Laserfiche WebLink
W <br />0 <br />Section 22 40 00 <br />Plumbing <br />V10092017 <br />General <br />1. Summary <br />1.1.1 Provide all materials and equipment and perform all labor required to install <br />plurnbing complete as indicated, as required by code, and as specified herein. <br />All sizes, etc. are Publix minimum and if local code requirements are higher, <br />the work shall be bid and installed accordingly. <br />1.1.1.1 Obtain and pay for all pernihs, bonds, inspection. <br />1.1.1.2 Provide 2-1/2" water service line, with water meter and 2-1/2" <br />backflow preventer. <br />1.1.1.3 Provide hot and cold water mains and distribution piping, all overhead <br />and concealed except main water supply into building and where <br />indicated on the Drawings. No PVC pipe allowed above floor stab, <br />(except plumbing waste piping, unless not code approved). <br />1.1.1.4 Provide a system of soil and waste drains, vents, and connections to all <br />sewer, and water mains and all fixtures. <br />1.1.1.5 Plumbing Fixtures: Provide and adjust, except as herein specified. <br />1.1.1.6 Provide Grease Interceptors as specified and as required by local codes. <br />1.1.1.7 Provide all piping hanging and hangers. <br />1.1.1.8 Provide gas piping and all indirect drains required for equipment <br />firnished in other sections, and by Owner, except provide indicated <br />drains (floor drains, hub drains, floor sinks, etc.) for refrigerated cases, <br />walk-in coolers, and freezers. <br />1.1.1.9 Provide rough -in plumbing for fixtures indicated as fiimished by Publix <br />or others, and make required connections. Include uncrating equipment, <br />moving into place, and installing complete. <br />1. 1. 1. 10 Coordinate plumbing work with all other trades including Refrigeration <br />Contractor's work. <br />1. I. 1. I I Provide all other materials and services required for a complete <br />working installation described in Contract Documents. <br />1.1.2 All apparatus shall be installed at exact height and locations as shown on the <br />Architectural Drawings, or if not shown, at heights and locations detennined by <br />applicable codes and laws. <br />1.1.3 Perform all excavation and backfill required for services, and for all plumbing <br />and work inside and outside the building. Cutting of curbs, walks, concrete and <br />paving required for excavation shall be done by appropriate trade. <br />1. 1.4 All store cases, coolers, and freezers will be furnished and set in place by Publix. <br />The Reffigeration Contractor shall make all condensate waste connections <br />required to Plumbing Contractors stub ups. Check equipment drawings against <br />Drawings in order to verify exact locations. Provide gas piping as indicated. <br />1.2. Definitions: Explanation and Precedence of Documents: <br />1.2.1 For purposes of clarity and leg;ibility, Plumbing Drawings are essentially <br />diagrammatic and, although size and location of equipment are drawn to scale <br />wherever possible, Contractor shall make use of all Contract Documents. <br />1.2.2 The Drawings indicate size, connection points and routes of pipe. It is not <br />intended, however, that all offsets, rises and drops are shown. Install piping as <br />required to fit structure, avoid obstructions, and retain clearance, headroom, <br />openings and passageways. <br />1.2.3 Carefully examine all existing conditions, existing piping and premises and <br />compare the Drawings with the existing conditions. Submittal of bid indicates <br />that the Contractor has examined the site and Drawings and has included all <br />required work in his bid. No allowances will be made for any error resulting <br />from Contractor's failure to visit Job Sites and to review Drawings. <br />1.2.4 Conflicts, discrepancies, interferences and omissions in documents shall be <br />brought to the attention of the Publix Engineer for clarification prior to <br />commencement of work. <br />1.3. Submittals: <br />1.3.1 Submit LOI in accordance with Section 01 33 00 Submittal Procedures. <br />1.3.2 Within 30 days of Contract Commencement (Authorization to Proceed), submit <br />for Publix' Architect's approval: <br />Fixtures and trim with cuts including rough -in dimensions. <br />Equipment (water heaters, expansion tanks, other items) <br />Drains and cleanouts (floor and wall) <br />Valves, stops, hose bibbs <br />Miscellaneous <br />Roof flashing <br />Hangers and Seismic Bracing <br />Piping, piping diagrams <br />Other items required to complete the Work <br />1.3.3 Submit two (2) identical bound copies of all items. Arrange categories in order <br />listed above. <br />1.3.4 All cuts for the above shall have rough -in dimensions, connection sizes, and any <br />special installation requirements. In addition, furnish motor horsepower voltage <br />and phase for all equipment. <br />1.3.5 Project Record Drawings: Comply with Section 0 1 78 39. <br />1.3.6 Do not order materials or proceed with work untill all submittals have been <br />reviewed, and approved. <br />1.3.7 Confirm electrical and other requirements with other contractors. <br />1.4. Quality: <br />1.4.1 Subcontractor: <br />1.4.1.1 The Plumbing Subcontractor shall be a reputable firm regularly <br />engaged in this type of work, employing skilled workmen, and with <br />proper equipment. <br />1.4.1.2 Upon request Subcontractor shall show evidence of at least two similar <br />jobs, of comparable size and character, installed and operating within <br />the previous two years prior to bid opening. <br />1.4.1.3 Publix. reserves the right to refuse any Subcontractor with or without <br />disclosing cause. <br />1.4.2 Personnel: W <br />1.4.2.1 Employ an experienced Superintendent to oversee all operation. <br />1.4.2.2 Work shall not proceed without adequate supervision present at all <br />times. <br />1.4.2.3 Work shall be accomplished by workers certified in their trade as <br />masters, journeymen, and apprentices in accordance with regulations of <br />the governing authority or customary practice. Utilize workers with <br />skills in proportion to complexity of tasks required. <br />1.4.2.4 Publix reserves the right to refiise assignment of workers to Publix <br />work with or without disclosing cause. <br />1.4.3 Quality Standards <br />1.4.3.1 Work shall be accomplished to ensure leak -proof installation. <br />1.4.3.2 Work will be judged by Publix in comparison to work of similar types. <br />Substandard construction as judged by Publix Representative will not <br />be accepted. <br />1.4.3.3 Neatness counts. Make all joints, connections, unions, etc. with proper <br />care to insure that tight connections are made without excess material, <br />well secured to supports. <br />1.4.3.4 Install piping with runs straight, accurately formed radiuses at bends, <br />and adequate supports. <br />1.4.4 Regulations: Comply with applicable provisions of the following codes (latest <br />version adopted by governing agencies): <br />State Sanitary Code <br />Local Building Code <br />ASME Code for Unfired Pressure Vessels <br />International Plumbing & Gas Code <br />Florida State Plumbing & Gas Code <br />Georgia State Plumbing & Gas Code <br />North Carolina State Plumbing & Gas Code <br />OSHA - for construction <br />Other applicable laws and regulations. <br />1.4.5 Coordination: Work shall be accomplished along with the work of other trades. <br />Cooperate with others to benefit the job as a whole. <br />1.4.6 Participate in the Pre -Construction Conference. <br />1.5. Sequencing: <br />1.5.1 Notify General Contractor, or any others, of all required chases, sleeves and <br />openings required so that the work can be accomplished without delay. Provide <br />necessary sleeves, etc., to be installed. Otherwise, Plumber shall pay for <br />appropriate trades to perform cutting and patching. <br />1.5.2 Joists, girders, beams, columns or reinforcing steel shall not be cut. <br />1.5.3 Where construction necessitates the routing of piping through structural <br />members, framing or under footings, permission to make such installation shall <br />first be obtained from the Publix Field Representative <br />1.6. Temporary Operation: <br />1.6.1 The Owner may require operation of parts or all of the installation prior to Final <br />Acceptance. <br />1.6.2 Cost of utilities for such operation shall be paid by the Contractor. This <br />operation does not constitute acceptance of the Contractor's work. <br />1.6.3 All gas and water used for construction shall be paid for by the General <br />Contractor. Furnish and install all temporary water piping required for <br />construction purposes and remove piping when use is no longer required. <br />Restore site and piping to original conditions. <br />1.7. The Owner reserves the right to make emergency repairs as required to keep equipment <br />in operation without voiding the Contractor's guarantee nor relieving the Contractor of <br />his responsibilities during the guarantee period. <br />1.8. Operating Instructions and Service Manual: <br />1.8.1 Provide two (2) neatly bound copies of maintenance and instructions book, parts <br />lists pertaining to all equipment furnished. <br />1.8.2 Each section shall be indexed and include parts lists, instruction books, <br />suppliers' phone numbers and addresses, and individual equipment guarantees <br />all in separate sections. <br />1.8.3 Representatives of the Owner shall be instructed by the Contractor as to complete <br />care and operation of the plumbing system. Inform the Architect in writing as to <br />the persons who received the instructions and the date that this was done. <br />1.9. Polypropylene Piping and Products Warranty: <br />1.9.1 Manufacturer shall warranty pipe and fittings for 10 years to be free of defects in <br />materials or workmanship. <br />1.9.2 Warranty shall cover labor and material costs of repairing and/or replacing <br />defective materials and repairing any incidental damage caused by failure of the <br />piping system due to defects in materials or workmanship. <br />2. Products: <br />2.1. Materials: <br />2.1.1 All materials shall be new, full weight, of the best quality with the same brand or <br />manufacturer used for each class of materials or equipment. All similar materials <br />such as valves, pumps, boilers, fixtures, shall be of the same type and <br />manufacturer unless otherwise designated. <br />2.1.2 All plumbing fixtures shall be "first quality" as defined and set forth in <br />Commercial Standard CS 20-36 As Promulgated By The U.S. Department of <br />Commerce. <br />2.2. Fixtures <br />2.2.1 Provide vitreous white china fixtures (unless otherwise noted). <br />2.2.2 Support wall -mounted fixtures w/ manufacturer approved carriers. <br />12.3 American Standard product designations have been used for consistency. <br />Equivalent fixtures by Crane, Kohler, Zum, Sloan, or Toto may be accepted. <br />2.2.4 Install all owner furnished fixtures and provide all the necessary components <br />as required for a complete Installation. <br />Equipment <br />2.3.1 Grease Interceptor: Rectangular, pre -cast concrete, all in accordance with state <br />and local codes. Two cast iron traffic tops with traffic cast iron clean -outs are <br />required. Tanks and lids shall be designed for an H-20 traffic load. Tanks shall <br />be reinforced with welded wire mesh and steel bars. Compressive strength of <br />concrete shall be a minimum of 5500 PSI at 28 days. Provide additives or <br />coatings to protect tank interiors to minimum PH of 3. <br />2.3.2 Drains, Clean -outs: As scheduled. Approved manufacturers: <br />JR Smith <br />Zurn <br />Pipe and Fittings: <br />2.4.1 Hot and cold water piping: <br />2.4.1.1 ASTM B88 type "L" seamless copper tubing. Main service type "K" <br />with red lion seal cote coating, or approved equal. <br />2.4.1.2 Fittings: Wrought copper solder fittings, solder with silvaloy, <br />streamline 122, phos-copper or approved equal no -lead solder. <br />2.4.1.3 Alternate: Copper press fittings shall conforrn to the material and <br />sizinge requirements of ASME B16.18 or ASME B16.22. O-ringsfior <br />copper press fittings shall be EPDM. Approved Manufacturers: <br />Viega <br />2.4.2 Gas Piping: Shall be schedule 40-A-120 black steel pipe with black banded <br />malleable iron fittings, pipe shall be welded. Grounding by Electrical <br />Contractor. <br />2.4.2.1 Indoors: ASTM A53 steel pipe, schedule 40, black forged steel weld <br />fittings. <br />2.4.2.2 Outdoors: ASTM A53 steel pipe, schedule 40, mill galvanized, fittings <br />as required. <br />2.4.3 Plastic Gas Piping: Used underground only. Shall conform to the requirements <br />of ASTM D2513 for medium -density polyethylene pipe and tubing. Fittings <br />shall comply with the requirements of ASTM D2683 for socket type, ASTM <br />D3261 for butt fitsion and ASTM F 1055 for electrofusion. Pipe shall be yellow <br />and marked in accordance with ASTM D2513. <br />2.4.4 Soil, Waste, Vent Pipe: <br />2.4.4.1 PVC DWV pipe (where allowed by codes): PVC schedule 40 solid wall <br />pipe and PVC DWV fittings used in sanitary drain, waste, and vent <br />(DWV) and storm drainage applications. Pipe shall be IPS conforming <br />to ASTM D 1785 and ASTM D2665. Fittings shall conform to ASTM <br />D2665. Solvent cement shall conform to ASTM D2564. <br />2.4.4.2 ABS DWV pipe (where allowed by codes): Unplasticized, ASTM <br />D266 1, Type 1, Grade 1, solvent cement joints, DWV fittings. schedule <br />40 unless indicated otherwise on the Drawings, all elbows shall be long <br />sweep type. Use only where indicated on the drawings. <br />2.4.4.3 Cast Iron Pipe: Coated service weight cast iron soil pipe using coated <br />service weight cast iron fittings. <br />2.4.4.4 Vent Piping Option: All vent piping above grade may be copper DWV, <br />with copper drainage fittings, solder as for hot and cold water. <br />2.4.5 Provide field fabricated DWV copper or cast brass traps with an integral clean <br />out at bottom of traps for stainless steel utility sinks, except those which <br />discharge to a floor sink. <br />2.5. Valves, Stops, Specialties <br />2.5.1 Materials: Valves 3" and smaller shall be bronze with threaded or soldered ends. <br />Furnish unions adjacent to all screwed central valves and at all connections to <br />equipment. Valves shall be made in the USA. All water service valves, stops and <br />specialties shall be lead free. <br />2.5.2 Approved Manufacturers: <br />Apollo <br />Hammond/Milwaukee <br />Mueller <br />Nibco <br />Watts <br />Wilkins <br />2.5.3 Gate Valves: 1/4"-3", bronze body, solid bronze wedge, rising stem, union <br />bonnet, 300 psi non -shock CWP, MSS-80. <br />2.5.3.1 Basisofdesign: NibcoT/S-111-LF <br />2.5.4 Check Valves: <br />2.5.4.1 Swing Check Valves: 1/4"-2", bronze body, horizontal swing, Y- <br />pattern renewable seat and PTFE disc, 200 psi non -shock CWP, MSS- <br />SP-80. <br />2.5.4.1.1 Basisofdesign: NibcoT/S-413-Y-LF <br />2.5.4.2 Lift Check Valves: 1/2"-2", bronze body, inline lift, PTFE discs, <br />stainless steel spring, MSS-SP-80. <br />2.5.4.2.1 Basis of design: Nibco T/S-480-Y-LF <br />2.5.5 Ball Valves: 1/4"-2", two piece bronze body, fall port, bronze trim, chrome <br />plated brass ball, blow out proof stem, 600 psi non -shock CWP, MSS-SP- I 10. <br />2.5.5.1 Basis of design: NibcoT/S-585-66-LF <br />2.5.6 Gas Valves: 1/4"-3", two piece bronze body, full port, bronze trim, chrome <br />plated brass ball, blow out proof stem, 600 psi non -shock CWP, MSS-SP- I I 0, <br />ASME B 16.33. <br />2.5.6.1 Basis of design: Nibco T-585-70-UL(1/4"-I") <br />2.5.6.2 T-580-70-UL(I-1/4"-3") <br />2.5.7 Mechanical Gas Valve with Remote Pull: ASCO Automatic Switch Co., Model <br />as indicated on Drawings. <br />2.5.8 Mixing Valves: Anti -scald, thermostatic point of use. Bronze body, locking <br />control, integral check valves, ASSE 1070 approved. <br />2.5.8.1 Approved Manufacturers: <br />Apollo <br />Bradley <br />Lawler <br />Powers <br />Watts <br />Wilkins <br />Zurn <br />2.5.9 Interior Hose Bibbs and Stops <br />2.5.9.1 Stops: Quarter turn, angle ball stop valve, all brass construction. <br />Brasseraft, McGuire, Eastman <br />2.5.9.2 Interior Hose Bibbs: <br />Chicago 9387 Brass 3/4" R.C.P W/Watts No. 813C Vacuum Breaker, <br />or T&S Brass B-0737-POL. <br />2.5. 10 Exterior Hose Bibbs and Hydrants: <br />2.5.10.1 Description: All shall have integral vacuum breakers and an integral <br />stop valve. If an integral stop valve is not available, provide an in -line <br />gate valve. <br />2.5.10.2 Approved Manufacturers: <br />Acorn <br />J.R. Smith <br />Zurn. <br />2.5.11 Flush Valves: <br />2.5.11.1 Description: Cast brass or bronze body with corrosion -resistant internal <br />components; non -hold open, control stop with check valve; vacuum <br />breaker and copper or brass tubing; polished, chrome -plated finish on <br />exterior parts; vandal -resistant stop cap; ADA compliant handle. <br />2.5.11.2 Manufacturers: <br />Toto <br />Sloan - Sloan <br />Zurn - Z6000AV <br />2.5.12 Faucets: <br />2.5.12.1 Description: Cast brass body with corrosion -resistant internal <br />components; polished, chrome -plated finish. <br />2.5.12.2 Manufacturers: <br />Chicago Faucet <br />T & S Brass <br />Sloan-Basys EPX-250-500 (lavatories onIv) <br />2.5.13 Drain Valves <br />2.5.13.0.1 Description: Cast brass body stainless steel ball dual teflon <br />seals, vandal resistant stainless steel strainer. 1/4" turn lever <br />handle. <br />2.5.13.0.2 Manufacturers: <br />Drain King <br />2.5.14 Hand Sinks: <br />2.5.14.1 Description: Wall hanging; 18 gauge, 304 stainless steel, polished <br />finish, basin with radius comers; back for faucet; integral side support <br />panels, approximate size - 17"x I 6"x5" with 2-3/16" drain outlet. <br />2,5.14.2 Manufacturers: <br />Elkay <br />Just <br />Amtekco <br />2.5.15 Storage Water Heaters: <br />2.5.15.1 Electric: Where indicated to be contractor provided tanks shall be glass - <br />lined steel, 2" foam insulation and enamel finish on metal outer jacket. <br />Electric heating elements shall be low or medium density, screw in type, <br />ceramic terminal blocks, heavy duty contactors and internal power <br />circuit fusing. Element operation shall be linear sequencing. Corrosion <br />resistant drain valve, replaceable anode rod. <br />2.5.15.2 Gas: Where indicated to the contractor provided tanks shall be glass - <br />lined steel, 2" foam insulation and enamel finish on metal outerjacket. <br />Sealed combustion chamber with helical heat exchanger, integral <br />intelligent control panel. Corrosion resistant drain valve, replaceable <br />anoderod. <br />2.5.15.3 Approved Manufacturers: <br />AO Smith/State <br />Rheem/Ruud <br />2.6. Miscellaneous: <br />2.6. 1 Faucet (Janitor Room): Sink faucet with top brace, 9" - I 0" rigid spout with <br />bucket hook vacuum breaker and integral stops; at 36" above floor. <br />T&S Brass <br />Chicago Faucet <br />2.6.2 Vacuum Breakers, Backflow Preventers, Dual Check Valves: Bronze body, lead <br />free threaded connections for 2" NPS and smaller. Shall be installed on all <br />fixtures where required. <br />Apollo <br />Watts <br />Wilkins <br />2.6.3 Unions: Malleable iron ground joint equivalent and similar to Crane 519, up to <br />and including 2 inch. Over 2 inch shall be cast iron flanged with a Garlock 7022 <br />Gasket. <br />2.6.4 Reducing and Regulation: Water, air, gas, Watts or approved equal, model as <br />indicated on the Drawings. <br />2.6.5 A shut off valve shall be placed near the building on the water main. It shall be <br />placed in a box or tile pipe and have a removable plate cover of cast iron, equal <br />to Mckinley Iron Works, Fort Worth, Texas; Type MB 14, for 8000# loading. <br />2.7. Pipe Insulation <br />2.7.1 Rigid fiberglass pipe insulation: <br />2.7.1.1 Heavy density molded insulation from Inorganic glass fibers bonded <br />with a thermosetting resin; jacketed with a reinforced, wrinkle - <br />resistant, all -service vapor retarder facing and a factory -applied <br />longitudinal double -pressure adhesive closure system. Use factory butt <br />strips to complete joints. Thermal conductivity ['K' Factor (BTU -inch/ <br />ftl-hr-'F) at 75'F mean] shall be 0.23 maximum. <br />2.7.1.2 Manufacturers: <br />Owens -Coming <br />Johns Manville <br />CertainTeed <br />2.7.2 Flexible polyethylene/polyolefin pipe insulation: <br />2.7.2.1 Unicellular polyethylene then-nal plastic, prefon-ned pipe insulation; <br />white color, 25/50 rated, pre -slit with factory -applied adhesive on both <br />surfaces. Use factory adhesive for gluing buttjoints. Thermal <br />conductivity ['K' Factor (BTU-inch/ft2 -hr-'F) at 75'F mean] shall be <br />0.27 maximum. <br />2.7.2.2 Manufacturers: <br />Armacell <br />Nomaco <br />2.7.3 Insulation thickness: <br />2.7.3.1 For domestic hot water: <br />Diameter' Thickness <br /><= F, 0.51, <br />>= 1 1/4" 2.8. Pipe Hangers and Supports: <br />2.8.1 Piping shall be held firmly in place by adjustable galvanized carbon steel band <br />or clevis hangers which comply with MSS-SP-69. Hangers shall be located <br />adjacent to fittings, at each offset or change of direction, at ends of branches <br />over 5 feet long, at riser pipes, and along piping where necessary to prevent <br />sags, bends or vibrations. <br />2.8.2 Band Hangers: Steel and PVC piping equal to Empire fig. 3 1 OG. Copper and <br />PPR piping equal to Empire fig. 3 IOCTI. <br />2.8.3 Clevis Hangers: Steel and PVC piping equal to Empire fig. I IOEG. Copper and <br />PPR piping equal to Empire fig. I I OCTI. <br />2.8.4 Stainless steel pipe straps and hangers shall be used for all exposed piping and <br />underslab piping where structural slabs are provided. <br />2.8.5 Pipe straps shall be heavy gauge galvanized iron factory fabricated to fit against <br />supporting surface when installed. Makeshift devices are not acceptable. No <br />plumbing tape is allowed. Use insulation shields at each pipe hanger and <br />support. <br />2.8.6 The maximum spacing between hangers or supports measured along the piping <br />shall be as listed below: <br />Steel Copper PVC/ <br />Polypropylene <br />H V H V H V <br />1/2" and 3/4" 12 ft. 15 ft. 6 ft. 10 ft. 4.0 ft. 10 ft. <br />I" and I- 1/4" 12 ft. 15 ft. 6ft. 10 ft. 4.0 ft. 10 ft. <br />1-1/2", 2" & 2-1/2" 12 ft. 15 ft. 10 ft. 10 ft. 4.0 ft 10 ft. <br />3" 12 ft. 15 ft. 10 ft. 10 ft. 4.0 ft 10 ft. <br />4" 12 ft. 15 ft. 10 ft. 10 ft. 4.0 ft. 10 ft. <br />6" 12 ft. 15 ft. 10 ft. 10 ft. 4.0 ft. 10 ft. <br />2.9. Roof flashings: All vent and roof drains shall be flashed by Roofing Contractor with <br />lead flashing furnished by the Plumbing Contractor. Flashing shall turn down 2" into <br />vent pipes. <br />2.10. Isolating Couplings: Provide dielectric protection for gas and water main risers inside <br />building. Isolate connections of copper and steel pipe with cathodic isolating unions. <br />Acceptable Manufacturers: <br />EPCO <br />W & K Dielectric <br />F.H. Maloney <br />2.1 1. Polypropylene Pipe and Piping Products (PPR): <br />2.1 1.1 Polypropylene pipe and fittings shall be manufactured from a P-R resin meeting <br />the short-term properties and long-term strength requirements meeting the short- <br />term properties and long-term strength requirements of ASTM F 2389. The pipe <br />shall contain no rework or recycled materials except that generated in the <br />manufacturer's own plant from resin of the same specification from the same <br />raw material. All pipe shall be made in a three layer extrusion process. <br />Domestic hot water and heating piping shall contain a fiber layer (faser) to <br />restrict thermal expansion. All piping shall comply with the rated pressure <br />requirements of ASTM F 2389. All pipe shall be certified by NSF International <br />as complying with NSF 14, NSF 6 1, and ASTM F 2389 or CSA B 137.1 1. <br />Valves with brass components shall be manufactured in accordance with the <br />manufacturer's specifications and shall be certified by NSF International as <br />complying with NSF 6 1. <br />2.11.2 Polypropylene hot water piping shall be insulated as required to meet the <br />equivalent insulation rating indicated for copper piping systems. <br />2.11.3 Acceptable Manufacturer: <br />Aquatherm Greenpipe, Aquatherm, Inc. <br />Aquatherm Faser, Aquatherm, Inc. <br />3. Execution <br />3.1. Examination: <br />3.1.1 Verify all field dimensions and locations of equipment and fixtures within the <br />layout as established by the General Contractor to insure close, neat fit, with <br />other trades work. <br />3.1.2 Examine all work of others. Notify Architect in writing if any conditions exist <br />which will prevent satisfactory installation of materials or equipment. Start of <br />work without notification indicates acceptance of work in place, <br />3.2. Excavation: <br />3.2.1 Perform excavation for trenches under slab and outside building lines as <br />required for installation. Excavate true to lines and grades shown to achieve <br />adequate fall on drain lines and as needed for refrigeration drainage. <br />3.2.2 Bell holes shall be dug to allow soil pipe to lie fully supported. <br />3.2.3 Rock shall be excavated 3 inches below the laying depth, and the trench <br />shall be backfilled with sand 3 inches deep. <br />3.2.4 Over -excavation shall be added in 12 inch lifts (max) and mechanically <br />compacted. Flooding or puddling not permitted. <br />3.2.5 All piping which will be under walks, planters, arcades, parking lots, concrete or <br />asphalt shall be mechanically compacted in 12 inch lifts (max). <br />3.3. Interface with Site Utilities: <br />3.3.1 Coordinate with other work. Connect to site supplies and storm drain at 5'-O" <br />dernising line. <br />3.3.2 Provide waste connection to site sewer at 5'-O" demising line. Provide grease - <br />bearing waste connection to grease trap and from grease trap to waste line <br />located as shown on the Drawings or otherwise indicated. <br />3.4. Pipe Installation: <br />3.4.1 Install horizontal sanitary and drain piping, to a uniform grade of not less than I/ <br />8" per foot, unless otherwise noted. <br />3.4.2 Openings in pipes, drains, fitting, apparatus and equipment shall be kept covered <br />or plugged to prevent accumulating obstructions in the piping. <br />3.4.3 Run piping free of traps, sags, bends or other defects. grade and valve for <br />complete drainage and control of the system. <br />3.4.4 All waste, vent and water lines shall be concealed, and all water lines shall be <br />overhead. <br />3.4.5 Maintain headroom and keep passageways clean. offset to maintain the required <br />clearance and conform with architectural and structural features of building. Run <br />parallel and straight with adjacent walls or ceilings to present a uniform <br />appearance. Group long runs together. Run concealed in finished rooms. <br />3.4.6 All rough -ins shall be set exactly to measurements furnished by manufacturer. <br />Batteries of fixtures shall have rough outlets set in straight lines at equal <br />spacing. <br />3.4.7 Flush out all lines to insure that they are clear of obstructions prior to the setting <br />of refrigerated cases. If lines are not clear and a case is set, the Plumbing <br />Contractor shall be responsible for the removal and re -set cost. <br />3.4.8 Water piping shall not be embedded in concrete nor concealed within the floor <br />slab within the building. unless shown on drawings). Isolate copper piping from <br />concrete with tar paper or PVC sleeve. <br />3.4.9 All piping shall be installed to prevent unusual noise from the flow of water <br />under normal conditions. Install pipe isolators at ring hangers consisting of a <br />metal sheath with end flanges assuring positive retention in the ring hangers. <br />Separate cold lines from hot lines by 6". <br />3.4. 10 Provide dirt pockets on low point of vertical gas piping. Install full pipe size drip <br />pockets at low point in change of grade. <br />3.4. 11 For refrigeration case drains, stub up a 3" line I" above floor; no hub required. <br />3.5. Pipe,joints, fittings, and connection -installation <br />3.5.1 Cast Iron Soil Pipe: Pack tight with first quality oakum to within I inch of end <br />hub. Fill remaining space with one pouring of molten lead and caulk tight; or <br />make-up with neoprene gaskets. <br />3.5.2 Screwed Piping: Make up with pipe dope, applied only to male thread. Remake <br />leaky joints with new material without use of thread cement or caulking. Paint <br />exposed threads of all pipe with asphaltic paint. <br />3.5.3 Copper Tubing: <br />3.5.3.1 Solder with 95-5 (no -lead solder) and a noncorrosive flux. Thoroughly <br />clean inside and outside surfaces with sandpaper or wire brush before <br />assembly. Defective joints shall be dismantled, cleaned, and resoldered. <br />Do not use acid Solder. <br />3.5.3.2 Press Connections: Copper press fittings shall be made in accordance <br />with the manufacturer's installation instructions. The tubing shall be <br />fully inserted into the fitting and the tubing marked at the shoulder of <br />the fitting. The fitting alignment shall be checked against the mark on <br />the tubing to assure that the tubing is fully engaged (inserted) in the <br />fitting. The joints shall be pressed using the tool approved by the <br />manufacturer. <br />3.5.4 Copper, brass pipe and chromed, polished or painted connections from fixtures <br />shall show no tool marks. <br />3.5.5 PVC Joints: Clean socket and pipe ends with cleaner recommended by cement <br />manufacturer. Liberally apply solvent cement to both socket and pipe ends. <br />Make up joint firmly. <br />3.5.6 Gas Piping: <br />3,5.6.1 Black iron schedule 40, welded except at equipment connections. <br />Certified welding is required. <br />3.5.6.2 At each piece of equipment, provide shut-off valve, union, drip leg <br />(minimum 4 times pipe diameter, capped) and flexible pipe connection <br />3.5.7 Springing, bending or forcing of pipe will not be allowed. Use fittings for all <br />offsets or changes in alignment of piping. Center hubs so cast iron will lay <br />straight without pinched joints. <br />3.5.8 Street elbows, bushings, and long screw fittings will not be allowed on metal <br />pipe. <br />3.5.9 Cleanly cut pipe and tubing and rernove burrs to full diameter of pipe. Excessive <br />reaming will not be permitted. Remove metal particles from ends of pipe and <br />clear each section of foreign material before assembling. <br />3.5. 10 Cut pipe threads to full depth of die and screw up tight to fully engage thread in <br />fitting. Threads to comply with ASA No B 2. 1, and be cut with clean sharp dies. <br />3.5.11 Clean outs: Clean outs shall be placed as shown on Drawings, or max. 50' o.c., <br />at bases of stacks, at major changes in direction, and at the ends of all lines that <br />have 2 or more openings going into that line, or as required by code. Clean outs <br />shall be as indicated on Drawings. If PVC. is used include hub adaptor. <br />3.5.12 Provide shut-off valves in access panels to allow shut down of area of fixtures <br />where indicated on Drawings. <br />3.5.13 Provide shock absorbers with isolating gate or ball valves as indicated on the <br />Drawings. Mount in the vertical position as recommended by the manufacturer. <br />3.5.14 The inside of all pipes shall be clean, reamed smooth with no buffs, fins or other <br />obstructions. All drains including trap under utility sinks shall be copper with <br />solderedjoints. No pipe shall be run exposed, unless approved by Publix <br />Representative. <br />3.6. Polypropylene Piping System: <br />3.6.1 Install listed pipe materials and joining methods below in the following <br />applications: <br />3.6.1.1 Underground: Service entrance piping shall be Type K copper with the <br />transition to Polypropylene (PP-R) no less than I ft. A.F.F. <br />3.6.1.2 Aboveground: Polypropylene (PP-R) piping in SDR 6, 7.5 or I I based <br />on the required minimum pressure rating and use temperature. <br />3.6.2 Fusion Welding of Joints: <br />3.6.2.1 Install fittings and joints using socket -fusion, electro fusion or butt - <br />fusion as applicable of the fitting type. All fusion -well joints shall be <br />made in accordance with the pipe and fitting manufacturer's <br />specifications and product standards. <br />3.6.2.2 Fusion -weld tooling, welding machines and electro ftision devices shall <br />be as specified by the pipe and fittings manufacturer. <br />3.6.2.3 Prior to joining, the pipe and fittings shall be prepared in accordance <br />with ASTM F 2389 and the manufacturer's specifications. <br />3.6.14 Joint preparation, setting and alignment, fusion process, cooling times <br />and working pressure shall be in accordance with the pipe and fitting <br />manufacturer's specifications. <br />3.7. Pipe Insulation <br />3.7.1 Sealed at all joints and seams with adhesive in accordance with insulation <br />manufacturer's recommendations. Pipe supports shall be on the outside of the <br />insulation with 6" minimum length saddles of galvanized sheet metal. <br />3.7.2 Fiberglass seams shall be sealed with factory furnished self sealing lap and butt <br />joints in accordance with manufacturer's recommendation. <br />3.7.3 Polyolefin seams shall be sealed with factory-finnished, self -adhering, pressure <br />sensitive seams. Buttjoints shall also be glued with factory -furnished adhesive <br />3.8. Fixture Installation <br />3.8.1 Stub out to the exact location of the fixtures. All stubs shall beset <br />symmetrically with fixture. <br />3.8.2 Install fixtures and trim supplied by Publix or others. Connect to plumbing as <br />required. Finish out and trim fixtures as needed for complete installation. <br />3.8.3 Caulking: All plumbing fixtures shall be bedded and caulked alongjoint at <br />walls, and other intersecting surfaces with butyl caulking compound, counter <br />tops and brass shall be caulked with "plumbers putty". <br />3.8.4 Backing shall be of 2 x 6 pressure treated wood flush with stud face and <br />extending to next stud beyond fixture on each side. Secure as required. <br />3.9. Inspection: <br />3.9.1 The Work shall be installed under the inspection and with the approval of <br />Publix' Authorized Representative. <br />3.9.2 Notify the Publix' Representative two days in advance of backfilling, enclosing <br />or covering all plumbing lines so that he may inspect installation. <br />3.9.3 Do not cover or enclose plumbing until inspection is made and installation is <br />acceptable. Correct deficiencies in installation as directed by Publix' <br />Representative. <br />3.10. Tests and Adjustments <br />3. 1 0. I All soil, waste, and vent piping shall be filled with water to the highest point in <br />each system with all air removed. The lines shall be flushed by removing the teE <br />plug. Piping may be tested in sections providing that all portions to be conceale, <br />shall be subjected to not less than a 10 ft. head for 24 hours with no leaks. <br />Standpipe installed for head test shall be 2 in. minimum diameter. <br />3.10.2 Sewer piping shall be filled with water to it's highest point. <br />3.10.3 Verify that all drain lines have been flushed and are clear of debris prior to <br />completion of Work. <br />3.10.4 Water piping shall be flushed out, tested at I 00 psi and shall be left under <br />pressure of supply main for the balance of the construction period. <br />3.10.5 Plumbing fixtures shall be filled with water and checked for leaks or retarded <br />flow. <br />3.10.6 All flush valves, loose key stops, valves and similar equipment shall be adjust( <br />and balanced to provide for the proper operation of the various systems. <br />3.10.7 Each piece of plumbing equipment and the entire plumbing system shall be <br />adjusted and readjusted as required to insure proper functioning and shall be le <br />in first class operating condition. <br />3.10.8 Gas piping, shall be tested at 15 psi air pressure for 24 hours, in excess of the <br />requirements of NFPA 54. <br />3.11. Disinfection: <br />3.1 1.1 Purge system of all deleterious material before proceeding with disinfection. <br />3.11.2 Comply with local health department regulations. <br />3.1 1.3 Flush with clean, potable water until water runs clear. <br />3.11.4 Fill system with with chlorine solution containing at least 50 ppm of chlorine. <br />Allow to stand for at least 24 hours. <br />3.11.5 Purge system of chlorine solution before putting into service. <br />3.12. Inspection <br />3.12.1 Notify Inspector as required by local authority when all work is completely <br />installed and tested leak -tight. <br />3.12.2 Do not conceal piping or fixtures until approval has been obtained from <br />inspector. <br />3.13. Cleaning Equipment and Premises: <br />3.13.1 Thoroughly clean all parts of fixtures and equipment. exposed parts which are t <br />be painted shall be thoroughly cleaned of foreign matter with grease, oil, <br />soldering flux, etc. removed. <br />3.13.2 Exposed metal work shall be carefully brushed down with steel brushes to <br />remove rust and other spots and touched up with primer, <br />End of Section 22 40 00 <br />Note: <br />Not all project specifications may be applicable to this remodel. <br />End of section <br />Section 23 70 00 <br />Central HVAC Equipment <br />V10092017 <br />1. General <br />1. 1. Summary <br />1.1.1 Provide all materials and equipment and perform all labor required to install <br />HVAC systems complete as indicated, as required by code, and as specified <br />herein. All sizes, etc. are Publix minimum and if local code requirements are <br />higher, the work shall be bid and installed accordingly. <br />1.1.1.1 Obtain and pay for all pennits, bonds, inspection. <br />1.1.1.2 Provide roof top and split HVAC systems or install systems provided <br />by Publix as described below. <br />1.1.1.3 All A/C curbs shall be set for drying -in by Roofer. <br />1.1.1.4 All roof mounted fans will be furnished by Publix and installed by <br />HVAC Contractor. Curbs will be furnished by Publix for installation by <br />Roofer. <br />1.1.1.5 Provide hurricane brackets and other supports required to secure units <br />to structure for wind and seismic conditions. <br />Seismic: Seismic hazard level as designated by Authority Having <br />Jurisdiction. <br />Hurricane: FM 1-90 or higher if designated by Authority Having <br />Jurisdiction. <br />1.1.1.6 Provide sheet metal duct systems as indicated on Drawings and <br />described in Specifications. <br />1.1.1.7 Provide exhaust ducts between the cooking hoods and the roof mounted <br />exhaust fans. <br />1.1.1.8 Provide double -wall metal gas vents. <br />1.1.1.9 Provide all other materials and services required for installation <br />described in Contract Documents. <br />1. 1.2 HVAC Equipment: <br />1.1.2.1 Publix will provide equipment delivered to the site of Construction. <br />Coordinate delivery schedule with construction progress. Provide all <br />labor, equipment, materials, and services required for installation and <br />satisfactory completion of HVAC work. <br />1.1.2.2 In addition to above, provide equipment, delivery, required staging and <br />storage, and all other services required to complete the Work. <br />1.1.3 Coordinate work with work of others. Notify concerned parties before <br />proceeding with work that will affect them. <br />1.2. Definitions: Explanation and precedence of Documents: <br />1.2.1 For purposes of clarity and legibility, HVAC drawings are essentially <br />diagrammatic and, although size and location of equipment are drawn <br />to scale wherever possible, Contractor shall make use of all Contract <br />Documents. <br />1.2.2 Although the locations of the equipment and ductwork may be shown on the <br />Drawings in certain positions, the Contractor shall be guided by the architectural <br />details and conditions existing at the job, correlating this work with that of <br />others. <br />1.2.3 The Drawings indicate size, connection points and routes of ducts and <br />equipment. It is not intended, however, that all offsets, rises and drops are shown. <br />Install all items as required to fit structure, avoid obstructions, and retain <br />clearance, headroom, openings and passageways. <br />1.2.4 Remodels: Carefully examine all existing conditions, existing work in place and <br />premises and compare the Drawings with the existing conditions. Submittal of <br />bid indicates that the Contractor has examined the Site and Drawings and has <br />included all required work in his bid. No allowances will be made for error <br />resulting from Contractor's failure to visit job sites and to review Drawings. <br />1.2.5 Conflicts, discrepancies, interferences and omissions in Documents shall be <br />brought to the attention of the Publix Engineer for clarification prior to <br />commencement of work. <br />1.3. Submittals: <br />1.3.1 Submit LON in accordance with Section 0 1 33 00 Submittal Procedures. <br />1.3.2 Within 30 days of Contract Commencement (Authorization to Proceed), submit <br />the following shop drawings and cut sheets for Publix Engineer's approval: <br />Cooling Equipment <br />Air Handling Equipment <br />Heating Equipment <br />Air Distribution <br />Valves, Gauges, Specialties, Thermometers, Misc. <br />Insulation <br />Round and Oval Duct - submittals and shop drawings <br />All submittal data shall have rough -in dimensions, connection sizes, <br />any special installation requirements, certified performance data and <br />horsepower, voltage and phase for all equipment. <br />Equipment, fixtures and trim with cuts including rough -in dimensions. <br />Other items required to complete the work <br />1.3.3 Submit two (2) identical bound copies of all iterns. Arrange categories in order <br />listed above. <br />1.3.4 Literature for the above shall have rough -in dimensions, connection sizes, and <br />special installation requirements. <br />1.3.5 Project Record Drawings: Comply with Section 0 1 78 39. <br />1.3.6 Do not order materials or proceed with work untill all submittals have been <br />reviewed, and approved. <br />1.3.7 Confirm electrical and other requirements with other contractors. <br />1.4. Quality: <br />1.4.1 Subcontractor: <br />1.4.1.1 The HVAC Subcontractor shall be a reputable firm regularly engaged in this type <br />of work, employing skilled workmen, and with proper equipment. <br />1.4.1.2 Upon request Subcontractor shall show evidence of at least two similar <br />jobs, of comparable size and character, installed and operating within <br />the previous two years prior to Bid Opening. <br />1.4.1.3 Publix reserves the right to refuse any Subcontractor with or without <br />cause. <br />1.4.2 Personnel: <br />1.4.2.1 Employ an experienced Superintendent to oversee all operation. <br />1.4.2.2 Work shall not proceed without adequate supervision present at all <br />times. <br />1.4.2.3 Work shall be accomplished by workers certified in their trade as <br />masters, journeymen, and apprentices in accordance with regulations of <br />the governing authority or customary practice. Utilize workers with <br />skills in proportion to complexity of tasks required. <br />1.4.2.4 Publix reserves the right to reject personnel with or without cause. <br />1.4.3 Quality standards: Work will be judged in comparison to work of similar types. <br />Substandard construction as judged by Publix Representative will not be <br />accepted. <br />1.4.4 Regulations: Comply with applicable provisions of the following codes (latest <br />version adopted by governing agencies): <br />Local Building Code <br />ASME Code for Unfired Pressure Vessels <br />International Mechanical & Energy Codes <br />Florida State Mechanical & Energy Codes <br />Georgia State Mechanical & Energy Codes <br />North Carolina State Mechanical & Energy Codes <br />OSHA - for construction <br />1.4.5 Coordination: Work shall be accomplished along with the work of other trades. <br />Corporate with others to benefit the job as a whole. <br />1.4.6 Participate in the pre -construction conference. <br />1.5. Sequencing: <br />1.5.1 Notify General Contractor, or any others, of all chases, sleeves and openings <br />required so that the work can be accomplished without delay. Provide necessary <br />sleeves, etc., to be installed. Otherwise, HVAC Sub -Contractor shall pay for <br />appropriate trades to perform cutting and patching. <br />1.5.2 Joists, girders, beams, columns or reinforcing steel shall not be cut. <br />1.5.3 Where construction necessitates the routing of ducts or piping through structural <br />members, or framing, permission to make such installation shall first be obtained <br />from the Publix Field Representative <br />1.6. Temporary Operation: The Owner may require operation of part or all of the installation prior to <br />Final Acceptance. <br />1.7 After acceptance of the Work, the Owner reserves the right to make emergency repairs <br />as required to keep equipment in operation without voiding the Contractor's guarantee <br />nor relieving the Contractor of his responsibilities during the guarantee period. <br />1.8. Operating Instructions and Service Manual: <br />L8.1 Provide two (2) neatly bound copies of maintenance and instructions book, parts <br />lists pertaining to all equipment furnished. <br />1.8.2 Each section shall be indexed and include parts lists, instruction books, <br />suppliers' phone numbers and addresses, and individual equipment guarantees <br />all in separate sections. <br />1.8.3 Representatives of the Owner shall be instructed by the Contractor as to complete <br />care and operation of the HVAC system. Inforin the Architect in writing as to the <br />persons who received the instructions and the date that this was done. <br />1.9. Warranty: <br />1.9.1 Units shall have a manufacturer's standard one-year warranty against all defects. <br />1.9.2 Provide industry standard five-year compressor replacement warranty. <br />2. Products <br />2.1. General: All equipment and materials shall be furnished in strict accordance with the <br />equipment schedule and specifications requirements. See Section 0 1 1 1 00 - Summary <br />of Work to determine responsabilities regarding supplying and installing of equipment. <br />2.2. Nameplates <br />2.2.1 Nameplates shall not be painted. <br />2.2.2 All switches, starters, and major pieces of equipment shall be identified with <br />black plastic nameplates with engraved white letters. <br />2.3. Packaged Rooftop Air Conditioners: Self-contained, factory assembled and wired unit. <br />Consists of cabinet compressor(s), evaporator fan, evaporator coil(s), air filters, air <br />cooled condenser, fully charged with refrigerant and oil, and controls. <br />2.4. Power Ventilators: Direct or belt -drive centrifugal fans consisting of housing, wheel, <br />fan, shaft, bearings, motor and disconnect switch drive assembly, curb base and <br />accessories. <br />2.5. Controls: <br />2.5.1 An Environmental Control Panel will be ftimished and installed by Publix to <br />control all AC units. Conduit, line voltage circuits, interlocks, etc., shall be <br />furnished and installed by the Contractor, as shown on drawings. <br />2.6. Filter Media: Fall two inch thick dual density polyester material. <br />2.7. Air Distribution <br />2.7. 1 General: <br />2.7.1.1 All air distribution shall be supplied by manufacturers whose testing <br />procedures are in accordance with ASHRAE Standard 70. <br />2.7.1.2 Furnish and install, unless otherwise noted, all grilles, registers, and outlets at the <br />location and of the type and size shown on the Drawings. Install foam rubber <br />gaskets behind flanges of all grilles and registers to prevent leakage and streaking. <br />Adjust air volumes and set deflection in accordance with Drawings. <br />2.7.1.3 Approved manufacturers: <br />Airguide <br />Anemostat <br />Bailey and Tuttle <br />Lindab <br />Krueger <br />Metal Industries <br />Nailor Industries <br />Price <br />Titus <br />Other manufacturer as approved by Publix Engineer. <br />2.7.2 Return Air Grilles and Registers: <br />2.7.2.1 Return air grilles, outlets, registers and door grilles shall be of etched <br />aluminum with acrylic finish and as indicated. <br />2.7.2.2 All grilles shall be suitable for smooth surface mounting, Coordinate <br />installation door grilles with door installation. <br />2.7.2.3 Where indicated, provide opposed blade dampers. <br />2.7.3 Supply Registers and Diffusers: <br />2.7.3.1 All supply outlets shall be aluminum (or aluminized steel where <br />required when part of rated roof -ceiling assembly) and products of a <br />single manufacturer. <br />2.7.3.2 Provide steel grilles and fire dampers, radiation dampers as indicated on <br />the Drawings and in accordance with U.L. roof -ceiling assembly design <br />where indicated. <br />2.7.3.3 Where indicated, provide opposed blade dampers. <br />2.7.4 Louvers: Aluminum, drainable with bird screen, AMCA certified. <br />Greenheck ESD403 <br />Ruskin #ELF-375D <br />Louvers and Dampers Inc. I EL-4-104, ALL Series <br />Pottorff <br />2.8. Bypass Terminal Units: 22 gage galvanized steel construction, 1/2" thick 1.5 Ib/ft3 <br />density coated fibrous glass insulation, complying with NFPA 90A and UL- 1 8 1. Steel <br />damper and actuator shaft with self-lubricating bearings. Field adjusted minimum air <br />volume stop and 24V AC actuator. <br />2.8.1 Approved Manufacturers: <br />Metal Industries <br />Price <br />Titus <br />2.9. Sheet Metal Ductwork: <br />2.9.1 Galvanized Ductwork: All duct and fittings shall be manufactured from <br />galvanized steel of lock forming quality per ASTM A653. The zinc coating shall <br />be minimum G90 (1.25 oz. I sq. ft.) per ASTM A924. Seams on fittings shall be <br />welded or tacked & sealed. Individual fittings are required, manifolding is not <br />permitted. Comply with SMACNA requirements for duct construction for <br />ventilation and air conditioning systems. <br />2.9.2 Stainless steel ductwork: ASTM A480, Type 316 sheet -form with 44 finish for <br />surfaces exposed to view; Type 304sheet-forin, with # I finish for concealed <br />ducts. <br />2.9.3 Rectangular Duct Work: <br />2.9.3.1 <br />Panels shall be cross broken. (Beaded duct not acceptable) <br />2.9.3.2 <br />Longitudinal standing seams may be used <br />2.9.3.3 <br />Comer closures are not required <br />2.9.3.4 <br />Hangers shall be galvanized steel strapping and galvanized rods. <br />2.9.3.5 <br />Elbows shall be as drawn. <br />2.9.3.6 <br />Where indicated vaned elbows shall be double vaned. <br />2.9.3.7 <br />Connections shall be either 90 degree straight with Titus Model AG-45 <br />control grid or radius tap -in. <br />2.9.3.8 <br />Inspection plates and test holes are not required. <br />2.9.3.9 <br />Fresh air intake shall be square or rectangular standard. <br />2.9.3.10 Access doors shall be insulated and removable. <br />2.9.3.11 <br />Sealer on all joints: Sealants shall have a Flamespread Rating of 25 or <br />less, Smoke Developed Rating of less than 50 to comply with NFPA <br />90A. <br />Hardcast Iron Grip Water -Based Duct Sealant 60 1. <br />United McGill, United Duct Sealer. <br />Precision Adhesives PA-2084A Duct Sealant. <br />Fosters 32-19 <br />2.9.4 Round and Flat Oval Duct: <br />2.9.4.1 <br />All exposed ductwork shall be spiral locksearn construction standard <br />SMACNA gauges tested to + I OWG. Longitudinal seam duct is <br />prohibited. Comply fully with SMACNA recommendations. <br />2.9.4.2 <br />Where ductwork is exposed to view, provide G90 galvanized metal <br />suitable for painting. <br />2.9.4.3 <br />Field Joints in Exposed Ductwork: Lindab Inc. SPIRO safe duct <br />system, or Ductmate industries Spiralmate Round Duct Connector and <br />"Ovalmate Flat Oval Duct Connector" or approved equals. <br />2.9.4.4 <br />Substitutions of sizes by cross section area or equivalent round <br />formula must have written prior approval. <br />2.9.4.5 <br />Ductwork assemblies shall be the type tested to 10" WG (min.) by UL <br />181. <br />2.9.4.6 <br />Approved Duct Manufacturers: <br />Eastern Sheet Metal <br />Lindab, Inc <br />Semco <br />United McGill Corp. <br />Crown Products Company <br />Hamlin Sheet metal <br />2.9.4.7 <br />Gauges (Single Wall Ductwork): <br />Round Duct <br />Diameter Spiral Fitting <br />3" - 18" 26 Ga. 26 Ga. <br />19" - 24" 26 Ga. 24 Ga. <br />25" - 42" 24 Ga. 22 Ga. <br />43" - 60" 22 Ga. 20 Ga. <br />61" - 66" 22 Ga. 18 Ga. <br />67" - 84" 20 Ga. 18 Ga. <br />Oval Duct <br />Major Axis Spiral Fitting <br />3" - 24" 24 Ga. 24 Ga. <br />25" - 26" 22 Ga. 24 Ga. <br />27" - 42" 22 Ga. 22 Ga. <br />43" - 48" 22 Ga. 20 Ga. <br />49" - 60" 20 Ga. 20 Ga. <br />6 I" - 70" 20 Ga. 18 Ga. <br />71" - 84" 18 Ga. 18 Ga. <br />2.9.4.8 <br />Doublewall Ductwork <br />2.9.4.8.1 Double wall duct and fittings shall consist of a perforated <br />inner liner, a I inch, 1.50 Ib./ft3 (unless otherwise specified) <br />layer of fiber glass insulation and a solid outer pressure shell. <br />A retaining fabric shall be wrapped between the perforated <br />inner duct and the fiber glass insulation. <br />2.9.4.8.2 All fitting ends from 5" to 24" O.D. shall have rolled edges <br />for added strength and rigidity during installation and <br />shipping. <br />2.9.4.8.3 Double wall to single wall transitions shall be provided <br />where insulated duct connects to non -insulated, single wall <br />duct. Transitions also act as insulation ends reducing the <br />double wall outer shell diameter to the inner shell diameter. <br />2.9.4.8.4 Gauges (Double Wall Ductwork) <br />Round Duct <br />Diameter Spiral Fitting <br />3" - 18" 26 Ga. 26 Ga. <br />19" - 24" 26 Ga. 24 Ga. <br />25" - 42" 24 Ga. 22 Ga. <br />43" - 60" 22 Ga. 20 Ga. <br />61" - 66" 22 Ga. 18 Ga. <br />67" - 84" 20 Ga. 18 Ga. <br />Oval Duct <br />Diameter Spiral Fitting <br />3" - 22" 24 Ga. 20 Ga. <br />23" - 34" 22 Ga. 20 Ga. <br />35" - 46" 22 Ga. 18 Ga. <br />47" - 58" 20 Ga. 18 Ga. <br />59" - 60" 20 Ga. 16 Ga. <br />6 1 " - 68" 20 Ga. 16 Ga. <br />69" - 84" 18 Ga. 16 Ga. <br />2.9.4.9 Duct Hangers - 8' 0" C/C max distance. <br />2.10. FlexibleDuct: <br />2. 10.1 Factory insulated on aluminum liner, UL listed Class I Air Duct, STD. 181 and <br />NFPA Bulletin 90A, with F/S kraft metallized mylar vapor barrier jacket. <br />Flamespread rating less than 25, and smoke developed 50 or less. <br />2.10.2 Minimum working pressure 6" w.g. <br />2.10.3 Maximum length- I 0 feet. <br />2.10.4 Supports shall be spaced maximum 3 feet, support band min. 2 in. wide: Use <br />Wiremold duct collars and galvanized strap clamps or equal as approved by <br />Engineer. <br />2.10.5 Spin in fittings shall be Metal Masters Model MS 1-6G or equal as approved by <br />Engineer. <br />2.10.6 Approved products: <br />Flexmaster TL-M <br />Insulated Metalflex V-250-UL <br />Thermo -Fin Type A-300 <br />2.11. Duct Leakage Loss: <br />2.1 1.1 Each system shall meet SMACNA and ASHRAE leakage class 3. This leakage <br />will be determined by the test and balance consultant. <br />2.11.2 Loss exceeding leakage class 3 requirements shall be corrected by the HVAC <br />Contractor prior to acceptance by Publix. <br />2.12. Duct Hangers: <br />2.12.1 Duct hangers shall be threaded rods or metal straps with metal bands or angles <br />see details in the mechanical drawings. <br />2.12.2 Preferred Method for Exposed Ductwork system: Load -rated cable suspension <br />system. The system shall have a specified manufacturer's safe working load <br />(SWL) and supplementary safety factor of at least five times the SWL. The <br />system shall be verified by SMACNA Testing & Research and shall be in <br />compliance with SMACNA Duct Construction Standards guidelines. <br />2.12.3 Approved System: Chipple Hang -Fast. <br />2.12.4 Seismic bracing and design to comply with local conditions. <br />2.13. Grease Hoods: Owner furnished, contractor installed. <br />2.13.1 Install UL classified range hoods as indicated on the Drawings and in <br />accordance with NFPA 96. Hoods shall be 18 gage (stainless steel to be <br />specified on drawings), liquid tight welds, grease extractors, vapor proof lights <br />and factory pre -piped fire suppression system. <br />2.13.2 Grade of stainless steel to be listed in the mechanical drawings. <br />2.14. Fire Suppression <br />2.14.1 Provide fire protection system (specified Section 15355-Automatic Fire <br />Suppression System) for all grease -laden air removal hoods (Designated GH-). <br />Shall conform to NFPA 17. <br />2.14.2 Fire dampers shall be at the supply air inlets. <br />2.15. Grease Hood Exhaust Duct <br />2.15.1 Fabricate kitchen hood ducts from 16 ga. galvanized steel sheets, 18 ga. <br />stainless steel where exposed. Conform to NFPA 96. All joints and seams shall be <br />welded liquid tight. Provide a flange for duct at top of exhaust fan curb. <br />2.15.2 Access doors shall be U.L. listed. <br />Ductmate, F2 <br />Flame Gard <br />Acudor Products Inc. <br />2.16. Prefabricated Oven, Grease and Engine Exhaust Venting <br />2.16.1 Approved Manufacturers <br />Metal- Fab <br />Selkirk <br />Captive Aire <br />2.16.2 Type B Venting <br />2.16.2.1 Provide a complete insulated double wall gas venting system (U.L. <br />Listed # 1 03),1400 degrees F. rating and draft hood for the gas fired <br />equipment and bakery ovens where indicated. <br />2.16.2.2 Thimbles, flashing, rain cap as required. <br />2,16.2.3 Air Intake: Single wall construction. <br />2.16.3 Grease Duct <br />2.16.3.1 Provide complete doublewall, fiber insulated exhaust system as listed <br />and compliant with NFPA 96 <br />2.16.3.2 Use manufacturers sealants and support system and components for a <br />complete system. <br />2.16.3.3 Exhaust piping shall terminate per local code or as required by NFPA <br />96. <br />2.16.3.4 Minimum I 0 year warranty <br />2.16.4 Engine Exhaust <br />2.16.4.1 Provide complete double wall fiber insulated exhaust system with <br />insulation thickness as listed on the project plans <br />2.16.4.2 Use manufacturers sealants and support system and components for a <br />complete system. <br />2.16.4.3 Exhaust piping shall terminate per local code or as required by NFPA <br />37. <br />2.16.4.4 Minimum I 0 year Warranty. <br />2.17. Devices and other miscellaneous items: <br />2.17.1 Dampers: Opposed blade, butterfly type, or splitter, all factory made as <br />indicated. Each shall have a locking quadrant accessible for adjustment, with <br />extension sleeve for duct wrap insulation. <br />2.17.2 Air Turning Device for Registers: Titus model AG-45 or similar device as <br />approved by Architect. <br />2.17.3 Radiation Dampers: UL listed and installed where indicated <br />2.17.4 Piping System for Condensate: Schedule 40 PVC. <br />2.18. Insulation: <br />2.18.1 Concealed HVAC Ductwork: <br />2.18.1.1 Insulate externally with foil scrim kraft (FSK) fiberglass blanket type <br />insulation, ASTM C 1 136, thickness and R value as indicated on the <br />Drawings. <br />2.18.1.2 Comply with ASHRAE 90.1 and energy code requirements of the AHJ. <br />2.18.1.3 Materials shall have flamespread less than 25, and smoke developed <br />less than 50. <br />2.18.1.4 Approved manufacturers: <br />Johns Manville <br />CetainTeed <br />Owens Coming <br />Knauf <br />2.18.1.5 Neatly cut and fit insulation to the duct surface with all duct joints <br />overlapped 2" minimum, secured with outward -clinch staples 4" on <br />center each way. <br />2.18.1.6 On ducts 24" or greater in width the insulation on the underside of the <br />duct shall be secured to the sheet metal surface with Foster'S #85-20, <br />or equal, adhesive, and secured mechanically with sheet metal screws <br />and caps, or mechanical fasteners adhered to the duct on not more <br />than 18" centers each way. <br />2.18.1.7 All transverse and longitudinal seams, and penetrations of the vapor <br />barrier facing shall be covered with SMACNA rated foil backed tape <br />applied in and sealed with Foster's #30-80 or 930-65, or equal, vapor <br />barrier mastic. <br />2.18.2 Where indicated, exposed double wall HVAC duct work shall be internally <br />insulated with fiberglass. <br />2.18.2.1 Insulate internally with fiberglass rigid board type insulation and <br />retaining fabric, AS TM C 1 136, thickness and R value as indicated on <br />the Drawings. <br />2.18.2.2 Materials shall have flamespread less than 25, and smoke developed <br />less than 50. <br />2.18.2.3 Approved manufacturers: <br />Johns Manville <br />CetainTeed <br />Owens Corning <br />Knauf <br />2.18.3 Whre indicated, exposed rectangular ductwork shall be internally lined. <br />2.18.3.1 Flexible duct liner shall be glass fibers bonded with a thermo-setting <br />resin. <br />2.18.3.2 Airstream surface shall be protected by a flexible glass mat coating. <br />2.18.3.3 Edges, joints and seams shall be sealed using manufacturer's approved <br />coating/sealer. <br />2.18.4 Fire-resistant Grease Duct Wrap <br />2.18.4.1 Alternative to I and 2 hour fire resistant rated gypsum shaft enclosures. <br />Product shall be a flexible, 0" clearance, non -asbestos system, <br />encapsulated with a scrim. re -enforced foil. no flame, no smoke <br />characteristics for the foil blanket. Install per manufacturer's <br />guidelines. <br />2.18.4.2 Follow the manufacturer's guidelines for securing duct wrap, welded <br />stickpins only, banding and sealers. <br />2.18.4.3 Approved Manufacturers: <br />FireWrap Elite, Unifrax <br />Fire Barrier Ductwrap 15A, 3M <br />FastWrap+, Thermal Ceramics FireMaster <br />2.19. Ductwork accessories: <br />2.19.1 Control Dampers <br />2.19. 1. I Provide dampers with parallel blades for 2 position control, or opposed <br />blades for modulating control. <br />2.19.1.2 All metal parts galvanized steel, Blades: 16ga., bearings: Heavy duty <br />molded nylon, axles: 1/2" dia. steel, 9" OC. <br />2.19.1.3 Steel Frames: <br />2.19.1.3.1 Up to 25 sq. ft.: 2"XI/2"XI/8" <br />2.19.1.3.2 Over 25 sq. ft.: 4"X I 1/4"X l6ga. <br />2.19.1.4 Acceptable Manufacturers: <br />Greenheck <br />Ruskin <br />2.19.2 Fire Dampers: <br />2.19.2.1 Fire dampers shall be rated where indicated and shall be UL 5 5 5 listed. <br />2.19.2.2 2 All metal parts galvanized steel, dynamically tested, casings: 20 ga., <br />blades: 24 ga., fitsible Link: 160 - 165 deg. F. <br />2.19.2.3 Damper: Positive lock type with curtain type blade, positive lock in <br />closed position, with curtain I 00% out of airstream. <br />2.19.2.4 Steel Frames: <br />2.19.2.4.1 Up to 25 sq. ft.: 2"XI/2"XI/8" <br />2.19.2.4.2 Over25 sq. ft.: 4"XI 1/4"Xl6ga <br />Z. t9.2.5 Acceptable Manufacturers: <br />Greenheck <br />Ruskin <br />2.19.3 Duct access doors: <br />2.19.3.1 Construct of same gauge or heavier as ductwork served. Provide <br />insulated doors for insulated ductwork. Provide flush frames for un- <br />insulated ductwork, extended frames for externally insulated ductwork. <br />Provide one side hinged, other side with one handle type cam latch for <br />all doors. If space is limited for a hinged door swing, then provide a <br />two handle type cam latch door. <br />2.19.3.2 Door sizes shall accommodate to allow fire dampers and other devices <br />to be accessed for repair or reset to normal position after being <br />activated. <br />Largest Dimension of Duct Access Door Nom. Dimension <br />Up to 10" 6"X6" <br />I 0" to 16" 8"X8" <br />17" to 24" 12"X12" <br />25" to 36" 16"X 16" <br />37" and larger 24"X16" <br />2.19.3.3 Acceptable manufacturers: <br />Greenheck <br />Ruskin <br />3.3. Equipment Start -Up: <br />3.3.1 All rooftop A.C. units shall be started and adjusted for proper operation by the <br />manufacturer or his representative. No equipment shall be run prior to this start- <br />up. All units shall be made ready for start-up at the same time. <br />3.3.2 Contractor shall have qualified personnel in attendance to coordinate ductwork <br />and electrical aspects of the start-up. <br />3.3.3 While in operation during construction, all returns in areas under construction <br />shall be closed off or have filters installed over openings or grilles to minimize <br />contamination. <br />3.3.4 Prior to test and balance, contractor is to replace all air filters. <br />3.4. Substantial Completion Inspection <br />3.4.1 All of the following items must be cornpleted prior to Substantial Completion <br />Inspections. No exceptions will be made and no payment will be made until all <br />items are completed. <br />3.4.2 Cleaning Equipment and Premises: <br />3.4.2.1 Thoroughly clean all parts of the apparatus and equipment. Exposed <br />parts which are to be painted shall be thoroughly cleaned of cement, <br />plaster, and other material and all oil and grease spots shall be <br />removed. Repaint or touch up as required to make look like new. <br />Surfaces shall be carefully wiped and all cracks and comers scraped <br />out. <br />3.4.2.2 Exposed metal work shall be carefully brushed down with steel brushes <br />to remove rust and other spots and touched up with primer. <br />3.4.3 Testing and Balancing Systems <br />3.4.3.1 Publix will provide a test and balance contractor. This service will be <br />done in the presence of the HVAC Sub- Contractor, so that deficiencies <br />can be noted. <br />3.4.3.2 Comply with "Standards for Field Measurement and Instrumentations" <br />Form No. 81266 Volume One. as published by the Associated Air <br />Balance Council. <br />3.4.3.3 Submit three (3) copies of the complete test reports to the Publix <br />Refrigeration Department prior to Final Acceptance of the Project. <br />3.4.3.4 Provide sufficient time before the completion date so that testing and <br />balancing can be accomplished, and remediation made. <br />3.4.3.5 Put all HVAC Equipment into full operation and continue operation <br />during each working day of testing and balancing. <br />3.4.3.6 All dampers shall be in wide open or neutral position prior to test and <br />balance of the system. <br />3.4.3.7 Implement changes recommended by the testing and balancing <br />contractor, including pulley changes, balancing dampers and other <br />items as required to obtain proper system balance as judged by the <br />testing and balancing contractor and the Publix Engineer. <br />3.4.3.7 Maintain operation of the system for a minimum of 24 hours after <br />balance has been obtained. Notify Publix Architect so that he <br />may inspect the system under operating conditions. <br />3.5. Prior to requesting a Final Inspection, submit a typed schedule or a marked up set of <br />Drawings indicating the observed velocity of each grille, register or outlet. These test <br />data shall be final readings after balancing the system. <br />3.6. Dust streaking on exposed duct systems: After 6 months, examine all exposed ductwork <br />for dust streaking. Where streaking has occurred, the causes of the streaking shall be <br />determined and repaired. Streaked surfaces shall be cleaned and touched up to match <br />the original finish. <br />3. Execution: <br />3. 1. General <br />3.1.1 Neatness counts. Make all joits, connections, unions, etc. with proper care to insure that <br />fight connections are made without excess material, well secured to supports. <br />3.1.2 Install duct with runs straight, shop formed radiuses at bends, and adequate <br />supports. <br />3.1.3 Verify all field dimensions and locations of equipment and fixtures within the <br />layout to ensure close, neat fit, with other trades work. <br />3.2. Installation: <br />3.2.1 All equipment shall be protected from dust, moisture and odors by sealing all <br />openings with plastic sheeting before and during installation. <br />3.2.2 Installation of rooftop A.C. units: <br />3.2.2.1 Publix will furnish factory fabricated steel roof curbs complete with <br />wood nailer strips. Curbs are shipped fully assembled and tapered to fit <br />roof slope. <br />3.2.2.2 Provide materials and coordination with other trades required to ensure <br />that curbs are installed properly and level. Use gasket material provided <br />by curb manufacturer for sealing A/C equipment to roof curbs. <br />3.2.2.3 Attach units to curbs as indicated on the Drawings. <br />3.2.2.4 Lift all A/C units with spreader bars to prevent cable damage to <br />cabinets and components. <br />3.2.2.5 Publix will accept only those units which are in new condition without <br />dents or other damage. Scratches or paint damage are to be re -painted <br />with manufacturer's paint. <br />3.2.2.6 In the event that field repair involves the reffigeration circuit of any <br />unit, such repair is to be made by the unit manufacturer or their <br />representative. <br />3.2.2.7 Provide each unit with a PVC condensate drain trap in accordance with <br />Drawings and unit manufacturer's recommendation. <br />3.2.2.8 Piping of unit mounted heat reclaim coil(s) will be by the refirigeration <br />contractor. <br />3.2.3 Installation of rooftop fans: <br />3.2.3.1 Publix will fin-nish factory fabricated steel roof curbs complete with <br />wood nailer strips. Curbs are shipped fully assembled and pre -sloped. <br />Additional slope accommodation is through steel frame provided under <br />other sections. <br />3.2.3.2 Provide materials and coordination with other trades required to ensure <br />that curbs are installed properly and level. <br />3.2.3.3 Attach fans to curbs as indicated on the Drawings. <br />3.2.4 Installation of Ductwork: <br />3.2.4.1 Comply: with SMACNA Duct Cleanliness for New Construction <br />Guidelines Intermediate Level.Protect ductwork during shipment, <br />delivery to the jobsite and storage on site.Sections to be clear of debris <br />before installing Protect risers fi7om entry of the debri and moisture into <br />the duct. <br />3.2.4.2 Run straight and level or slope with roof as indicated in Construction <br />Drawings. <br />3.2.4.3 Hanger for ductwork shall attach to the top chord of bar joist. <br />3.2.4.4 Install seismic bracing as required to comply with local conditions. <br />End of Section 23 70 00 <br />Note: <br />Not all project specifications may be applicable to this remodel. <br />End of section <br />NOTE: THIS DOCUMENT MAY <br />HAVE BEEN ELECTRONICALLY <br />TRANSMITTED. IF UNSIGNED, IT <br />CANNOT BE FILED FOR PUBLIC <br />RECORD. PUBLIC RECORD <br />FILINGS REQUIRE SIGNED AND <br />SEALED DOCUMENTS. <br />10 <br />C4 <br />00 <br />U <br />U <br />U <br />< <br />LU <br />Cn a- <br />0 <br />0 <br />Con Z <br />0 <br />BRANDT ENGINEERING, INC. <br />C) <br />M <br />PHONE: 1804)794-6656 <br />FAX: (804)794-8588 CDO <br />EMAIL c_add0beinc.coT__J <br />FL Certificate of Authority # <br />26689, Expiration Date: 2128121. <br />JOHNS. PARKER - MECHANICAL <br />LICENSE #63481, <br />E"IRATIONDATE: 212812021 <br />C" <br />C> <br />cl� <br />Z LU <br />CN <br />Z <br />W LU <br />L0 <br />C0 <br />U) <br />0 <br />0 <br />0 <br />III <br />M <br />0 <br />W <br />CL <br />U) <br />U) <br />MR <br />XC-) <br />0 CY) <br />_J <br />LL <br />X <br />LU <br />M <br />Zi M Z <br />5:5F_ CL <br />Z <br />LU <br />M <br />C� LU <br />CD �e <br />ce) <br />0 <br />ce) <br />LO <br />1�4_ <br />04 <br />V_ <br />4t <br />U) <br />Z <br />0 <br />0 <br />C%4 <br />CD <br />r M <br />ce) <br />LU ce) <br />0 <br />_J <br />LL_ <br />15 _J <br />LL, Zm6w <br />LLI 00 <br />M SO Lu <br />Z <br />F_ <br />LL1 <br />LLJ <br />0 <br />LLI <br />I <br />0 <br />o63481 <br />�O <br />LU <br />STATE OF ell\ <br />A\- <br />//111111� <br />C14 <br />C14 <br />C� <br />ca <br />LU <br />:D <br />U) <br />LU <br />W <br />Q <br />CD <br />IIIIIIII <br />6 <br />CD <br />2 <br />Z <br />M <br />co <br />8 <br />CD <br />Go <br />a. <br />- <br />cf) <br />.,LLI <br />12 <br />C <br />LLJ <br />=1 <br />0 <br />LLJ <br />a &51 ift <br />­4 <br />00001711 2 8 2019 <br />W�,wkins "on-druction- Inr <br />