SECTION 0501 STRUCTURAL FRAMING AND MISC. FABRICATION (CONT) <br />2.01 FABRICATION: <br />A. All structural steel shall be manufactured in accordance with <br />AISC standards. <br />B. Make bolt holes 1/16th inch larger than nominal bolt <br />diameter. All bolts shall have threads excluded from shear <br />plane. <br />C. Make fillet welds 1/4 inch minimum. Make butt weld full <br />penetration. <br />D. All welding shall comply with AWS D1.1 Structural Welding <br />Code. <br />2.02 ERECTION: <br />A. Erect structural steel framing plumb, level and properly <br />aligned in accordance with building lines and elevation on <br />Drawings and reference standards. <br />B. Field cutting and modifications of structural framing will <br />not be allowed unless specifically approved by Architect. <br />C. Provide necessary bracing and shoring during erection to <br />ensure safety of personnel and structure. Allow superimposed <br />construction loads only after erection is complete. <br />D. Apply touch-up primer to field welds, bolted connections, <br />and areas where shop primer has been damaged. <br />3.00 STEEL JOISTS: (Owner Furnished) <br />3.01 MATERIALS: <br />A. Steel Joists Designed in accordance with SJI <br />Standards, LH or K-Series, as noted on <br />Sheet S-3,50,000 PSI Steel, Camber Joists <br />to accommodate dead load deflection. <br />B. Welding Materials As recommended by AWS. <br />3.02 ERECTION: <br />A. Coordinate and verify proper placement of required anchors <br />and accessories. <br />B. Erect in accordance with AISC and SJI Standard Specifications <br />C. Field weld joists to steel beams, bearing plates or angles <br />after alignment and positioning. Weld each side with 1/8th <br />inch fillet weld one inch long minimum. <br />D. Provide temporary bracing, as required, to ensure safety <br />during erection of joists. <br />4.00 METAL DECK: (Owner Furnished) <br />4.01 MATERIALS: <br />A. Roof Decking ASTM A446, Grade C, 33,000 PSI 1.5" Type <br />"B" wide rib, 22 gage, galvanized, coating <br />conforming to ASTM A525-660. <br />B. Fasteners TEK #12 - 1 1/4" at supports, 3/4' at side <br />caps self tapping screws. <br />C. Metal decking must be stored off the ground with one end <br />elevated to provide drainage and shall be protected from the <br />weather with a water proof covering that is ventilated to <br />avoid condensation. <br />SECTION 0501 STRUCTURAL FRAMING AND MISC. FABRICATION (CONT) <br />4.02 ERECTION: <br />A. Install in accordance with SDI requirements and manufacturers <br />printed instructions. <br />B. Lap decking sheets at supports only, properly nested. <br />C. Provide temporary shoring, as required, during application <br />of dead loads to maintain decking level to avoid damage. <br />Do not leave placed sheets unattached at the end of the day. <br />D. Secure decking to support members with self -drilling, <br />self -tapping screws at each rib and at each side lap. Align <br />all screws. Weld deck to perimeter angles with 5/8" <br />diameter puddle weld at 12" o.c. <br />E. DO NOT install any dull or oxidized metal decking. Contact <br />the Architect for instructions. <br />5.00 METAL FABRICATION: <br />5.01 SCOPE OF WORK <br />A. Work included but not limited to: <br />1. Anchor Bolts <br />2. Column Setting Plates <br />3. Joist Bearing Plates <br />4. RTU Equipment Supports <br />5. Overhead Door Frames <br />6. Steel Pipe Guards <br />7. Metal Edge Angles <br />8. Pipe Railings <br />9. Roof Access Frame and Ladder <br />B. Provide detailed, complete shop drawings in accordance with <br />General conditions and with AISC Standards. <br />A. Steel Tubing ASTM A501 <br />B. Steel Angles & Plates ASTM A36 <br />C. Nuts and Bolts ASTM A307 <br />D. Welding Electrodes As recommended by AWS <br />E. Primer Rust inhibitive type compatible to <br />finish coat. <br />5.03 FABRICATION: <br />A. Arc weld all connections unless indicated otherwise. <br />B. Insofar. as practicable, shop fabricate all items complete <br />and ready for installation. <br />C. Punch or drill holes required for connections. Burned holes <br />are not permitted. <br />6.00 TESTING AND INSPECTION: <br />A. The contractor shall be responsible for furnishing any special <br />inspections specifically required by Building Codes and local <br />Authorities. If none are required the minimum requirements <br />for this section shall consist of inspections and reports on <br />all field welded and bolted connections. <br />B. Testing and inspections shall be performed by on independent <br />organization from the Contractor and signed by a Registered <br />Professional Engineer. <br />C. Work failing to meet minimum requirements shall be replaced <br />and/or modified to meet the satisfaction of the inspecting <br />engineer at no cost to the owner. <br />SECTION 0502 SHEET METAL FLASHING <br />v <br />o 4M <br />tE <br />1.00 <br />MATERIALS: <br />U <br />i t <br />4M Cn <br />A. <br />Metal Flashing ASTM A526, G90 coating <br />® <br />o 0 <br />phosphotized 25 gage, unless <br />otherwise indicated on drawings. <br />B. <br />Solder 50-50 Composition for galvanized <br />metals. <br />o <br />C. <br />Flux Raw muriatic acid or a type <br />® <br />Z <br />specifically suited to the <br />WM <br />conditions used. <br />j2! <br />D. <br />Nails, Rivets, and Fasteners Having rust resistive coating <br />IL cvi <br />compatible to, and designed <br />0 <br />for, the material being anchored <br />® <br />E. <br />Plumbing Vent Flashing 2 1/2 lb. lead. <br />; <br />W� <br />� a <br />2.00 <br />METAL FLASHING INSTALLATION: <br />W z <br />A. <br />Install metal flashing as detailed on Drawings and in a <br />0 <br />manner that will ensure water tight conditions. <br />B. <br />Hem exposed edges of metal flashing a minimum of 1/2" <br />N C> <br />Flashing joints shall be 3" loose slip joints filled with an <br />elastic cement. <br />Z <br />C. <br />Fabricate metal flashing with lines, risers and angles <br />Z <br />sharp, true and plain surfaces free of waves and buckles. <br />D. <br />No exposed fasteners in metal flashing, except at coping. <br />0 - <br />0 <br />Q <br />U <br />3.00 <br />PLUMBING VENT FLASHING INSTALLATION: <br />} � <br />� <br />A. <br />Turn on to roof a minimum of 4 inches and up, over and down <br />W <br />U <br />into vents a minimum of 1 .inches. <br />0 UL� <br />CL <br />4.00 <br />COPING COVER SYSTEM: <br />J <br />J <br />A. <br />Furnish and install Cheney Coping Cover System (or equal) <br />Q Z <br />IF <br />as manufactured by Cheney Flashing Co., <br />623 Prospect Street, Trenton, NJ. <br />a <br />- <br />U <br />B. <br />All exposed members shall be furnished in Fluropon-Kynar 500 <br />'t Ln(L <br />W <br />fluorocarbon. Color #30 BLACK. 10'-0" lengths. <br />a M LU <br />= <br />C. <br />Coping system shall be assembled and installed in strict <br />U <br />accordance with manufacturers specifications and instructions <br />Q <br />SECTION <br />0503 . LIGHT GAGE FRAMING <br />REVISION <br />1.00 <br />MATERIALS <br />t. <br />W <br />A. <br />Studs and Tracks Formed galvanized sheet coated in <br />2. <br />6 <br />accordance with ASTM A525. 6" channel <br />Z <br />shaped sections with punched 16 gauge <br />a <br />steel ASTM A446, Grade D minimum yield <br />4 <br />50,000 PSI. <br />ARCHUM <br />Framing shall be assembled and installed <br />to withstand 110 m.p.h. (30 PSF wind loads <br />with a deflection of less than L/240. <br />B. <br />Accessories 1. Bracing, furring, bridging formed <br />galvanized sheet steel, channel <br />A <br />shaped. <br />O/16/95 <br />2. Plates, gussets, clips, galvanized <br />thickness determined for conditions <br />SPECSb <br />encountered; manufacturer's standard <br />shapes. <br />AS5 <br />