FULL EXTENT OF THE EXISTING
<br />FIRE PROTECTION WORK AND EXISTING
<br />CONDITIONS, BECOME TOTALLY FAMILIAR WITH THE
<br />DISCONNECTIONS, REMOVALS, RELOCATIONS
<br />AND/OR RECONNECTIONS OF EXISTING FIRE
<br />PROTECTION EQUIPMENT REQUIRED, AND
<br />CONDITIONS IN THE PROPOSAL FOR THIS PROJECT.
<br />NO EXTRA COMPENSATION WILL BE PAID FOR LACK
<br />OF SUCH DETERMINATION, FAMILIARIZATION,
<br />AND/OR ALLOWANCE.
<br />4. SUBMIT A REQUEST FOR INFORMATION FOR
<br />QUESTIONS REGARDING THE FIRE PROTECTION
<br />DOCUMENTS PER RFI PROCESS LOCATED IN THE
<br />FIRE PROTECTION SPECIFICATIONS.
<br />5. NEUTRALIZATION WALLS, IF PROVIDED, ARE SHOWN
<br />ON THE ARCHITECTURAL DRAWINGS. REFER TO
<br />MECHANICAL DRAWINGS FOR NEUTRALIZATION
<br />WALL PENETRATION DETAIL.
<br />6. PENETRATIONS OF "RATED ASSEMBLIES" SHALL BE
<br />FIRE STOPPED WITH AN APPROVED MATERIAL PER
<br />METHODS REQUIRED BY PROJECT SPECIFICATIONS
<br />AND THE AUTHORITY HAVING JURISDICTION.
<br />MECHANICAL SYMBOLS
<br />18"x12"
<br />RECTANGULAR DUCT 18" WIDE
<br />BY 12" DEEP
<br />12" 0
<br />12" DIAMETER ROUND DUCT
<br />SUPPLY DUCT IN SECTION
<br />RETURN OR EXHAUST DUCT IN
<br />SECTION
<br />ELBOW WITH TURNING VANES
<br />TEE WITH TURNING VANES
<br />ROUND (OR OVAL) ELBOW
<br />VOLUME/BALANCE DAMPER
<br />SUPPLY AIR DIFFUSER WITH
<br />ROUND SUPPLY DUCT
<br />RETURN OR EXHAUST AIR DIFFUSER
<br />WITH ROUND DUCT
<br />24"x24"
<br />CD
<br />450
<br />BRANCH DUCT AND/OR NECK SIZE
<br />DIFFUSER OR GRILLE TYPE
<br />CFM
<br />0
<br />THERMOSTAT
<br />@S
<br />TIMER
<br />O
<br />TEMPERATURE SENSOR
<br />CONNECT TO EXISTING
<br />ETR
<br />EXISTING TO REMAIN
<br />FD
<br />FIRE DAMPER
<br />EXISTING CONDITIONS WERE TAKEN FROM
<br />ORIGINAL DRAWINGS AND MAY NOT REFLECT
<br />EXACT "AS -BUILT" CONDITIONS. CONTRACTOR
<br />SHALL FIELD VERIFY ALL EXISTING CONDITIONS
<br />PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR
<br />SHALL CAREFULLY COORDINATE NEW WORK AND
<br />DEMOLITION WITH ALL OTHER DISCIPLINES AND
<br />EXISTING CONDITIONS.
<br />GENERAL NOTES CONT.
<br />7. THE FIRE PROTECTION ENGINEER OF RECORD
<br />SHALL NOT BE RESPONSIBLE FOR THE
<br />CONTRACTOR'S FAILURE TO CARRY OUT THE
<br />CONSTRUCTION WORK IN ACCORDANCE WITH THE
<br />CONTRACT DOCUMENTS, NOR SHALL THEY BE
<br />REQUIRED TO SUPERVISE THE CONDUCT OF THE
<br />WORK, THE CONSTRUCTION PROCEDURES
<br />FOLLOWED BY THE CONTRACTOR,
<br />SUBCONTRACTORS, THEIR RESPECTIVE
<br />EMPLOYEES OR ANY OTHER PERSON AT THE JOB
<br />SITE OTHER THAN THAT OF THE ENGINEERING
<br />FIRM'S EMPLOYEES.
<br />8. CONTRACTOR MUST REVIEW ALL CONSTRUCTION
<br />DOCUMENTS PRIOR TO BID. SHOULD
<br />MODIFICATIONS TO THESE PLANS BECOME
<br />NECESSARY TO PROPERLY COORDINATE THE
<br />SYSTEM WITH ALL OTHER TRADES, IT WILL BE THE
<br />CONTRACTOR'S RESPONSIBILITY TO OBTAIN
<br />APPROVAL OF THE CHANGES FROM BOTH THE
<br />AUTHORITY HAVING JURISDICTION AND THE
<br />OWNER'S DESIGNATED REVIEW CONSULTANT IN
<br />ADDITION TO OBTAINING THE NECESSARY
<br />APPROVALS, THE CONTRACTOR MUST MAKE NOTE
<br />OF ANY FIELD OR COORDINATION CHANGES ON THE
<br />INSTALLATION DRAWINGS, AND THEN MUST
<br />PROVIDE A SET OF AS -BUILT DRAWINGS ONCE
<br />COMPLETE.
<br />9. CONTRACTOR MUST VERIFY ALL DROP DOWN
<br />LOCATIONS AT EXTERIOR WALLS WITH THE
<br />PROJECT MANAGER PRIOR TO INSTALLATION.
<br />10. ALL PIPING MUST BE COORDINATED AROUND
<br />FRAMING MEMBERS AND PROPERLY INSTALLED
<br />INSIDE THE BAR JOIST.
<br />11. CONTRACTOR SHALL ROUTE PIPING AROUND ALL
<br />OBSTRUCTIONS AND PROVIDE SPRINKLER
<br />PROTECTION UNDER OBSTRUCTIONS, AS DETAILED
<br />IN NFPA 13 STANDARDS AS PART OF THE FIELD
<br />COORDINATION AT NO ADDITIONAL COST TO
<br />OWNER.
<br />12. ALL SPRINKLER DEFLECTOR DISTANCE
<br />REQUIREMENTS SHALL BE IN ACCORDANCE TO THE
<br />STANDARDS OUTLINED IN NFPA 13.
<br />13. ALL PIPING PASSING THROUGH CMU WALLS SHALL
<br />BE INSTALLED WITH ONE INCH CLEARANCE ON ALL
<br />SIDES. (CORE DIAMETER EQUAL TO PIPE +2"). ALL
<br />CORES SHALL BE COORDINATED WITH STRUCTURAL
<br />REINFORCING. CONTRACTOR IS RESPONSIBLE FOR
<br />PROVIDING ALL CORING WITH PROPER CLEARANCE
<br />AT ALL CMU WALLS. GENERAL CONTRACTOR SHALL
<br />BE RESPONSIBLE FOR PROVIDING A TWO INCH
<br />CLEARANCE AROUND ALL PIPING PASSING
<br />THROUGH CONCRETE SLABS. THE SPRINKLER
<br />CONTRACTOR SHALL FILL ALL CLEARANCES WITH
<br />APPROVED MASTIC.
<br />14. PROVIDE FLUSHING CONNECTIONS IN ACCORDANCE
<br />WITH THE STANDARDS OUTLINED IN NFPA 13.
<br />15. PROVIDE ALL NECESSARY OFFSETS, RISES OR
<br />DROPS IN PIPING AND AUXILIARY DRAINS REQUIRED
<br />BY BUILDING CONDITIONS.
<br />16. EXAMINE THE JOB CONDITIONS AND VERIFY ALL
<br />MEASUREMENTS, DISTANCES, ELEVATIONS,
<br />CLEARANCES, ETC.
<br />17. ARCHITECTURAL AND ELECTRICAL BACKGROUND
<br />INFORMATION IS SHOWN FOR COORDINATION
<br />PURPOSES ONLY. REFER TO THE CONTRACT
<br />DOCUMENTS FOR LOCATIONS, SIZES AND
<br />QUANTITIES OF OTHER TRADE WORK.
<br />18. SPRINKLER SPACING SHALL BE PER NFPA 13
<br />UNLESS OTHERWISE NOTED ON PLANS AND/ OR
<br />PROTECTION CRITERIA LEGEND.
<br />19. INTERFACE SPRINKLER SYSTEM WITH FIRE
<br />PROTECTION SUPERVISORY SYSTEM.
<br />20. ALL MATERIALS SHALL BE UL LISTED OR FM
<br />APPROVED. SPRINKLER PIPE SHALL BE
<br />MANUFACTURED TO STANDARDS RECOGNIZED BY
<br />NFPA 13., THREADED PIPE SHALL HAVE A
<br />CORROSION RESISTANCE RATING OF 1.0 OR
<br />GREATER. CRIMP -TYPE COUPLINGS SHALL NOT BE
<br />USED. THREADABLE THINWALL PIPE WITH
<br />CORROSION RESISTANCE RATING OF LESS THAN 1.0
<br />SHALL BE USED ONLY WITH ROLL GROOVE FITTINGS.
<br />21. IF REQUIRED, PROVIDE 24 VOLT AC, ELECTRIC BELL,
<br />MODEL NO. PBA248, ELECTRIC BELL BY POTTER
<br />ELECTRIC SIGNAL OF ST. LOUIS, MISSOURI, LOCATE
<br />AS REQUIRED BY AUTHORITIES HAVING
<br />JURISDICTION. PROVIDE NEW DOUBLE POLE VANE
<br />TYPE FLOW DETECTOR, MODEL NO. VSR-F, BY
<br />POTTER ELECTRIC SIGNAL OF ST. LOUIS, MISSOURI.
<br />SET ADJUSTABLE DELAYED SIGNAL AT 30 SECONDS.
<br />MOUNT WATER FLOW INDICATORS NO HIGHER THAN
<br />6 FEET ABOVE FINISH FLOOR.
<br />22. ALL SPRINKLER SYSTEMS THAT ARE TO BE
<br />MODIFIED SHALL BE HYDROSTATICALLY TESTED PER
<br />NFPA 13 PRIOR TO SPRINKLER SYSTEM
<br />MODIFICATION AND SHALL BE RE -HYDROSTATICALLY
<br />TESTED AFTER COMPLETION OF WORK.
<br />23. DO NOT HANG OR SUPPORT ANY LOADS OR MAKE
<br />ANY ATTACHMENTS TO THE METAL ROOF DECK OR
<br />JOIST BRIDGING.
<br />24. SAMMY SCREWS ARE NOT PERMITTED.
<br />25. CEILING FLANGES ARE NOT PERMITTED.
<br />26. PROVIDE RETAINING STRAPS ON HANGERS WHERE
<br />REQUIRED.
<br />27. CONTRACTOR IS TO COORDINATE FINAL SPRINKLER
<br />HEAD LOCATIONS AND PIPE ROUTING SUCH THAT
<br />THEY DO NOT INTERFERE WITH NOR RECEIVE
<br />DAMAGE FROM THE NORMAL OPERATIONS OF THE
<br />AREA.
<br />28. THE CONTRACTOR SHALL DIVERT ALL DRAINS AND
<br />INSPECTORS TEST CONNECTION DISCHARGE AWAY
<br />FROM FINISHED SURFACES AND PIPE TO APPROVED
<br />DRAIN LOCATIONS. ROUTE DISCHARGE TO NEARBY
<br />GREENSPACE OR STORM WATER DRAIN BY USE OF
<br />BACKWASH HOSE.. THE CONTRACTOR WILL BE
<br />BACKCHARGED FOR ANY REPAIR, REPLACEMENT,
<br />OR CLEANING OF RUST STAINS ON
<br />PAVEMENT,/CONCRETE DUE TO WATER DISCHARGE
<br />FROM SPRINKLER SYSTEM DRAINS.
<br />EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING
<br />A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
<br />SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
<br />TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
<br />NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
<br />THE WORK PROPERLY. NO ADDITIONAL
<br />COMPENSATION SHALL BE ALLOWED BECAUSE OF
<br />CONDITIONS THAT OCCUR DUE TO FAILURE TO
<br />FAMILIARIZE WORKERS WITH THIS KNOWLEDGE.
<br />p+enb2
<br />hitecture
<br />ginee(ng
<br />2809 Ajax Avenue Suite 100
<br />Rogers Arkansas 72758
<br />Phone: 479.636.3545
<br />Fax: 479.636.1209
<br />Engineer of Record
<br />Joshua Dale McCall, P.E.
<br />Florida License No. 79905
<br />COA License No. 26880
<br />w uw w �"6w
<br />w Do Wwop>
<br />�
<br />co O W,-) aw""R�
<br />J ww�z�-aazm
<br />w w
<br />wz
<br />F-tnLLlllLLp�p W�
<br />wa~¢g�awaaiom
<br />0 ��c�Zza�W��=a>
<br />U_ aFEmaot-O=>a~�
<br />z <990 -u we oW�o=p
<br />~ ZdJ�oot,TwFQp
<br />�Qia-w��w`no�ZN
<br />0 w 0-JUtgJ�Wp0E
<br />4 pOiww¢�x�QMzacwn=g
<br />~ T U)W oQ p cr U. X W U Uj W WS2
<br />� HpNUpwmoWmJwKa1-
<br />m
<br />H
<br />z
<br />J
<br />Cl)
<br />z
<br />0
<br />U
<br />N
<br />rn
<br />00
<br />Q
<br />CD C:D
<br />Q
<br />0 O
<br />0
<br />LjL
<br />0
<br />ti
<br />O
<br />0
<br />m
<br />N
<br />o
<br />w
<br />O
<br />J
<br />o
<br />a
<br />J
<br />J
<br />Q
<br />z
<br />w
<br />N=
<br />LL
<br />COO
<br />00
<br />o
<br />O
<br />CL
<br />N
<br />N
<br />w
<br />N
<br />w
<br />m
<br />0
<br />z
<br />m
<br />0
<br />ISSUE BLOCK
<br />CHECKED BY:
<br />JDM
<br />DRAWN BY:
<br />CMW
<br />PROTO:
<br />192
<br />PROTO CYCLE:
<br />08-27-21
<br />DOCUMENT DATE:
<br />10-01-21
<br />�Q N - E MCC'9
<br />No. 79905
<br />0 STATE of
<br />�ORIDP �k
<br />10/5/2021
<br />DOCUMENTS THAT DO NOT
<br />HAVE THE ARCHITECT OR
<br />ENGINEER OF RECORD SEAL
<br />AND SIGNATURE SHALL BE
<br />CONSIDERED NOT FOR
<br />CONSTRUCTION
<br />ENLARGED
<br />MECHANICAL
<br />PLANS
<br />PENDENT SPRINKLER WITH FLEXIBLE PIPING
<br />12" = 1'-0"
<br />PHARMACY HVAC- PLAN
<br />1/4" = 1'-0"
<br />SHEET:
<br />m 1
<br />
|