ELECTRICAL SYMBOLS GENERAL MODULAR NOTES
<br />LEGEND
<br />04.24.20
<br />(SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS)
<br />1. COORDINATE AREA OF EXISTING CEILING GRID TO
<br />SYMBOL DESCRIPTION BE REPLACED WITH GENERAL CONTRACTOR.
<br />LIGHT FIXTURE COORDINATE ANY REQUIRED ELECTRICAL WORK
<br />FO =1/0 O (WALL MOUNTED/CEILING MOUNTED) INCLUDING REMOVAL OF EXISTING FIXTURES.
<br />MAINTAIN EXISTING LAYOUT, CIRCUITRY, AND
<br />CONTROLS UNLESS OTHERWISE NOTED.
<br />O
<br />LIGHT FIXTURE
<br />LIGHT FIXTURE,
<br />NIGHT LIGHT
<br />2
<br />VOLUMETRIC LIGHT FIXTURE
<br />3
<br />17
<br />ZA
<br />TRACK LIGHTING
<br />/ ®
<br />EXIT FIXTURE
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />4
<br />/ coy
<br />EMERGENCY LIGHT
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />aN /
<br />EMERGENCY LIGHT REMOTE HEADS
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />SINGLE POLE SWITCH
<br />$3
<br />3-WAY SWITCH
<br />5
<br />$4
<br />4-WAY SWITCH
<br />$K
<br />KEYED SWITCH
<br />6
<br />$D
<br />DIMMER SWITCH
<br />*VS
<br />VARIABLE SPEED SWITCH
<br />$M
<br />MANUAL MOTOR SWITCH
<br />$0S
<br />SINGLE POLE OCCUPANCY
<br />SENSOR SWITCH
<br />$OS2
<br />DOUBLE POLE OCCUPANCY
<br />SENSOR SWITCH
<br />(
<br />( OS )
<br />CEILING MOUNTED OCCUPANCY
<br />SENSOR SWITCH, FOUR -DIRECTION
<br />SENSING
<br />7.
<br />LIGHT FIXTURE SCHEDULE
<br />"OW" FIXTURES AND LAMPS ARE FURNISHED BY THE OWNER FOR INSTALLATION BY THE CONTRACTOR. "GC" FIXTURES AND LAMPS ARE FURNISHED AND INSTALLED BY THE CONTRACTOR.
<br />TYPE
<br />SUPPLIED
<br />BY
<br />DESCRIPTION
<br />VENDOR /
<br />MANUFACTURER
<br />MODEL
<br />VOLTAGE
<br />INPUT
<br />VA
<br />COLOR
<br />TEMP
<br />LIGHT SOURCE
<br />LAMP
<br />QTY
<br />MOUNTING
<br />COUNT
<br />9
<br />OW
<br />2' x 2' VOLUMETRIC TROFFER
<br />CREE INC
<br />ZR22C-40L-40K-10V-FD
<br />120/277
<br />32 VA
<br />4000K
<br />INTEGRAL LED
<br />RECESSED
<br />2
<br />17
<br />OW
<br />EMERGENCY LIGHT
<br />REXEL INC
<br />EVHC61DP-WM
<br />120/277
<br />3 VA
<br />-
<br />INTEGRAL LED
<br />-
<br />WALL
<br />1
<br />COORDINATE WITH GENERAL CONTRACTOR FOR
<br />PHARMACY DEMOLITION REQUIREMENTS.
<br />ELECTRICAL CONTRACTOR TO COORDINATE WITH
<br />GENERAL CONTRACTOR ON ACTUAL PHASING OF
<br />PHARMACY CONSTRUCTION. REUSE EXISTING
<br />COUNTER BRANCH CIRCUITRY AS MUCH AS
<br />POSSIBLE.
<br />ELECTRICAL CONTRACTOR TO RELOCATE ALL
<br />DRIVE THRU EQUIPMENT POWER AND DATA AS
<br />REQUIRED. COORDINATE WITH GENERAL
<br />CONTRACTOR AND CONSTRUCTION
<br />MANAGER.PROVIDE LISTED HANDLE -TIE BETWEEN
<br />FRONT COUNTER CIRCUIT BREAKERS THAT SHARE
<br />COMMON NEUTRAL FOR SIMULTANEOUS TRIP.
<br />PHARMACY REFRIGERATION SYSTEMS TO REMAIN
<br />ENERGIZED DURING ALL PHASES OF
<br />CONSTRUCTION.
<br />PHARMACIST BENCH CAN BE RELOCATED PER THE
<br />FOLLOWING MAXIMUM DIMENSIONS, AS NEEDED
<br />TO RELOCATE THE POWER POLE THAT IS PLACED
<br />OPPOSITE END OF BENCH FROM HEALTH SERVICE
<br />ROOM TO MISS OBSTRUCTIONS IN THE CEILING
<br />ABOVE POWER POLE (LIGHTING AND/OR
<br />DIFFUSERS). THE BENCH CAN SLIDE A MAXIMUM 6"
<br />TO EITHER SIDE. THE BENCH MUST BE A MINIMUM
<br />OF 4'-0" FROM FRONT OF WILL CALL TO THE FRONT
<br />COUNTER, AND A MINIMUM OF 4'-0" FROM REAR OF
<br />WIRING DIAGRAM
<br />BENCH TO FILL POD. COORDINATE WITH GENERAL
<br />CONTRACTOR PRIOR TO PHARMACIST BENCH
<br />GROUND �-) (BARE OR GREEN)
<br />ANCHORING
<br />LINE 1 (BLACK)
<br />PROVIDE LISTED HANDLE -TIE BETWEEN FRONT
<br />LINE 2 ( (RED)
<br />COUNTER CIRCUIT BREAKERS THAT SHARE
<br />LINE 3 ( (BLUE)
<br />COMMON NEUTRAL FOR SIMULTANEOUS TRIP.
<br />NEUTRAL (WHITE)
<br />WALL MOUNTED OCCUPANCY SENSOR 8. BRANCH CIRCUITRY AT FRONT COUNTER TO BE
<br />OS SWITCH, ONE -DIRECTION SENSING RUN THROUGH SIDEWALLS. COORDINATE DEVICE TRA
<br />MOUNTING WITH JUNCTION BOXES PRE INSTALLED BUIL
<br />RECEPTACLE, DUPLEX IN PANELS. MANU
<br />RECEPTACLE DUPLEX 9 VENDOR FURNISHED MODULAR POWER
<br />MOUNTED HORIZONTALLY
<br />16
<br />RECEPTACLE, GFI
<br />0
<br />RECEPTACLE, DUPLEX FLUSH FLOOR
<br />RECEPTACLE, DUPLEX ISOLATED
<br />0
<br />GROUND FLUSH FLOOR
<br />1
<br />RECEPTACLE, DOUBLE DUPLEX
<br />}�
<br />RECEPTACLE, DUPLEX
<br />ll
<br />ISOLATED GROUND
<br />1
<br />RECEPTACLE, DOUBLE DUPLEX,
<br />U
<br />NSITION
<br />BETWEEN
<br />DING WIRING AND
<br />FACTURED WIRING
<br />DISTRIBUTION INCLUDES ALL REQUIRED LINE N L1 G N L2 G
<br />ENTRY CABLES, POWER -TO -POWER CABLE (LINE 1) (LINE 2)
<br />ASSEMBLIES, POWER DISTRIBUTION MODULES,
<br />POWER STRIPS AND OUTLETS. REFER TO
<br />MANUFACTURER'S INSTRUCTIONS FOR PROPER MODULAR
<br />MOUNTING OF MODULAR POWER DISTRIBUTION.
<br />0. WHEN MAKING FINAL CONNECTIONS, ELECTRICAL 6 NTS
<br />CONTRACTOR TO CONNECT DEVICES TO MODULAR
<br />POWER IN THAT SECTION OF COUNTER ONLY. DO
<br />NOT CONNECT TO OTHER SECTIONS OF FRONT
<br />COUNTER.
<br />1. ELECTRICAL CONTRACTOR TO INSTALL VENDOR
<br />FURNISHED 50' WHIP FOR PHARMACIST BENCH IF
<br />ISOLATED GROUND
<br />PANELBOARD BEING USED TO SERVE WHIP
<br />CIRCUITS IS MORE THAN 50' CIRCUIT FEET,
<br />RECEPTACLE, SIMPLEX TWIST LOCK,
<br />L5-15R, UNO
<br />ELECTRICAL CONTRACTOR TO SPLICE FEEDER TO
<br />WHIP PER NEC. DO NOT SPLICE WHIP IF
<br />PANELBOARD IS LESS THAN 50' CIRCUIT FEET
<br />RECEPTACLE, SIMPLEX TWIST LOCK,
<br />ISOLATED GROUND, L5-15R, UNO
<br />FROM PHARMACIST BENCH.
<br />RECEPTACLE, DUPLEX TWIST LOCK,
<br />IZPI
<br />,
<br />PANELBOARD NOTES Q
<br />40-
<br />RECE
<br />RECEPTAACLCL E, DUPLEX TWIST LOCK,
<br />ISOLATED GROUND, L5-15R, UNO
<br />08.28.20
<br />RECEPTACLE, SPECIAL
<br />1.
<br />RECEPTACLE, SIMPLEX
<br />2'
<br />RECEPTACLE, PLUG -MOLD
<br />O
<br />JUNCTION BOX
<br />3.
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />THERMOSTAT
<br />O
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />4
<br />O
<br />ALARM JUNCTION BOX,
<br />5.
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />ALARM JUNCTION BOX,
<br />6.
<br />®
<br />FOR REMOTE TEST/RESET
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />OS
<br />SMOKE DETECTOR
<br />7.
<br />Eh
<br />NON -FUSED DISCONNECT
<br />8.
<br />FUSED DISCONNECT
<br />9.
<br />EQUIPMENT CONNECTION POINT
<br />1
<br />(PROVIDED WITH EQUIPMENT)
<br />1
<br />CIRCUIT, CONCEALED IN WALLS OR
<br />CEILING, E INDICATES EXISTING WIRING
<br />CIRCUIT, CONCEALED IN SLAB FLOOR,
<br />E INDICATES EXISTING WIRING
<br />CIRCUIT, EXPOSED,
<br />E INDICATES EXISTING WIRING
<br />1
<br />------------
<br />LOW VOLTAGE WIRING
<br />F--i
<br />CONDUIT SLEEVE
<br />1
<br />=
<br />FLUSH MOUNTED PANELBOARD
<br />1
<br />SURFACE MOUNTED PANELBOARD
<br />1
<br />-
<br />TELEPHONE / DATA BOX FOR ISD
<br />1
<br />LOW VOLTAGE CABLE
<br />1
<br />BOX FOR OTHER
<br />©
<br />TELEPHONE, FLUSH FLOOR
<br />1
<br />O
<br />MOTOR
<br />z
<br />TELEPOWER POLE
<br />1
<br />PUSH BUTTON
<br />2
<br />BUZZER
<br />SAIL SWITCH
<br />HSS
<br />JUNCTION BOX
<br />2
<br />( KI
<br />HORN/STROBE
<br />DH
<br />DOOR HOLD OPEN
<br />2
<br />ETC
<br />TIME CLOCK
<br />ABBREVIATIONS
<br />2
<br />a, b, c
<br />LOWER CASE LETTERS INDICATE
<br />SWITCHING CONFIGURATION
<br />2
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />AFG
<br />ABOVE FINISHED GRADE
<br />C
<br />CONDUIT
<br />CCT
<br />CIRCUIT
<br />CIF
<br />CEILING FAN
<br />CW
<br />CASH WRAP
<br />EC
<br />ELECTRICAL CONTRACTOR
<br />EF
<br />EXHAUST FAN
<br />2
<br />ETR
<br />EXISTING TO REMAIN
<br />EWC
<br />ELECTRIC WATER COOLER
<br />G
<br />GROUND
<br />GC
<br />GENERAL CONTRACTOR
<br />GFEP
<br />GROUND FAULT EQUIPMENT PROTECTION
<br />G
<br />GFI
<br />GROUND FAULT CIRCUIT INTERRUPTER
<br />1
<br />HD
<br />HAND DRYER
<br />IG
<br />ISOLATED GROUND
<br />LCU
<br />LIGHTING CONTROL UNIT
<br />NL
<br />NIGHT LIGHT
<br />NTS
<br />NOT TO SCALE
<br />2
<br />REC
<br />REFRIGERATION ELECTRICAL CONTRACTOR
<br />RC
<br />REFRIGERATION CONTRACTOR
<br />RH
<br />RADIANT HEATER
<br />Sc
<br />SECURITY CAMERA
<br />TR
<br />TAMPER RESISTANT
<br />TYP
<br />TYPICAL
<br />3
<br />UH
<br />UNIT HEATER
<br />UNO
<br />UNLESS NOTED OTHERWISE
<br />WH
<br />WATER HEATER
<br />WP
<br />WEATHER PROOF
<br />WR
<br />WEATHER RESISTANT
<br />MODULAR WHIP WIRING:
<br />2 CIRCUIT WHIPS WITH UPS: ELECTRICAL CONTRACTOR TO
<br />WIRE WHIP'S TO LINE 1, LINE 2, NEUTRAL AND ISOLATED
<br />GROUND.
<br />3 CIRCUIT WHIPS (NO UPS): ELECTRICAL CONTRACTOR TO
<br />WIRE WHIP'S TO LINE 1, LINE 2, LINE 3, NEUTRAL, AND
<br />GROUND.
<br />REFER TO MODULAR POWER WIRING DIAGRAM 6-EPHM1.
<br />TERMINATE GROUND ON ISOLATED GROUND BUS.
<br />CIRCUITS FEEDING FRONT COUNTER
<br />INSTALL LOCKING DEVICE (LOCK -OFF FOR
<br />ARE SUPPLIED VIA ONE WHIP. EXTEND
<br />°
<br />MAINTENANCE). LOCKING DEVICE SHALL BE UL
<br />FEEDERS AND SPLICE TO WHIP PER NEC.
<br />LP-a,b,c
<br />LISTED. MANUFACTURER SHALL MATCH EXISTING
<br />16.145
<br />PANELBOARD MANUFACTURER.
<br />LU2 w
<br />INSTALL LOCKING DEVICE (LOCK -ON FOR CRITICAL
<br />16.145
<br />LOAD).
<br />IG w
<br />2
<br />1 3 2
<br />POWER AND DATA FOR
<br />GFI BREAKER FOR PERSONNEL PROTECTION (5MA).
<br />DIGITAL DISPLAYS, +104" AFF.
<br />GFI BREAKER FOR EQUIPMENT PROTECTION (30MA).
<br />P
<br />P P
<br />VA
<br />CONDUCTOR SIZE HAS BEEN INCREASED FOR
<br />HEALTH
<br />VOLTAGE DROP. SIZE EQUIPMENT GROUNDING
<br />SERVICES
<br />P®
<br />w
<br />CONDUCTOR PROPORTIONATELY PER NEC.
<br />ROOM
<br />LP
<br />16.145
<br />16.451
<br />REFER TO ONE -LINE DIAGRAM FOR AVAILABLE FAULT
<br />CURRENT FOR INTERRUPT RATINGS.
<br />+24"
<br />N L3 G
<br />GROUND
<br />LINE 1
<br />LINE 2
<br />ISOLATED
<br />GROUND
<br />NEUTRAL
<br />TRAP
<br />BUIL
<br />MANU
<br />WIRING DIAGRAM WITH ISOLATED GROUND
<br />(BARE OR GREEN)
<br />(BLACK)
<br />_ (RED)
<br />(GREEN WITH
<br />YELLOW STRIPE)
<br />(WHITE)
<br />UU
<br />lSITION BETWEEN
<br />DING WIRING AND
<br />FACTURED WIRING
<br />(LINE 3) N Li IG
<br />(LINE 1G)
<br />POWER WIRING DIAGRAM
<br />"1 3m, 2 1
<br />0 0
<br />REFER TO ONE -LINE DIAGRAMS FOR WIRE SIZES. /d
<br />HEALTH SERVICES RECEPTACLES, SWITCHES,
<br />FACTORY WIRED TO LOAD. DATA BOXES AND THEIR CORRESPONDING
<br />COVER PLATES SHALL BE WHITE NYLON.
<br />0. BREAKER SHALL BE HIGH MAGNETIC TYPE. L LP
<br />1. BREAKER REMOVAL - FIELD VERIFY CIRCUIT 16.145 P®
<br />BREAKER IS NOT SERVING AN EXISTING LOAD. IF NO
<br />EXISTING LOAD, REMOVE CIRCUIT BREAKER AND
<br />PROVIDE FILLER PLATE. IF BREAKER IS SERVING A
<br />LOAD, IDENTIFY LOAD SERVED. UPDATE CIRCUIT
<br />IDENTIFICATION SCHEDULE AS "SPACE" OR INDICATE
<br />LOAD SERVED.
<br />2. DUAL TAP SOLENOID OPERATED BREAKER. CONNECT
<br />EMERGENCY/NIGHT LIGHTING TO UNSWITCHED TOILET
<br />TERMINATION.
<br />3. EXISTING CIRCUIT AND/OR CIRCUIT BREAKER. ■
<br />4. ROUTE CIRCUIT THROUGH CONTACTOR.
<br />n
<br />5. PROVIDE INTERLOCK WIRING WITH EXHAUST HOOD n
<br />ANSUL SYSTEM.
<br />6. RELOCATED CIRCUIT FROM EXISTING PANELBOARD.
<br />7. PROVIDE BLANK CIRCUIT BREAKER FILLER PLATE PHARMACY POWER PLAN
<br />FOR EXPOSED SPACE IN PANELBOARD.
<br />9.
<br />0.
<br />1.
<br />2.
<br />4.
<br />5.
<br />/�
<br />T
<br />1 /4" = V-0"
<br />8. PROVIDE U.L. LISTED OVERCURRENT DEVICE TO
<br />COORDINATE AND MAINTAIN MANUFACTURER'S
<br />SERIES RATED SYSTEM.
<br />HEALTH SERVICES RECEPTACLES, SWITCHES,
<br />EXISTING CIRCUIT BREAKER TO REMAIN. VERIFY
<br />DATA BOXES AND THEIR CORRESPONDING
<br />CONDITION OF CIRCUIT BREAKER TO ENSURE THAT IT
<br />COVER PLATES SHALL BE WHITE NYLON.
<br />IS OPERATIONAL AND MEETS ALL U.L. RATINGS.
<br />ROUTE CIRCUIT THROUGH EXISTING LCU CABINET
<br />UTILIZING EXISTING RELAY AND CONTROLS. UPDATE
<br />P$
<br />JUNCTION BOX FOR
<br />LCU IDENTIFICATION SCHEDULE WITH LOAD
<br />P$OS/D
<br />SWITCH PRE -INSTALLED
<br />IDENTIFICATION.
<br />BY MODULAR
<br />MANUFACTURER.
<br />SOLENOID OPERATED CIRCUIT BREAKER. REFER TO
<br />ENERGY MANAGEMENT PLANS FOR CIRCUIT
<br />LUTRON MAESTRO 0-10V DIMMER/VACANCY
<br />BREAKER CONTROL.
<br />SENSOR MS-Z1 01 -V-IV. PROGRAM FOR MANUAL
<br />ON AT 100% LIGHT LEVEL AND 15 MINUTE
<br />TIME
<br />EXISTING LOAD - TRACE EXISTING CIRCUIT, IDENTIFY
<br />DELAY. WIRE PER MANUFACT
<br />R R'S
<br />LOAD AND UPDATE CIRCUIT IDENTIFICATION
<br />RECOMMENDATIONS.
<br />SCHEDULE FOR LOAD SERVED. IF CIRCUIT IS NOT IN
<br />P
<br />USE, REFER TO PANELBOARD NOTE (11).
<br />ab
<br />DIMMING CONTROL ROUTED
<br />3. ROUTE CIRCUIT THROUGH ENCLOSED GFI BREAKER
<br />TO FIXTURE, TYP OF 2.
<br />FOR PERSONNEL PROTECTION (5MA).
<br />HEALTH
<br />SPARE - FIELD VERIFY CIRCUIT BREAKER IS NOT
<br />SERVICES
<br />Q
<br />a
<br />SERVING AN EXISTING LOAD. IF NO EXISTING LOAD,
<br />S
<br />ROOMS
<br />-
<br />PROVIDE LOCK OFF DEVICE TO LOCK SPARE
<br />17
<br />a
<br />BREAKER IN THE OFF POSITION. IF BREAKER IS
<br />0
<br />SERVING A LOAD, IDENTIFY LOAD SERVED. UPDATE
<br />LIGHTING
<br />LIGHTING FIXTURE SUPPLIED
<br />C
<br />CIRCUIT IDENTIFICATION SCHEDULE AS "SPARE" OR
<br />OWNER AND INSTALLED BY
<br />INDICATE LOAD SERVED.
<br />PANEL MANUFACTURER. FINAL e
<br />EXISTING LOAD - TRACE EXISTING CIRCUIT, IDENTIFY
<br />CONNECTIONS BY E.C. TYP OF 2.
<br />LOAD AND UPDATE CIRCUIT IDENTIFICATION
<br />16.470
<br />SCHEDULE FOR LOAD SERVED. IF CIRCUIT IS NOT IN
<br />o
<br />USE, REFER TO PANELBOARD NOTE (24).
<br />16.125 E
<br />ENERAL NOTES:
<br />16.102
<br />b
<br />NEW OVERCURRENT PROTECTIVE DEVICES PLACE IN
<br />EXISTING PANELBOARDS OR DISTRIBUTION BOARDS
<br />0
<br />SHALL MATCH THE TYPE AND AIC RATING OF
<br />EXISTING OVERCURRENT PROTECTION DEVICES IN
<br />SAID BOARD.
<br />E.C. SHALL TRACE ALL ELECTRICAL CIRCUITS FOR
<br />TOILET
<br />EVERY EXISTING PANELBOARD AFFECTED BY THIS
<br />'I]
<br />-I
<br />PROJECT. IDENTIFY LOADS ON EACH CIRCUIT.
<br />I
<br />PROVIDE A COMPLETE TYPEWRITTEN CIRCUIT
<br />°
<br />C
<br />N L2 G NOT
<br />(LINE 2G) USED
<br />EXISTING ELECTRICAL DEVICES
<br />NOT SHOWN TO REMAIN D-REG40
<br />D-RXPCO2
<br />D-RXPC01 D-RXZP02
<br />D-RXZP01 V-135
<br />V-134
<br />D-RXTV01
<br />CIRCUITRY NOTED WITH "W" INDICATES PRE-
<br />MONITOR
<br />MANUFACTURED WHIP. E.0 TO PROVIDE
<br />V-137
<br />CONNECTION TO WHIP AS SHOWN. COORDINATE
<br />EXACT LOCATION AND CIRCUIT CONFIGURATION
<br />OF HEALTH
<br />WHIP WITH ARCHITECTURAL DRAWINGS AND
<br />MANUFACTURER'S INSTALLATION INSTRUCTIONS. SERVICES
<br />ROOM
<br />WIRING BETWEEN MODULAR
<br />OUTLETS PROVIDED BY
<br />MANUFACTURER, FINAL CONNECTION
<br />BY GENERAL CONTRACTOR TYP, REF
<br />°ARCH DWGS. °
<br />P-d,e,f
<br />pq in 16.145
<br />X�aO� ���� Q��� w
<br />ROUTE MANUFACTURER
<br />G1G1G1G 3 2 1 2 1
<br />PROVIDED WHIP THROUGH
<br />N21
<br />WALL PENETRATION AT 2'-4"
<br />AFF TO EC INSTALLED
<br />® ® ®
<br />JUNCTION BOX LOCATED
<br />IN WALL ABOVE CEILING.
<br />CONNECT TO CIRCUITRY AS
<br />SHOWN, TYP OF 2.
<br />ROVIDE 2" CONDUIT WITH PULL
<br />_
<br />IRE IN WALL FROM EC INSTALLED
<br />o
<br />NCTION BOX MOUNTED 2'-6" AFF
<br />O ABOVE ACCESSIBLE CEILING
<br />0 o
<br />SPACE, TYP OF 2.
<br />PHARMACY
<br />°
<br />a
<br />ADDITION UNLESS NOTED
<br />KEYNOTES
<br />GENERAL LIGHTING NOTES
<br />GENERAL NOTES
<br />01.31.20
<br />08.28.20
<br />1. EXIT SIGN MOUNTING
<br />1. FURNISH AND INSTALL ALL MATERIALS, EQUIPMENT, AND LABOR,
<br />16.101 REPLACE ALL LIGHT LENSES WITH NEW
<br />A. WALL FIXTURE: CENTER 12" ABOVE DOOR
<br />FOR A COMPLETE INSTALLATION IN ALL RESPECTS, READY FOR
<br />PRISMATIC ACRYLIC LENS FOR ALL LAY -IN LIGHT
<br />OPENING.
<br />INTENDED USE AND IN STRICT ACCORDANCE WITH NEC, NESC,
<br />FIXTURES IN THIS AREA.
<br />B. CEILING FIXTURE: ON CEILING OR AT HEIGHT
<br />STATE, AND LOCAL CODES, AND MANUFACTURER'S
<br />16.102 FURNISH AND INSTALL NEW TUBE GUARDS AND
<br />SPECIFIED ON DRAWINGS.
<br />RECOMMENDATIONS. PAY ALL NECESSARY FEES AND PERMITS.
<br />CAPS ON ALL EXPOSED LAMPS IN THIS AREA.
<br />C. PENDANT FIXTURE: MATCH HEIGHT OF EXISTING
<br />16.125 EXISTING LIGHT FIXTURES TO REMAIN UNLESS
<br />PENDANT MOUNTED EXIT SIGNS. IF STORE DOES
<br />A. NO CIRCUITRY SHALL BE ALLOWED TO BE ROUTED ACROSS THE
<br />NOTED OTHERWISE.
<br />NOT HAVE PENDANT MOUNTED EXIT SIGNS, THEN
<br />ROOF OR THE EXTERIOR SIDE OF THE EXTERIOR WALLS.
<br />16.126 EXISTING LIGHT FIXTURE TO BE DEMOLISHED.
<br />PENDANT MOUNT SIGN 24" BELOW BOTTOM OF
<br />B. ALL EQUIPMENT SHALL BE UL LISTED WHERE APPLICABLE.
<br />16.145 CONNECT CIRCUIT(S) TO EXISTING BRANCH
<br />BAR JOIST.
<br />C. ARRANGE ALL WORK TO MINIMIZE DISRUPTIONS TO STORE
<br />CIRCUITRY. MINIMUM WIRE SIZE AND
<br />D. VERIFY MOUNTING HEIGHT WITH AHJ.
<br />OPERATIONS. COORDINATE ALL DISRUPTIONS WITH WALMART
<br />PANELBOARD CIRCUIT ARE NOTED. VERIFY SIZE,
<br />E. COORDINATE LOCATIONS OF EXIT SIGNS TO
<br />CONSTRUCTION MANAGER AND STORE MANAGER.
<br />RATING AND CONDITION OF EXISTING BRANCH
<br />ENSURE STORE SIGNAGE DOES NOT OBSTRUCT
<br />D. CONTRACTOR SHALL VERIFY ALL WALL FINISH THICKNESS
<br />CIRCUIT CONDUIT AND WIRE PRIOR TO USE TO
<br />THEIR VIEW.
<br />BEFORE INSTALLING BOXES. FURNISH AND INSTALL EXTENDED
<br />ENSURE THAT THEY MEET REQUIRED SIZE, AND
<br />F. THE USE OF TRITIUM BASED RADIOACTIVE EXIT
<br />BOXES OR BOX EXTENDERS WHERE REQUIRED.
<br />ALL U.L. RATINGS AND REPLACE AS REQUIRED.
<br />SIGNAGE IS PROHIBITED.
<br />E. CONTRACTOR SHALL VERIFY THAT ALL AFFECTED
<br />PANELBOARDS HAVE CIRCUIT BREAKER KNOCKOUTS
<br />16.451 PROVIDE EMT WITH PROPERLY INSTALLED
<br />2. EMERGENCY LIGHT FIXTURE INSTALLATION
<br />PROPERLY COVERED ANDTHAT ALL TRIM IS IN GOOD
<br />COMPRESSION OR SET -SCREW TYPE FITTINGS
<br />A. WALL FIXTURE: 12" BELOW FINISHED CEILING OR
<br />CONDITION, ALLOWING NO ACCESS TO LIVE PARTS.
<br />AND AN INSULATED EQUIPMENT GROUNDING
<br />+10'-0" IN AREAS OF EXPOSED STRUCTURE,
<br />CONDUCTOR FOR ALL RACEWAYS SERVING THIS
<br />UNLESS NOTED OTHERWISE.
<br />2. PROVIDE SEALS AT RACEWAY PENETRATIONS AS FOLLOWS:
<br />ROOM TO COMPLY WITH NEC, HEALTH CARE
<br />B. PENDANT FIXTURE: BOTTOM CHORD OF BAR
<br />A. FIRE RATED WALLS: SEAL PER SPECIFICATIONS FOR FIRE
<br />FACILITIES.
<br />JOIST OR AT HEIGHT SPECIFIED ON DRAWINGS.
<br />STOPPING.
<br />16.470 FURNISH AND INSTALL NEW 20 AMP, 120 VOLT
<br />C. REMOTE HEAD FIXTURE: HEADS CENTERED
<br />B. NEUTRALIZATION AREA: SEAL PER MECHANICAL DETAIL.
<br />CIRCUIT(S). FEED FROM PANELBOARD AS
<br />ABOVE DOOR OPENING +9'-0", UNLESS NOTED
<br />C. FREEZER/COOLER BOXES: SEAL WITH EXPANDING FOAM
<br />INDICATED. PROVIDE 20A-1 P CIRCUIT BREAKER
<br />OTHERWISE AND BATTERY PACK MOUNTED ON
<br />SEALANT.
<br />IF NEEDED. E.C. SHALL MATCH MANUFACTURER,
<br />INTERIOR SIDE OF WALL 12" BELOW FINISHED
<br />D. EXTERIOR: REFER TO ARCHITECTURAL DOCUMENTS FOR
<br />TYPE AND AIC RATINGS OF EXISTING CIRCUIT
<br />CEILING OR AT BAR JOIST IN AREAS OF EXPOSED
<br />SEALING REQUIREMENTS AT ALL EXTERIOR MOUNTED DEVICES,
<br />BREAKERS.
<br />STRUCTURE.
<br />FIXTURES, ENCLOSURES, AND RACEWAY PENETRATIONS.
<br />16.492 E.C. SHALL COORDINATE WITH GENERAL
<br />D. REFER TO MANUFACTURER'S WRITTEN
<br />CONTRACTOR AND ARCHITECTURAL
<br />INSTRUCTIONS. ALLOW BATTERY TO CHARGE
<br />3. PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR (SIZE
<br />DEMOLITION PLANS THE EXTENT OF ELECTRICAL
<br />CONTINUOUSLY FOR A MINIMUM OF 24 HOURS
<br />PER NEC) IN PVC TYPE CONDUIT, POWER AND LIGHTING CIRCUITS,
<br />DEMOLITION. REMOVE UNUSED DEVICES,
<br />BEFORE INITIAL TESTING.
<br />ISOLATED GROUND CIRCUITS, OR AS SHOWN ON PLANS. CONDUIT
<br />BOXES, CONDUITS, AND WIRING BACK TO
<br />E. AFTER EMERGENCY LIGHT HAS BEEN POWERED
<br />SHALL BE SIZED PER NEC BASED ON THWN 600 VOLT COPPER
<br />ORIGINATING JUNCTION BOXES OR
<br />DO NOT TURN OFF FOR EXTENDED PERIODS OF
<br />SINGLE CONDUCTORS, PLUS THE EQUIPMENT GROUNDING
<br />PANELBOARDS. REFERENCE POWER PLANS FOR
<br />TIME.
<br />CONDUCTOR.
<br />CIRCUITRY TO BE REUSED. DEMOLITION SHALL
<br />NOT AFFECT ACTIVE CIRCUITS. IF CIRCUIT IS
<br />3. EXIT SIGNS, EMERGENCY LIGHTS AND NIGHT LIGHTS
<br />4. WIRING DEVICES: DEVICE MOUNTING HEIGHTS ARE FROM FINISHED
<br />DEMOLISHED ALL THE WAY TO PANELBOARD,
<br />SHALL NOT BE SWITCHED.
<br />FLOOR TO CENTER OF OUTLET BOX UNLESS NOTED OTHERWISE ON
<br />REMOVE CIRCUIT BREAKER AND REPLACE WITH
<br />PLANS. COORDINATE THE STANDARD MOUNTING HEIGHTS WITH
<br />FILLER PLATE. UPDATE TYPEWRITTEN CIRCUIT
<br />4. IN AREAS OF OPEN STRUCTURE, MOUNT STRIP
<br />MASONRY:
<br />DIRECTORY IDENTIFYING CIRCUIT AS "SPACE".
<br />FIXTURE TO BOTTOM CHORD OF BAR JOIST, UNLESS
<br />A. SWITCHES +44"
<br />COORDINATE EXACT REQUIREMENTS WITH
<br />NOTED OTHERWISE.
<br />B. RECEPTACLES +20"
<br />EXISTING CONDITIONS PRIOR TO BID.
<br />C. VOICE/DATA +20"
<br />16.775 E.C. SHALL DISCONNECT, EXTEND, AND
<br />5. PROVIDE SEPARATE BOXES FOR GANGED SWITCHES
<br />RECONNECT ALL ELECTRICAL CIRCUITRY FOR
<br />ON SEPARATE BRANCH CIRCUITS.
<br />5. WIRING SHALL INCLUDE FINAL CONNECTION TO ALL EQUIPMENT IN
<br />NEW OR RELOCATED EQUIPMENT. REFERENCE
<br />CONFORMANCE WITH EQUIPMENT SUPPLIER WIRING DIAGRAMS.
<br />POWER PLANS AS APPLICABLE. VERIFY
<br />6. FIXTURES DENOTED WITH "ABS' ARE TO BE
<br />CONDITION OF BRANCH CIRCUIT, CONDUIT, AND
<br />FASTENED ON UNISTRUT CHANNELS MOUNTED TO
<br />6. CONTRACTOR IS RESPONSIBLE FOR PROVIDING AN UPDATED AND
<br />WIRE PRIOR TO USE TO ENSURE THAT THEY
<br />THE BOTTOM SIDE OF THE TOP CHORD OF BAR
<br />COMPLETE TYPEWRITTEN CIRCUIT IDENTIFICATION SCHEDULE FOR
<br />MEET ALL U.L. RATINGS AND REPLACE AS
<br />JOISTS. LOCATE THE FIXTURES RUNNING
<br />EVERY PANELBOARD AFFECTED BY THIS PROJECT.
<br />REQUIRED. COORDINATE THIS PROCESS WITH
<br />PERPENDICULAR TO BAR JOISTS WITHIN BAR JOISTS
<br />CONSTRUCTION MANAGER TO MINIMIZE
<br />WEBBING SPACES. DO NOT FASTEN FIXTURE OR
<br />7. NEW OVERCURRENT PROTECTIVE DEVICES INSTALLED IN EXISTING
<br />DOWNTIME. LABEL ALL ASSOCIATED
<br />UNISTRUT CHANNELS TO ROOF DECK.
<br />PANELBOARDS OR DISTRIBUTION BOARDS SHALL MATCH THE TYPE
<br />PANELBOARD SCHEDULES TO REFLECT LOAD
<br />AND AIC RATING OF EXISTING OVERCURRENT PROTECTIVE
<br />DESCRIPTIONS.
<br />GENERAL POWER NOTES
<br />DEVICES.
<br />8• BRANCH CIRCUIT CONDUCTORS SHALL BE MINIMUM #12 AWG
<br />D-REG4 D-REG42
<br />UNLESS NOTED OTHERWISE IN SCHEDULES. WHERE 20A BRANCH
<br />D-RXPC03 D-RXPC04
<br />07,26.19
<br />CIRCUITS HAVE #8 AND LARGER WIRE SPECIFIED, #10 AWG WIRE
<br />1. TELEPOWER POLE(S): MOUNT JUNCTION BOX(ES) TO
<br />D-RXZP03 D-RXZP04
<br />SHALL BE USED FOR THE FINAL CONNECTION (15-FT MAXIMUM).
<br />D-RXLP02 V-138
<br />TOP SIDE OF BOTTOM CHORD OF BAR JOIST. INSTALL
<br />g WHERE BRANCH CIRCUITS ARE GROUPED, SIZE CONDUIT AND
<br />V-1 6 D-RXPC05
<br />FURNISHED POWER POLE AND TERMINATE WIRING
<br />DERATE CURRENT CARRYING CONDUCTORS PER NEC.
<br />RXZP05
<br />TO JUNCTION BOX. PROVIDE UNISTRUT SUPPORTS
<br />V-141
<br />AND HARDWARE TO SECURE TELEPOWER POLE
<br />10. PROVIDE UL LISTED HANDLE TIES ON ALL MULTIWIRE BRANCH
<br />PLUMB TO BUILDING STRUCTURE. REF POWER POLE
<br />CIRCUITS PER NEC REQUIREMENTS.
<br />e e e e
<br />CONNECTION DETAIL.
<br />2. PROVIDE LIQUID -TIGHT FLEXIBLE METAL CONDUIT
<br />11. SUPPORTS FROM STRUCTURE: NO ATTACHMENT OF ANY TYPE
<br />SHALL BE MADE TO BRIDGING OR JOIST WEB MEMBERS. UTILIZE
<br />R
<br />AND WIRING FROM DISCONNECT SWITCH OR
<br />ONLY THE TOP AND BOTTOM CHORDS FOR SUPPORTING THE
<br />0 0 0
<br />JUNCTION BOX TO EQUIPMENT KNOCKOUT
<br />ELECTRICAL SYSTEM INSTALLATIONS.
<br />ELECTRICAL CONNECTION POINT.
<br />3. WHERE EQUIPMENT NAMEPLATE PROTECTIVE
<br />12. DEVICES SHOWN ON COOLER/FREEZER PANELS SHALL BE
<br />SURFACE MOUNTED UNLESS NOTED OTHERWISE. SEAL DEVICES TO
<br />DEVICE RATING DIFFERS FROM SIZE PROVIDED,
<br />COOLER/FREEZER PANELS WITH SILICONE SEALANT.
<br />NOTIFY WALMART CONSTRUCTION MANAGER
<br />IMMEDIATELY TO COORDINATE RESOLUTION.
<br />13. SURFACE MOUNTED CONDUIT ON COOLER/FREEZER PANELS OR IN
<br />FOOD PREP AREAS SHALL BE INSTALLED WITH GALVANIZED 1/2"
<br />4. ELECTRONIC FIRE PROTECTION/SECURITY ALARM
<br />STANDOFF CONDUIT HANGERS TO ALLOW FOR CLEANING.
<br />BOXES AND CONDUITS SHOWN ON POWER PLANS
<br />SHALL BE PROVIDED UNDER THIS CONTRACT. IN
<br />OTHERWISE THE
<br />14. ONLY FEEDER CIRCUITS NOTED ON THE ONE LINE DIAGRAM AND
<br />` L n FOLLOWING GENERAL NOTES APPLY: BRANCH CIRCUITS NOTED BY LEGEND SHALL BE INSTALLED UNDER
<br />A. ALL ALARM JUNCTION BOXES SHALL BE SLAB. PROVIDE EXTERIOR COATED GRC BENDS ON ALL CONDUIT
<br />PHARMACY TELECOM PLAN 4"X4"X2-1 /8" MINIMUM. RUNS THAT HAVE 45 DEGREE BENDS OR GREATER. REFER TO
<br />5 B. ALARM RACEWAYS SHALL BE 3/4" MINIMUM WITH SPECIFICATION SECTION 16.100 FOR UNDER SLAB.
<br />1/8" = 1'-0" PULL WIRE AND INSULATING BUSHINGS AT END
<br />OF VERTICAL RACEWAY RUN.
<br />15. SEISMIC ZONE REQUIREMENTS. PROVIDE EXPANSION COUPLINGS
<br />AND BRACING FOR ELECTRICAL EQUIPMENT AS REQUIRED BY
<br />C. VERTICAL RACEWAYS FROM ALARM BOXES
<br />LOCAL CODES.
<br />SHALL BE EITHER CONCEALED INSIDE WALL OR
<br />SURFACE MOUNTED (TO MATCH JUNCTION BOX
<br />16. EXISTING ELECTRICAL AND ALARM:
<br />MOUNTING). ALL VERTICAL RUNS SHALL BE
<br />A. WHERE DEMOLITION OR NEW CONSTRUCTION INTERRUPTS
<br />TURNED 90-DEGREES AT TOP SIDE OF BOTTOM
<br />EXISTING ELECTRICAL CIRCUITS FEEDING EXISTING EQUIPMENT,
<br />CHORD OF BAR JOIST AND EXTENDED
<br />DEVICES, OR LIGHTING TO REMAIN, BUT NOT SHOWN ON
<br />HORIZONTALLY TO A LOCATION ACCESSIBLE BY
<br />DRAWINGS, PROVIDE LABOR AND MATERIALS TO REWORK
<br />VERTICAL FLOOR TYPE LIFT.
<br />CIRCUITRY, AS REQUIRED, TO MAINTAIN EXISTING OPERATION.
<br />5. UPON COMPLETION OF ELECTRICAL INSTALLATION
<br />B. IF DEMOLITION OR NEW CONSTRUCTION WILL DISRUPT
<br />AND PRIOR TO ENERGIZING CIRCUIT:
<br />EXISTING UNDERGROUND SERVICES (ELECTRICAL, TELEPHONE,
<br />A. INSPECT WIRE AND CABLE FOR PHYSICAL
<br />PARKING LOTLIGHTING CIRCUITRY, ETC.) PROVIDE ALL
<br />MATERIALS AND LABOR AS REQUIRED TO REROUTE, SLEEVE,
<br />DAMAGE.
<br />OR OTHERWISE REWORK THESE SERVICES TO MAINTAIN THEIR
<br />B. PERFORM CONTINUITY TEST.
<br />EXISTING OPERATION
<br />ELECTRICAL C. VERIFY PROPER PHASING CONNECTION TO ALL C. EXERCISE CAUTION AROUND ALARM AND SECURITY CABLES
<br />° DEVICES AND THREE PHASE MOTOR LOADS. DURING DEMOLITION AND CONSTRUCTION. PROTECT ALARM
<br />REF 4- EPHM1 CIRCUITRY AND SECURITY CABLES FROM ACCIDENTAL DAMAGE SO THAT
<br />SYSTEMS 16.775 N OPERATIONAL AT ALL TIMES.
<br />- 16.492
<br />-- 20A WIRE SIZING SCHEDULE D. DISPOSE OF ALL REMOVED MATERIALS, UNLESS OTHERWISE
<br />��-�I-----�£C r----T ; NOTED.
<br />_ -
<br />---------------------� III �� - - - - - I ����- - - - - -�-� I
<br />r 17. EXISTING ELECTRICAL DEMOLITION:
<br />o f _ ___ ___ _____________ _ ALL WIRE SIZES SHOWN ON PLANEL SCHEDULES AND
<br />C ; -----------------------' A. GENERAL: REMOVE OR RELOCATE EXISTING ELECTRICAL
<br />_ PLANS ARE INTENDED TO BE MINIMUM ACCEPTABLE EQUIPMENT, CONDUIT AND CONDUCTORS AS INDICATED ON
<br />WIRE SIZE. THE DRAWINGS, OR ONLY AS REQUIRED BY DEMOLITION.
<br />' I ;
<br />a THE FOLLOWING SCHEDULE IS TO BE USED TO SIZE REMOVE ALL PANELBOARDS, DISCONNECT SWITCHES, BOXES,
<br />'-------�---\ -- -----; WIRE FOR 20 AMP CIRCUITS (120 AND 277 VOLT). RELAYS, TIME SWITCHES, LIGHTS, DEVICES, ETC., WHICH WILL
<br />�- LENGHTS (IN FEET) ARE INTENDED TO BE MAXIMUM. NOT BE REUSED.
<br />`' -- PHARMACY B. SALES FLOOR: REMOVE UNUSED POWER DROP CONDUIT,
<br />lyl I� Ij I
<br />lyl
<br />lid^ �i1^ �i
<br />0 0 0 0
<br />F7
<br />NL
<br />TOILET
<br />n
<br />FINAL CONNECTIONS: WHERE 20A BRANCH CIRCUITS CONDUCTORS AND RELATED DEVICES SERVING SALES AREA
<br />HAVE #8 AND LARGER WIRE CALLED OUT, #10AWG WIRE GONDOLAS BEING RELOCATED OR REMOVED. EXISTING
<br />y y MAY BE USED FOR THE FINAL CONNECTION (15' MAX.). CONDUIT AND CONDUCTORS MAY BE REUSED FOR NEW POWER
<br />DROPS WHERE SIZE, RATING, AND CONDITION MEET
<br />REQUIREMENTS INDICATED ON PLANS AND ALL U L RATINGS
<br />REMOVE ALL UNUSED CONDUIT AND CONDUCTORS BACK TO
<br />POINT OF ORIGIN WHENEVER FEASIBLE. IF CIRCUIT IS NOT
<br />REUSED, REMOVE CIRCUIT BREAKER AND REPLACE WITH
<br />FILLER PLATE. EXCEPTION: DISTRIBUTION AND POWER SWITCH
<br />PHARMACY DEMO POWER PLAN
<br />BREAKERS SHALL BE ETR AS "SPARE". PROVIDE HANDLE LOCK
<br />OFF DEVICE TO LOCK "SPARE" CIRCUIT BREAKER IN THE "OFF"
<br />1/8" = V-0" POSITION. UPDATE TYPEWRITTEN CIRCUIT IDENTIFICATION
<br />0X 0 0
<br />° 16.125
<br />NL
<br />PHARMACY 16.492
<br />16.101
<br />°U 16.126 --- �
<br />I III I °
<br />UUNL
<br />107 107 107 flo
<br />IDENTIFICATION SCHEDULE FOR EVERY AFFECTED
<br />PANELBOARD.
<br />ALL NOTED OTHERWISE.
<br />R ENTWISE DEVICES ARE NEW UNLESS PHARMACY LIGHTING PLAN
<br />NOTED OTHERWISE.
<br />n
<br />1/4" = 1'-0"
<br />120 VOLT
<br />#12
<br />#10
<br />#8
<br />#6
<br />1-5 AMPS
<br />200 FT.
<br />325 FT.
<br />490 FT.
<br />770 FT.
<br />6-10 AMPS
<br />100 FT.
<br />160 FT.
<br />245 FT.
<br />385 FT.
<br />11-15 AMPS
<br />70 FT.
<br />110 FT.
<br />165 FT.
<br />255 FT.
<br />277 VOLT
<br />#12
<br />#10
<br />#8
<br />#6
<br />1-5 AMPS
<br />480 FT.
<br />760 FT.
<br />1170 FT.
<br />1865 FT.
<br />6-10 AMPS
<br />240 FT.
<br />380 FT.
<br />585 FT.
<br />930 FT.
<br />11-15 AMPS
<br />1 160 FT.
<br />250 FT.
<br />390 FT.
<br />1 620 FT.
<br />SCHEDULE AS "SPACE" OR "SPARE".
<br />C. CONDUIT AND WIRING TO BE ABANDONED IN CEILING SPACES
<br />AND OTHER NON-PUBLIC AREAS (I.E., THROUGH STOCKROOM
<br />AREA): CUT WIRING LOOSE AND REMOVE FROM RACEWAY(S),
<br />LEAVING RACEWAY(S) IN PLACE. CONDUIT TO BE ABANDONED IN
<br />WALLS OR FLOORS SHALL BE REMOVED BACK TO FINISHED
<br />SURFACE AND CAPPED INSIDE. REPAIR SURFACE(S) TO MATCH
<br />ADJACENT.
<br />D ALL CIRCUIT BREAKERS EREMOVED.REMOVECIRCUITRVING BRANCH CIRCUITS TO BE
<br />LEGEND FOR MODULAR
<br />REMOVED SHALL A SO E.
<br />COMPONENTS
<br />BREAKER AND REPLACE WITH FILLER PLATE. EXCEPTION:
<br />DISTRIBUTION AND POWER SWITCH BREAKERS SHALL BE ETR
<br />AS "SPARE". PROVIDE HANDLE LOCK OFF DEVICE TO LOCK
<br />"SPARE" CIRCUIT BREAKER IN THE "OFF" POSITION. UPDATE
<br />RECEPTACLE INSTALLED
<br />TYPEWRITTEN CIRCUIT IDENTIFICATION SCHEDULE AS "SPACE"
<br />IN POWER STRIP
<br />OR "SPARE".
<br />E. DEMOLISHED FLUORESCENT LIGHT FIXTURES: REFER TO
<br />POWER STRIP
<br />SELECTIVE SITE DEMOLITION SPECIFICATION FOR DISPOSAL OF
<br />LIGHT FIXTURE.
<br />MODULAR POWER DISTRIBUTION
<br />F. BUILDING COMPONENTS ABANDONED BY THE SCOPE OF WORK
<br />1 2 3 1 SYSTEM FURNISHED BY VENDOR,
<br />SHALL BE SECURED TO PREVENT FALLING, LOOSENING, OR
<br />INSTALLED BY E.C.
<br />CREATING DAMAGE OF ANY KIND IN THE FUTURE.
<br />NUMBER DENOTES WHICH CIRCUIT
<br />18. DATA AND PHONE CONDUIT INSTALLATION MILESTONE DATE:
<br />THE RECEPTACLE IS ATTACHED TO.
<br />ALL RACEWAY AND CONDUIT SLEEVES FOR DATA AND PHONE
<br />CABLING TO BE INSTALLED 3 WEEKS PRIOR TO CONTRACT
<br />VOICE/DATA BOX PRE -INSTALLED BY
<br />VP
<br />SUBSTANTIAL COMPLETION DATE.
<br />MODULAR MANUFACTURER.
<br />19. ETHERNET CABLE:
<br />A FURNISH AND INSTALL JUNCTION BOXES AS SHOWN ON PLANS
<br />��
<br />P
<br />OUTLET, BOX, AND WIRING BETWEEN
<br />DEVICES PRE -INSTALLED BY MODULAR
<br />PROVIDE CONDUIT AS REQUIRED BY LOCAL CODES AND/OR
<br />_ _ _ _ _ _ _ _ _
<br />_ _ III T
<br />- \ �I
<br />_
<br />MANUFACTURER. E.C. TO MAKE FINAL
<br />ORDINANCES.
<br />TYP_ 16.125 1F
<br />CONNECTION AS REQUIRED.
<br />B. ETHERNET CABLE IS FURNISHED BY OTHERS.
<br />C. ELECTRICAL CONTRACTOR SHALL INSTALL CABLE IN POWER
<br />OA
<br />ALARM SYSTEM JUNCTION BOX PRE-
<br />POLES.
<br />D. ELECTRICAL CONTRACTOR SHALL INSTALL OTHER CABLE AS
<br />P
<br />INSTALLED BY MODULAR
<br />16.125
<br />MANUFACTURER.
<br />DIRECTED BY WALMART CONSTRUCTION MANAGER.
<br />o
<br />o
<br />TYP
<br />16.125
<br />W
<br />PRE -MANUFACTURED WHIP. E.C. TO
<br />ANL
<br />H
<br />ANL
<br />TH
<br />Ell
<br />PROVIDE CONNECTION TO WHIP AS
<br />PH RM
<br />Cy
<br />SHOWN.
<br />25 " IG
<br />W PNL-#1 G
<br />W PNL-#1,#2,#3
<br />OILET
<br />CIRCUITS INDICATED IN HOMERUNS
<br />FOR MODULAR EQUIPMENT
<br />CORRESPOND TO LINE #'S IN DETAIL 4-
<br />PHARMACY DEMO LIGHTING PLAN EPHM1.
<br />1 /8" = V-0"
<br />2
<br />p+enb
<br />hitecture
<br />gineering
<br />2809 Ajax Avenue Suite 100
<br />Rogers Arkansas 72758
<br />Phone: 479.636.3545
<br />Fax: 479.636.1209
<br />Engineer of Record
<br />Keith Allen Williams, P.E.
<br />Florida License No. 64983
<br />COA License No. 26880
<br />UJ
<br />> >o irWo��
<br />j
<br />WwZ�a�zczn�
<br />cc
<br />xzLLmW�aW¢UO
<br />¢
<br />Ir
<br />.. �.. fA LL_W OLLort W
<br />a¢ �rorwa�Qo�w
<br />wwa}o;11 w �nmm
<br />O
<br />LL
<br />mFn r�ZzaaWg�=a>
<br />a - - cn
<br />LLo�Lt:,O 3W�°1ZZo
<br />U --WUOaQ2dJ aa dwz=¢
<br />.
<br />¢¢ao�OQ
<br />w�W
<br />wwz¢3iZOOa oo0MTz¢w05
<br />u
<br />Nw.
<br />=cn IZO;,�CWaMwHwFUo(na0wEwcJcccc¢
<br />N
<br />rn
<br />%0
<br />Q
<br />CD C.:D 0
<br />0%
<br />E
<br />O
<br />�
<br />-1
<br />O
<br />>
<br />0
<br />.. N
<br />(%% J o
<br />a-
<br />Jmo
<br />Q z
<br />=0w
<br />a
<br />CV)O
<br />o
<br />C/)
<br />N
<br />0
<br />=
<br />o
<br />N
<br />G�g
<br />w
<br />N
<br />6=
<br />w
<br />m
<br />2
<br />D
<br />z
<br />m
<br />>
<br />2021 CSP
<br />ISSUE BLOCK
<br />CHECKED BY:
<br />KAW
<br />DRAWN BY:
<br />BMS
<br />PROTO:
<br />192
<br />PROTO CYCLE:
<br />08-27-21
<br />DOCUMENT DATE:
<br />10-01-21
<br />Wit 4
<br />.% ,ENS
<br />No. 64983
<br />t
<br />11 STATE OF 44/
<br />-4
<br />10/05/2021
<br />DOCUMENTS THAT DO NOT
<br />HAVE THE ARCHITECT OR
<br />ENGINEER OF RECORD SEAL
<br />AND SIGNATURE SHALL BE
<br />CONSIDERED NOT FOR
<br />CONSTRUCTION
<br />PHARMACY
<br />ELECTRICAL
<br />PLANS
<br />SHEPHM1
<br />
|