HANG 4 AND 6 INCH PIPE WITHIN 3 INCHES OF PANEL POINT <br />PIPE 3 INCH AND SMALLER NOT REQUIRED TO BE WITHIN 3 <br />INCHES OF PANEL POINT <br />FOR 6 AND 8 INCH PIPE, USE THRU BOLT CONNECTION <br />WHERE POSSIBLE. USE TRAPEZE HANGER WHERE <br />JOIST PANEL POINTS TYP JOIST WEB CONFLICTS WITH THRU BOLT <br />BEAM CLAMP <br />6 INCH AND SMALLER PIPE <br />MAX /-DECK TYP ' <br />iv)nl)l4i miN vi�,uLE CLEARANCE BETWEEN <br />PIPE AND JOIST MEMBERS TYP <br />4, 6 AND 8 INCH PIPE 8 INCH PIPE <br />MAXIMUM HANGER SPACING FOR PIPING PERPENDICULAR TO JOISTS <br />BEAM CLAMP <br />THRU-BOLT <br />BEAM CLAMP <br />NOT TRAPEZED <br />NOT TRAPEZED <br />TRAPEZED <br />4" PIPE EVERY 12'-0" <br />4" PIPE EVERY 12'-0" <br />4" PIPE <br />EVERY OTHER JOIST <br />EVERY OTHER JOIST <br />NOT NECESSARY <br />6" PIPE EVERY 6'-0" <br />6" PIPE EVERY 12'-0" <br />6" PIPE <br />EVERY JOIST <br />EVERY OTHER JOIST <br />NOT NECESSARY <br />8" PIPE <br />8" PIPE EVERY 6'-0" <br />8" PIPE EVERY 6'-0" <br />NOT ALLOWED <br />EVERY JOIST <br />EVERY JOIST <br />PIPE RUNNING PERPENDICULAR TO JOISTS <br />6" <br />1 /4"x2"x2" SQUARE WASHER & HEX NUT THRU BOLT TYP MAX <br />1/2" ALL THREAD ROD'`,, <br />it � <br />FENDER WASHER & HEX NUT <br />1 <br />PROVIDE 4-WAY BRACE <br />AT TOP OF RISERS <br />TO AUX SYSTEM <br />3.5" X 2.5" X .25" ANGLE - <br />TRAPEZE REQ'D FOR 6" MAINS <br />4" X 4" X .25" ANGLE <br />TRAPEZE REQ'D FOR 8" MAINS-7 <br />TOP CHORD OF JOIST TYP <br />ONE OPEN JOIST BAY <br />MINIMUM BETWEEN <br />TRAPEZE HANGERS E <br />12" DO NOT HANG 2 OR MORE <br />MIN MAINS 4" OR LARGER BETWEEN <br />THE SAME JOIST SPACE <br />MAXIMUM HANGER SPACING FOR PIPES PARALLEL TO JOISTS <br />4" PIPE EVERY 12'-0" <br />6" PIPE EVERY 12'-0" <br />8" PIPE EVERY 12'-0" <br />NOT TRAPEZED <br />TRAPEZED <br />TRAPEZED <br />BEAM CLAMP <br />THRU BOLT <br />THRU BOLT <br />PIPE RUNNING PARALLEL TO JOIST <br />CONTRACTOR MAY SUBSTITUTE ANGLE IRON TRAPEZE <br />MEMBER WITH PIPE MEMBER. SIZE PIPE MEMBER IN <br />ACCORDANCE WITH NFPA-13 AND MAINTAIN 12 INCH <br />MAXIMUM DEFLECTOR DISTANCE <br />12" <br />MIN <br />UTILIZE THESE HANGING METHODS FOR ALL SPRINKLER <br />PIPING. SPACE TRAPEZE HANGERS IN ACCORDANCE <br />WITH SCHEDULE. LOCATE HANGERS WITHIN 3 INCHES <br />OF JOIST PANEL POINTS U.N.O. <br />NOTE: DO NOT SUPPORT SPRINKLER PIPING FROM BOTTOM CHORD OF BAR JOISTS <br />6 NTS 10.30.07 F027 <br />PIPE SUPPORT <br />VANE TYPE WATER <br />FLOW SWITCHk <br />z MAIN DRAIN PIPED <br />x N OUTSIDE <br />Q <br />BUTTERFLY VALVE <br />WITH TAMPER SWITCH <br />1" AUXILIARY DRAIN - <br />FLOOR <br />AUX RISER <br />3 NTS 10.30.07 F05 <br />2" TEST AND DRAIN VALVE WITH <br />SIGHT GLASS AND SMOOTH BORE <br />CORROSION RESISTANT ORIFICE <br />WITH FLOW EQUAL TO ONE <br />SPRINKLER. VALVE SHALL INCLUDE <br />A PRESSURE -RELIEF VALVE <br />FROM SYSTEM <br />6" <br />2" THREADED <br />OUTLET <br />2" RISER STAND <br />BOLT TO FLOOR <br />5" <br />REv0 <br />pN <br />EXTERIOR WALL <br />1/2" WIDE MOUTH <br />TOP BEAM CLAMP <br />ATTACHED WITHIN <br />3" OF JOIST GIRDER <br />PANEL POINT <br />SUPPLY MAIN <br />3'°M� <br />U-BOLT STYLE STRAP <br />RESTRAINED WITH MINIMUM <br />3/8" FENDER WASHER, <br />LOCK WASHER, AND NUTS <br />JOIST GIRDER <br />SYS 5 SYS 4 <br />SYS 3 SYS 2 <br />SYS 1 <br />G <br />i�s..ra€LJfS,Is,,'t �,u <br />ALVE <br />a- <br />y . 8" <br />8„ <br />1'0 <br />F C <br />BOR <br />R <br />� <br />SPG <br />00 <br />FINISHED FLOOR <br />', <br />EXISTING <br />RISER <br />DETAIL <br />EXISTING SER <br />7 <br />FOR HYD AI ULIIC RE FEIRENCOEWONLY. <br />N TS <br />1/2" TOP BEAM CLAMP ATTACHED <br />WITHIN 3" OF PANEL POINT <br />ROOF DECK <br />1/2" ALL THREAD ROD <br />1/2" FENDER WASHER AND NUT ON <br />TOP AND BOTTOM OF ANGLE TYP <br />FOR 8" MAIN USE 4 x 4 x 1 /4 ANGLE <br />DRILLED WITH MAXIMUM 9/16" HOLES <br />(MAXIMUM 6 FT SPAN ALLOWED) <br />INSTALL ON EVERY JOIST OR MAXIMUM <br />10'-0" SPACING <br />FOR 6" MAIN USE 3 x 3 x 5/16 <br />ANGLE DRILLED WITH MAXIMUM 9/16" <br />HOLES (MAXIMUM 6 FT SPAN <br />ALLOWED) INSTALL ON EVERY JOIST <br />OR MAXIMUM 10'-0" SPACING <br />FOR 4" MAIN USE 3 x 2 x 1 /4 ANGLE <br />DRILLED WITH MAXIMUM 7/16" HOLES <br />(MAXIMUM 6 FT SPAN ALLOWED) <br />INSTALL ON EVERY OTHER JOIST OR <br />MAXIMUM 12'-0" SPACING <br />OPTION "A" INSTALLATION PROCEDURE <br />1. CORE DRILL 2 1/2" DIAMETER HOLE IN THE FREEZER/COOLER INSULATED <br />CEILING PANEL. LOCATE HOLE AND REQUIRED SPRINKLER PROTECTION <br />IN ACCORDANCE WITH NFPA 13 OBSTRUCTION CRITERIA (SSP TYPE <br />SPRINKLERS). MAINTAIN 6" CLEARANCE FROM COOLER SEAMS. <br />2. INSTALL DRY PENDENT SPRINKLER PER MANUFACTURERS INSTALLATION <br />REQUIREMENTS. <br />3. COMPLETELY FILL ANNULAR CEILING OPENING BETWEEN THE ESCUTCHEON AND <br />TOP OF CEILING PANEL WITH OPEN -CELL POLYETHYLENE FOAM BACKER ROD. <br />EXPANDED FOAM IS NOT PERMITTED. <br />4. INJECT DOW CORNING 739 PLASTIC ADHESIVE SEALANT INTO AND AROUND <br />THE TOP OF THE FREEZER/COOLER CEILING CORE OPENING IN ACCORDANCE <br />WITH SEALANT MANUFACTURERS INSTRUCTIONS <br />OPTION "B" INSTALLATION PROCEDURE <br />1. CORE DRILL 2 1/2" DIAMETER HOLE IN THE FREEZER/COOLER INSULATED <br />CEILING PANEL FROM BELOW. LOCATE HOLE AND REQUIRED SPRINKLER <br />PROTECTION IN ACCORDANCE WITH NFPA 13 OBSTRUCTION CRITERIA (SSP <br />TYPE SPRINKLERS). MAINTAIN 6" CLEARANCE FROM COOLER SEAMS. <br />2. INSTALL TYCO DRY PENDENT SPRINKLER PER MANUFACTURERS INSTALLATION <br />REQUIREMENTS. INSERT BOOT PRIOR TO MAKE-UP WITH PIPING. <br />3. COMPLETELY SEAL INTERFACE BETWEEN BOOT FLANGE AND TOP OF <br />FREEZER/COOLER PANEL WITH ADHESIVE PROVIDED WITH BOOT IN <br />ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS. <br />4. APPLY STRAP TIES ON BOOT AROUND DRY SPRINKLER BARREL PER <br />MANUFACTURERS INSTRUCTIONS. <br />SUPPLY FROM WET <br />PIPE SPRINKLER SYSTEM <br />UPRIGHT TRUSS GIRDER ROOF JOISTS SPRINKLE I J TEE WITH PLUG <br />TEE WITH PLUG <br />LIGHTS <br />CONDENSER <br />DRY CONCEALED <br />PENDENT SPRINKLER <br />STORAGE <br />FREEZER/COOLER <br />FREEZER SECTION, <br />NTS <br />SALES <br />NOTE: COORDINATE <br />EXACT LOCATION OF <br />SPRINKLERS AT <br />COOLERS/FREEZERS <br />WITH LIGHTS, <br />EVAPORATORS AND <br />OTHER <br />OBSTRUCTIONS. <br />NOTE THAT FINAL <br />LIGHT AND <br />EVAPORATOR <br />LOCATIONS MAY <br />DIFFER FROM THOSE <br />SHOWN ON PLANS <br />1" DRY <br />SPRINKLER DROP <br />FREEZER/COOLER <br />CEILING <br />I <br />2 NYLON STRAP TIES N <br />(INSTALL OPPOSITE DIRECTIONS) <br />TYCO RUBBER SEAL o ~ <br />BOOT MODEL DSB-2 Z z <br />_ w <br />-SEALANT PER BOOT J <br />0' <br />MANUFACTURER Z <br />Q <br />U <br />z <br />SPRINKLER CUP TYCO MODEL TY3555 <br />CONCEALED 2007 DRY <br />PENDENT SPRINKLER <br />vv� 2j» CONCEALED 2007 DRY COVER PLATE 24" (NO SUBSTITUTIONS) <br />PENDENT SPRINKLER <br />OPT10N A (NO SUBSTITUTIONS) OPTION B <br />NOTE: CONTRACTOR TO SEAL DRY PENDENT SPRINKLERS AT FREEZER/COOLER USING ONE OF THE OPTIONS ABOVE. NO OTHER SEALANTS ARE PERMITTED. <br />DRY PENDENT SPRINKLER <br />j-)__FREEZERZC00LER NTS 01.28.11 F19 <br />a <br />Ogg <br />U <br />tt <br />II <br />N <br />O <br />�0. <br />U <br />v � \ <br />W w u <br />V)HZ o¢'n <br />NzaF 0W�F-WQ3 <br />W o urnL ¢SUwa <br />a¢ F~¢aoo`"=io¢Nw <br />p �N Z ¢)`wwmcFzoo <br />L� a raa��a�¢U�oF <br />J Z W <br />V) �'nw¢3Xcnwpj¢> <br />~ ZVV)V) 0 cn��U�o Z <br />¢ m0-jo <br />Z�-_j �r <br />�zm�o�Uwwo�WzoW <br />H ¢� Z <br />Now=az��o��ooc�a'om <br />h_DNwoUm!=nancxaawOa� <br />Zy <br />c <br />� <br />o <br />0 <br />HW <br />o ! <br />E <br />W W <br />M n <br />WZ <br />o' <br />d o <br />cn <br />Zt'� <br />a� <br />o <br />o <br />d �aN <br />z <br />WZ <br />==o <br />= .2tl <br />• ^OX <br />„Z, ,Z,N <br />M <br />W <br />co <br />V/ <br />J <br />W <br />Z <br />F <br />LJ <br />p <br />LL <br />U <br />z <br />0 <br />%49 <br />E <br />a <br />>4 <br />� o <br />O O <br />C9 <br />cr <br />� <br />� <br />CD <br />O <br />z <br />rye <br />1--�--� <br />L LJ <br />� <br />ca <br />0 <br />o <br />0 <br />O <br />I— <br />ca <br />w <br />N <br />z <br />0 <br />ISSUE BLOCK <br />, <br />REISSUE 120405 <br />/2\ ADD#3 07/11 /16 <br />CHECKED BY: <br />NAW/JEC <br />DRAWN BY: <br />NM <br />PROTO: <br />LBA <br />PROTO CYCLE: <br />051514 <br />DOCUMENT DATE: <br />120415, <br />DARRELL E. STEIN <br />LICENSE # 58463 <br />FIRE <br />PROTECTION <br />DETAILS <br />SHEET: <br />FP3 <br />