Laserfiche WebLink
TYPICAL REFRIGERATED CASE SYSTEM <br />CASE HEATER CASE HEATER CASE HEATER <br />1\/ �/ w <br />6..882�A 116.82 A 13.46 A <br />/ V V . <br />A 1B B1 I C A 1C <br />I I / AO <br />/ BO <br />CO <br />PROVIDE 208/30 HOME RUN TO PRE -WIRED PANEL IN <br />COMPRESSOR HOUSE. - - - -- - <br />NOTE: <br />ARRANGE CONNECTIONS FOR MAXIMUM BALANCE ON SYSTEMS <br />WITH UNEQUAL LOADS <br />CALCULATED UNBALANCED 30 LOAD <br />AO LOAD = (16.82 A + 13.46 A) x .866 = 26.2 A <br />BO LOAD = (16.82 A + 16.82 A) x .866 = 29.1 A (HIGH LEG) <br />CO LOAD =(16.82A+13.46A)x.866=26.2A <br />3 E- <br />NTSASE DEFROST WIRING <br />CONDUITS FOR REFRIGERATED CASE SYSTEM. CONDUIT(S) WILL SERVE 120V <br />CASE FAN, CASE LIGHT AND CASE ANTI -SWEAT CIRCUITS, IN ADDITION, <br />CONDUIT(S) WILL SERVE 208V CASE ELECTRIC DEFROST CIRCUIT (IF <br />APPLICABLE). NOTE: CIRCUITS MAY BE GROUPED TOGETHER TO MINIMIZE <br />NUMBER OF CONDUITS PROVIDED THAT ALL NEC REQUIREMENTS ARE MET <br />PROVIDE 5' LENGTH OF LIQUID -TIGHT FLEXIBLE METAL CONDUIT, <br />FURNISH APPROXIMATELY 12" PIGTAIL STUBBED FROM END OF <br />EACH FLEX CONDUIT FOR TERMINATION TO REFRIGERATED CASE <br />ELECTRICAL CONNECTION POINT BY R.C. <br />PROVIDE TRANSITION FROM PVC TO EMT <br />TYPICAL REFRIGERATED CASE SYSTEM <br />ROUTE EMT CONDUITS (UNDER CASES, ABOVE <br />SLAB) TO POINT OF TRANSITION TO FLEX <br />12" WIRE PIGTAILS (TYP) <br />5' FLEX CONDUIT (TYP) <br />FLOOR <br />BRACKET CONDUIT TO FLOOR <br />AS REQUIRED PER CODE (TYP) <br />PROVIDE TRANSITION FROM EMT TO FLEX <br />REFRIGERATION PIT <br />UNDERSLAB PVC CONDUIT FOR <br />REFRIGERATED CASE BRANCH CIRCUITS. <br />0CASE CONNECTION WIRING (TUNNEL) <br />2 NTS <br />Q <br />I <br />I <br />COMPRESSOR <br />HOUSE #2 <br />MDP2 <br />TCH2 <br />F SDP2 - <br />CH2L <br />CH2F <br />I <br />I <br />I <br />2 3 4 <br />I I <br />C181a 0 LS3C, C181b I D7.3a LS3C, D7.3b r _ 0 <br />��Oo �,� CH2F-29 C16.145 <br />G �� 16.145 2 O <br />��' 16.991 16.713 V043A (ED) �� RE1.1 <br />��/ 16.145 II 16.711 <br />CH2F-31 (TYP) <br />16.708 16.145 <br />I (TYP) i-----------�---------- i CH2F-40 <br />N i i M C18.3c C18.3b ; U,I <br />16.145 I °O C18.3e C18.3f u) I <br />U I <br />CH2F-42 --/ <br />------------------- C= <br />I � U' � 16.145 C18.3a I <br />CO CH2F-27 <br />2 <br />N ASR <br />16.145 16.944 16.145 <br />CH2F-10(TYP) CH2F-12 ` -1-1 <br />16.145------------ -- -------------L Q� E= -------------- M <br />CH2F-36 D7.1c D7.1b LS3C' D7.1a D7.2c D7.2b LS3C, D7.2a <br />16.145 � - <br />CH2F-25'- <br />43 (ED)4 - -� <br />16.145 <br />16.991 �6 <br />r-J ----- C15.3a <br />LS3C: I <br />I I <br />I <br />�ti I I <br />I I <br />I <br />I I I <br />I <br />I <br />I <br />I I <br />I I ch ch I <br />Sri I U U I <br />I I <br />I <br />CH2F-23 I <br />CH2F-38 <br />U , 16.145 <br />�W; <br />IN I I <br />� 16.145 <br />CH1 F-26 <br />16.145 <br />CH1F-35 <br />o (ED) <br />713 f <br />� I <br />I <br />-J, S3C, B12a I <br />I -- <br />I I <br />I I <br />I ' <br />I I <br />I N N I <br />U ; I <br />I I <br />I I <br />I <br />I I m m <br />I <br />I I I <br />I I i B12d <br />U I <br />CH1 F-28 <br />I 16.145 <br />I <br />; 16.145 <br />CH2F-19 <br />-- I <br />,U, <br />,cl,, <br />, rn , <br />- <br />CH1F-18 <br />I <br />I � � <br />CH1F-29-� <br />53 (ED)', - 1 <br />16.145 <br />16.991 0 <br />LS3C, B7a <br />I I <br />U I I <br />I I <br />I I <br />I I <br />I I <br />I � I <br />I <br />I <br />I <br />I I <br />I I I <br />I I I <br />I I I <br />U I I I <br />I I I <br />I I I <br />I I I <br />I I <br />; 16.145 <br />CH2F-17 <br />CH2L-15 I 00 C0 <br />0 16.145 <br />CH 1 F-20 16.708 <br />(TYP) <br />16.145 <br />I I <br />REAR REFRIGERATION ELECTRICAL PLAN <br />KEYNOTES <br />16.145 CONNECT CIRCUIT(S) TO EXISTING BRANCH <br />CIRCUITRY. MINIMUM WIRE SIZE AND <br />PANELBOARD CIRCUIT ARE NOTED. VERIFY SIZE, <br />RATING AND CONDITION OF EXISTING BRANCH <br />CIRCUIT CONDUIT AND WIRE PRIOR TO USE TO <br />ENSURE THAT THEY MEET REQUIRED SIZE, AND <br />ALL U.L. RATINGS AND REPLACE AS REQUIRED. <br />16.708 PROVIDE WIRING AND FINAL CONNECTIONS TO <br />RECEPTACLE. RECEPTACLE FURNISHED WITH <br />REFRIGERATED CASE. <br />16.711 POINT OF TRANSITION FROM EMT TO FLEX. <br />PROVIDE CONDUIT AND BRANCH CIRCUITS FOR <br />REFRIGERATED CASE FANS, LIGHTS, <br />ANTI -SWEAT HEATERS, AND ELECTRICAL <br />DEFROST (IF REQUIRED). TERMINATION TO <br />REFRIGERATED CASE ELECTRICAL CONNECTION <br />POINT BY R.C. REFER TO CASE CONNECTION <br />WIRING DETAIL. <br />16.713 ROUTE EVAPORATOR COIL FAN (CF) AND/OR <br />ELECTRIC DEFROST (ED) CIRCUITS TO <br />REFRIGERATION EQUIPMENT DEFROST <br />TERMINATION TROUGH. TERMINATIONS AT <br />EVAPORATOR COIL, CASE AND REFRIGERATION <br />EQUIPMENT BY RC. <br />16.944 REFRIGERATION ENERGY MANAGEMENT SYSTEM <br />CONTROLLER POWER: PROVIDE 120V CIRCUIT <br />FOR VENDOR FURNISHED REFRIGERATION <br />CONTROLLER. WHEN ENCLOSURE IS MOUNTED <br />ON REFRIGERATED CASE, CONNECT TO CASE <br />120V FAN CIRCUIT, UNLESS SHOWN OTHERWISE. <br />REFERENCE REFRIGERATION ENERGY <br />MANAGEMENT SHEETS FOR CONTROLLER <br />WIRING. <br />16.991 E.C. SHALL REMOVE EXISTING CONTACTOR IN <br />RACK CABINET AND CONNECT CIRCUITRY <br />DIRECTLY TO CIRCUIT OVERCURRENT <br />PROTECTION DEVICE. REFRIGERATION SYSTEM <br />EVAPORATOR FAN/DEFROST CIRCUITS SHALL BE <br />CONTROLLED BY FACTORY INSTALLED <br />CONTROLS IN NEW CASES OR BY FIELD <br />INSTALLED CONTROLS AT WALK-INS. IF <br />REQUIRED, E.C. SHALL INSTALL NEW VENDOR <br />FURNISHED OVERCURRENT PROTECTION <br />DEVICE FOR REFRIGERATION SYSTEM <br />EVAPORATOR FAN/DEFROST CIRCUIT. PROVIDE <br />A NEW NEMA 1 ENCLOSURE FOR FAN/DEFROST <br />CIRCUIT OVERCURRENT PROTECTION DEVICE, IF <br />NEEDED. MOUNT NEMA 1 ENCLOSURE AS CLOSE <br />AS POSSIBLE TO EXISTING RACK CABINET. <br />REFER TO REFRIGERATION LEGEND(S). <br />FEEDER SCHEDULE <br />ALL CONDUIT AND CONDUCTOR SIZES ARE BASED ON EMT WITH 40% <br />FILL, 750C RATED TERMINATIONS AND TYPE THHN/THWN-2 INSULATION. <br />FOR NON -EMT CONDUIT OR TERMINATIONS OR INSULATION TYPES <br />RATED LESS THAN 75°C. MODIFY SIZES ACCORDING TO NEC. <br />® <br />FEEDER OR GROUND SIZE <br />43 <br />(3)#8, (1)#10 G, 3/4" C <br />(3)#8, (1) #10 G, 3/4" C <br />(3) #6, (1 #8 G, 3/4" C <br />53 <br />_ <br />V043A <br />w J O <br />() <br />O Zwo a-w0Zrr <br />w Z~ O - <br />W <br />O a- 0 <br />waw��z <br />W' <br />xZLLo <br />Qf- F-ulLLFwppO�W OU <br />as ��ogwaLQopw <br />W n0- <br />O <br />Ew >oa <br />U) �¢Oa�=>Ua¢ <br />z <br />O <br />aLLw pNW�c7~pw�0xo <br />3: - <br />O= p z Z 0 S Z F Z <br />Q <br />Z <br />O,U"i<'W �awO0Oa <br />zm�;B0�-Qz m of "a�ao <br />J O w 0 U W <br />Zfr 2ZWU'0WwO00 <br />d <br />Op=�- <,y2Dz�cwm <br />�. <br />Dwa.Z�t0F__Q axF- W <br />-wwOax�LLXwUwwDm <br />�DNU0V)Q pwo <br />Z <br />0 <br />00 <br />w <br />CD <br />ti <br />M <br />w <br />w <br />;°Ln <br />W <br />co CV <br />Z <br />m� <br />LuLu <br />z <br />�poo <br />Z�Y� <br />Z <br />�Q <br />Z <br />O <br />OZc� <br />oclfw <br />U) <br />- <br />LuC7 <br />Wo <br />w <br />��rr <br />z <br />T Z <br />2 <br />wz, <br />w <br />cDa <br />F- <br />W <br />w` <br />Z <br />of w <br />J <br />ti <br />l!i m <br />_ <br />-1 <br />LL <br />m <br />a, <br />z <br />O <br />co <br />U <br />F <br />O <br />m <br />2i <br />O <br />00 J <br />O C==) LjL 0 <br />p O <br />0 � O <br />co a <br />O <br />O <br />N <br />`� <br />zi0 <br />o <br />Lu CD <br />0 <br />0 O N <br />0 W <br />Cn <br />W <br />N m <br />W <br />m <br />z <br />m <br />O <br />ISSUE BLOCK <br />CHECKED BY: JPL/JDS <br />DRAWN BY: RR <br />DOCUMENT DATE: 06/30/23 <br />THIS ITEM HAS BEEN <br />ELECTRONICALLY SIGNED <br />AND SEALED BY JOHN D <br />STOWELL ON THE DATE <br />LISTED BELOW USING A <br />DIGITAL SIGNATURE. <br />PRINTED COPIES OF THIS <br />DOCUMENT ARE NOT <br />CONSIDERED SIGNED AND <br />SEALED AND THE <br />SIGNATURE MUST BE <br />VERIFIED ON ANY <br />ELECTRONIC COPIES. <br />JOHN D. STOWELL <br />LICENSE # 91727 <br />`�`�,bp4lrllEt�,e�,d <br />a S TO si <br />x,,N Q E N <br />No. 91 727 <br />Pam' STATE OF <br />0•'• <br />1 )�4 1 % el-11 <br />Nmsi <br />06/30/2023 <br />REAR <br />REFRIGERATION <br />ELECTRICAL <br />PLAN AND <br />DETAILS <br />EXISTING CONDITIONS WERE TAKEN FROM EACH SUEiCON I I;ACTOR IS RESPONSIBLE FOR HAVING <br />ORIGINAL DRAWINGS AND MAY NOT REFLECT A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND <br />EXACT "AS -BUILT" CONDITIONS. CONTRACTOR SPEC IFICkTION`, IN THEIR RELATED FIELD. THE FAILURE <br />SHALL FIELD VERIFY ALL EXISTING CONDITIONS TO ACQU�IN I I I If MSELF WITH THIS KNOWLEDGE DOES <br />PRIOR TO SUBMITTING FINAL BIDS, CONTRACTOR NOT REI EVE THE RESPONSIBILITY OF PERFORMING <br />SHALL CAREFULLY COORDINATE NEW WORK AND THE WOKK PROPERLY. NO ADDITIONAL SHEFT- <br />DEMOLITION WITH ALL OTHER DISCIPLINES AND COMPEPSATION SHALL BE ALLOWED BECAUSE OF RE1.1 <br />EXISTING CONDITIONS. CONDITONS THAT OCCUR DUE TO FAILURE TO <br />FAMII IARIZE WORKERS WITH THIS KNOWLEDGE. <br />