<br />ELECTRICAL SPECIFICATIONS
<br />GENERAL REQUIREMENTS
<br />1 PROVIDE ALL WORK TO MEET OR EXCEED REGULATORY REQUIREMENTS, INCLUDING LATEST EDITION OF THE NFPA 101 (LIFE
<br />SAFETY CODE), THE NATIONAL ELECTRICAL CODE, STANDARD BUILDING CODE AND LOCAL REQUIREMENTS & BUILDING CODES
<br />2 THE FOLLOWING MINIMUM REQUIREMENTS ALONG WITH FLORIDA BUILDING CODE 2020, 7TH EDITION, THE NFPA 70 LATEST
<br />EDITION, THE NATIONAL ELECTRICAL CODE (NEC 2017) REQUIREMENTS SHALL GOVERN.
<br />3 THE ELECTRICAL WORK SHALL INCLUDE BUT IS NOT LIMITED TO THE FOLLOWING:
<br />A COMPLETE POWER AND LIGHTING DISTRIBUTION SYSTEMS INCLUDING PANELS, AS SHOWN ON PLANS
<br />B COMPLETE BRANCH CIRCUIT WIRING SYSTEM
<br />C TEMPORARY ELECTRIC SERVICE AS REQUIRED FOR CONSTRUCTION
<br />D TESTING OF ALL ELECTRICAL EQUIPMENT
<br />E PROVIDE AND INSTALL COMPLETE LIGHTING SYSTEM AS SHOWN ON PLANS
<br />4 THE CONTRACTOR SHALL EXAMINE ALL DRAWINGS AND BECOME THOROUGHLY FAMILIAR WITH PROVISIONS CONTAINED HEREIN
<br />THE SUBMISSION OF HIS/HER BID SHALL BE CONSTRUED AS INDICATING SUCH KNOWLEDGE ELECTRICAL DRAWINGS ARE
<br />DIAGRAMMATIC AND ARE INTENDED TO SHOW THE APPROXIMATE LOCATIONS OF EQUIPMENT AND DEVICES DIMENSIONS GIVEN ON
<br />THE PLANS SHALL BE VERIFIED IN THE FIELD DRAWINGS MAY NOT BE SCALED TO OBTAIN EXACT DIMENSIONS THE EXACT
<br />LOCATIONS OF APPARATUS, FIXTURES, EQUIPMENT AND CONDUITS SHALL BE VERIFIED WITH THE OWNER'S REPRESENTATIVE IN
<br />THE FIELD, AND THE WORK SHALL BE INSTALLED ACCORDINGLY SHOULD THE CONTRACTOR FAIL TO VERIFY SUCH LOCATIONS,
<br />THE WORK SHALL BE CHANGED AT HIS/HER OWN EXPENSE THE OWNER RESERVES THE RIGHT TO MAKE MINOR CHANGES IN
<br />THE LOCATION OF CONDUIT AND EQUIPMENT UP TO THE TIME OF INSTALLATION, WITHOUT ADDITIONAL COST
<br />5 THE ELECTRICAL DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL OR
<br />LABOR CALLED FOR IN ONE SHALL BE FURNISHED AND SUPPLIED EVEN THOUGH NOT SPECIFICALLY MENTIONED IN BOTH
<br />LABOR AND/OR MATERIALS NEITHER SHOWN NOR SPECIFIED, BUT NECESSARY FOR A COMPLETE AND PROPERLY OPERATING
<br />SYSTEM SHALL BE PROVIDED THE WORK REQUIRED OUTLINED IN THESE SPECIFICATIONS INCLUDES ALL LABOR, MATERIALS,
<br />EQUIPMENT AND SERVICES REQUIRED TO PROVIDE LIGHTING AND POWER SYSTEMS, SERVICE ENTRANCE(S), MOTOR CONTROLS
<br />AND CONNECTIONS, BRANCH CIRCUITING, FEEDERS, PANELS, FIXTURES, WIRING DEVICES, DATA AND TELEPHONE DEVICES, TVSS,
<br />FIRE ALARM AND OTHER DEVICES SHOWN ON THE PLANS OR SPECIFIED WHEN THE SPECIFICATION OF AN ITEM IS NOT
<br />IDENTIFIED WITH A PARTICULAR AREA, THE ITEM SHALL PERTAIN TO ALL AREAS THE CONTRACTOR SHALL FURNISH ALL LABOR
<br />AND MATERIALS AS SPECIFIED AND AS REQUIRED TO PROVIDE ELECTRICAL CONNECTIONS FOR COMPLETE AND OPERATIONAL
<br />SYSTEMS IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS
<br />6 LATER CLAIMS FOR LABOR, EQUIPMENT OF MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE
<br />BEEN FORESEEN HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED DEFINITIONS "INSTALL" SHALL MEAN TO PLACE,
<br />FIX IN POSITION, SECURE, ANCHOR, WIRE, ETC , INCLUDING NECESSARY APPURTENANCES AND LABOR SO THAT EQUIPMENT OR
<br />INSTALLATION WILL FUNCTION AS SPECIFIED AND INTENDED "FURNISH" SHALL MEAN TO PURCHASE AND SUPPLY EQUIPMENT OR
<br />COMPONENTS "PROVIDE" SHALL MEAN TO "FURNISH AND INSTALL" "OR APPROVED EQUAL" SHALL MEAN EQUAL IN TYPE,
<br />DESIGN, QUALITY, STYLE, COLOR, ETC , AS DETERMINED BY THE ENGINEER/ARCHITECT INTERFERENCES IT SHALL BE THE DUTY
<br />OF THIS CONTRACTOR TO REPORT ANY INTERFERENCES BETWEEN HIS WORK AND THAT OF ANY OTHER CONTRACTOR TO THE
<br />OWNER OR ARCHITECT AS SOON AS THEY ARE DISCOVERED THE OWNER OR ARCHITECT WILL DETERMINE WHICH EQUIPMENT
<br />SHALL BE RELOCATED REGARDLESS OF WHICH WAS FIRST INSTALLED, AND HIS DECISION SHALL BE FINAL MATERIALS AND
<br />WORKMANSHIP ALL WORK SHALL BE INSTALLED IN A PRACTICAL AND WORKMANLIKE MANNER BY COMPETENT WORKMEN,
<br />SKILLED IN THEIR BRANCH OF THE TRADE
<br />7 UNLESS OTHERWISE SPECIFIED OR INDICATED ON THE DRAWINGS, ALL MATERIALS SHALL BE NEW AND FREE FROM DEFECTS
<br />AND SHALL BE THE BEST OF THEIR SEVERAL KINDS ALL MATERIAL AND EQUIPMENT SHALL MEET OR EXCEED STANDARDS
<br />SPECIFIED BY UL, NEMA, ANSI AND IEEE WHEREVER SUCH STANDARDS HAVE BEEN ESTABLISHED FROM TIME —TO —TIME
<br />DURING THE OPERATION AND AT THE COMPLETION THEREOF, THIS CONTRACTOR SHALL REMOVE ALL DEBRIS AND EXCESS
<br />MATERIALS CAUSED BY HIS WORK AND HE SHALL LEAVE THE AREA OF THE OPERATION BROOM CLEAN ALL ELECTRICAL
<br />EQUIPMENT AND MATERIAL SHALL BEAR THE UNDERWRITER'S LABORATORIES LABEL SUPPORTS THIS CONTRACTOR SHALL
<br />FURNISH AND INSTALL ALL ANGLE IRON, CHANNEL IRON, RODS, SUPPORTS OR HANGERS REQUIRED TO INSTALL OR MOUNT
<br />PANELBOARDS, SWITCHBOARDS, OR ANY ELECTRICAL EQUIPMENT CALLED -FOR ON THE PLANS, IN THESE SPECIFICATIONS, OR
<br />AS NECESSARY TO MOUNT ANY PIECE OF ELECTRICAL EQUIPMENT, MATERIAL, OR DEVICE
<br />8 THE CONTRACTOR SHALL KEEP AS BUILT DRAWINGS (ONE (1) SET) AND SHOP DRAWINGS AT THE JOB SITE FOR SOLE
<br />PURPOSE OF RECORDING ALL CHANGES MADE DURING CONSTRUCTION AFTER COMPLETION OF THE WORK AND BEFORE
<br />REQUESTING FINAL PAYMENT, THE ABOVE MENTIONED DRAWINGS SHALL BE DELIVERED TO THE OWNER
<br />9 PROVIDE ALL SWITCHES, DISCONNECTS, FUSES, STARTERS, CONTACTORS, CONTROLS, FIXTURES, DEVICES, OUTLETS,
<br />RECEPTACLES, CORDS, CORD CAPS, FLEXIBLE CONNECTIONS TO MATCH EQUIPMENT CONNECTIONS, PER MANUFACTURER'S
<br />RECOMMENDATIONS, BOXES, SUPPORTS, HARDWARE, EQUIPMENT, CONDUIT AND WIRE, TO PROVIDE FOR COMPLETE OPERATION
<br />OF ALL ELECTRICAL EQUIPMENT AND SYSTEMS COORDINATE THE LOCATION, ELEVATION AND TYPE OF ALL LIGHT FIXTURES,
<br />RECEPTACLE OUTLETS, DATA AND SYSTEM OUTLETS, DEVICES, JUNCTION BOXES AND EQUIPMENT WITH THE OWNER/ARCHITECT
<br />10 ALL CIRCUIT NUMBERS INDICATED ON THE DRAWINGS ARE FOR REFERENCE USE, CONTRACTOR TO BALANCE THE LOADS IN
<br />ALL PANELS IN WHICH WORK IS PERFORMED PROVIDE COMPLETE AS —BUILT DRAWINGS.
<br />11 CONTRACTOR SHALL COORDINATE ELECTRICAL REQUIREMENTS AND MAKE FINAL CONNECTIONS OF EQUIPMENT FURNISHED
<br />BY OTHER TRADES
<br />12 CONTRACTOR SHALL MAINTAIN A COMPLETE TEMPORARY POWER SYSTEM DURING CONSTRUCTION COORDINATE ALL POWER
<br />OUTAGES & CHANGEOVERS WITH THE OWNER
<br />13 CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FOR ONE YEAR CONTRACTOR SHALL OBTAIN AND
<br />PAY - FOR ALL PERMITS AND INSPECTIONS
<br />14 ALL PERMANENTLY ABANDONED CIRCUITS, CONDUITS AND WIRING SHALL BE REMOVED BACK TO THEIR SOURCE ALL
<br />ABANDONED TELEPHONE AND DATA WIRING SHALL BE REMOVED ALL ABANDONED WALL OUTLETS EITHER POWER DATA OR
<br />TELEPHONE SHALL BE CLOSED WITH AN APPROPRIATE BLANK COVER TO MATCH EXISTING FINISH AND COLOR
<br />15 CARE SHALL BE TAKEN WHEN TRENCHING, TO AVOID UNDERGROUND ELECTRIC, WATER, SPRINKLER & DRAIN LINES
<br />CONTRACTOR SHALL REPAIR TO LIKE NEW CONDITION, AT HIS EXPENSE, ANY DAMAGE THAT HE MAY CAUSE BY HIS WORK
<br />RESTORE LANDSCAPE AREAS TO ORIGINAL CONDITION WITH APPROPRIATE SODDING AND PLANTING UNDERGROUND CONDUIT
<br />ELBOWS SHALL BE GALVANIZED RIGID STEEL PAINTED WITH HEAVY COAT OF BITUMASTIC
<br />16 PROVIDE ENGRAVED LAMINATED PHENOLIC NAMEPLATES WITH 3/8" LETTERS ENGRAVED THROUGH BLACK TO WHITE
<br />17 THE ELECTRICAL CONTRACTOR SHALL PROVIDE AND CONNECT A COMPLETE SYSTEM OF PANELS, CONDUITS, WIRE, FITTINGS,
<br />BOXES, SUPPORTS AND ALL OTHER MISCELLANEOUS MATERIALS REQUIRED FOR EQUIPMENT AS INDICATED ON THE PLANS TO
<br />PROVIDE A COMPLETE AND OPERABLE ELECTRICAL DISTRIBUTION SYSTEM
<br />LIGHTING
<br />ELECTRICAL EQUIPMENT AND DEVICES
<br />1 PANELS SHALL HAVE 20 AMP SINGLE, DOUBLE OR 3—POLE CIRCUIT BREAKERS (CAPABLE OF
<br />1 EMERGENCY AND EXIT LIGHTING SHALL BE CONNECTED TO UNSWITCHED LOCAL LIGHTING CIRCUITS
<br />INTERRUPTING AVAILABLE SHORT CIRCUIT CURRENT) AS REQUIRED IN EACH BRANCH CIRCUIT.
<br />WHERE BREAKERS LARGER THAN 20 AMPERES ARE REQUIRED, THE SIZES ARE NOTED ON THE
<br />DRAWINGS BREAKERS SHALL BE BOLTED TO BUS TYPE, QUICK —MAKE, QUICK —BREAK AND
<br />2 LIGHTING FIXTURES ALL FIXTURES SHALL BE AS SHOWN ON FIXTURE SCHEDULES, AND APPROVED BY OWNER UNLESS
<br />CAPABLE OF INTERCHANGING 1,2 OR 3—POLE UNITS. MULTIPLE UNITS SHALL BE COMMON TRIP.
<br />OTHERWISE INDICATED, ALL LIGHTING FIXTURES SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR AS
<br />PROVIDE SPARE BREAKERS IN EACH PANEL AS SHOWN. ELECTRICAL CONTRACTOR SHALL
<br />INDICATED ON THE LIGHTING FIXTURE SCHEDULES, INCLUDING LAMPS ALL FIXTURES SHALL BEAR THE UNDERWRITER'S
<br />ARRANGE CIRCUITS AS NEAR AS POSSIBLE TO CIRCUIT NUMBERS ON THE DRAWINGS. UPON
<br />LABORATORIES LABEL AND SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTION ALL FIXTURES SHALL BE NEW
<br />COMPLETION OF JOB, ELECTRICAL CONTRACTOR SHALL TAKE CURRENT READING CHECKS OF ALL
<br />PHASES CIRCUIT CONNECTIONS SHALL BE REARRANGED TO BALANCE THE LOAD ON THE PANEL.
<br />AND UNDAMAGED THIS CONTRACTOR SHALL PROVIDE AND INSTALL ALL NECESSARY SUPPORT MEDIA FOR ALL LIGHTING
<br />ALL LUGS SHALL BE U.L. APPROVED CU/AL TYPE.
<br />FIXTURES INCLUDING STRUCTURAL STEEL, ANGLES, RODS, ETC IN GENERAL, FIXTURES SHALL BE SUPPORTED IN A MANNER
<br />ACCEPTABLE TO THE LOCAL INSPECTION AUTHORITIES ALL FIXTURES SHALL BE FIRMLY SUPPORTED FROM BEAMS OR JOISTS
<br />2 ALL GENERAL PURPOSE RECEPTACLES AND SWITCHES COLOR SHALL BE SELECTED BY
<br />ARCHITECT/OWNER ACCEPTABLE DEVICE MANUFACTURERS ARE HUBBELL, LEVITON, OR EQUAL.
<br />OUTDOOR RECEPTACLES SHALL BE WEATHERPROOF WHILE IN USE IN ACCORDANCE WITH NEC
<br />3 ALL RECESSED LIGHTING FIXTURES SHALL HAVE THERMAL PROTECTION. PROVIDE A FIXTURE SUPPORT AT EACH CORNER
<br />ARTICLE 408. RECEPTACLES SHALL BE LEVITON 5362 SERIES OR EQUAL.
<br />FOR ALL LAY —IN LIGHT FIXTURES, OR PROVIDE UL LISTED FIXTURE CLIPS, PROVIDE ALL REQUIRED MOUNTING HARDWARE &
<br />ACCESSORIES, ALL BALLASTS SHALL BE FUSED
<br />3 LOCATIONS OF OUTLETS ARE SHOWN APPROXIMATELY ON THE DRAWINGS. APPROXIMATE
<br />LOCATIONS OF LIGHT FIXTURES ARE SHOWN ON THE DRAWINGS. OUTLET BOXES FOR CONCEALED
<br />WORK SHALL BE PRESSED STEEL BOXES, GALVANIZED AND NOT LESS THAN #12 GAUGE. WALL
<br />4 LETTER INSIDE OR ADJACENT TO FIXTURE SYMBOL INDICATED TYPE — SEE FIXTURE SCHEDULE
<br />OUTLETS SHALL BE 4" SQUARE BY 1Y2" DEEP, SINGLE OR DOUBLE COVER, EXCEPT GANG BOXES
<br />OF SIMILAR DEPTH SHALL BE USED AT LOCATIONS REQUIRING MORE THAN 2—GANG OUTLETS ON
<br />THE EXTERIOR OF THE BUILDING SHALL BE WEATHERPROOF TYPE. ALL OUTLETS SHALL BE FIRMLY
<br />SECURED IN PLACE
<br />CONDUIT
<br />4 ALL PANELS, SAFETY SWITCHES, STARTERS AND IN GENERAL, ALL EQUIPMENT REQUIRING LUGS
<br />SHALL BE EQUIPPED WITH SOLDERLESS TYPE U L APPROVED LUGS PROVIDE ALL NECESSARY
<br />UNISTRUT, CHANNEL, BACKING AND SUPPORTS TO MOUNT SWITCHBOARD AND PANELBOARDS
<br />1 CONDUIT AND E.M.T. SHALL BE DELIVERED TO THE BUILDING IN 10—FOOT LENGTHS AND EACH LENGTH SHALL
<br />SECURELY IN PLACE FUSES THIS CONTRACTOR SHALL REPLACE ALL FUSES BLOWN DURING
<br />HAVE THE UNDERWRITER'S LABORATORIES LABEL. CONDUIT AND E.M.T. SHALL BE RUN CONCEALED IN ALL
<br />CONSTRUCTION AND TESTING AND SHALL PROVIDE A COMPLETE SET OF FUSES IN ALL FUSE
<br />HOLDERS, SWITCHES, PANELS AND ALL OTHER DEVICES REQUIRING FUSES FUSES SHALL BE AS
<br />FINISHED AREAS OF THE BUILDING. E.M.T. CONNECTORS AND COUPLERS SHALL BE SET SCREW TYPE MADE OF DIE
<br />SPECIFIED HEREIN AND INDICATED ON DRAWINGS. ALTERNATE MANUFACTURER IS LITTELFUSE
<br />CAST AS MANUFACTURED BY THOMAS & BETTS, STEEL CITY, OR APPLETON. BENDS AND OFFSETS SHALL BE
<br />MADE WITH A HICKEY OR POWER BENDER WITHOUT KINKING OR DESTROYING THE SMOOTH BORE OF THE CONDUIT
<br />5 MARK EVERY JUNCTION OR PULL BOX COVER PLATES WITH THE CIRCUIT NUMBER(S) OF ALL
<br />PARALLELED CONDUITS SHALL RUN STRAIGHT AND TRUE WITH OFFSETS UNIFORM AND SYMMETRICAL.
<br />WIRES CONTAINED THEREIN
<br />CONDUIT TERMINALS AT BOXES AND CABINETS SHALL BE RIGIDLY SECURED WITH LOCKNUTS AND BUSHINGS AS
<br />REQUIRED BY THE NEC. INSULATED BUSHINGS SHALL BE USED ON ALL CONDUIT 1" TRADE SIZE AND LARGER.
<br />6 VERIFY EQUIPMENT RATINGS AND LOCATIONS PRIOR TO ROUGH —IN
<br />CONDUIT SHALL BE SECURELY FASTENED IN PLACE AT NO MORE THAN 8—FOOT CENTERS, AND HANGERS,
<br />SUPPORTS OR FASTENINGS SHALL BE PROVIDED AT EACH CONDULET, ELBOW AND AT THE END OF EACH
<br />7 PROVIDE A NEATLY TYPEWRITTEN ACCURATE PANEL DIRECTORY SCHEDULE ON THE INSIDE OF
<br />STRAIGHT RUN, TERMINATING AT A BOX OR CABINET. CONDUIT SHALL NOT BE SUSPENDED FROM THE CEILING OR
<br />EACH ELECTRICAL PANEL DOOR. PROVIDE COPIES TO THE OWNER & A/E
<br />CEILING SUSPENSION WIRES HORIZONTAL AND VERTICAL CONDUIT RUNS SHALL BE SUPPORTED BY ONE —HOLE
<br />MALLEABLE STRAPS OR OTHER APPROVED METAL DEVICE WITH SUITABLE BOLTS, EXPANSION SHIELD OR BEAM
<br />8 PROVIDE A SERVICE RATED SECONDARY SURGE ARRESTOR AT EACH ELECTRICAL SERVICE
<br />CLAMP FOR MOUNTING TO BUILDING STRUCTURE OR SPECIAL BRACKETS CONDUIT SHALL BE SUPPORTED FROM
<br />ENTRANCE. PROVIDE A SERVICE ENTRANCE RATED TVSS DEVICE AT EACH SERVICE ENTRANCE
<br />MAIN. PROVIDE A SUBPANEL RATED TVSS DEVICE AT EACH PANEL SERVING HIGH HARMONIC
<br />STRUCTURAL STEEL OR JOIST AND INDEPENDENT OF OTHER PIPING. DO NOT SUPPORT CONDUIT FROM METAL
<br />LOADS, LIGHTING, HVAC, MOTORS, SWITCHING LOADS, COMPUTERS OR SENSITIVE ELECTRICAL
<br />ROOF DECK OR ANY OTHER SUPPORT DEVICE OF ANOTHER TRADE. ARMORED CABLE (BX) OR NONMETALLIC
<br />EQUIPMENT
<br />SHEATHED CABLE (ROMEX) SHALL NOT BE USED. NO ALUMINUM CONDUIT SHALL BE USED
<br />9 PROVIDE ENGRAVED NAMEPLATES FOR ALL ELECTRICAL EQUIPMENT
<br />2 ALL OUTDOOR CONDUIT, WIRING, BOXES AND EQUIPMENT SHALL BE WEATHERPROOF CONNECTIONS TO
<br />MECHANICAL EQUIPMENT SHALL MADE WITH FLEXIBLE CONDUIT AND WIRING
<br />10 PANELBOARDS SHALL BE "NQOD" CIRCUIT BREAKER TYPE AS MANUFACTURED BY SQUARE
<br />"D", SIEMENS,CHALLENGER, GENERAL ELECTRIC OR WESTINGHOUSE, OR AS NOTED PANELBOARDS
<br />3 ALL TV, SOUND & INTERCOM SYSTEMS CONDUIT 3/4" UNLESS OTHERWISE NOTED.
<br />SHALL HAVE A HINGED LOCKING DOOR PROVIDE A TYPEWRITTEN CIRCUIT DIRECTORY WITH
<br />PROTECTIVE COVERING ALL WIRES IN PANEL SHALL BE TAGGED WITH CIRCUIT NUMBER CIRCUIT
<br />BREAKERS FOR MECHANICAL EQUIPMENT SHALL BE HACR TYPE
<br />4 PROVIDE TELEPHONE/DATA OUTLETS WITH WIRING BACK TO TELEPHONE BOARD AND NETWORK SERVER
<br />5 ONLY SHORT RUNS OF FLEXIBLE METAL CONDUIT NOT OVER 6' IN LENGTH AND HAVING A GROUND CONDUCTOR
<br />SHALL BE USED FOR TERMINAL CONNECTIONS TO MOTORS AND ALSO FOR ELECTRICAL EQUIPMENT WHERE IT IS
<br />NOT PRACTICAL TO MAKE FINAL CONNECTION WITH RIGID CONDUIT FLEXIBLE CONDUIT EXPOSED TO WEATHER
<br />SHALL BE SEALTITE ALL CONDUIT SHALL BE RUN PARALLEL TO THE BUILDING STRUCTURE CONDUIT INSTALLATION
<br />SHALL CONFORM TO ALL THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE (NEC/N.F.P.A.-70), FLORIDA
<br />BUILDING CODE 2020, 7th EDITION AND ALL LOCAL CODES
<br />6 PROVIDE ALL REQUIRED CONDUIT & CABLE PENETRATIONS THROUGH PARTITIONS, WALLS, FLOORS, SLABS &
<br />ROOFS, WITH APPROVED FIRE SEALANT COMPOUND
<br />7 CONDUIT, FIXTURES, OR ANY ELECTRICAL DEVICES SHALL NOT BE SUPPORTED FROM STEEL DECK, BRIDGING,
<br />CEILING, OR CEILING SUPPORT WIRES.
<br />8 ALL EXPOSED EXTERIOR CONDUIT SHALL BE RIGID GALVANIZED STEEL ALL EXPOSED INTERIOR CONDUIT SHALL
<br />BE RIGID GALVANIZED STEEL OR E.M.T. CONDUIT INSTALLED BELOW SLAB OR UNDERGROUND MAY BE SCHEDULE 40
<br />PVC (3/4" MINIMUM). ALL CONDUIT SHALL BE CONCEALED WHERE POSSIBLE. ALL CONCEALED CONDUIT IN WALLS
<br />AND CEILINGS SHALL BE EMT, EMT FITTINGS SHALL BE DIE CAST SET SCREW TYPE AT DRY INTERIOR LOCATIONS
<br />EMT FITTINGS AT EXTERIOR, DAMP, OR WET LOCATIONS SHALL BE DIE CAST COMPRESSION RAIN —TIGHT TYPE WIRE.
<br />CONDUCTORS AND WIRING
<br />1 ALL WIRING (POWER, LIGHTING, SECURITY, SOUND, INTERCOM, FIRE ALARM, CONTROL, CCTV, TELEPHONE,
<br />COMPUTER DATA, TELECOM, ETC ) SHALL ALL BE IN CONDUIT.
<br />2 BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR NO MORE THAN 3% VOLTAGE DROP AT THE FARTHEST
<br />POINT. 20 AMPERE BRANCH CIRCUITS SHALL HAVE MINIMUM #10 COPPER HOMERUN WIRING FOR CIRCUITS OVER
<br />57' LONG AND #10 WIRING THROUGHOUT FOR CIRCUITS OVER 150' LONG.
<br />3 PROVIDE GREEN GROUND WIRE IN EACH RACEWAY, SIZE WIRE IN ACCORDANCE WITH ARTICLE 250 OF THE NEC
<br />4 PROVIDE WIRE MARKERS ON EACH CONDUCTOR AT TERMINAL STRIPS AND AT FINAL LINE AND LOAD
<br />CONNECTIONS IDENTIFY WITH BRANCH CIRCUIT OR FEEDER NUMBER OF POWER AND LIGHTING CIRCUITS, AND WITH
<br />CONTROL WIRE NUMBER AS INDICATED ON EQUIPMENT MANUFACTURER'S SHOP DRAWINGS FOR CONTROL WIRING OR
<br />AS DRAWINGS INDICATE
<br />5 ALL WIRES SHALL BE COLOR CODED COLOR CODE BRANCH CIRCUIT WIRING AS FOLLOWS:
<br />1 THREE PHASE SYSTEM: 120/208V PHASE A: BLACK PHASE B: RED PHASE C: BLUE NEUTRAL: WHITE
<br />GROUND: GREEN
<br />2 SWITCHED WIRES: OTHER THAN COLORS LISTED ABOVE
<br />3 TRAVELERS BETWEEN 3—WAY SWITCHES: PURPLE
<br />4 ISOLATED GROUND: GREEN WITH YELLOW STRIPS
<br />6 SIZES OF CONDUCTORS FOR FEEDERS ARE GIVEN ON THE DRAWINGS AND NO WIRE SMALLER THAN #12 GAUGE
<br />SHALL BE USED FOR BRANCH LIGHTING OR POWER CIRCUITS. ALL WIRING SHALL BE THHN. ALUMINUM WIRE OR
<br />ALUMINUM CABLE IS NOT ACCEPTABLE WHERE LIGHTING FIXTURES ARE USED AS RACEWAYS, 90 DEGREE C
<br />MINIMUM INSULATED WIRE SHALL BE USED
<br />7 A STURDY MECHANICAL AND ELECTRICAL CONNECTION SHALL BE MADE WITH APPROVED GROUNDING
<br />CONNECTORS ELECTRICAL SYSTEM AND EQUIPMENT GROUNDS SHALL COMPLY WITH THE NEC PANELS, CONDUIT
<br />SYSTEMS, MOTOR FRAMES, LIGHTING FIXTURES AND OTHER EQUIPMENT THAT ARE PART OF THIS INSTALLATION
<br />SHALL BE SECURELY GROUNDED BOTH MECHANICALLY AND ELECTRICALLY IN ACCORDANCE WITH ALL CODES
<br />SYSTEM GROUND SHALL NOT EXCEED A MAXIMUM OF 5 OHMS RESISTANCE MAIN GROUNDING SYSTEM SHALL BE
<br />SIZED TO CONFORM WITH SECTION 250 OF THE NEC. PROVIDE CONDUIT TO PROTECT WIRE FROM DAMAGE TO AN
<br />AREA EIGHT FEET (8') ABOVE FLOOR A GROUND CONDUCTOR SHALL BE SUPPLIED IN ALL CONDUIT. IT SHALL BE
<br />INSULATED, STRANDED, ANNEALED COPPER CONDUCTOR
<br />11 PANELBOARDS, CIRCUIT BREAKERS, DISCONNECT SWITCHES, STARTERS OR OTHER
<br />ELECTRICAL APPARATUS INSTALLED FOR THE OPERATION OF ANY EQUIPMENT SHALL BE
<br />PROPERLY IDENTIFIED WITH ENGRAVED LAMINATED PLASTIC NAMEPLATES ATTACHED TO
<br />EQUIPMENT BY STAINLESS STEEL SCREWS.
<br />12 ALL WIREWAYS, PULLBOXES, OUTLETS AND JUNCTION BOXES SHALL BE PROPERLY SIZED
<br />PER THE NATIONAL ELECTRICAL CODE. PULLBOXES AND OUTLET BOX SHALL HAVE ALL
<br />WIRING TAGGED TO INDICATE PANEL AND CIRCUIT NUMBERS
<br />13 DISCONNECT SWITCHES SHALL BE SQUARE "D", WESTINGHOUSE, SIEMENS, CHALLENGER
<br />OR G E SAFETY SWITCHES SWITCHES SHALL BE HEAVY DUTY AND RATED FOR THE
<br />PROPER VOLTAGE. SWITCHES SHALL BE RATED AS INDICATED ON THE DRAWINGS FOR SIZE,
<br />NUMBER OF POLES AND TYPE ENCLOSURE.
<br />14 ALL FUSES SHALL BE BUSSMAN CURRENT LIMITING TYPE.
<br />15 WHERE RECEPTACLES ARE INSTALLED CLOSER THAN 72" FROM EDGE OF SINK OR LAV,
<br />RECEPTACLE SHALL BE OF THE GROUND FAULT CIRCUIT INT. TYPE ALL GFI RECEPTACLES
<br />SHALL BE INDIVIDUAL DEVICES AND SHALL NOT BE SLAVED OR SHALL NOT BE GFI
<br />BREAKERS.
<br />16 ALL EXTERIOR RECEPTACLES SHALL BE WP GFCI TYPE. PROVIDE RECEPTACLE AT HVAC
<br />EQUIPMENT OUTDOOR EQUIPMENT, CONDUIT & CONNECTIONS SHALL BE WEATHERPROOF
<br />17 IN ADDITION TO THE LEGEND THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
<br />OUTLETS AND DEVICES WITH ARCHITECTURAL INTERIOR ELEVATIONS & CABINET WORK.
<br />18 ALL MOTOR STARTERS, SAFETY SWITCHES, VARIABLE SPEED DRIVES, RELAYS, MOTOR
<br />CONTROL CENTER, MDP'S, SWITCHBOARDS, PANELBOARDS, CONTACTORS, & ALL OTHER
<br />ELECTRICAL EQUIPMENT, SHALL BE OF THE SAME MANUFACTURER, UNLESS PROVIDED AS
<br />ELECTRICAL EQUIPMENT ON APPROVED FACTORY FABRICATED EQUIPMENT, SUCH AS CHILLER
<br />STARTERS, ROOF TOP UNITS, CONDENSING UNITS, ETC.
<br />19 ALL EQUIPMENT SHALL BE RATED FOR MAXIMUM AVAILABLE VOLTAGE AND GROUND FAULT
<br />CURRENT. ALL EQUIPMENT SHALL HAVE U.L. LISTING.
<br />PROJECT NAME
<br />MEDICAL BUILDING
<br />MODIFICATIONS
<br />OWNER:
<br />ADAA REAL ESTATE LLC
<br />2653 BRUCE B DOWNS BLVD.
<br />WESLEY CHAPEL , FL 33544
<br />PROJECT ADDRESS
<br />38058 ARBOR RIDGE DRIVE.
<br />ZEPHYRHILLS, FL 33540
<br />DRAWING BY:
<br />DANIEL JALIL
<br />Associate AIA
<br />M.A. In Architecture & Planning
<br />10233 CELTIC ASH DR.
<br />Ruskin, FL 33753
<br />Phone (813) 240-3537
<br />THIS DRAWING MEASURING 24"x36" IS THE PROPERTY OF DANIEL
<br />JALIL AND MAY NOT BE USED OR REPRODUCED WITHOUT HIS
<br />WRITTEN PERMISSION..
<br />THIS DRAWING AND DESIGN IS VALID FOR 12 MONTHS AFTER THE
<br />DATE IS SIGNED AND SEALED.
<br />ENGINEER:
<br />I HEREBY CERTIFY THAT I HAVE
<br />REVIEWED THE ATTACHED DESIGN AND
<br />FOUND IT TO BE IN COMPLIANCE WITH
<br />THE 7TH EDITION QF THE FLORIDA
<br />BUILDING
<br />No.77065• - ,4
<br />%�'��'••�ORID .••'��1��•
<br />ZONA L E
<br />''���11111111111\\\
<br />DANIEL JAMES COOREY P.E.
<br />FL 77065
<br />Phone (813) 507-9166
<br />DATE ISSUED FOR:
<br />SHEET TITLE
<br />GENERAL ELECTRICAL
<br />NOTES
<br />JOB No. ZPH-0821
<br />SCALE AS NOTED
<br />DATE AUG-09-21
<br />DRAW BY DJ
<br />CHECKED BY DJ
<br />PLOT DATE 08-09-21
<br />DRAWING No
<br />18 DISPOSE OF ALL LAMPS, BALLASTS, & OTHER HAZARDOUS MATERIALS IN ACCORDANCE WITH ALL FEDERAL, STATE, LOCAL,
<br />& EPA REGULATIONS
<br />8 ALL CONDUCTORS SHALL BE COPPER, 600 VOLT WITH MINIMUM SIZE OF #12 AWG THWN / THHN, UNLESS
<br />OTHERWISE SPECIFIED. WIRE SIZES OF #10 AND LARGER SHALL BE STRANDED.