OWNERS
<br />ROOFTOP UNIT SCHEDULE
<br />(LENNOX)
<br />OUTSIDE AIR REQUIREMENTS, IMC-2018 (IP)
<br />SINGLE -ZONE SYSTEMS ONLY FLOOR AREA SYSTEM AVERAGED SYSTEM SYSTEM AVERAGED REQUIRED REQUIRED
<br />SYSTEM SYSTEM TAB NAME SINGLE -ZONE SYSTEM SERVED AREA -BASED POPULATION PEOPLE -BASED OA INTAKE DCV OA INTAKE DESIGN OA NOTES
<br />DESIGNATION OR LIST'SINGLE' ASSOCIATED BY SYSTEM [As] OUTDOOR AIR RATE [Ps) OUTDOOR AIR RATE FLOW [Vot] FLOW [Vat] INTAKE FLOW [Vot]
<br />VENTILATION ZONE (SF) (CFM/SF) (PEOPLE) (CFM/P) (CFM) (CFM) (CFM)
<br />RTU-1 MZ RTU-1 - 980 0.120 6 7.50 172 N/A 400
<br />RTU-2 SINGLE ZONE FOOD TENANT SEATING 1,480 0.180 20 7.50 521 333 200 A, B
<br />RTU-3 SINGLE ZONE GR VESTIBULE 1,462 0.060 11.696 7.50 219 N/A 400
<br />RTU-4 SINGLE ZONE NAILPORT 820 0.120 20.5 20.00 636 123 125 A
<br />RTU-5 MZ RTU-5 - 644 0.097 5.21 6.92 99 N/A 120
<br />RTU-6 SINGLE ZONE CASH CENTER 728 0.120 5 7.50 156 N/A 160
<br />RTU-7 MZ RTU-7 - 1,571 0.076 12 7.50 240 N/A 240
<br />RTU-8 SINGLE ZONE TENANT 837 0.120 5 7.50 172 N/A 175
<br />RTU-9 SINGLE ZONE TENANT 1,030 0.120 5 7.50 201 N/A 210
<br />RTU-10 SINGLE ZONE GM VESTIBULE 1,526 0.120 22.89 7.50 444 N/A 450
<br />RTU-11 MZ RTU-11 - 1,119 0.084 18.975 20.00 634 126 175 A
<br />RTU-12 MZ RTU-12 - 591 0.158 8 5.00 133 N/A 135
<br />RTU-13 MZ RTU-13 - 1,319 0.120 4 0.00 180 N/A 180
<br />RTU-14 SINGLE ZONE DELI/BAKERY PREP 1,420 0.120 6 7.50 269 N/A 2,000 C
<br />RTU-15 MZ RTU-15 - 930 0.120 8 5.63 157 N/A 200
<br />RTU-19 MZ RTU-19 - 922 0.120 3 7.50 134 N/A 0 B
<br />RTU-20 SINGLE ZONE SEASONAL SALES 4,731 0.120 32 7.50 1,010 710 0 B, D
<br />RTU-21 SINGLE ZONE GR STOCKROOM 2,416 0.120 0 0.00 362 WA 365
<br />RTU-27 MZ RTU-27 - 1,743 0.103 9.64 7.32 271 N/A 275
<br />RTU-28 SINGLE ZONE GR RECEIVING 3,194 0.120 5 10.00 542 WA 545
<br />RTU-29 SINGLE ZONE BREAKROOM 1,448 0.180 48 7.50 776 326 330 A
<br />RTU-30 MZ RTU-30 - 1,798 0.111 1.32 5.00 207 WA 210
<br />RTU-31 SINGLE ZONE UPC 308 0.000 0 0.00 0 N/A 120
<br />RTU-32 MZ RTU-32 - 1,437 0.041 0.00001 0.00 58 N/A 175
<br />RTU-33 SINGLE ZONE TRAINING 508 0.060 10 5.00 101 WA 105
<br />RTU-34 MZ RTU-34 - 7,233 0.031 6.7 1.27 232 N/A 350
<br />RTU-35 SINGLE ZONE GM RECEIVING 5,204 0.120 5 10.00 843 N/A 845
<br />AHU-1,2 SINGLE ZONE GR SALES 32,946 0.060 219.64 7.50 4,530 2,471 10,000 D
<br />RTU16-19, RTU22-26, AHU-3 SINGLE ZONE GM SALES 101,642 0.120 594 7.50 20,815 15,246 5,000 B, D
<br />TOTALS 34,113 19,335 23,490
<br />GENERAL NOTES:
<br />1. VENTILATION CALCULATIONS BASED ON IMC-2018.
<br />2. SYSTEM POPULATIONS BASED ON MAX SEATING AND/OR CODE MAXIMUM VALUES.
<br />3. 100% OA SYSTEMS (Vot = fall zones Voz): WHEN ONE AIR HANDLER SUPPLIES ONLY OUTDOOR AIR TO ONE OR MORE ZONES. EACH ZONE IS INDIVIDUALLY CALCULATED WITH ITS WORST CASE ZONE AIR DISTRIBUTION EFFECTIVENESS (HEATING/COOLING).
<br />4. MULTI -ZONE RECIRCULATING SYSTEMS: CALCULATOR USED TO DETERMINE VENTILATION AIRFLOW INCOMPLIANCE WITH IMC-2018 VRP AND ASHRAE 62.1-2016 APPENDIX A. VENTILATION RATE SHOWN IS ACTUAL CALCULATED WITH CORRECTION FACTORS
<br />INCLUDED. EACH ZONE IS CALCULATED WITH ITS WORST CASE ZONE AIR DISTRIBUTION EFFECTIVENESS (HEATING/COOLING) AS PART OF CALCULATIONS TO FIND Ev.
<br />NOTES:
<br />A. UNIT SUPPLIED WITH CO2 SENSOR FOR DCV FLOW RATE. DESIGN OA SHOWN IS MINIMUM, UNIT IS CAPABLE TO BRING IN MAX OA TO MEET [Vol]. REFER TO RTU SCHEDULE.
<br />B. VENTILATION AIR PROVIDED VIA TRANSFER FROM SPACES SERVED BY AHUlRTU.
<br />C. AIRFLOW IS FOR EXHAUST MAKEUP AS REQUIRED BY THE VENTILATION STANDARD.
<br />D. UNIT SUPPLIED WITH CO2 SENSOR FOR DCV FLOW RATE WHERE INDICATED ON THE PLANS. NOTE THAT RTU-17, RTU-23, RTU-24 ARE CAPABLE OF PROVIDING ADDITIONAL 27,000 CFM TOTAL OA TO THE SALES FLOOR FOR THESE UNITS HAVING CO2 SENSORS.
<br />aLu
<br />co
<br />Lu
<br />. E2 .1
<br />.
<br />OEI
<br />EXISTING RTU INFORMATION
<br />CAPACITY HEAT HEAT INPUT
<br />MARK EMS DESIGNATION MANUFACTURER MODEL (TONS) TYPE (KW) NOTES
<br />RTU-1 FOOD TENANT KITCHEN AAON RK-10-3-GO-1C2 10 EL 30 A
<br />RTU-2 FOOD TENANT SEATING AAON RK-05-3-GO-1131 5 EL 20 A,B
<br />RTU-3 GR VESTIBULE AAON RK-10-3-GO-1 C2 10 EL 30 C
<br />RTU-4 NAIL TENANT AAON RK-03-3-GO-8A1 3 EL 10 A
<br />RTU-5 TENANT/CASH/COUNT AAON RK-03-3-GO-8A1 3 EL 10 A
<br />RTU-0 MONEY CENTER AAON RK-03-3-GO-8A1 3 EL 10
<br />RTU-25 GM SALES AAON RK-20-3-GO-000 20 C
<br />RTU-31 UPC AAON RK-03-3-GO-000 3
<br />3. IF EXISTING RTU(S) HAVE EXISTING CURB ADAPTER(S) AND ARE BEING REPLACED, REMOVE
<br />A
<br />RTU-7 COURTESY/RRs AAON RK-05-3-GO-161 5 EL 20 A
<br />RTU-8 TENANT AAON RK-03-3-GO-8A1 3 EL 10 A
<br />RTU-9 TENANT AAON RK-05-3-GO-161 5 EL 20 A
<br />RTU-10 GM VESTIBULE AAON RK-10-3-GO-1C1 10 EL 30 C
<br />RTU-11 BEAUTY SALON AAON RK-05-3-GO-000 5 - -- A
<br />RTU-12 PHARMACY LENNOX SCA060H46E1G 5 EL 15 A
<br />RTU-13 PRODUCE/SEAFOOD PREP AAON RK-03-3-GO-8A1 3 EL 10 A
<br />RTU-14 DELI/BAKERY PREP AAON RK-20-3-GO-000 20 - -- q
<br />RTU-15 DELI/BAKERY SALES AAON RK-05-3-GO-000 5 -- -- A
<br />RTU-16 CHECKOUT AAON RK-20-3-GO-1 D2 20 EL 40 C
<br />RTU-17 CHECKOUT AAON RK-20-3-GO-1 20 EL 40 B,C
<br />RTU-18 CHECKOUT AAON RK-20-3-GO-1 D2 20 EL 40 C
<br />RTU-19 GM SALES / VC AAON RK-20-3-GO-1 D2 20 EL 40 A
<br />RTU-20 SEASONAL AAON RK-10-3-GO-1D1 10 EL 40 C
<br />RTU-21 GR STOCK AAON RK-05-3-GO-1 B1 5 EL 20 C
<br />RTU-22 GM SALES AAON RK-20-3-GO-000 20 -- - C
<br />RTU-23 GM SALES AAON RK-20-3-GO-1 D2 20 EL 40 B,C
<br />RTU-24 GM SALES AAON RK-20-3-GO-000 20 B,C
<br />-- -- -- --
<br />RTU-26 GM SALES AAON RK-20-3-GO-000 20 - -- C
<br />RTU-27 TLE AAON RK-05-3-GO-161 5 EL 20 A
<br />RTU-28 GR RECEIVING AAON RK-10-3-GO-1D2 10 EL 40 C
<br />RTU-29 BREAKROOM AAON RK-05-3-GO-000 5 -- -- A
<br />RTU-30 OFFICE/LOCKER AAON RK-05-3-GO-1B1 5 EL 20 C
<br />-- -- A
<br />RTU-32 REAR RRs AAON RK-05-3-GO-000 5 -- - A
<br />RTU-33 TRAINING AAON RK-03-3-GO-000 3 -- -- A
<br />RTU-34 CLAIM/STOCK AAON RK-10-3-GO-iB1 10 EL 20 C
<br />RTU-35 GM RECEIVING AAON RK-20-3-GO-000 20 EL 40 C
<br />GENERAL INFORMATION:
<br />1. EXISTING RTU INFORMATION PROVIDED FOR BAS AND REFERENCE PURPOSES ONLY AND NOT
<br />INTENDED FOR PURCHASE ORDER REQUESTS.
<br />2. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL EXISTING
<br />RTU INFORMATION.
<br />EXISTING CURB ADAPTER(S) PRIOR TO INSTALLING NEW CURB ADAPTER(S). DO NOT INSTALL
<br />A CURB ADAPTER ON TOP OF AN EXISTING CURB ADAPTER. COORDINATE ORIGINAL CURB
<br />DIMENSIONAL CHARACTERISTICS WITH AES AS REQUIRED FOR REPLACEMENT RTU COMPATIBILITY.
<br />4. EXISTING BAS VENDOR IS NOVAR.
<br />NOTES:
<br />A. EXISTING RTU TO BE REPLACED AS INDICATED.
<br />B. EXISTING RTU IS A DEDICATED INDOOR AIR QUALITY UNIT EQUIPPED WITH CO2 CONTROLS.
<br />C. EXISTING ROOFTOP UNIT TO REMAIN AND BE REFURBISHED BY
<br />COTRACTOR.
<br />=F7 c)
<br />0
<br />U O m zuio aWOo>
<br />� w
<br />� u. m�wmzFoazai
<br />W W xzLL��'aW��z
<br />� �a 3tag`�!` ay�apw
<br />w m m
<br />O o_� �zQO�OWj�HaQ
<br />O �LLLL W"�OZouWi�OSO
<br />zdw2Z0
<br />3u�=u9a��t. 4~�~
<br />ociawoOWWyo:)zNa aZWFfnJW06
<br />�
<br />a_oo �,o„�aSz�vW,=g
<br />mwd z��o �awam Pw
<br />LOW 0Q7Q: WUWW7R�Q=
<br />:/i ��NUDVJdO 0.'�F-
<br />OEI
<br />EXISTING RTU INFORMATION
<br />CAPACITY HEAT HEAT INPUT
<br />MARK EMS DESIGNATION MANUFACTURER MODEL (TONS) TYPE (KW) NOTES
<br />RTU-1 FOOD TENANT KITCHEN AAON RK-10-3-GO-1C2 10 EL 30 A
<br />RTU-2 FOOD TENANT SEATING AAON RK-05-3-GO-1131 5 EL 20 A,B
<br />RTU-3 GR VESTIBULE AAON RK-10-3-GO-1 C2 10 EL 30 C
<br />RTU-4 NAIL TENANT AAON RK-03-3-GO-8A1 3 EL 10 A
<br />RTU-5 TENANT/CASH/COUNT AAON RK-03-3-GO-8A1 3 EL 10 A
<br />RTU-0 MONEY CENTER AAON RK-03-3-GO-8A1 3 EL 10
<br />RTU-25 GM SALES AAON RK-20-3-GO-000 20 C
<br />RTU-31 UPC AAON RK-03-3-GO-000 3
<br />3. IF EXISTING RTU(S) HAVE EXISTING CURB ADAPTER(S) AND ARE BEING REPLACED, REMOVE
<br />A
<br />RTU-7 COURTESY/RRs AAON RK-05-3-GO-161 5 EL 20 A
<br />RTU-8 TENANT AAON RK-03-3-GO-8A1 3 EL 10 A
<br />RTU-9 TENANT AAON RK-05-3-GO-161 5 EL 20 A
<br />RTU-10 GM VESTIBULE AAON RK-10-3-GO-1C1 10 EL 30 C
<br />RTU-11 BEAUTY SALON AAON RK-05-3-GO-000 5 - -- A
<br />RTU-12 PHARMACY LENNOX SCA060H46E1G 5 EL 15 A
<br />RTU-13 PRODUCE/SEAFOOD PREP AAON RK-03-3-GO-8A1 3 EL 10 A
<br />RTU-14 DELI/BAKERY PREP AAON RK-20-3-GO-000 20 - -- q
<br />RTU-15 DELI/BAKERY SALES AAON RK-05-3-GO-000 5 -- -- A
<br />RTU-16 CHECKOUT AAON RK-20-3-GO-1 D2 20 EL 40 C
<br />RTU-17 CHECKOUT AAON RK-20-3-GO-1 20 EL 40 B,C
<br />RTU-18 CHECKOUT AAON RK-20-3-GO-1 D2 20 EL 40 C
<br />RTU-19 GM SALES / VC AAON RK-20-3-GO-1 D2 20 EL 40 A
<br />RTU-20 SEASONAL AAON RK-10-3-GO-1D1 10 EL 40 C
<br />RTU-21 GR STOCK AAON RK-05-3-GO-1 B1 5 EL 20 C
<br />RTU-22 GM SALES AAON RK-20-3-GO-000 20 -- - C
<br />RTU-23 GM SALES AAON RK-20-3-GO-1 D2 20 EL 40 B,C
<br />RTU-24 GM SALES AAON RK-20-3-GO-000 20 B,C
<br />-- -- -- --
<br />RTU-26 GM SALES AAON RK-20-3-GO-000 20 - -- C
<br />RTU-27 TLE AAON RK-05-3-GO-161 5 EL 20 A
<br />RTU-28 GR RECEIVING AAON RK-10-3-GO-1D2 10 EL 40 C
<br />RTU-29 BREAKROOM AAON RK-05-3-GO-000 5 -- -- A
<br />RTU-30 OFFICE/LOCKER AAON RK-05-3-GO-1B1 5 EL 20 C
<br />-- -- A
<br />RTU-32 REAR RRs AAON RK-05-3-GO-000 5 -- - A
<br />RTU-33 TRAINING AAON RK-03-3-GO-000 3 -- -- A
<br />RTU-34 CLAIM/STOCK AAON RK-10-3-GO-iB1 10 EL 20 C
<br />RTU-35 GM RECEIVING AAON RK-20-3-GO-000 20 EL 40 C
<br />GENERAL INFORMATION:
<br />1. EXISTING RTU INFORMATION PROVIDED FOR BAS AND REFERENCE PURPOSES ONLY AND NOT
<br />INTENDED FOR PURCHASE ORDER REQUESTS.
<br />2. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL EXISTING
<br />RTU INFORMATION.
<br />EXISTING CURB ADAPTER(S) PRIOR TO INSTALLING NEW CURB ADAPTER(S). DO NOT INSTALL
<br />A CURB ADAPTER ON TOP OF AN EXISTING CURB ADAPTER. COORDINATE ORIGINAL CURB
<br />DIMENSIONAL CHARACTERISTICS WITH AES AS REQUIRED FOR REPLACEMENT RTU COMPATIBILITY.
<br />4. EXISTING BAS VENDOR IS NOVAR.
<br />NOTES:
<br />A. EXISTING RTU TO BE REPLACED AS INDICATED.
<br />B. EXISTING RTU IS A DEDICATED INDOOR AIR QUALITY UNIT EQUIPPED WITH CO2 CONTROLS.
<br />C. EXISTING ROOFTOP UNIT TO REMAIN AND BE REFURBISHED BY
<br />COTRACTOR.
<br />=F7 c)
<br />0
<br />U O m zuio aWOo>
<br />� w
<br />� u. m�wmzFoazai
<br />W W xzLL��'aW��z
<br />� �a 3tag`�!` ay�apw
<br />w m m
<br />O o_� �zQO�OWj�HaQ
<br />O �LLLL W"�OZouWi�OSO
<br />zdw2Z0
<br />3u�=u9a��t. 4~�~
<br />ociawoOWWyo:)zNa aZWFfnJW06
<br />�
<br />a_oo �,o„�aSz�vW,=g
<br />mwd z��o �awam Pw
<br />LOW 0Q7Q: WUWW7R�Q=
<br />:/i ��NUDVJdO 0.'�F-
<br />0
<br />U O m zuio aWOo>
<br />� w
<br />� u. m�wmzFoazai
<br />W W xzLL��'aW��z
<br />� �a 3tag`�!` ay�apw
<br />w m m
<br />O o_� �zQO�OWj�HaQ
<br />O �LLLL W"�OZouWi�OSO
<br />zdw2Z0
<br />3u�=u9a��t. 4~�~
<br />ociawoOWWyo:)zNa aZWFfnJW06
<br />�
<br />a_oo �,o„�aSz�vW,=g
<br />mwd z��o �awam Pw
<br />LOW 0Q7Q: WUWW7R�Q=
<br />:/i ��NUDVJdO 0.'�F-
<br />Z
<br />�
<br />N
<br />W
<br />�
<br />Ii to
<br />~�M
<br />�.-
<br />W
<br />Z
<br />~�
<br />mN
<br />ff
<br />LU W
<br />lA�C�
<br />_
<br />WN
<br />o�
<br />o}cam
<br />W
<br />Z
<br />�wYW
<br />o
<br />Z
<br />O
<br />p
<br />$$�2
<br />z
<br />W �
<br />Q.
<br />�
<br />N '�
<br />Z
<br />WZur)
<br />W
<br />U'
<br />O
<br />m
<br />O
<br />O O a
<br />U
<br />O O
<br />o O
<br />~ N
<br />0
<br />Z o
<br />W o
<br />O
<br />N
<br />0
<br />W
<br />N cf-
<br />w
<br />m
<br />Z
<br />in
<br />O
<br />CHECKED BY: TDD
<br />DRAWN BY: NCL
<br />DOCUMENT DATE: 06/30/23
<br />ft
<br />THIS ITEM HAS BEEN
<br />ELECTRONICALLY SIGNED
<br />AND SEALED BY MICHAEL
<br />DEAN SCHAEFER ON THE
<br />DATE LISTED BELOW
<br />USING A DIGITAL
<br />SIGNATURE.
<br />PRINTED COPIES OF THIS
<br />DOCUMENT ARE NOT
<br />CONSIDERED SIGNED AND
<br />SEALED AND THE
<br />SIGNATURE MUST BE
<br />VERIFIED ON ANY
<br />ELECTRONIC COPIES.
<br />MICHAEL D. SCHAEFER
<br />LICENSE # 89591
<br />�% %1%ZtiSl:; 11111.$
<br />: �;• Mor 8959� t��
<br />y •
<br />�i •' OtiwDp.•' i
<br />06/30/2023
<br />MECHANICAL
<br />SCHEDULES
<br />SHEET:
<br />M 3