1. GENERAL REQUIREMENTS - DIVISION 16 ELECTR CAL:
<br />A. PERFORM ALL WORK IN COMPLIANCE WITH THE LATEST ADOPTED EDITION OF THE FLORIDA BUILDING CODE,
<br />NFPA 70 (NEC-2017 ORDINANCE 68831) AND NFPA 101 (LIFE SAFETY CODE), ADA ANSI A117.1, AND FEDERAL
<br />FAIR HOUSING ACT (42 U.S.C. 3601), INSTALL AND CONNECT PER AND THE REGULATIONS OF THE LOCAL UTILITY
<br />TELEPHONE, CABLE TELEVISION AND POWER UTILITY COMPANIES. OBTAIN AND PAY FOR ANY AND ALL REQUIRED
<br />PERMITS, INSPECTIONS, CERTIFICATES OF INSPEC11ONS AND APPROVAL, AND THE LIKE, AND DELIVER SUCH
<br />CER11FICATES TO THE OWNER.
<br />B. THE CONTRACTOR SHALL FURNISH, PERFORM, OR OTHERWISE PROVIDE ALL LABOR (INCLUDING, BUT NOT
<br />LIMITED TO, ALL PLANNING, PURCHASING, PAINTING, TRANSPORTING, RIGGING, HOISTING, STORING, INSTALLING,
<br />TESTING, CHASING, CHANNELING, CUTTING, TRENCHING, EXCAVATING AND BACKFILLING), COORDINATION, FIELD
<br />VERIFICATION, EQUIPMENT INSTALLATION, SUPPORT, AND SAFETY, SUPPLIES, AND MATERIALS NECESSARY FOR THE
<br />CORRECT INSTALLAT10N OF COMPLETE AND FUNCTIONAL ELECTRICAL SYSTEMS (AS DESCRIBED OR IMPLIED BY
<br />THESE SPECIFICATIONS AND THE APPLICABLE DRAWINGS).
<br />C. ALL DRAWINGS AND SPECIFICATIONS ON THE PRoJECT ARE COMPLEMENTARY, EACH TO ALL OTHER SETS,
<br />AND THEY SHALL BE USED IN COMBINATION FOR THE EXECUTION OF THIS WORK. DIVISION 16 WORK SHOWN ON
<br />ANY ONE SET OF DRAWINGS, INCLUDING ALL ARCHITECTURAL DRAWINGS, MECHANICAL, PLUMBING AND FIRE
<br />PROTECTION DRAWINGS FOR GENERAL WORK AND EQUIPMENT, AND DIVISION 16 WORK CALLED FOR UNDER ANY
<br />SECTION OF THE PROJECT SPECIFICATIONS, SHALL BE CONSIDERED AS INCLUDED IN THIS WORK UNLESS
<br />SPECIFICALLY EXCLUDED BY INCLUSION IN SOME OTHER BRANCH OF THE WORK. THIS SHALL INCLUDE
<br />ROUGHING -IN FOR CONNECTIONS AND EQUIPMENT AS CALLED FOR OR INFERRED. THE CONTRACTOR SHALL
<br />CHECK ALL DRAWINGS AND SPECIFICATIONS FOR THE PROJECT AND SHALL BE RESPONSIBLE FOR THE
<br />INSTALLATION OF ALL DIVISION 16 WORK.
<br />D. THE CONTRACTOR SHALL CAREFULLY CHECK THE' DRAWINGS AND SPECIFICATIONS OF ALL OTHER
<br />TRADES AND DIVISIONS BEFORE INSTALLING ANY OF HIS WORK. HE SHALL IN ALL CASES CONSIDER THE WORK
<br />OF ALL OTHER TRADES, AND SHALL COORDINATE HIS WORK WITH THEM SO THAT THE BEST ARRANGEMENTS OF
<br />ALL EQUIPMENT, PIPING, CONDUIT, DUCTS, ROUGH -IN, ETC., CAN BE OBTAINED.
<br />E. LOCATIONS DESIGNATED FOR OUTLETS, SWITCHES, DEVICES, EQUIPMENT, ETC., ARE
<br />APPROXIMATE AND FINAL LOCATIONS SHALL BE VERIFIED IN THE FIELD AND CHECKED WITH ARCHITECTURAL AND
<br />iD DRAWINGS. CONTRACTOR SHALL LOCATE ALL DEVICES UP TO 5 FEET IN ANY DIRECTION AS DIRECTED BY
<br />OWNER AND PER CODE. WHERE INSTRUCTIONS OR NOTES ARE INSUFFICIENT TO CONVEY THE INTENT OF THE
<br />DESIGN, CONSULT THE OWNER PRIOR TO BIDDING AND INSTALLATION.
<br />F. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING AND COORDINATING THE LOCATIONS OF DEVICES TO
<br />BE USED AND COORDINATING THE FINAL LOCATIONS 07 ELECTRICAL EQUIPMENT WITH MILLWORK, SINKS,
<br />BENCHES, COUNTERS AND SHELVING PRIOR TO BIDDING AND INSTALLATION. ALL DISCREPANCIES SHALL BE
<br />BROUGHT TO THE ATTENTION OF THE OWNER.
<br />G. DIVISION 16 CONTRACTOR SHALL HAVE HAD EXPERIENCE OF AT LEAST THE SAME SIZE AND SCOPE AS
<br />THIS PROJECT, ON AT LEAST TWO OTHER PROJECTS WITHIN THE LAST FIVE YEARS IN ORDER TO BE QUALIFIED
<br />TO BID THIS PROJECT.
<br />H. CONTRACTOR SHALL AND DOES HEREBY WARRANT ALL MATERIALS AND EQUIPMENT FURNISHED UNDER THIS
<br />SECTION OF THE SPECIFICATIONS TO BE FREE FROM DEFECTS AND TO FUNCTION OR OPERATE SATISFACTORILY
<br />FOR ONE YEAR AFTER FINAL ACCEPTANCE OF THE WORK, AND THAT ANY ITEMS NOT MEETING THIS REQUIREMENT
<br />WILL BE MADE GOOD BY HIM WITHOUT COST TO OWNER, PROVIDED SUCH DEFECTS OR FAILURES ARE NOT DUE
<br />TO ABUSE, NEGLECT, OR LACK OF REASONABLE AND ORDINARY MAINTENANCE.
<br />1. ALL WORK SHALL BE EXECUTED IN A WORKMANSHIP MANNER AND SHALL PRESENT A NEAT
<br />MECHANICAL APPEARANCE UPON COMPLETION.
<br />J. BALANCE LOAD AS EQUALLY AS PRACTICABLE ON ALL FEEDERS, BRANCH CIRCUITS AND PANEL BUSES.
<br />K. THE CONTRACTOR SHALL PROVIDE ADEQUATE PROTECTION, WHEREVER WORK IS TO BE PERFORMED IN
<br />FINISHED/CICCUPIED SPACES, TO PREVENT DAMAGE TO ADJACENT AREAS, EQUIPMENT, OR FURNISHINGS; TO
<br />PREVENT ACCIDENTAL INJURY TO BUILDING OCCUPANTS AND THE PUBLIC; TO PREVENT THE SPREADING OF DUST,
<br />DIRT, DEBRIS, AND MOISTURE FROM THE AREA WHERE WORK IS BEING PERFORMED; AND TO PREVENT DUST,
<br />DIRT, DEBRIS, AND MOISTURE FROM GETTING ON OR IN THE BUILDING OCCUPANT'S FURNISHINGS OR EQUIPMENT.
<br />L THE CONTRACTOR SHALL REPAIR, AT NO COST TO THE OWNER, ANY DAMAGE DONE BY HIMSELF
<br />OR HIS EMPLOYEES. HE SHALL ALSO BE RESPONSIBU--- FOR ALL CUTTING AND PATCHING REQUIRED TO
<br />PROPERLY INSTALL HIS WORK. THIS SHALL ALSO INCLUDE THE PATCHING OF EXISTING ROADWAYS (PAVED OR
<br />IMPROVED), PARKING AREAS, SIDEWALKS, WALLS, STAIRS, MECHANICAL WORK, CURBS, GUTTERS, ETC., CUT TO
<br />INSTALL WORK PROVIDED BY THE CONTRACTOR. PATCH WORK SHALL COMPLY WITH THE APPLICABLE SECTIONS
<br />OF THESE SPECIFICATIONS AND SHALL MATCH THE EXISTING FINISHES.
<br />M. UPON COMPLETION OF WORK, THE ENTIRE WIRING SYSTEM SHALL BE TESTED, AND SHALL BE
<br />SHOWN TO BE IN PROPER WORKING CONDITION IN ACCORDANCE WITH INTENT OF SPECIFICATIONS AND DRAWINGS.
<br />IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO HAVE ALL SYSTEMS READY FOR OPERATION AND TO
<br />HAVE AN ELECTRICIAN AVAILABLE TO OPERATE SAME 114 ACCORDANCE WITH AND UNDER THE SUPERVISION OF
<br />THE INSPECTION REPRESENTATIVE OF THE ENGINEER. THE CONTRACTOR SHALL BE AVAILABLE TO ASSIST IN
<br />REMOVAL OF PANEL FRONTS, TO PERMIT INSPECT10N AS REQUIRED. IN ACCORDANCE WITH DIVISION 1 AND THE
<br />CONDITIONS OF THE CONTRACT, THE CONTRACTOR SHALL PROVIDE AND KEEP UP TO DATE A COMPLETE RECORD
<br />SET OF CONSTRUCTION 7AS-BUILTS" BLUEUNE PRINTS WHICH SHALL BE CORRECTED DAILY, AND SHALL SHOW
<br />EVERY CHANGE FROM THE ORIGINAL CONTRACT DRAWINGS, INCLUDING ADDENDA AND CHANGE ORDERS IN
<br />ACCORDANCE WITH GENERAL REQUIREMENTS AND SPECIAL CONDITIONS. THIS SET OF PRINTS SHALL BE KEPT ON
<br />THE JOB SITE, AND SHALL BE USED ONLY AS A RECORD SET. THIS SHALL NOT BE CONSTRUED AS
<br />AUTHORIZATION FOR THE CONTRACTORS TO MAKE CHAAGES IN THE LAYOUT WITHOUT DEFINITE INSTRUCTION IN
<br />EACH CASE.
<br />11. ELECTRICAL SCOPE:
<br />A. FURNISHING AND INSTALLATION OF ELECTRIC LIGHTING SYSTEMS, POWER SYSTEMS, AND AUXILIARY SYSTEMS
<br />AS SHOWN OR HEREIN SPECIFIED.
<br />B. CONNECTION OF ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTION, MENTIONED IN THIS DIVISION OR
<br />SHOWN ON DRAWINGS, WHETHER FURNISHED BY DIVISION 16 OR UNDER OTHER DIVISIONS, OR FURNISHED BY
<br />OWNER, INCLUDING FIRE PROTECTION AND FIRE SPRINKLER SYSTEMS.
<br />C. FURNISHING AND INSTALLATION OF OUTLET BOXES, CONDUIT RACEWAYS, TERMINAL BOARDS, POWER AND
<br />GROUNDING FOR A COMPLETE TELEPHONE, TELEVISION AND DATA RACEWAY DISTRIBUTION SYSTEM. (TELEPHONE
<br />AND DATA HARDWARE, AS WELL AS SOFTWARE IS NOT INCLUDED.)
<br />D. FURNISH AND INSTALL A COMPLETE LIGHTNING PROTECTION SYSTEM.
<br />E. THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR CONTACTING THE OFFICES OF ALL LOCAL
<br />AND/CIR STATE AUTHORITIES HAVING JURISDICTION OVE_R THIS PROJECT IN ORDER TO SCHEDULE ALL REQUIRED
<br />INSPECTIONS AND OBTAIN ALL NECESSARY PERMITS, ETC. THE CONTRACTOR SHALL NOTIFY THE
<br />ARCHITECT/ENGINEER OF ALL SCHEDULED INSPECTIONS AT LEAST TWO WEEKS IN ADVANCE OF THE SCHEDULED
<br />DATE.
<br />F. THE CONTRACTOR SHALL REPLACE ANY DEFECTIVE MATERIALS, EQUIPMENT, OR WORKMANSHIP WITHOUT
<br />COST TO THE OWNER WITHIN THE STIPULATED GUARANTEED PERIOD.
<br />G. IT SHALL BE THE RESPONSIBILITY OF THE DIVISION 16 CONTRACTOR TO HAVE ALL SYSTEMS READY FOR
<br />OPERATION AND TO HAVE AN ELECTRICIAN AVAILABLE FOR ALL INSPECTIONS. THE CONTRACTOR SHALL PROVIDE
<br />PERSONNEL TO ASSIST IN REMOVAL OF PANEL FRONTS, ETC. TO PERMIT INSPECTION AS REQUIRED.
<br />H. SUBMIT TO THE ARCHITECT/ENGINEER PROMPTU( AFTER AWARD OF CONTRACT AND PRIOR TO PURCHASING,
<br />SIX COPIES OF MANUFACTURER'S SHOP DRAWINGS IN ACCORDANCE WITH DIVISION 1, SUBMITTALS FOR THE
<br />FOLLOWING ITEMS. ALL SHOP DRAWINGS OF A SPECIFIC ITEM OR SYSTEM SHALL BE MADE IN ONE SUBMITTAL
<br />AND WITHIN TEN DAYS AFTER AWARD OF CONTRACT.
<br />1. PANELBOARDS 6. DISCONNECT SWITCHES
<br />2. LIGHTING FIXTURES 7. CONDUIT
<br />3. 120V SMOKE/CO2 DETECTORS 8. CONDUCTORS
<br />4. WIRING DEVICES 9. LOAD CENTERS
<br />5. METER CENTERS 10. TVSS
<br />J. COMPLETED WIRING SYSTEMS SHALL BE FREE FROM SHORT CIRCUITS AND AFTER COMPLETION, PERFORM
<br />TESTS FOR INSULA11ON RESISTANCE IN ACCORDANCE WITH THE REQUIREMENTS OF THE NAT10NAL ELECTRICAL
<br />CODE. ALL WIRING SYSTEMS SHALL BE COMPLETELY AND TOTALLY "SAFED'DURING CONSTRUCTION. ONLY
<br />QUALIFIED PERSONNEL SHALL HANDLE ELECTRICAL SYSTEMS.
<br />K. THE ELECTRICAL CIRCUITS, COMPONENTS, AND CONTROLS FOR ALL EQUIPMENT ARE SELECTED AND SIZED,
<br />BASED ON THE EQUIPMENT SPECIFIED. IF SUBSTITUTIONS AND/OR EQUIVALENT EQUIPMENT ARE FURNISHED, IT
<br />SHALL BE THE RESPONSIBILITY OF ALL PARTIES CONCERNED, INVOLVED IN, AND FURNISHING THE SUBSTITUTE
<br />AND/OR EQUIVALENT EQUIPMENT TO VERIFY AND COMPARE THE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS
<br />OF THAT FURNISHED TO THAT SPECIFIED AND/CIR SHOWN. IF GREATER CAPACITY OR MORE MATERIALS OR LABOR
<br />IS REQUIRED FOR THE ROUGH -IN, CIRCUITRY OR CONNECTIONS THAN FOR THE ITEM SPECIFIED AND PROVIDED
<br />FOR, THEN IT SHALL BE THE RESPONSIBILITY OF THE PARTIES INVOLVED IN PROVIDING THE SUBSTITUTE AND/OR
<br />EQUIVALENT ITEMS OF EQUIPMENT TO PROVIDE ALL COMPENSATION FOR ADDITIONAL CHARGES MADE FOR THE
<br />PROPER ROUGH -IN, CIRCUITRY AND CONNECTIONS FOR THE EQUIPMENT FURNISHED. NO ADDITIONAL CHARGES
<br />ABOVE THE BASE BID SHALL BE ALLOWED FOR SUCH REVISIONS.
<br />BEFORE ROUGH -IN OF CIRCUITRY OR CONNECTING TO EQUIPMENT, FURNISHED UNDER THIS DIVISION, ANY OTHER
<br />DIVISION, OR BY THE OWNER, THE CONTRACTOR SHALL VERIFY THE ELECTRICAL CHARACTERISTICS AND
<br />REQUIREMENTS OF THE EQUIPMENT BEING FURNISHED AND FOR THAT SPECIFIED AND SHOWN ON THE DRAWINGS
<br />AND PROVIDE FOR PROPER ROUGH -IN AND CONNECTION.
<br />M. ENCAVATION FOR UNDERGROUND ELECTRICAL STRUCTURES: CONFORM TO ELEVATIONS AND DIMENSIONS
<br />SHOWN WITHIN A TOLERANCE OF PLUS OR MINUS 0.10% PLUS A SUFFICIENT DISTANCE TO PERMIT PLACING AND
<br />REMOVAL OF CONCRETE FORMWORK, INSTALLATION OF SERVICES, OTHER CONSTRUCTION, AND FOR INSPECTION.
<br />N * TRENCHING: ENCAVATE TRENCHES FOR ELECTRICAL INSTALLATIONS AS FOLLOWS:
<br />1. EXCAVATE TRENCHES TO THE UNIFORM WIDTH, SUFFICIENTLY WIDE TO PROVIDE AMPLE
<br />WORKING ROOM AND A MINIMUM OF 6* TO 9" CLEARANCE ON BOTH SIDES OF
<br />RACEWAYS AND EQUIPMENT.
<br />2. EXCAVATE TRENCHES TO DEPTH INDICATED OR REQUIRED.
<br />3. LIMIT THE LENGTH OF OPEN TRENCH TO THAT IN WHICH INSTALLATIONS CAN BE MADE AND THE
<br />TRENCH BACKFILLED WITHIN THE SAME DAY.
<br />4. WHERE ROCK IS ENCOUNTERED, CARRY EXCAVATION BELOW REQUIRED ELEVATION AND BACKFILL
<br />WITH A LAYER OF CRUSHED STONE OR GRAVEL PRIOR TO INSTALLATION OF RACEWAYS AND EQUIPMENT.
<br />PROVIDE A MINIMUM OF 6" OF STONE OR GRAVEL CUSHION BETWEEN ROCK BEARING SURFACE AND
<br />ELECTRICAL INSTALLATIONS.
<br />0. THE CONTRACTOR SHALL PROVIDE ALL INSERTS FOR THE SUPPORT OF DIVISION 16 EQUIPMENT
<br />TO BE PLACED IN CONCRETE OR THROUGH CONCRETE SLABS AS CONSTRUCTION PROGRESSES. HE
<br />SHALL PROVIDE ALL MISCELLANEOUS HANGING AND SUPPORTING HARDWARE. ALL ELECTRICAL WORK IS
<br />TO BE CONCEALED IN OR BUILT INTO GENERAL CONSTRUCTION SHALL BE PLACED AS CONSTRUCTION
<br />PROGRESSES. FAILURE OF THE CONTRACTOR TO COORDINATE WORK WITH OTHER TRADES AND THE
<br />PROJECT CONSTRUCTION PROGRESS SHALL MAKE HIM RESPONSIBLE FOR ALL COST OF CUTTING AND
<br />PATCHING, AS REQUIRED TO INSTALL WORK. NO STRUCTURAL MEMBER, MASONRY CONSTRUCTION OR
<br />FINISHED WORK SHALL BE CUT OR ALTERED WITHOUT PRIOR WRITTEN APPROVAL BY THE
<br />ARCHITECT/ENGINEER. CONTRACTOR SHALL FIRE RATE ALL PENETRATIONS THROUGH ALL FIRE RATED
<br />SLABS OR WALLS PER THE INTENDED RATING.
<br />P. THE CONTRACTOR SHALL SUPPLY AND SET INTO PLACE ALL WALL SLEEVES FOR CONDUITS AND
<br />CEILING INSERTS FOR HANGERS IN AREAS OF NEW CONSTRUCTION AS BUILDING CONSTRUCTION
<br />PROGRESSES. INSTALL EQUIPMENT NOTED TO BE CONCEALED IN WALLS BEFORE WALLS ARE
<br />CONSTRUCTED IN ORDER THAT WALLS MAY BE CONSTRUCTED AROUND CONDUITS, ENCLOSURES, ETC.
<br />Q. METALUC MATERIALS SHALL BE PROTECTED AGAINST CORROSION. EQUIPMENT ENCLOSURES SHALL
<br />BE GIVEN RUST -INHIBITING TREATMENT AND STANDARD FINISH BY MANUFACTURER. ALUMINUM SHALL
<br />NOT BE USED ON CONTACT WITH EARTH, AND, WHERE CONNECTED TO DISSIMILAR METAL, SHALL BE
<br />PROTECTED BY SUITABLE FITTINGS AND TREATMENT. ALL FERROUS METALS SUCH AS ANCHORS, BOLTS,
<br />BRACES, BOXES, BODIES, CLAMPS, FITTINGS, GUARDS, NUTS, PINS, RODS, SHIMS, THIMBLES, WASHERS,
<br />AND MISCELLANEOUS PARTS, NOT OF STAINLESS STEEL OR NONFERROUS MATERIALS, SHALL BE
<br />HOT -DIPPED GALVANIZED.
<br />R. ALL CONDUITS STUBBED OUT FOR FUTURE USE SHALL HAVE A PULL WIRE INSTALLED, A
<br />PLASTIC CAP INSTALLED AND BE IDENTIFIED AS TO THE CONDUIT ORIGIN.
<br />S. THE RESPONSIBILITY FOR ANY CUTTING OF CONSTRUCTION WHICH IS REQUIRED FOR THE
<br />INSTALLATION OF DIVISION 16 WORK, SHALL BE BY THE CONTRACTOR. THE CONTRACTOR SHALL
<br />COORDINATE WITH ALL OTHER TRADES AND THE OWNER BEFORE ANY CUTTING AND OBTAIN APPROVAL
<br />FROM THE ARCHITECT/ENGINEER PRIOR TO ANY CUTTING. ALL PATCHING AND FINISHING SHALL BE BY
<br />THE CONTRACTOR.
<br />T. WHERE OPENINGS OR HOLES ARE CUT IN CONSTRUCTION AND THE CUTTING BREAKS ELECTRICAL
<br />CIRCUITRY OR CONTROL CIRCUITRY CONDUIT AND WIRING, THEN IT SHALL BE THE RESPONSIBILITY OF
<br />THE CONTRACTOR TO REROUTE THE CIRCUITRY CONDUIT AND REWIRING AND TO COMPLETE THE
<br />CIRCUITRY AS REQUIRED AND AS APPROVED BY THE ARCHITECT/ENGINEER. TEMPORARY COMPLETION
<br />SHALL BE PROVIDED WHERE NECESSARY BEFORE THE PERMANENT REROUTING AND COMPLETION WORK
<br />IS FINISHED.
<br />U. ANY PENETRATIONS OF FIRE OR SMOKE RATED ASSEMBLIES MADE BY THIS CONTRACTOR IN
<br />VERTICAL OR HORIZONTAL CONSTRUCTION SHALL BE SEALED AND PROTECTED BY THIS CONTRACTOR IN
<br />ORDER TO MAINTAIN THE ESTABLISHED FIRE RATING WITH METHODS AS APPROVED BY THE AUTHORITY
<br />HAVING JURISDICTION AND U.L
<br />111. IDENTIFICATION:
<br />A. IDENTIFICATION NAMEPLATES SHALL BE LAMINATED PLASTIC, SECURED TO EQUIPMENT WITH TWO
<br />STAINLESS STEEL SCREWS.
<br />B. EACH PANELBOARD AND METER CENTER SHALL BE EQUIPPED WITH A PERMANENT PLASTIC
<br />NAMEPLATE WITH 1/2" MINIMUM LEITERS, SECURELY FASTENED TO THE DEVICE.
<br />C. EACH INDIVIDUALLY MOUNTED CIRCUIT BREAKER, SWITCH, MOTOR STARTER, RELAY PANEL,
<br />LIGHTING CONTACTOR, TRANSFORMER AND/OR ANY OTHER CONTROL OR PROTECTIVE DEVICE INCLUDING
<br />EQUIPMENT DISCONNECT SWITCHES SHALL BE EQUIPPED WITH A PERMANENT PLASTIC NAMEPLATE WITH
<br />1/2- MINIMUM LETTERS.
<br />D. PANELBOARDS SHALL HAVE TYPEWRITTEN DIRECTORIES. ALL CIRCUITS TO BE IDENTIFIED BY
<br />DEVICES SERVED AND ROOM NUMBERS (I.E., LIGHTING ROOM 216). HANDWRITTEN DIRECTORIES WILL
<br />NOT BE ALLOWED.
<br />E. EACH JUNCTION BOX CABINET OR WIREWAY LARGER THAN 6* X 6" SHALL BE EQUIPPED WITH A
<br />PERMANENT PLASTIC NAMEPLATE WITH 1/2- MINIMUM LETTERS INDICATING THE SYSTEM ENCLOSED.
<br />F. ALL SYSTEMS JUNCTION BOXES AND CONDUIT SHALL BE COLOR CODED INSIDE AND OUTSIDE OF
<br />THE BOX PRIOR TO THE INSTALLATION OF CONDUCTORS PER THE FOLLOWING:
<br />1. CCTV SYSTEM: VIOLET
<br />2. TELEPHONE DATA SYSTEM: BLUE
<br />G. ENTIRE BOX INSIDE AND OUT , INCLUDING COVER, SHALL BE PAINTED PRIOR TO INSTALLING
<br />CONDUCTORS.
<br />IV. WIRING DEVICES:
<br />A. SWITCHES SHALL BE 20 AMP COMMERCIAL GRADE 125 VAC. GRAY IN COLOR WITH STAINLESS
<br />STEEL COVERPLATES FOR COMMON AREAS.
<br />B. RECEPTACLES SHALL BE 20 AMP SPECIFICATION GRADE 125 VAC. GRAY IN COLOR WITH
<br />STAINLESS STEEL COVERPLATES FOR COMMON AREAS.
<br />C. SWITCHES AND OUTLETS FOR RESIDENTIAL UNITS SHALL BE RESIDEN11AL LINE SILENT OPERATION
<br />TYPE RATED FOR 15AMPS, 120VOLTS. ALL DEVICES AND COVER PLATES SHALL BE WHITE.
<br />D. WEATHERPROOF RECEPTACLES SHALL BE GFCI TYPES WITH GASKETED STAINLESS STEEL KEY
<br />LOCKABLE FLIP COVER TYPE COVERPLATES. SURGE SUPPRESSION TYPE OUTLETS IN MDFS AND IDFS
<br />SHALL BE HUBBELL #83625 (BLUE) OR EQUAL.
<br />E. RECEPTACLES PROVIDED FOR ATTACHMENT OF CORD AND PLUG EQUIPMENT SHALL BE HEAVY
<br />DUTY, SPECIFICATION GRADE, NON- INTERCHANGEABLE, FLUSH MOUNTED TYPES OF THE PROPER NEMA
<br />CONFIGURATION TO SERVE THE EQUIPMENT. NEMA CONFIGURATIONS SHALL BE VERIFIED PRIOR TO
<br />INSTALLATION OF CIRCUIT CONDUCTORS. PROVIDE ALL FINAL FLEXIBLE. CONDUIT CONNECTIONS, TO
<br />GARBAGE DISPOSAL, DISHWASHER, RANGE, MICROWAVES AND HVAC EQUIPMENT.
<br />F. ALL DEVICES SHALL HAVE PROPER PLATES, CARPET FLANGES, TRIMS, RINGS, ESCUTCHEONS, ETC.,
<br />AS MANUFACTURED BY SAME MANUFACTURER AS DEVICES. ANY TELEPHONE OR OTHER OUTLET WHICH
<br />IS NOT EQUIPPED WITH A PLATE FURNISHED BY OTHERS SHALL HAVE ONE PROVIDED BY THIS
<br />CONTRACTOR.
<br />G. MOUNTING HEIGHTS ARE APPROXIMATE. THE EXACT LOCATIONS AND MOUNTING HEIGHTS SHALL BE
<br />DETERMINED ON THE JOB AND PER ARCHITECTURAL DRAWINGS AND IT SHALL BE THE CONTRACTOR'S
<br />RESPONSIBILITY TO COORDINATE WITH ALL TRADES TO INSURE CORRECT INSTALLATION, I.E., OVER
<br />COUNTERS IN OR ABOVE BACK -SPLASHES, IN BLOCK WALLS, TILE, AND OTHER SPECIFIC CONSTRUCTION
<br />FEATURES. LOCATION OF OUTLETS MOUNTED IN BUILT-INS, MILLWORK, AND CABINETRY SHALL BE
<br />VERIFIED. OUTLETS MOUNTED IN KICK OR TOE SPACES SHALL BE MOUNTED HORIZONTALLY. OUTLET
<br />BOXES SHALL BE MOUNTED TO PREVENT DEVICE PLATE FROM OVERLAPPING BACKSPLASH, TRIM, TILE,
<br />ETC. LOCATE SO DEVICE PLATE WILL LAY FLAT AGAINST SURFACE COMPLETELY AROUND THE PERIMETER
<br />OF PLATE.
<br />H. OUTLETS, OTHER THAN THOSE COORDINATED WITH COUNTER TOPS, SHELVES, AND CABINETS,
<br />SHALL BE LOCATED WITH THE CENTER LINE OF OUTLET BOXES THE FOLLOWING DISTANCE ABOVE THE
<br />FINISHED FLOOR, UNLESS OTHERWISE INDICATED:
<br />1. RECEPTACLES, GENERAL: l'-6* AFF
<br />2. TELEPHONE OUTLETS: V-6m AFF
<br />3. SWITCHES, GENERAL: 4'-0" AFF
<br />V. RACEWAYS
<br />A. SHALL BE GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING. E.M.T. SHALL BE
<br />ELECTRO-GALVANIZED. CONDUITS SHALL BE AS MANUFACTURED BY REPUBLIC, PITTSBURGH STANDARD,
<br />WHEATLAND, TRIANGLE, ALLIED, OR YOUNGSTOWN.
<br />B. SHALL BE STANDARD THREADED TYPE, GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING.
<br />THREADLESS AND CLAMP TYPE NOT ACCEPTABLE. SHALL BE AS MANUFACTURED BY RACO, EFCOR, OR
<br />APPLETON.
<br />C. SHALL BE STEEL THREADED COMPRESSION TYPE. ALL COUPLINGS AND CONNECTORS SHALL BE
<br />EFCOR OR RACO. PRESSURE INDENTED TYPE CONNECTORS OR CAST METAL WILL NOT BE APPROVED
<br />FOR ANY LOCATION.
<br />D. CONNECTORS SHALL HAVE PLASTIC INSULATED THROAT INSERTS.
<br />E. THE USE OF METAL CLAD CABLE IS ACCEPTABLE IN LOCATIONS AS ACCEPTED BY THE NEC AND
<br />ALL LOCAL JURISDICTIONAL CODES.
<br />F. STEEL METAL CLAD CABLE, TYPE MC, EMPLOYING CIRCUIT CONDUCTORS #12 SOLID TO #2 AWG,
<br />SOLID OR STRANDED COPPER WITH THHN INSULATION, AN INSULATED GREEN
<br />GROUNDING CONDUCTOR AND GALVANIZED STEEL INTERLOCKED ARMOR CLADDING. THE CABLES SHALL
<br />BE SUITABLE FOR USE IN CONCEALED DRY LOCATIONS AT TEMPERATURES NOT EXCEEDING 90' C ON
<br />AD CIRCUITS UP TO 600 VOLTS IN ACCORDANCE WITH N.E.C., ARTICLE 334. THE CABLE SHALL BE
<br />ONE AND TWO HOUR FIRE RATED PER ANSI/UL 1479 FOR USE CONCEALED IN WALL, CEILING AND
<br />FLOOR ASSEMBLIES.
<br />G. FLEXIBLE METALLIC CONDUIT RACEWAYS MAY BE USED TO CONNECT HVAC UNITS LOCATED IN
<br />INTERIOR MECHANICAL AREAS. MINIMUM SIZE 3/4-.
<br />H. CONDUIT SHALL BE SIZED IN ACCORDANCE WITH THE LATEST NATIONAL ELECTRICAL CODE
<br />EXCEPT THAT NO CONDUIT SHALL BE SMALLER THAN 3/4- UNLESS OTHERWISE NOTED. CONDUIT
<br />SHALL BE SIZED LARGER THAN REQUIRED ABOVE WHEN SO SHOWN ON THE DRAWINGS OR WHEN
<br />REQUIRED BY LOCAL CODE.
<br />1. ANY CONDUIT STUBBED OUT FOR FUTURE SHALL BE CAPPED WITH A PLASTIC CAP AND MARKED
<br />WITH A 2" MINIMUM RED METAL TAG WHICH IDENTIFIES CONDUIT ORIGIN. CONDUITS STUBBED UP
<br />ABOVE GRADE OR ROOF SHALL BE TAGGED ON THE CONDUIT. CONDUIT STUBBED OUT BELOW GRADE
<br />SHALL BE TAGGED ON NEAREST BUILDING WALL, CURB, ETC., DIRECTLY OVER THE CONDUIT ALL EMPTY
<br />CONDUITS SHALL HAVE PULL WIRES.
<br />J. THE USE OF NON-METALUC SHEATHED CABLE (ROMEX) SHALL BE PERMISSIBLE FOR USE WITHIN
<br />RESIDENTIAL UNITS AS ACCEPTED BY THE AUTHORITY HAVING JURISDICTION AND INSTALLED PER THE
<br />MANUFACTURES RECOMMENDATIONS. PRIOR WRITTEN APPROVAL FROM THE AHU IS MANDATORY AND
<br />MUST BE SUBMITTED WITH CONDUCTOR SHOP DRAWINGS.
<br />VI. SCHEDULE 40 RIGID PVC:
<br />A. CONDUIT SHALL BE COMPOSED OF POLYVINYLCHLORIDE (PVC) AND SHALL BE UL RATED TYPE
<br />40 FOR USE WITH 90*C RATED CONDUCTORS. CONDUIT SHALL CONFORM TO NEMA STANDARDS AND
<br />APPUCABLE SECTIONS OF NEC.
<br />B. INSTALLATION OF RIGID NON-METALUC CONDUIT SHALL COMPLY WITH ARTICLE 347 OF THE
<br />NATIONAL ELECTRICAL CODE (NFPA 70) AND THESE SPECIFICATIONS.
<br />C. PROVIDE A CONTINUOUS, INSULATED, GROUNDING CONDUCTOR IN EVERY RIGID, NON-METALUC
<br />RACEWAY EVEN IF NOT SHOWN ON THE DRAWINGS. THE GROUNDING CONDUCTOR SHALL BE
<br />CONNECTED TO GROUND AT EACH END OF THE RACEWAY IN ACCORDANCE WITH ARTICLE 250 OF THE
<br />NATIONAL ELECTRICAL CODE (NFPA 70).
<br />D. WHERE RIGID NON-METALUC CONDUIT TRANSITIONS TO METALLIC CONDUIT, THE LOCATION OF
<br />THE TRANSITION SHALL BE UNDERGROUND.
<br />NO PVC CONDUIT SHALL BE RUN EXPOSED, OR ABOVE GRADE.
<br />VII. WIRE AND CABLE 600 VOLT:
<br />A. CONDUCTORS SHALL HAVE CURRENT CARRYING CAPACITIES AS PER NEC AND WITH 600 VOLT
<br />INSULATION, 112 AVERAGE MINIMUM FOR 20 AMP CIRCUITS. CONDUCTORS SHALL BE COPPER.
<br />B. #12 AND #10 SHALL BE SOLID, TYPE THWN/THHN INSULATION.
<br />C. #8 AND LARGER, AND ANY SIZE TO MOTORS SHALL BE STRANDED TYPE THHN.
<br />D. SHALL BE MADE WITH T & B STA-KON WIRE JOINTS, PT SERIES, COMPLETE WITH INSULATING
<br />CAPS AND INSTALLED WITH WT161 TOOL OR WT2000 TOOL, IDEAL SUPER -NUTS (NOT WIRE IDEAL
<br />WING NUTS, OR BUCHANAN ELEC. PRODUCTS B CAP OR SERIES 2000 PRESSURE CONNECTORS
<br />COMPLETE WITH NYLON SNAP -ON INSULATORS AND INSTALLED WITH C24 PRESSURE TOOL.
<br />E. ALL JOINTS AND SPLICES IN WIRE SHALL BE MADE WITH APPROVED SOLDERLESS CONNECTORS,
<br />AND COVERED SO THAT INSULATION IS OWNER APPROVED EQUAL TO CONDUCTOR INSULATION. SPLICES
<br />SHALL NOT BE PERMITTED IN CONTROL, SECURITY, FIRE ALARM, TELEVISION OR COMMUNICATIONS
<br />SYSTEMS, OR WHERE OTHERWISE NOTED. SPLICING OF WIRE OR CABLES WILL
<br />NOT BE ALLOWED BELOW GRADE, INCLUDING IN BOXES BELOW GRADE.
<br />F. BOTH CONDUCTORS AND CONDUITS SHALL BE CONTINUOUS FROM OUTLET TO OUTLET.
<br />G. IN INSTALLING THE MAIN ELECTRICAL SERVICE, ADDITIONAL SLACK CONDUCTORS SHALL BE
<br />PROVIDED AND TERMINATED AS REQUIRED BY ELECTRIC UTILITY FOR CONNECTION TO THEIR
<br />EQUIPMENT. FIELD COORDINATE WITH UTILITY PRIOR TO INSTALLING CONDUCTORS.
<br />H. IN INSTALLING PARALLEL CONDUCTORS IT IS MANDATORY THAT ALL CONDUCTORS MAKING UP
<br />THE FEEDER BE EXACTLY THE SAME LENGTH, THE SAME SIZE AND THE SAME TYPE OF CONDUCTOR
<br />WITH THE SAME INSULATION. FURTHER, EACH GROUP OF CONDUCTORS MAKING UP A PHASE OR
<br />NEUTRAL MUST BE BONDED AT BOTH ENDS IN AN APPROVED MANNER.
<br />1. CONDUCTOR SIZES INDICATED ON CIRCUIT HOMERUNS OR IN PANELBOARD SCHEDULES SHALL BE
<br />INSTALLED OVER THE ENTIRE LENGTH OF THE CIRCUIT UNLESS NOTED OTHERWISE ON THE DRAWINGS.
<br />J. CONDUCTORS SHALL BE CONTINUOUS AND UNSPUCED WHERE INSTALLED IN CONDUIT. SPLICES
<br />SHALL OCCUR ONLY WITHIN WIRING TROUGHS, WIREWAYS, JUNCTION BOXES, OUTLET BOXES, OR
<br />EQUIPMENT ENCLOSURES WHERE SUFFICIENT ADDITIONAL ROOM IS PROVIDED FOR ALL SPLICES.
<br />K. EACH BRANCH CIRCUIT AND FEEDER CONDUCTOR SHALL BE COLOR CODED. FOR CONDUCTOR
<br />SIZES THRU NO. 6 AWG, THE INSULATION SHALL BE OF THE COLOR AS INDICATED BELOW. COLOR
<br />CODE SHALL BE STRICTLY ADHERED TO. FOR CONDUCTOR SIZES NO. 4 AWG AND LARGER, COLOR
<br />CODED PHASE TAPE MAY BE APPLIED COMPLETELY AROUND THE CONDUCTOR INSULATION WITHIN 8*
<br />OF EACH END OF THE CONDUCTOR AND IN EACH PULL OR JUNCTION BOX OR WHENEVER
<br />CONDUCTORS ARE PHYSICALLY EXPOSED TO VIEW. GROUNDING CONDUCTORS AND GROUNDED
<br />CONDUCTORS SHALL HAVE INSULATION COLOR AS INDICATED FOR SIZES THROUGH #6 AWG.
<br />120/240 V, 1PHASE, 3W
<br />PHASE A, COLOR: BLACK
<br />PHASE B, COLOR: RED
<br />NEUTRAL, COLOR: WHITE
<br />GROUND, COLOR: GREEN
<br />L THE USE OF NON-METALUC SHEATHED CABLE (ROMEX) SHALL PERMISSIBLE FOR USE WITHIN
<br />RESIDENTIAL UNITS AS ACCEPTED BY THE AUTHORITY HAVING JURISDICTION AND INSTALLED PER THE
<br />MANUFACTURES RECOMMENDATIONS. PRIOR WRITTEN APPROVAL FROM THE AHU IS MANDATORY AND
<br />MUST BE SUBMITTED WITH CONDUCTOR SHOP DRAWINGS.
<br />M. PRIOR AUTHORIZATION FROM THE ARCHITECT/ENGINEER IF CONDUCTORS ARE SUBSTITUTED TO
<br />ALUMINUM CONDUCTORS. CONDUCTORS MUST HAVE THE EQUIVALENT OR GREATER AMPACITY VALUE
<br />THAN THAT OF SPECIFIED COPPER, SHALL PHYSICALLY FIT BELOW THE CONNECTION LUG AND SHALL
<br />BE SUBMITTED TO THE ENGINEER FOR APPROVAL. ALL LUGS SHALL BE RATED FOR COPPER AND
<br />ALUMINUM CONDUCTORS. CONDUCTORS SHALL BE INSTALLED UTILIZING "NO -LOX" ANTI -OXIDATION
<br />COMPOUND AND CONDUCTORS SHALL BE DESIGNATED AS "COMPACT ALUMINUM".
<br />V1 1. GROUNDING:
<br />A. THIS SECTION DEALS WITH THE GROUNDING OF SERVICE EQUIPMENT, TRANSFORMERS,
<br />NON -CURRENT CARRYING CONDUCTIVE SURFACES OF EQUIPMENT, METAL BUILDING, STRUCTURES AND
<br />OTHER EQUIPMENT. MAXIMUM RESISTANCE SHALL NOT EXCEED 10 OHMS
<br />B. ALL GROUNDING CONNECTIONS SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL
<br />ELECTRICAL CODE AND ALL LOCAL CODES AND REQUIREMENTS. SUCH CODES SHALL BE CONSIDERED
<br />MINIMUM REQUIREMENTS AND THE INSTALLATION OF THE GROUNDING SYSTEM SHALL INSURE FREEDOM
<br />FROM DANGEROUS SHOCK EXPOSURE AND SHALL PROVIDE A LOW IMPEDANCE GROUND FAULT PATH
<br />TO PERMIT OPERATION OF OVERCURRENT AND GROUND FAULT PROTECTIVE DEVICES.
<br />C. ALL SERVICE AND EQUIPMENT GROUNDING CONDUCTORS, AND BONDING JUMPERS SHALL BE
<br />INSULATED COPPER, TYPE THHN, THWN, OR THW CONDUCTORS (UNLESS NOTED OTHERWISE) AND
<br />SHALL BE SIZED IN ACCORDANCE WITH THE APPLICABLE PORTIONS OF ARTICLES 250 AND 517 OF
<br />THE NATIONAL ELECTRICAL CODE. GROUNDING CONDUCTORS #6 AWG AND SMALLER SHALL HAVE A
<br />GREEN COLOR INSULATION. ALL GROUNDING CONDUCTORS #4 AWG AND LARGER SHALL BE
<br />ADEQUATELY IDENTIFIED WITH A GREEN TRACER AND/OR GREEN COLORED TAPE AT EACH END OF THE
<br />GROUNDING CONDUCTOR AND AT EACH PULLBOX OR OTHER ACCESSIBLE LOCATION.
<br />D. THE MAIN SERVICE GROUNDING ELECTRODE SYSTEM SHALL CONSIST OF THE FOLLOWING ITEMS
<br />BONDED TOGETHER BY THE GROUNDING ELECTRODE CONDUCTORS IN ACCORDANCE WITH NEC ARTICLE
<br />250:
<br />1. THE MAIN UNDERGROUND COLD WATER PIPE, NEC 250
<br />2. METAL FRAME OF BUILDING WHERE AVAILABLE, NEC 250
<br />3. CONCRETE ENCASED ELECTRODE, NEC 250-81(C)
<br />4. LIGHTNING PROTECTION SYSTEM.
<br />E. THE NEUTRAL CONDUCTOR SHALL BE GROUNDED AT THE SERVICE ENTRANCE MAIN DISCONNECT,
<br />AND AT EACH SEPARATELY DERIVED SYSTEM ONLY PER NEC ARTICLE 250.
<br />F. A #4 INSULATED COPPER CONDUCTOR INSTALLED IN 3/4- CONCEALED CONDUIT SHALL BE
<br />CONNECTED FROM THE BUILDING GROUNDING ELECTRODE SYSTEM TO EACH BUILDING FIRE ALARM
<br />CONTROL CABINETS, CCTV SYSTEM CABINETS, EMS CABINETS, RELAY CABINETS, AND SECURITY SYSTEM
<br />CABINETS. TERMINATE ON AN APPROPRIATELY SIZED (8) TERMINAL MULTI -CONDUCTOR CONNECTION
<br />GROUNDING LUG LOCATED WITHIN CABINET OR ON TERMINAL BOARDS.
<br />IX. PANELBOARDS:
<br />A. PANELBOARDS SHALL BE DEAD FRONT TYPE AND SHALL BE IN ACCORDANCE WITH UNDERWRITERS'
<br />LABORATORIES, INC., STANDARD FOR PANELBOARDS AND ENCLOSING CABINETS AND SO LABELED.
<br />B. PANELBOARDS SHALL BE FACTORY ASSEMBLED WITH BRANCH BREAKERS ARRANGED AS SHOWN IN
<br />SCHEDULES. BREAKERS SHALL BE NUMBERED VERTICALLY BEGINNING TOP LEFT. BREAKER NUMBERS SHALL
<br />BE PERMANENTLY ATTACHED TO TRIM. PANEL SHALL BE MINIMUM 20" WIDE, UNLESS SPECIFICALLY NOTED
<br />OTHERWISE.
<br />D. ANY SPECIAL REQUIREMENTS ON THE DRAWINGS OR SCHEDULES, SUCH AS GROUND FAULT
<br />PROTECTION, INCREASED INTERRUPTING CAPACITY, ARC -FAULT CIRCUIT BREAKERS SHUNT TRIP TYPE CIRCUIT
<br />BREAKER, FEED THRU PANELBOARDS, ETC., SHALL SUPERSEDE THESE SPECIFICATIONS, BUT ONLY INSOFAR
<br />AS THAT PARTICULAR REQUIREMENT IS CONCERNED AND AS INDICATED.
<br />E. WIRING IN PANELBOARD GUTTERS SHALL BE PERFORMED IN A NEAT AND WORKMAN LIKE MANNER.
<br />WIRING SHALL BE GROUPED INTO NEAT BUNDLES AND SECURED WITH NYLON TIE WRAPS.
<br />F. PROVIDE TYPE WRITTEN DIRECTORIES FOR EACH PANELBOARD INDICATING THE LOAD SERVED.
<br />G. RESIDENTIAL LOAD CENTERS:
<br />A. PANELS LOCATED WITHIN RESIDENTIAL UNITS ONLY, SHALL BE LOAD CENTERS.
<br />B. MAXIMUM ALLOWABLE PHYSICAL DIMENSIONS: 16 INCHES WIDE BY 3.5 INCHES DEEP PER SECTION.
<br />C. ALL LOAD CENTERS AND PANELBOARDS SHALL USE MOLDED CASE CIRCUIT BREAKERS.
<br />D. COMPLETELY SEALED ENCLOSURE. TOGGLE TYPE OPERATING HANDLE. TRIP AMPERE RATING AND
<br />CIN/OFF INDICATION CLEARLY VISIBLE.
<br />E. THERMAL -MAGNETIC TRIP -FREE, TRIP- INDICATING, QUICK -MAKE, QUICK -BREAK, WITH INVERSE TIME
<br />CHARACTERISTIC. SINGLE -HANDLE AND COMMON TRIPPING ON MULTI -POLE BREAKERS.
<br />F. EXTERNAL HANDLE SHALL BE SUITABLE FOR LOCKING IN THE OFF POSITION.
<br />G. SILVER ALLOY CONTACTS WITH AUXILIARY ARC -QUENCHING DEVICES.
<br />H. BREAKERS FOR LIGHTING CIRCUITS SHALL BE SWD RATED.
<br />1. PROVIDE ARC FAULT CIRCUIT BREAKERS FOR ALL CIRCUIT BREAKERS AS REQUIRED PER NEC
<br />LOCATED IN RESIDENTIAL UNITS.
<br />H. METER CENTERS
<br />A. GANGABLE AND WEATHERPROOF NEMA 3R METERING SHALL BE COMPLETE WITH: ALUMINUM CROSS
<br />BUSSING AND METER STACKS.
<br />B. MINIMUM SHORT CIRCUIT RATING OR INTEGRATED ASSEMBLY SHALL NOT BE LESS THAN 22,000
<br />AMPERES.
<br />C. METER BASES SHALL CONFORM TO U.L. STANDARD 175, AND BE CONFIGURED TO CONFORM TO THE
<br />SERVING UTILITY REQUIREMENTS.
<br />D. RESIDENTIAL UNIT CIRCUIT BREAKERS SHALL BE 2-POLE, WITH AMPERE RATINGS AND SERIES
<br />INTERRUPTING RATINGS TO LIMIT FAULT CURRENTS TO LESS THAN 10,000 AMPERES. PROVIDE PERMANENT
<br />PLASTIC IDENTIFICATION LABEL INDICATING THE UNIT SERVED ON EACH CIRCUIT BREAKER.
<br />E. PHASE SEQUENCED BUSSING SHALL BE USED THROUGHOUT, WITH LOAD BALANCE AS EQUAL AS
<br />POSSIBLE.
<br />X. LIGHTING FIXTURES:
<br />A. LIGHTING FIXTURES SHALL BE FURNISHED AS SHOWN ON DRAWINGS AND IN THE LIGHTING
<br />FIXTURE SCHEDULE. IT SHALL SPECIFICALLY BE THE RESPONSIBILITY OF THE CONTRACTOR TO
<br />VERIFY EXACT TYPE CEILING AND RECESSING DEPTH OF ALL RECESSED FIXTURES AND TO FURNISH THE
<br />MOUNTING TRIMS AND ACCESSORIES OF THE SPECIFIED AND/OR APPROVED FIXTURES FOR THE CEILING TO
<br />BE INSTALLED. LIGHTING FIXTURES SHALL BE PROVIDED WITH JOINER PLATES, END CAPS, RETAINING CUPS,
<br />PLASTER FRAMES, HOUSINGS, AND ALL OTHER ACCESSORIES REQUIRED FOR A COMPLETE INSTALLATION.
<br />B. ALL RXTURES SHALL BE EQUIPPED WITH LAMPS UNLESS OTHERWISE NOTED. LAMPS SHALL BE
<br />INSTALLED NEW, IMMEDIATELY PRIOR TO FINAL INSPECTION, AND SHALL NOT BE USED FOR CONSTRUCTION.
<br />C. FIXTURE CATALOG NUMBER REPRESENTS BASIC LUMINARY SIZE, TYPE, QUALITY AND
<br />CONFIGURATION. ACCESSORIES SHALL BE FURNISHED WITH EACH UNIT AS REQUIRED FOR A
<br />COMPLETE FINISHED INSTALLATION. BASIC ACCESSORIES SHALL INCLUDE, BUT ARE NOT LIMITED
<br />TO, THE FOLLOWING:
<br />1. JOINING PLATES, END CAPS, RETAINING CUPS, DRYWALL FLANGES, ETC.
<br />2. TRIMS FOR RECESSED FIXTURES.
<br />3. FIXTURE STEMS AND CANOPIES FINISHED TO MATCH FIXTURES.
<br />4. SPECIAL MOUNTING BRACKETS, TENONS, SUP FILTERS, CONCRETE BASES, POLES, ANCHOR BOLTS,
<br />JUNCTION BOXES, AND STANCHIONS FOR ALL EXTERIOR LIGHTING FIXTURES. PROVIDE ALL
<br />WEATHERPROOFING FOR ALL LIGHTING FIXTURES TO BE INSTALLED IN EXTERIOR LOCATIONS.
<br />D. STRUCTURAL SUPP09T OF ALL FIXTURES SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
<br />E. THE SYSTEM GROUNDING CONDUCTOR SHALL BE SECURED TO EACH FIXTURE BODY BY MEANS OF A
<br />BONDING SCREW.
<br />F. OWNER WILL HAVE RIGHT TO RELOCATE LIGHTING FIXTURES OR LIGHTING SWITCHES WITHIN 72" OF
<br />LOCATION SHOWN ON FIRST WALK-THROUGH AT NO ADDITIONAL EXPENSE. COORDINATE THE WALK-THROUGH
<br />PRIOR TO THE INSTALLATION OF THE WIRING.
<br />CA# 26308 121270.00
<br />Alk I N G E N U I TY
<br />ENGIN EERS, INC.
<br />Moir "PROA 0 VE ENGINEERING SOLUTIONS"
<br />4798 NEW BROAD ST. SUITE 300 1 ORLANDO, FLORIDA 1407.398.6007
<br />�113111111
<br />Mu u
<br />THIS DOCUMENT AND/OR THE DESIGN
<br />CONCEPTS EXPRESSED HEREIN ARE THE
<br />PROPERTY OF KEESEE ASSOCIATES AND
<br />ALL RIGHTS OF OWNERSHIP, INCLUDING
<br />COPYRIGHT OF INTELLECTUAL PROPERTY,
<br />ARE RESERVED THE REPRODUCTIONS,
<br />COPYING, OR USE OF THIS DOCUMENT
<br />AND/OR THE DESIGN CONCEPT WITHOUT
<br />THE WRITTEN CONSENT OF KEESEE
<br />ASSOCIATES IS STRICTLY PROHIBITED AND
<br />PROTECTED BY UNITED STATES AND
<br />INTERNATIONAL LAW
<br />xo�
<br />M c K
<br />Lu
<br />C/'>
<br />- _3
<br />06
<br />Lu - 'A'
<br />Of
<br />QDD
<br />NAL
<br />Jodu 16 1114 .53M
<br />i6
<br />U)
<br />E
<br />ca
<br />z
<br />a -
<br />Lu M
<br />uj
<br />Z
<br />LL
<br />a W U)
<br />0 z w
<br />N
<br />00 Lu