Laserfiche WebLink
1. GENERAL REQUIREMENTS - DIVISION 16 ELECTR CAL: <br />A. PERFORM ALL WORK IN COMPLIANCE WITH THE LATEST ADOPTED EDITION OF THE FLORIDA BUILDING CODE, <br />NFPA 70 (NEC-2017 ORDINANCE 68831) AND NFPA 101 (LIFE SAFETY CODE), ADA ANSI A117.1, AND FEDERAL <br />FAIR HOUSING ACT (42 U.S.C. 3601), INSTALL AND CONNECT PER AND THE REGULATIONS OF THE LOCAL UTILITY <br />TELEPHONE, CABLE TELEVISION AND POWER UTILITY COMPANIES. OBTAIN AND PAY FOR ANY AND ALL REQUIRED <br />PERMITS, INSPECTIONS, CERTIFICATES OF INSPEC11ONS AND APPROVAL, AND THE LIKE, AND DELIVER SUCH <br />CER11FICATES TO THE OWNER. <br />B. THE CONTRACTOR SHALL FURNISH, PERFORM, OR OTHERWISE PROVIDE ALL LABOR (INCLUDING, BUT NOT <br />LIMITED TO, ALL PLANNING, PURCHASING, PAINTING, TRANSPORTING, RIGGING, HOISTING, STORING, INSTALLING, <br />TESTING, CHASING, CHANNELING, CUTTING, TRENCHING, EXCAVATING AND BACKFILLING), COORDINATION, FIELD <br />VERIFICATION, EQUIPMENT INSTALLATION, SUPPORT, AND SAFETY, SUPPLIES, AND MATERIALS NECESSARY FOR THE <br />CORRECT INSTALLAT10N OF COMPLETE AND FUNCTIONAL ELECTRICAL SYSTEMS (AS DESCRIBED OR IMPLIED BY <br />THESE SPECIFICATIONS AND THE APPLICABLE DRAWINGS). <br />C. ALL DRAWINGS AND SPECIFICATIONS ON THE PRoJECT ARE COMPLEMENTARY, EACH TO ALL OTHER SETS, <br />AND THEY SHALL BE USED IN COMBINATION FOR THE EXECUTION OF THIS WORK. DIVISION 16 WORK SHOWN ON <br />ANY ONE SET OF DRAWINGS, INCLUDING ALL ARCHITECTURAL DRAWINGS, MECHANICAL, PLUMBING AND FIRE <br />PROTECTION DRAWINGS FOR GENERAL WORK AND EQUIPMENT, AND DIVISION 16 WORK CALLED FOR UNDER ANY <br />SECTION OF THE PROJECT SPECIFICATIONS, SHALL BE CONSIDERED AS INCLUDED IN THIS WORK UNLESS <br />SPECIFICALLY EXCLUDED BY INCLUSION IN SOME OTHER BRANCH OF THE WORK. THIS SHALL INCLUDE <br />ROUGHING -IN FOR CONNECTIONS AND EQUIPMENT AS CALLED FOR OR INFERRED. THE CONTRACTOR SHALL <br />CHECK ALL DRAWINGS AND SPECIFICATIONS FOR THE PROJECT AND SHALL BE RESPONSIBLE FOR THE <br />INSTALLATION OF ALL DIVISION 16 WORK. <br />D. THE CONTRACTOR SHALL CAREFULLY CHECK THE' DRAWINGS AND SPECIFICATIONS OF ALL OTHER <br />TRADES AND DIVISIONS BEFORE INSTALLING ANY OF HIS WORK. HE SHALL IN ALL CASES CONSIDER THE WORK <br />OF ALL OTHER TRADES, AND SHALL COORDINATE HIS WORK WITH THEM SO THAT THE BEST ARRANGEMENTS OF <br />ALL EQUIPMENT, PIPING, CONDUIT, DUCTS, ROUGH -IN, ETC., CAN BE OBTAINED. <br />E. LOCATIONS DESIGNATED FOR OUTLETS, SWITCHES, DEVICES, EQUIPMENT, ETC., ARE <br />APPROXIMATE AND FINAL LOCATIONS SHALL BE VERIFIED IN THE FIELD AND CHECKED WITH ARCHITECTURAL AND <br />iD DRAWINGS. CONTRACTOR SHALL LOCATE ALL DEVICES UP TO 5 FEET IN ANY DIRECTION AS DIRECTED BY <br />OWNER AND PER CODE. WHERE INSTRUCTIONS OR NOTES ARE INSUFFICIENT TO CONVEY THE INTENT OF THE <br />DESIGN, CONSULT THE OWNER PRIOR TO BIDDING AND INSTALLATION. <br />F. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING AND COORDINATING THE LOCATIONS OF DEVICES TO <br />BE USED AND COORDINATING THE FINAL LOCATIONS 07 ELECTRICAL EQUIPMENT WITH MILLWORK, SINKS, <br />BENCHES, COUNTERS AND SHELVING PRIOR TO BIDDING AND INSTALLATION. ALL DISCREPANCIES SHALL BE <br />BROUGHT TO THE ATTENTION OF THE OWNER. <br />G. DIVISION 16 CONTRACTOR SHALL HAVE HAD EXPERIENCE OF AT LEAST THE SAME SIZE AND SCOPE AS <br />THIS PROJECT, ON AT LEAST TWO OTHER PROJECTS WITHIN THE LAST FIVE YEARS IN ORDER TO BE QUALIFIED <br />TO BID THIS PROJECT. <br />H. CONTRACTOR SHALL AND DOES HEREBY WARRANT ALL MATERIALS AND EQUIPMENT FURNISHED UNDER THIS <br />SECTION OF THE SPECIFICATIONS TO BE FREE FROM DEFECTS AND TO FUNCTION OR OPERATE SATISFACTORILY <br />FOR ONE YEAR AFTER FINAL ACCEPTANCE OF THE WORK, AND THAT ANY ITEMS NOT MEETING THIS REQUIREMENT <br />WILL BE MADE GOOD BY HIM WITHOUT COST TO OWNER, PROVIDED SUCH DEFECTS OR FAILURES ARE NOT DUE <br />TO ABUSE, NEGLECT, OR LACK OF REASONABLE AND ORDINARY MAINTENANCE. <br />1. ALL WORK SHALL BE EXECUTED IN A WORKMANSHIP MANNER AND SHALL PRESENT A NEAT <br />MECHANICAL APPEARANCE UPON COMPLETION. <br />J. BALANCE LOAD AS EQUALLY AS PRACTICABLE ON ALL FEEDERS, BRANCH CIRCUITS AND PANEL BUSES. <br />K. THE CONTRACTOR SHALL PROVIDE ADEQUATE PROTECTION, WHEREVER WORK IS TO BE PERFORMED IN <br />FINISHED/CICCUPIED SPACES, TO PREVENT DAMAGE TO ADJACENT AREAS, EQUIPMENT, OR FURNISHINGS; TO <br />PREVENT ACCIDENTAL INJURY TO BUILDING OCCUPANTS AND THE PUBLIC; TO PREVENT THE SPREADING OF DUST, <br />DIRT, DEBRIS, AND MOISTURE FROM THE AREA WHERE WORK IS BEING PERFORMED; AND TO PREVENT DUST, <br />DIRT, DEBRIS, AND MOISTURE FROM GETTING ON OR IN THE BUILDING OCCUPANT'S FURNISHINGS OR EQUIPMENT. <br />L THE CONTRACTOR SHALL REPAIR, AT NO COST TO THE OWNER, ANY DAMAGE DONE BY HIMSELF <br />OR HIS EMPLOYEES. HE SHALL ALSO BE RESPONSIBU--- FOR ALL CUTTING AND PATCHING REQUIRED TO <br />PROPERLY INSTALL HIS WORK. THIS SHALL ALSO INCLUDE THE PATCHING OF EXISTING ROADWAYS (PAVED OR <br />IMPROVED), PARKING AREAS, SIDEWALKS, WALLS, STAIRS, MECHANICAL WORK, CURBS, GUTTERS, ETC., CUT TO <br />INSTALL WORK PROVIDED BY THE CONTRACTOR. PATCH WORK SHALL COMPLY WITH THE APPLICABLE SECTIONS <br />OF THESE SPECIFICATIONS AND SHALL MATCH THE EXISTING FINISHES. <br />M. UPON COMPLETION OF WORK, THE ENTIRE WIRING SYSTEM SHALL BE TESTED, AND SHALL BE <br />SHOWN TO BE IN PROPER WORKING CONDITION IN ACCORDANCE WITH INTENT OF SPECIFICATIONS AND DRAWINGS. <br />IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO HAVE ALL SYSTEMS READY FOR OPERATION AND TO <br />HAVE AN ELECTRICIAN AVAILABLE TO OPERATE SAME 114 ACCORDANCE WITH AND UNDER THE SUPERVISION OF <br />THE INSPECTION REPRESENTATIVE OF THE ENGINEER. THE CONTRACTOR SHALL BE AVAILABLE TO ASSIST IN <br />REMOVAL OF PANEL FRONTS, TO PERMIT INSPECT10N AS REQUIRED. IN ACCORDANCE WITH DIVISION 1 AND THE <br />CONDITIONS OF THE CONTRACT, THE CONTRACTOR SHALL PROVIDE AND KEEP UP TO DATE A COMPLETE RECORD <br />SET OF CONSTRUCTION 7AS-BUILTS" BLUEUNE PRINTS WHICH SHALL BE CORRECTED DAILY, AND SHALL SHOW <br />EVERY CHANGE FROM THE ORIGINAL CONTRACT DRAWINGS, INCLUDING ADDENDA AND CHANGE ORDERS IN <br />ACCORDANCE WITH GENERAL REQUIREMENTS AND SPECIAL CONDITIONS. THIS SET OF PRINTS SHALL BE KEPT ON <br />THE JOB SITE, AND SHALL BE USED ONLY AS A RECORD SET. THIS SHALL NOT BE CONSTRUED AS <br />AUTHORIZATION FOR THE CONTRACTORS TO MAKE CHAAGES IN THE LAYOUT WITHOUT DEFINITE INSTRUCTION IN <br />EACH CASE. <br />11. ELECTRICAL SCOPE: <br />A. FURNISHING AND INSTALLATION OF ELECTRIC LIGHTING SYSTEMS, POWER SYSTEMS, AND AUXILIARY SYSTEMS <br />AS SHOWN OR HEREIN SPECIFIED. <br />B. CONNECTION OF ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTION, MENTIONED IN THIS DIVISION OR <br />SHOWN ON DRAWINGS, WHETHER FURNISHED BY DIVISION 16 OR UNDER OTHER DIVISIONS, OR FURNISHED BY <br />OWNER, INCLUDING FIRE PROTECTION AND FIRE SPRINKLER SYSTEMS. <br />C. FURNISHING AND INSTALLATION OF OUTLET BOXES, CONDUIT RACEWAYS, TERMINAL BOARDS, POWER AND <br />GROUNDING FOR A COMPLETE TELEPHONE, TELEVISION AND DATA RACEWAY DISTRIBUTION SYSTEM. (TELEPHONE <br />AND DATA HARDWARE, AS WELL AS SOFTWARE IS NOT INCLUDED.) <br />D. FURNISH AND INSTALL A COMPLETE LIGHTNING PROTECTION SYSTEM. <br />E. THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR CONTACTING THE OFFICES OF ALL LOCAL <br />AND/CIR STATE AUTHORITIES HAVING JURISDICTION OVE_R THIS PROJECT IN ORDER TO SCHEDULE ALL REQUIRED <br />INSPECTIONS AND OBTAIN ALL NECESSARY PERMITS, ETC. THE CONTRACTOR SHALL NOTIFY THE <br />ARCHITECT/ENGINEER OF ALL SCHEDULED INSPECTIONS AT LEAST TWO WEEKS IN ADVANCE OF THE SCHEDULED <br />DATE. <br />F. THE CONTRACTOR SHALL REPLACE ANY DEFECTIVE MATERIALS, EQUIPMENT, OR WORKMANSHIP WITHOUT <br />COST TO THE OWNER WITHIN THE STIPULATED GUARANTEED PERIOD. <br />G. IT SHALL BE THE RESPONSIBILITY OF THE DIVISION 16 CONTRACTOR TO HAVE ALL SYSTEMS READY FOR <br />OPERATION AND TO HAVE AN ELECTRICIAN AVAILABLE FOR ALL INSPECTIONS. THE CONTRACTOR SHALL PROVIDE <br />PERSONNEL TO ASSIST IN REMOVAL OF PANEL FRONTS, ETC. TO PERMIT INSPECTION AS REQUIRED. <br />H. SUBMIT TO THE ARCHITECT/ENGINEER PROMPTU( AFTER AWARD OF CONTRACT AND PRIOR TO PURCHASING, <br />SIX COPIES OF MANUFACTURER'S SHOP DRAWINGS IN ACCORDANCE WITH DIVISION 1, SUBMITTALS FOR THE <br />FOLLOWING ITEMS. ALL SHOP DRAWINGS OF A SPECIFIC ITEM OR SYSTEM SHALL BE MADE IN ONE SUBMITTAL <br />AND WITHIN TEN DAYS AFTER AWARD OF CONTRACT. <br />1. PANELBOARDS 6. DISCONNECT SWITCHES <br />2. LIGHTING FIXTURES 7. CONDUIT <br />3. 120V SMOKE/CO2 DETECTORS 8. CONDUCTORS <br />4. WIRING DEVICES 9. LOAD CENTERS <br />5. METER CENTERS 10. TVSS <br />J. COMPLETED WIRING SYSTEMS SHALL BE FREE FROM SHORT CIRCUITS AND AFTER COMPLETION, PERFORM <br />TESTS FOR INSULA11ON RESISTANCE IN ACCORDANCE WITH THE REQUIREMENTS OF THE NAT10NAL ELECTRICAL <br />CODE. ALL WIRING SYSTEMS SHALL BE COMPLETELY AND TOTALLY "SAFED'DURING CONSTRUCTION. ONLY <br />QUALIFIED PERSONNEL SHALL HANDLE ELECTRICAL SYSTEMS. <br />K. THE ELECTRICAL CIRCUITS, COMPONENTS, AND CONTROLS FOR ALL EQUIPMENT ARE SELECTED AND SIZED, <br />BASED ON THE EQUIPMENT SPECIFIED. IF SUBSTITUTIONS AND/OR EQUIVALENT EQUIPMENT ARE FURNISHED, IT <br />SHALL BE THE RESPONSIBILITY OF ALL PARTIES CONCERNED, INVOLVED IN, AND FURNISHING THE SUBSTITUTE <br />AND/OR EQUIVALENT EQUIPMENT TO VERIFY AND COMPARE THE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS <br />OF THAT FURNISHED TO THAT SPECIFIED AND/CIR SHOWN. IF GREATER CAPACITY OR MORE MATERIALS OR LABOR <br />IS REQUIRED FOR THE ROUGH -IN, CIRCUITRY OR CONNECTIONS THAN FOR THE ITEM SPECIFIED AND PROVIDED <br />FOR, THEN IT SHALL BE THE RESPONSIBILITY OF THE PARTIES INVOLVED IN PROVIDING THE SUBSTITUTE AND/OR <br />EQUIVALENT ITEMS OF EQUIPMENT TO PROVIDE ALL COMPENSATION FOR ADDITIONAL CHARGES MADE FOR THE <br />PROPER ROUGH -IN, CIRCUITRY AND CONNECTIONS FOR THE EQUIPMENT FURNISHED. NO ADDITIONAL CHARGES <br />ABOVE THE BASE BID SHALL BE ALLOWED FOR SUCH REVISIONS. <br />BEFORE ROUGH -IN OF CIRCUITRY OR CONNECTING TO EQUIPMENT, FURNISHED UNDER THIS DIVISION, ANY OTHER <br />DIVISION, OR BY THE OWNER, THE CONTRACTOR SHALL VERIFY THE ELECTRICAL CHARACTERISTICS AND <br />REQUIREMENTS OF THE EQUIPMENT BEING FURNISHED AND FOR THAT SPECIFIED AND SHOWN ON THE DRAWINGS <br />AND PROVIDE FOR PROPER ROUGH -IN AND CONNECTION. <br />M. ENCAVATION FOR UNDERGROUND ELECTRICAL STRUCTURES: CONFORM TO ELEVATIONS AND DIMENSIONS <br />SHOWN WITHIN A TOLERANCE OF PLUS OR MINUS 0.10% PLUS A SUFFICIENT DISTANCE TO PERMIT PLACING AND <br />REMOVAL OF CONCRETE FORMWORK, INSTALLATION OF SERVICES, OTHER CONSTRUCTION, AND FOR INSPECTION. <br />N * TRENCHING: ENCAVATE TRENCHES FOR ELECTRICAL INSTALLATIONS AS FOLLOWS: <br />1. EXCAVATE TRENCHES TO THE UNIFORM WIDTH, SUFFICIENTLY WIDE TO PROVIDE AMPLE <br />WORKING ROOM AND A MINIMUM OF 6* TO 9" CLEARANCE ON BOTH SIDES OF <br />RACEWAYS AND EQUIPMENT. <br />2. EXCAVATE TRENCHES TO DEPTH INDICATED OR REQUIRED. <br />3. LIMIT THE LENGTH OF OPEN TRENCH TO THAT IN WHICH INSTALLATIONS CAN BE MADE AND THE <br />TRENCH BACKFILLED WITHIN THE SAME DAY. <br />4. WHERE ROCK IS ENCOUNTERED, CARRY EXCAVATION BELOW REQUIRED ELEVATION AND BACKFILL <br />WITH A LAYER OF CRUSHED STONE OR GRAVEL PRIOR TO INSTALLATION OF RACEWAYS AND EQUIPMENT. <br />PROVIDE A MINIMUM OF 6" OF STONE OR GRAVEL CUSHION BETWEEN ROCK BEARING SURFACE AND <br />ELECTRICAL INSTALLATIONS. <br />0. THE CONTRACTOR SHALL PROVIDE ALL INSERTS FOR THE SUPPORT OF DIVISION 16 EQUIPMENT <br />TO BE PLACED IN CONCRETE OR THROUGH CONCRETE SLABS AS CONSTRUCTION PROGRESSES. HE <br />SHALL PROVIDE ALL MISCELLANEOUS HANGING AND SUPPORTING HARDWARE. ALL ELECTRICAL WORK IS <br />TO BE CONCEALED IN OR BUILT INTO GENERAL CONSTRUCTION SHALL BE PLACED AS CONSTRUCTION <br />PROGRESSES. FAILURE OF THE CONTRACTOR TO COORDINATE WORK WITH OTHER TRADES AND THE <br />PROJECT CONSTRUCTION PROGRESS SHALL MAKE HIM RESPONSIBLE FOR ALL COST OF CUTTING AND <br />PATCHING, AS REQUIRED TO INSTALL WORK. NO STRUCTURAL MEMBER, MASONRY CONSTRUCTION OR <br />FINISHED WORK SHALL BE CUT OR ALTERED WITHOUT PRIOR WRITTEN APPROVAL BY THE <br />ARCHITECT/ENGINEER. CONTRACTOR SHALL FIRE RATE ALL PENETRATIONS THROUGH ALL FIRE RATED <br />SLABS OR WALLS PER THE INTENDED RATING. <br />P. THE CONTRACTOR SHALL SUPPLY AND SET INTO PLACE ALL WALL SLEEVES FOR CONDUITS AND <br />CEILING INSERTS FOR HANGERS IN AREAS OF NEW CONSTRUCTION AS BUILDING CONSTRUCTION <br />PROGRESSES. INSTALL EQUIPMENT NOTED TO BE CONCEALED IN WALLS BEFORE WALLS ARE <br />CONSTRUCTED IN ORDER THAT WALLS MAY BE CONSTRUCTED AROUND CONDUITS, ENCLOSURES, ETC. <br />Q. METALUC MATERIALS SHALL BE PROTECTED AGAINST CORROSION. EQUIPMENT ENCLOSURES SHALL <br />BE GIVEN RUST -INHIBITING TREATMENT AND STANDARD FINISH BY MANUFACTURER. ALUMINUM SHALL <br />NOT BE USED ON CONTACT WITH EARTH, AND, WHERE CONNECTED TO DISSIMILAR METAL, SHALL BE <br />PROTECTED BY SUITABLE FITTINGS AND TREATMENT. ALL FERROUS METALS SUCH AS ANCHORS, BOLTS, <br />BRACES, BOXES, BODIES, CLAMPS, FITTINGS, GUARDS, NUTS, PINS, RODS, SHIMS, THIMBLES, WASHERS, <br />AND MISCELLANEOUS PARTS, NOT OF STAINLESS STEEL OR NONFERROUS MATERIALS, SHALL BE <br />HOT -DIPPED GALVANIZED. <br />R. ALL CONDUITS STUBBED OUT FOR FUTURE USE SHALL HAVE A PULL WIRE INSTALLED, A <br />PLASTIC CAP INSTALLED AND BE IDENTIFIED AS TO THE CONDUIT ORIGIN. <br />S. THE RESPONSIBILITY FOR ANY CUTTING OF CONSTRUCTION WHICH IS REQUIRED FOR THE <br />INSTALLATION OF DIVISION 16 WORK, SHALL BE BY THE CONTRACTOR. THE CONTRACTOR SHALL <br />COORDINATE WITH ALL OTHER TRADES AND THE OWNER BEFORE ANY CUTTING AND OBTAIN APPROVAL <br />FROM THE ARCHITECT/ENGINEER PRIOR TO ANY CUTTING. ALL PATCHING AND FINISHING SHALL BE BY <br />THE CONTRACTOR. <br />T. WHERE OPENINGS OR HOLES ARE CUT IN CONSTRUCTION AND THE CUTTING BREAKS ELECTRICAL <br />CIRCUITRY OR CONTROL CIRCUITRY CONDUIT AND WIRING, THEN IT SHALL BE THE RESPONSIBILITY OF <br />THE CONTRACTOR TO REROUTE THE CIRCUITRY CONDUIT AND REWIRING AND TO COMPLETE THE <br />CIRCUITRY AS REQUIRED AND AS APPROVED BY THE ARCHITECT/ENGINEER. TEMPORARY COMPLETION <br />SHALL BE PROVIDED WHERE NECESSARY BEFORE THE PERMANENT REROUTING AND COMPLETION WORK <br />IS FINISHED. <br />U. ANY PENETRATIONS OF FIRE OR SMOKE RATED ASSEMBLIES MADE BY THIS CONTRACTOR IN <br />VERTICAL OR HORIZONTAL CONSTRUCTION SHALL BE SEALED AND PROTECTED BY THIS CONTRACTOR IN <br />ORDER TO MAINTAIN THE ESTABLISHED FIRE RATING WITH METHODS AS APPROVED BY THE AUTHORITY <br />HAVING JURISDICTION AND U.L <br />111. IDENTIFICATION: <br />A. IDENTIFICATION NAMEPLATES SHALL BE LAMINATED PLASTIC, SECURED TO EQUIPMENT WITH TWO <br />STAINLESS STEEL SCREWS. <br />B. EACH PANELBOARD AND METER CENTER SHALL BE EQUIPPED WITH A PERMANENT PLASTIC <br />NAMEPLATE WITH 1/2" MINIMUM LEITERS, SECURELY FASTENED TO THE DEVICE. <br />C. EACH INDIVIDUALLY MOUNTED CIRCUIT BREAKER, SWITCH, MOTOR STARTER, RELAY PANEL, <br />LIGHTING CONTACTOR, TRANSFORMER AND/OR ANY OTHER CONTROL OR PROTECTIVE DEVICE INCLUDING <br />EQUIPMENT DISCONNECT SWITCHES SHALL BE EQUIPPED WITH A PERMANENT PLASTIC NAMEPLATE WITH <br />1/2- MINIMUM LETTERS. <br />D. PANELBOARDS SHALL HAVE TYPEWRITTEN DIRECTORIES. ALL CIRCUITS TO BE IDENTIFIED BY <br />DEVICES SERVED AND ROOM NUMBERS (I.E., LIGHTING ROOM 216). HANDWRITTEN DIRECTORIES WILL <br />NOT BE ALLOWED. <br />E. EACH JUNCTION BOX CABINET OR WIREWAY LARGER THAN 6* X 6" SHALL BE EQUIPPED WITH A <br />PERMANENT PLASTIC NAMEPLATE WITH 1/2- MINIMUM LETTERS INDICATING THE SYSTEM ENCLOSED. <br />F. ALL SYSTEMS JUNCTION BOXES AND CONDUIT SHALL BE COLOR CODED INSIDE AND OUTSIDE OF <br />THE BOX PRIOR TO THE INSTALLATION OF CONDUCTORS PER THE FOLLOWING: <br />1. CCTV SYSTEM: VIOLET <br />2. TELEPHONE DATA SYSTEM: BLUE <br />G. ENTIRE BOX INSIDE AND OUT , INCLUDING COVER, SHALL BE PAINTED PRIOR TO INSTALLING <br />CONDUCTORS. <br />IV. WIRING DEVICES: <br />A. SWITCHES SHALL BE 20 AMP COMMERCIAL GRADE 125 VAC. GRAY IN COLOR WITH STAINLESS <br />STEEL COVERPLATES FOR COMMON AREAS. <br />B. RECEPTACLES SHALL BE 20 AMP SPECIFICATION GRADE 125 VAC. GRAY IN COLOR WITH <br />STAINLESS STEEL COVERPLATES FOR COMMON AREAS. <br />C. SWITCHES AND OUTLETS FOR RESIDENTIAL UNITS SHALL BE RESIDEN11AL LINE SILENT OPERATION <br />TYPE RATED FOR 15AMPS, 120VOLTS. ALL DEVICES AND COVER PLATES SHALL BE WHITE. <br />D. WEATHERPROOF RECEPTACLES SHALL BE GFCI TYPES WITH GASKETED STAINLESS STEEL KEY <br />LOCKABLE FLIP COVER TYPE COVERPLATES. SURGE SUPPRESSION TYPE OUTLETS IN MDFS AND IDFS <br />SHALL BE HUBBELL #83625 (BLUE) OR EQUAL. <br />E. RECEPTACLES PROVIDED FOR ATTACHMENT OF CORD AND PLUG EQUIPMENT SHALL BE HEAVY <br />DUTY, SPECIFICATION GRADE, NON- INTERCHANGEABLE, FLUSH MOUNTED TYPES OF THE PROPER NEMA <br />CONFIGURATION TO SERVE THE EQUIPMENT. NEMA CONFIGURATIONS SHALL BE VERIFIED PRIOR TO <br />INSTALLATION OF CIRCUIT CONDUCTORS. PROVIDE ALL FINAL FLEXIBLE. CONDUIT CONNECTIONS, TO <br />GARBAGE DISPOSAL, DISHWASHER, RANGE, MICROWAVES AND HVAC EQUIPMENT. <br />F. ALL DEVICES SHALL HAVE PROPER PLATES, CARPET FLANGES, TRIMS, RINGS, ESCUTCHEONS, ETC., <br />AS MANUFACTURED BY SAME MANUFACTURER AS DEVICES. ANY TELEPHONE OR OTHER OUTLET WHICH <br />IS NOT EQUIPPED WITH A PLATE FURNISHED BY OTHERS SHALL HAVE ONE PROVIDED BY THIS <br />CONTRACTOR. <br />G. MOUNTING HEIGHTS ARE APPROXIMATE. THE EXACT LOCATIONS AND MOUNTING HEIGHTS SHALL BE <br />DETERMINED ON THE JOB AND PER ARCHITECTURAL DRAWINGS AND IT SHALL BE THE CONTRACTOR'S <br />RESPONSIBILITY TO COORDINATE WITH ALL TRADES TO INSURE CORRECT INSTALLATION, I.E., OVER <br />COUNTERS IN OR ABOVE BACK -SPLASHES, IN BLOCK WALLS, TILE, AND OTHER SPECIFIC CONSTRUCTION <br />FEATURES. LOCATION OF OUTLETS MOUNTED IN BUILT-INS, MILLWORK, AND CABINETRY SHALL BE <br />VERIFIED. OUTLETS MOUNTED IN KICK OR TOE SPACES SHALL BE MOUNTED HORIZONTALLY. OUTLET <br />BOXES SHALL BE MOUNTED TO PREVENT DEVICE PLATE FROM OVERLAPPING BACKSPLASH, TRIM, TILE, <br />ETC. LOCATE SO DEVICE PLATE WILL LAY FLAT AGAINST SURFACE COMPLETELY AROUND THE PERIMETER <br />OF PLATE. <br />H. OUTLETS, OTHER THAN THOSE COORDINATED WITH COUNTER TOPS, SHELVES, AND CABINETS, <br />SHALL BE LOCATED WITH THE CENTER LINE OF OUTLET BOXES THE FOLLOWING DISTANCE ABOVE THE <br />FINISHED FLOOR, UNLESS OTHERWISE INDICATED: <br />1. RECEPTACLES, GENERAL: l'-6* AFF <br />2. TELEPHONE OUTLETS: V-6m AFF <br />3. SWITCHES, GENERAL: 4'-0" AFF <br />V. RACEWAYS <br />A. SHALL BE GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING. E.M.T. SHALL BE <br />ELECTRO-GALVANIZED. CONDUITS SHALL BE AS MANUFACTURED BY REPUBLIC, PITTSBURGH STANDARD, <br />WHEATLAND, TRIANGLE, ALLIED, OR YOUNGSTOWN. <br />B. SHALL BE STANDARD THREADED TYPE, GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING. <br />THREADLESS AND CLAMP TYPE NOT ACCEPTABLE. SHALL BE AS MANUFACTURED BY RACO, EFCOR, OR <br />APPLETON. <br />C. SHALL BE STEEL THREADED COMPRESSION TYPE. ALL COUPLINGS AND CONNECTORS SHALL BE <br />EFCOR OR RACO. PRESSURE INDENTED TYPE CONNECTORS OR CAST METAL WILL NOT BE APPROVED <br />FOR ANY LOCATION. <br />D. CONNECTORS SHALL HAVE PLASTIC INSULATED THROAT INSERTS. <br />E. THE USE OF METAL CLAD CABLE IS ACCEPTABLE IN LOCATIONS AS ACCEPTED BY THE NEC AND <br />ALL LOCAL JURISDICTIONAL CODES. <br />F. STEEL METAL CLAD CABLE, TYPE MC, EMPLOYING CIRCUIT CONDUCTORS #12 SOLID TO #2 AWG, <br />SOLID OR STRANDED COPPER WITH THHN INSULATION, AN INSULATED GREEN <br />GROUNDING CONDUCTOR AND GALVANIZED STEEL INTERLOCKED ARMOR CLADDING. THE CABLES SHALL <br />BE SUITABLE FOR USE IN CONCEALED DRY LOCATIONS AT TEMPERATURES NOT EXCEEDING 90' C ON <br />AD CIRCUITS UP TO 600 VOLTS IN ACCORDANCE WITH N.E.C., ARTICLE 334. THE CABLE SHALL BE <br />ONE AND TWO HOUR FIRE RATED PER ANSI/UL 1479 FOR USE CONCEALED IN WALL, CEILING AND <br />FLOOR ASSEMBLIES. <br />G. FLEXIBLE METALLIC CONDUIT RACEWAYS MAY BE USED TO CONNECT HVAC UNITS LOCATED IN <br />INTERIOR MECHANICAL AREAS. MINIMUM SIZE 3/4-. <br />H. CONDUIT SHALL BE SIZED IN ACCORDANCE WITH THE LATEST NATIONAL ELECTRICAL CODE <br />EXCEPT THAT NO CONDUIT SHALL BE SMALLER THAN 3/4- UNLESS OTHERWISE NOTED. CONDUIT <br />SHALL BE SIZED LARGER THAN REQUIRED ABOVE WHEN SO SHOWN ON THE DRAWINGS OR WHEN <br />REQUIRED BY LOCAL CODE. <br />1. ANY CONDUIT STUBBED OUT FOR FUTURE SHALL BE CAPPED WITH A PLASTIC CAP AND MARKED <br />WITH A 2" MINIMUM RED METAL TAG WHICH IDENTIFIES CONDUIT ORIGIN. CONDUITS STUBBED UP <br />ABOVE GRADE OR ROOF SHALL BE TAGGED ON THE CONDUIT. CONDUIT STUBBED OUT BELOW GRADE <br />SHALL BE TAGGED ON NEAREST BUILDING WALL, CURB, ETC., DIRECTLY OVER THE CONDUIT ALL EMPTY <br />CONDUITS SHALL HAVE PULL WIRES. <br />J. THE USE OF NON-METALUC SHEATHED CABLE (ROMEX) SHALL BE PERMISSIBLE FOR USE WITHIN <br />RESIDENTIAL UNITS AS ACCEPTED BY THE AUTHORITY HAVING JURISDICTION AND INSTALLED PER THE <br />MANUFACTURES RECOMMENDATIONS. PRIOR WRITTEN APPROVAL FROM THE AHU IS MANDATORY AND <br />MUST BE SUBMITTED WITH CONDUCTOR SHOP DRAWINGS. <br />VI. SCHEDULE 40 RIGID PVC: <br />A. CONDUIT SHALL BE COMPOSED OF POLYVINYLCHLORIDE (PVC) AND SHALL BE UL RATED TYPE <br />40 FOR USE WITH 90*C RATED CONDUCTORS. CONDUIT SHALL CONFORM TO NEMA STANDARDS AND <br />APPUCABLE SECTIONS OF NEC. <br />B. INSTALLATION OF RIGID NON-METALUC CONDUIT SHALL COMPLY WITH ARTICLE 347 OF THE <br />NATIONAL ELECTRICAL CODE (NFPA 70) AND THESE SPECIFICATIONS. <br />C. PROVIDE A CONTINUOUS, INSULATED, GROUNDING CONDUCTOR IN EVERY RIGID, NON-METALUC <br />RACEWAY EVEN IF NOT SHOWN ON THE DRAWINGS. THE GROUNDING CONDUCTOR SHALL BE <br />CONNECTED TO GROUND AT EACH END OF THE RACEWAY IN ACCORDANCE WITH ARTICLE 250 OF THE <br />NATIONAL ELECTRICAL CODE (NFPA 70). <br />D. WHERE RIGID NON-METALUC CONDUIT TRANSITIONS TO METALLIC CONDUIT, THE LOCATION OF <br />THE TRANSITION SHALL BE UNDERGROUND. <br />NO PVC CONDUIT SHALL BE RUN EXPOSED, OR ABOVE GRADE. <br />VII. WIRE AND CABLE 600 VOLT: <br />A. CONDUCTORS SHALL HAVE CURRENT CARRYING CAPACITIES AS PER NEC AND WITH 600 VOLT <br />INSULATION, 112 AVERAGE MINIMUM FOR 20 AMP CIRCUITS. CONDUCTORS SHALL BE COPPER. <br />B. #12 AND #10 SHALL BE SOLID, TYPE THWN/THHN INSULATION. <br />C. #8 AND LARGER, AND ANY SIZE TO MOTORS SHALL BE STRANDED TYPE THHN. <br />D. SHALL BE MADE WITH T & B STA-KON WIRE JOINTS, PT SERIES, COMPLETE WITH INSULATING <br />CAPS AND INSTALLED WITH WT161 TOOL OR WT2000 TOOL, IDEAL SUPER -NUTS (NOT WIRE IDEAL <br />WING NUTS, OR BUCHANAN ELEC. PRODUCTS B CAP OR SERIES 2000 PRESSURE CONNECTORS <br />COMPLETE WITH NYLON SNAP -ON INSULATORS AND INSTALLED WITH C24 PRESSURE TOOL. <br />E. ALL JOINTS AND SPLICES IN WIRE SHALL BE MADE WITH APPROVED SOLDERLESS CONNECTORS, <br />AND COVERED SO THAT INSULATION IS OWNER APPROVED EQUAL TO CONDUCTOR INSULATION. SPLICES <br />SHALL NOT BE PERMITTED IN CONTROL, SECURITY, FIRE ALARM, TELEVISION OR COMMUNICATIONS <br />SYSTEMS, OR WHERE OTHERWISE NOTED. SPLICING OF WIRE OR CABLES WILL <br />NOT BE ALLOWED BELOW GRADE, INCLUDING IN BOXES BELOW GRADE. <br />F. BOTH CONDUCTORS AND CONDUITS SHALL BE CONTINUOUS FROM OUTLET TO OUTLET. <br />G. IN INSTALLING THE MAIN ELECTRICAL SERVICE, ADDITIONAL SLACK CONDUCTORS SHALL BE <br />PROVIDED AND TERMINATED AS REQUIRED BY ELECTRIC UTILITY FOR CONNECTION TO THEIR <br />EQUIPMENT. FIELD COORDINATE WITH UTILITY PRIOR TO INSTALLING CONDUCTORS. <br />H. IN INSTALLING PARALLEL CONDUCTORS IT IS MANDATORY THAT ALL CONDUCTORS MAKING UP <br />THE FEEDER BE EXACTLY THE SAME LENGTH, THE SAME SIZE AND THE SAME TYPE OF CONDUCTOR <br />WITH THE SAME INSULATION. FURTHER, EACH GROUP OF CONDUCTORS MAKING UP A PHASE OR <br />NEUTRAL MUST BE BONDED AT BOTH ENDS IN AN APPROVED MANNER. <br />1. CONDUCTOR SIZES INDICATED ON CIRCUIT HOMERUNS OR IN PANELBOARD SCHEDULES SHALL BE <br />INSTALLED OVER THE ENTIRE LENGTH OF THE CIRCUIT UNLESS NOTED OTHERWISE ON THE DRAWINGS. <br />J. CONDUCTORS SHALL BE CONTINUOUS AND UNSPUCED WHERE INSTALLED IN CONDUIT. SPLICES <br />SHALL OCCUR ONLY WITHIN WIRING TROUGHS, WIREWAYS, JUNCTION BOXES, OUTLET BOXES, OR <br />EQUIPMENT ENCLOSURES WHERE SUFFICIENT ADDITIONAL ROOM IS PROVIDED FOR ALL SPLICES. <br />K. EACH BRANCH CIRCUIT AND FEEDER CONDUCTOR SHALL BE COLOR CODED. FOR CONDUCTOR <br />SIZES THRU NO. 6 AWG, THE INSULATION SHALL BE OF THE COLOR AS INDICATED BELOW. COLOR <br />CODE SHALL BE STRICTLY ADHERED TO. FOR CONDUCTOR SIZES NO. 4 AWG AND LARGER, COLOR <br />CODED PHASE TAPE MAY BE APPLIED COMPLETELY AROUND THE CONDUCTOR INSULATION WITHIN 8* <br />OF EACH END OF THE CONDUCTOR AND IN EACH PULL OR JUNCTION BOX OR WHENEVER <br />CONDUCTORS ARE PHYSICALLY EXPOSED TO VIEW. GROUNDING CONDUCTORS AND GROUNDED <br />CONDUCTORS SHALL HAVE INSULATION COLOR AS INDICATED FOR SIZES THROUGH #6 AWG. <br />120/240 V, 1PHASE, 3W <br />PHASE A, COLOR: BLACK <br />PHASE B, COLOR: RED <br />NEUTRAL, COLOR: WHITE <br />GROUND, COLOR: GREEN <br />L THE USE OF NON-METALUC SHEATHED CABLE (ROMEX) SHALL PERMISSIBLE FOR USE WITHIN <br />RESIDENTIAL UNITS AS ACCEPTED BY THE AUTHORITY HAVING JURISDICTION AND INSTALLED PER THE <br />MANUFACTURES RECOMMENDATIONS. PRIOR WRITTEN APPROVAL FROM THE AHU IS MANDATORY AND <br />MUST BE SUBMITTED WITH CONDUCTOR SHOP DRAWINGS. <br />M. PRIOR AUTHORIZATION FROM THE ARCHITECT/ENGINEER IF CONDUCTORS ARE SUBSTITUTED TO <br />ALUMINUM CONDUCTORS. CONDUCTORS MUST HAVE THE EQUIVALENT OR GREATER AMPACITY VALUE <br />THAN THAT OF SPECIFIED COPPER, SHALL PHYSICALLY FIT BELOW THE CONNECTION LUG AND SHALL <br />BE SUBMITTED TO THE ENGINEER FOR APPROVAL. ALL LUGS SHALL BE RATED FOR COPPER AND <br />ALUMINUM CONDUCTORS. CONDUCTORS SHALL BE INSTALLED UTILIZING "NO -LOX" ANTI -OXIDATION <br />COMPOUND AND CONDUCTORS SHALL BE DESIGNATED AS "COMPACT ALUMINUM". <br />V1 1. GROUNDING: <br />A. THIS SECTION DEALS WITH THE GROUNDING OF SERVICE EQUIPMENT, TRANSFORMERS, <br />NON -CURRENT CARRYING CONDUCTIVE SURFACES OF EQUIPMENT, METAL BUILDING, STRUCTURES AND <br />OTHER EQUIPMENT. MAXIMUM RESISTANCE SHALL NOT EXCEED 10 OHMS <br />B. ALL GROUNDING CONNECTIONS SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL <br />ELECTRICAL CODE AND ALL LOCAL CODES AND REQUIREMENTS. SUCH CODES SHALL BE CONSIDERED <br />MINIMUM REQUIREMENTS AND THE INSTALLATION OF THE GROUNDING SYSTEM SHALL INSURE FREEDOM <br />FROM DANGEROUS SHOCK EXPOSURE AND SHALL PROVIDE A LOW IMPEDANCE GROUND FAULT PATH <br />TO PERMIT OPERATION OF OVERCURRENT AND GROUND FAULT PROTECTIVE DEVICES. <br />C. ALL SERVICE AND EQUIPMENT GROUNDING CONDUCTORS, AND BONDING JUMPERS SHALL BE <br />INSULATED COPPER, TYPE THHN, THWN, OR THW CONDUCTORS (UNLESS NOTED OTHERWISE) AND <br />SHALL BE SIZED IN ACCORDANCE WITH THE APPLICABLE PORTIONS OF ARTICLES 250 AND 517 OF <br />THE NATIONAL ELECTRICAL CODE. GROUNDING CONDUCTORS #6 AWG AND SMALLER SHALL HAVE A <br />GREEN COLOR INSULATION. ALL GROUNDING CONDUCTORS #4 AWG AND LARGER SHALL BE <br />ADEQUATELY IDENTIFIED WITH A GREEN TRACER AND/OR GREEN COLORED TAPE AT EACH END OF THE <br />GROUNDING CONDUCTOR AND AT EACH PULLBOX OR OTHER ACCESSIBLE LOCATION. <br />D. THE MAIN SERVICE GROUNDING ELECTRODE SYSTEM SHALL CONSIST OF THE FOLLOWING ITEMS <br />BONDED TOGETHER BY THE GROUNDING ELECTRODE CONDUCTORS IN ACCORDANCE WITH NEC ARTICLE <br />250: <br />1. THE MAIN UNDERGROUND COLD WATER PIPE, NEC 250 <br />2. METAL FRAME OF BUILDING WHERE AVAILABLE, NEC 250 <br />3. CONCRETE ENCASED ELECTRODE, NEC 250-81(C) <br />4. LIGHTNING PROTECTION SYSTEM. <br />E. THE NEUTRAL CONDUCTOR SHALL BE GROUNDED AT THE SERVICE ENTRANCE MAIN DISCONNECT, <br />AND AT EACH SEPARATELY DERIVED SYSTEM ONLY PER NEC ARTICLE 250. <br />F. A #4 INSULATED COPPER CONDUCTOR INSTALLED IN 3/4- CONCEALED CONDUIT SHALL BE <br />CONNECTED FROM THE BUILDING GROUNDING ELECTRODE SYSTEM TO EACH BUILDING FIRE ALARM <br />CONTROL CABINETS, CCTV SYSTEM CABINETS, EMS CABINETS, RELAY CABINETS, AND SECURITY SYSTEM <br />CABINETS. TERMINATE ON AN APPROPRIATELY SIZED (8) TERMINAL MULTI -CONDUCTOR CONNECTION <br />GROUNDING LUG LOCATED WITHIN CABINET OR ON TERMINAL BOARDS. <br />IX. PANELBOARDS: <br />A. PANELBOARDS SHALL BE DEAD FRONT TYPE AND SHALL BE IN ACCORDANCE WITH UNDERWRITERS' <br />LABORATORIES, INC., STANDARD FOR PANELBOARDS AND ENCLOSING CABINETS AND SO LABELED. <br />B. PANELBOARDS SHALL BE FACTORY ASSEMBLED WITH BRANCH BREAKERS ARRANGED AS SHOWN IN <br />SCHEDULES. BREAKERS SHALL BE NUMBERED VERTICALLY BEGINNING TOP LEFT. BREAKER NUMBERS SHALL <br />BE PERMANENTLY ATTACHED TO TRIM. PANEL SHALL BE MINIMUM 20" WIDE, UNLESS SPECIFICALLY NOTED <br />OTHERWISE. <br />D. ANY SPECIAL REQUIREMENTS ON THE DRAWINGS OR SCHEDULES, SUCH AS GROUND FAULT <br />PROTECTION, INCREASED INTERRUPTING CAPACITY, ARC -FAULT CIRCUIT BREAKERS SHUNT TRIP TYPE CIRCUIT <br />BREAKER, FEED THRU PANELBOARDS, ETC., SHALL SUPERSEDE THESE SPECIFICATIONS, BUT ONLY INSOFAR <br />AS THAT PARTICULAR REQUIREMENT IS CONCERNED AND AS INDICATED. <br />E. WIRING IN PANELBOARD GUTTERS SHALL BE PERFORMED IN A NEAT AND WORKMAN LIKE MANNER. <br />WIRING SHALL BE GROUPED INTO NEAT BUNDLES AND SECURED WITH NYLON TIE WRAPS. <br />F. PROVIDE TYPE WRITTEN DIRECTORIES FOR EACH PANELBOARD INDICATING THE LOAD SERVED. <br />G. RESIDENTIAL LOAD CENTERS: <br />A. PANELS LOCATED WITHIN RESIDENTIAL UNITS ONLY, SHALL BE LOAD CENTERS. <br />B. MAXIMUM ALLOWABLE PHYSICAL DIMENSIONS: 16 INCHES WIDE BY 3.5 INCHES DEEP PER SECTION. <br />C. ALL LOAD CENTERS AND PANELBOARDS SHALL USE MOLDED CASE CIRCUIT BREAKERS. <br />D. COMPLETELY SEALED ENCLOSURE. TOGGLE TYPE OPERATING HANDLE. TRIP AMPERE RATING AND <br />CIN/OFF INDICATION CLEARLY VISIBLE. <br />E. THERMAL -MAGNETIC TRIP -FREE, TRIP- INDICATING, QUICK -MAKE, QUICK -BREAK, WITH INVERSE TIME <br />CHARACTERISTIC. SINGLE -HANDLE AND COMMON TRIPPING ON MULTI -POLE BREAKERS. <br />F. EXTERNAL HANDLE SHALL BE SUITABLE FOR LOCKING IN THE OFF POSITION. <br />G. SILVER ALLOY CONTACTS WITH AUXILIARY ARC -QUENCHING DEVICES. <br />H. BREAKERS FOR LIGHTING CIRCUITS SHALL BE SWD RATED. <br />1. PROVIDE ARC FAULT CIRCUIT BREAKERS FOR ALL CIRCUIT BREAKERS AS REQUIRED PER NEC <br />LOCATED IN RESIDENTIAL UNITS. <br />H. METER CENTERS <br />A. GANGABLE AND WEATHERPROOF NEMA 3R METERING SHALL BE COMPLETE WITH: ALUMINUM CROSS <br />BUSSING AND METER STACKS. <br />B. MINIMUM SHORT CIRCUIT RATING OR INTEGRATED ASSEMBLY SHALL NOT BE LESS THAN 22,000 <br />AMPERES. <br />C. METER BASES SHALL CONFORM TO U.L. STANDARD 175, AND BE CONFIGURED TO CONFORM TO THE <br />SERVING UTILITY REQUIREMENTS. <br />D. RESIDENTIAL UNIT CIRCUIT BREAKERS SHALL BE 2-POLE, WITH AMPERE RATINGS AND SERIES <br />INTERRUPTING RATINGS TO LIMIT FAULT CURRENTS TO LESS THAN 10,000 AMPERES. PROVIDE PERMANENT <br />PLASTIC IDENTIFICATION LABEL INDICATING THE UNIT SERVED ON EACH CIRCUIT BREAKER. <br />E. PHASE SEQUENCED BUSSING SHALL BE USED THROUGHOUT, WITH LOAD BALANCE AS EQUAL AS <br />POSSIBLE. <br />X. LIGHTING FIXTURES: <br />A. LIGHTING FIXTURES SHALL BE FURNISHED AS SHOWN ON DRAWINGS AND IN THE LIGHTING <br />FIXTURE SCHEDULE. IT SHALL SPECIFICALLY BE THE RESPONSIBILITY OF THE CONTRACTOR TO <br />VERIFY EXACT TYPE CEILING AND RECESSING DEPTH OF ALL RECESSED FIXTURES AND TO FURNISH THE <br />MOUNTING TRIMS AND ACCESSORIES OF THE SPECIFIED AND/OR APPROVED FIXTURES FOR THE CEILING TO <br />BE INSTALLED. LIGHTING FIXTURES SHALL BE PROVIDED WITH JOINER PLATES, END CAPS, RETAINING CUPS, <br />PLASTER FRAMES, HOUSINGS, AND ALL OTHER ACCESSORIES REQUIRED FOR A COMPLETE INSTALLATION. <br />B. ALL RXTURES SHALL BE EQUIPPED WITH LAMPS UNLESS OTHERWISE NOTED. LAMPS SHALL BE <br />INSTALLED NEW, IMMEDIATELY PRIOR TO FINAL INSPECTION, AND SHALL NOT BE USED FOR CONSTRUCTION. <br />C. FIXTURE CATALOG NUMBER REPRESENTS BASIC LUMINARY SIZE, TYPE, QUALITY AND <br />CONFIGURATION. ACCESSORIES SHALL BE FURNISHED WITH EACH UNIT AS REQUIRED FOR A <br />COMPLETE FINISHED INSTALLATION. BASIC ACCESSORIES SHALL INCLUDE, BUT ARE NOT LIMITED <br />TO, THE FOLLOWING: <br />1. JOINING PLATES, END CAPS, RETAINING CUPS, DRYWALL FLANGES, ETC. <br />2. TRIMS FOR RECESSED FIXTURES. <br />3. FIXTURE STEMS AND CANOPIES FINISHED TO MATCH FIXTURES. <br />4. SPECIAL MOUNTING BRACKETS, TENONS, SUP FILTERS, CONCRETE BASES, POLES, ANCHOR BOLTS, <br />JUNCTION BOXES, AND STANCHIONS FOR ALL EXTERIOR LIGHTING FIXTURES. PROVIDE ALL <br />WEATHERPROOFING FOR ALL LIGHTING FIXTURES TO BE INSTALLED IN EXTERIOR LOCATIONS. <br />D. STRUCTURAL SUPP09T OF ALL FIXTURES SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. <br />E. THE SYSTEM GROUNDING CONDUCTOR SHALL BE SECURED TO EACH FIXTURE BODY BY MEANS OF A <br />BONDING SCREW. <br />F. OWNER WILL HAVE RIGHT TO RELOCATE LIGHTING FIXTURES OR LIGHTING SWITCHES WITHIN 72" OF <br />LOCATION SHOWN ON FIRST WALK-THROUGH AT NO ADDITIONAL EXPENSE. COORDINATE THE WALK-THROUGH <br />PRIOR TO THE INSTALLATION OF THE WIRING. <br />CA# 26308 121270.00 <br />Alk I N G E N U I TY <br />ENGIN EERS, INC. <br />Moir "PROA 0 VE ENGINEERING SOLUTIONS" <br />4798 NEW BROAD ST. SUITE 300 1 ORLANDO, FLORIDA 1407.398.6007 <br />�113111111 <br />Mu u <br />THIS DOCUMENT AND/OR THE DESIGN <br />CONCEPTS EXPRESSED HEREIN ARE THE <br />PROPERTY OF KEESEE ASSOCIATES AND <br />ALL RIGHTS OF OWNERSHIP, INCLUDING <br />COPYRIGHT OF INTELLECTUAL PROPERTY, <br />ARE RESERVED THE REPRODUCTIONS, <br />COPYING, OR USE OF THIS DOCUMENT <br />AND/OR THE DESIGN CONCEPT WITHOUT <br />THE WRITTEN CONSENT OF KEESEE <br />ASSOCIATES IS STRICTLY PROHIBITED AND <br />PROTECTED BY UNITED STATES AND <br />INTERNATIONAL LAW <br />xo� <br />M c K <br />Lu <br />C/'> <br />- _3 <br />06 <br />Lu - 'A' <br />Of <br />QDD <br />NAL <br />Jodu 16 1114 .53M <br />i6 <br />U) <br />E <br />ca <br />z <br />a - <br />Lu M <br />uj <br />Z <br />LL <br />a W U) <br />0 z w <br />N <br />00 Lu <br />SHEET INFORMATION <br />DATE: 10/19/2021 <br />DRAWN BY: KR <br />PROJECT NO: 20 A (n) (n) 1 1 <br />I REVIEWED BY: im I <br />IvI Plan Revisions Date: I <br />1 06/04/2021 ISSUED FOR PERMIT <br />1 1 10/18/2021 OWNER REVISION <br />Sheet Name <br />ELECTRICAL <br />SPECIFICATION& <br />EO.2 <br />