<br />' GENERAL REQUIREMENTS - DIVISION 26 ELECTRICAL
<br />A. PERFORM ALL WORK IN COMPUANCE WITH THE LATEST ADOPTED EDITION OF THE INTERNATIONAL BUILDING
<br />CODE 2015, NFPA 70 (NEC-2017) AND NFPA 101 (UFE SAFETY CODE), ADA ANSI A117.1. INSTALL AND CONNECT
<br />PER AND THE REGULATIONS OF THE LOCAL UTILITY TELEPHONE, CABLE TELEVISION AND POWER UTIUTY
<br />COMPANIES. OBTAIN AND PAY FOR ANY AND ALL REQUIRED PERMITS, INSPECTIONS, CERTIFICATES OF
<br />INSPECTIONS AND APPROVAL, AND THE LIKE, AND DELIVER SUCH CERTIFICATES TO THE OWNER.
<br />B. THE CONTRACTOR SHALL FURNISH, PERFORM, OR OTHERWISE PROVIDE ALL LABOR (INCLUDING, BUT NOT
<br />UMITED TO, ALL PLANNING, PURCHASING, PAINTING, TRANSPORTING, RIGGING, HOISTING, STORING, INSTAWNG,
<br />TESTING, CHASING, CHANNEUNG, CUTTING, TRENCHING, EXCAVATING AND BACKFILLING), COORDINATION, FIELD
<br />VERIFICATION, EQUIPMENT INSTALLATION, SUPPORT, AND SAFETY, SUPPLIES, AND MATERIALS NECESSARY FOR
<br />THE CORRECT INSTALLATION OF COMPLETE AND FUNCTIONAL ELECTRICAL SYSTEMS (AS DESCRIBED OR
<br />IMPUED BY THESE SPECIFICATIONS AND THE APPLICABLE DRAWINGS).
<br />C. ALL DRAWINGS AND SPECIFICATIONS ON THE PROJECT ARE COMPLEMENTARY, EACH TO ALL OTHER
<br />SETS, AND THEY SHALL BE USED IN COMBINATION FOR THE EXECUTION OF THIS WORK. DIVISION 26 WORK
<br />DRAWINGS, INCLUDING ALL ARCHITECTURAL DRAWINGS, MECHANICAL, PLUMBING
<br />AND FIRE PROTECTION DRAWINGS FOR GENERAL WORK AND EQUIPMENT, AND DIVISION 26 WORK CALLED FOR
<br />UNDER ANY SECTION OF THE PROJECT SPECIFICATIONS, SHALL BE CONSIDERED AS INCLUDED IN THIS WORK
<br />EXCLUDED BY INCLUSION IN SOME OTHER BRANCH OF THE WORK. THIS SHALL INCLUDE
<br />ROUGHING -IN FOR CONNECTIONS AND EQUIPMENT AS CALLED FOR OR INFERRED. THE CONTRACTOR SHALL
<br />CHECK ALL DRAWINGS AND SPECIFICATIONS FOR THE PROJECT AND SHALL BE RESPONSIBLE FOR THE
<br />INSTALLATION OF ALL DIVISION 26 WORK.
<br />D. INGS AND SPECIFICATIONS OF ALL OTHER
<br />TRADES AND DIVISIONS BEFORE INSTALLING ANY OF HIS WORK. HE SHALL IN ALL CASES CONSIDER THE WORK
<br />OF ALL OTHER TRADES, AND SHALL COORDINATE HIS WORK WITH THEM SO THAT THE BEST ARRANGEMENTS
<br />OF ALL EQUIPMENT, PIPING, CONDUIT, DUCTS, ROUGH -IN, ETC., CAN BE OBTAINED.
<br />E. R OUTLETS, SWITCHES, DEVICES, EQUIPMENT, ETC., ARE
<br />RIFIED IN THE FIELD AND CHECKED WITH ARCHITECTURAL
<br />AND ID DRAWINGS. CONTRACTOR SHALL LOCATE ALL DEVICES UP TO 5 FEET IN ANY DIRECTION AS DIRECTED
<br />E. WHERE INSTRUCTIONS OR NOTES ARE INSUFFICIENT TO CONVEY THE INTENT OF
<br />THE DESIGN, CONSULT THE OWNER PRIOR TO BIDDING AND INSTALLATION.
<br />F. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING AND COORDINATING THE LOCATIONS OF DEVICES
<br />TO BE USED AND COORDINATING THE FINAL LOCATIONS OF ELECTRICAL EQUIPMENT WITH MILLWORK, SINKS,
<br />BENCHES, COUNTERS AND SHELVING PRIOR TO BIDDING AND INSTALLATION. ALL DISCREPANCIES SHALL BE
<br />BROUGHT TO THE ATTENTION OF THE OWNER.
<br />G. DIVISION 26 CONTRACTOR SHALL HAVE HAD EXPERIENCE OF AT LEAST THE SAME SIZE AND SCOPE AS
<br />THIS PROJECT, ON AT LEAST TWO OTHER PROJECTS WITHIN THE LAST FIVE YEARS IN ORDER TO BE QUAILIFIED
<br />TO BID THIS PROJECT.
<br />H. CONTRACTOR SHALL AND DOES HEREBY WARRANT ALL MATERIALS AND EQUIPMENT FURNISHED UNDER
<br />THIS SECTION OF THE SPECIFICATIONS TO BE FREE FROM DEFECTS AND TO FUNCTION OR OPERATE
<br />SATISFACTORILY FOR ONE YEAR AFTER FINAL ACCEPTANCE OF THE WORK, AND THAT ANY ITEMS NOT
<br />MEETING THIS REQUIREMENT WILL BE MADE GOOD BY HIM WITHOUT COST TO OWNER, PROVIDED SUCH DEFECTS
<br />OR FAILURES ARE NOT DUE TO ABUSE, NEGLECT, OR LACK OF REASONABLE AND ORDINARY MAINTENANCE.
<br />1. ALL WORK SHALL BE EXECUTED IN A WORKMANSHIP MANNER AND SHALL PRESENT A NEAT
<br />MECHANICAL APPEARANCE UPON COMPLETION. I
<br />J. BALANCE LOAD AS EQUALLY AS PRACTICABLE ON ALL FEEDERS, BRANCH CIRCUITS AND PANEL BUSES.
<br />K. IDE ADEQUATE PROTECTION, WHEREVER WORK IS TO BE PERFORMED IN
<br />FINISHED/OCCUPIED SPACES, TO PREVENT DAMAGE TO ADJACENT AREAS, EQUIPMENT, OR FURNISHINGS; TO
<br />PREVENT ACCIDENTAL INJURY TO BUILDING OCCUPANTS AND THE PUBLIC; TO PREVENT THE SPREADING OF
<br />DUST, DIRT, DEBRIS, AND MOISTURE FROM THE AREA WHERE WORK IS BEING PERFORMED; AND TO PREVENT
<br />DUST, DIRT, DEBRIS, AND MOISTURE FROM GETTING ON OR IN THE BUILDING OCCUPANT'S FURNISHINGS OR
<br />EQUIPMENT.
<br />L. THE CONTRACTOR SHALL REPAIR, AT NO COST TO THE OWNER, ANY DAMAGE DONE BY HIMSELF
<br />OR HIS EMPLOYEES. HE SHALL ALSO BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED TO
<br />PROPERLY INSTALL HIS WORK. THIS SHALL ALSO INCLUDE THE PATCHING OF EXISTING ROADWAYS (PAVED OR
<br />IMPROVED), PARKING AREAS, SIDEWALKS, WALLS, STAIRS, MECHANICAL WORK, CURBS, GUTTERS, ETC., CUT TO
<br />INSTALL WORK PROVIDED BY THE CONTRACTOR. PATCH WORK SHALL COMPLY WITH THE APPUCABLE
<br />SECTIONS OF THESE SPECIFICATIONS AND SHALL MATCH THE EXISTING FINISHES.
<br />M. RK, THE EN11RE WIRING SYSTEM SHALL BE TESTED, AND SHALL BE
<br />SHOWN TO BE IN PROPER WORKING CONDITION IN ACCORDANCE WITH INTENT OF SPECIFICATIONS AND
<br />DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO HAVE ALL SYSTEMS READY FOR
<br />OPERATION AND TO HAVE AN El ECTRICIAN AVAILABLE TO OPERATE SAME IN ACCORDANCE WITH AND UNDER
<br />THE INSPECTION REPRESENTATIVE OF THE ENGINEER. THE CONTRACTOR SHALL BE
<br />AVAILABLE TO ASSIST IN REMOVAL OF PANEL FRONTS, TO PERMIT INSPECTION AS REQUIRED. IN ACCORDANCE
<br />WITH DIVISION 1 AND THE CONDITIONS OF THE CONTRACT, THE CONTRACTOR SHALL PROVIDE AND KEEP UP TO
<br />D SET OF CONSTRUCTION "AS-BUILTS* BLUELINE PRINTS WHICH SHALL BE
<br />CORRECTED DAILY, AND SHALL SHOW EVERY CHANGE FROM THE ORIGINAL CONTRACT DRAWINGS, INCLUDING
<br />ADDENDA AND CHANGE ORDERS IN
<br />ACCORDANCE WITH GENERAL REQUIREMENTS AND SPECIAL CONDITIONS. THIS SET OF PRINTS SHALL BE KEPT
<br />ON THE JOB SITE, AND SHALL BE USED ONLY AS A RECORD SET. THIS SHALL NOT BE CONSTRUED AS
<br />S IN THE LAYOUT WITHOUT DEFINITE INSTRUCTION
<br />IN EACH CASE.
<br />ELECTRICAL SCOPE:
<br />A. FURNISHING AND INSTALLATION OF ELECTRIC UGHTING SYSTEMS, POWER SYSTEMS, AND AUXILIARY
<br />EIN SPECIFIED.
<br />B. CONNECTION OF ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTION, MENTIONED IN THIS DIVISION OR
<br />SHOWN ON DRAWINGS, WHETHER FURNISHED BY DIVISION 26 OR UNDER OTHER DIVISIONS, OR FURNISHED BY
<br />OWNER, INCWDING FIRE PROTECTION AND FIRE SPRINKLER SYSTEMS.
<br />C. FURNISHING AND INSTALLATION OF OUTLET BOXES, CONDUIT RACEWAYS, TERMINAL BOARDS, POWER
<br />OMPLETE TELEPHONE, TELEVISION AND DATA RACEWAY DISTRIBUTION SYSTEM.
<br />RE, AS WELL AS SOFTWARE IS NOT INCWDED.)
<br />D. ULLY RESPONSIBLE FOR CONTACTING THE OFFICES OF ALL LOCAL
<br />AND/OR STATE AUTHORITIES HAVING JURISDICTION OVER THIS PROJECT IN ORDER TO SCHEDULE ALL REQUIRED
<br />INSPECTIONS AND OBTAIN ALL NECESSARY PERMITS, ETC. THE CONTRACTOR SHALL NOTIFY THE
<br />OF ALL SCHEDULED INSPECTIONS AT LEAST TWO WEEKS IN ADVANCE OF THE
<br />SCHEDULED DATE.
<br />E. LACE ANY DEFECTIVE MATERIALS, EQUIPMENT, OR WORKMANSHIP WITHOUT
<br />COST TO THE OWNER WITHIN THE STIPULATED GUARANTEED PERIOD.
<br />F. IT NSIBILITY OF THE DIVISION 26 CONTRACTOR TO HAVE ALL SYSTEMS READY FOR
<br />OPERATION AND TO HAVE AN ELECTRICIAN AVAILABLE FOR ALL INSPECTIONS. THE CONTRACTOR SHALL
<br />PROVIDE PERSONNEL TO ASSIST IN REMOVAL OF PANEL FRONTS, ETC. TO PERMIT INSPECTION AS REQUIRED.
<br />G. SUBMIT TO THE ARCHITECT/ENGINEER PROMPTLY AFTER AWARD OF CONTRACT AND PRIOR TO
<br />PURCHASING, SIX COPIES OF MANUFACTURER'S SHOP DRAWINGS IN ACCORDANCE WITH DIVISION 1, SUBMITTALS
<br />IT ALL SHOP DRAWINGS OF A SPECIFIC ITEM OR SYSTEM SHALL BE MADE IN ONE
<br />SUBMITTAL
<br />AND WITHIN TEN DAYS AFTER AWARD OF CONTRACT.
<br />1. PANELBOARDS 6. DISCONNECT SWITCHES 10. FIRE ALARM
<br />2. LIGHTING FIXTURES 7. CONDUIT
<br />3. 120V SMOKE/CO2 DETECTORS 8. CONDUCTORS
<br />4. WIRING DEVICES 9. IVSS
<br />J. COMPLETED WIRING SYSTEMS SHALL BE FREE FROM SHORT CIRCUITS AND AFTER COMPLETION, PERFORM
<br />TESTS FOR INSULATION RESISTANCE IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL
<br />CODE. ALL WIRING SYSTEMS SHALL BE COMPLETELY AND TOTALLY ISAFED?DURING CONSTRUCTION. ONLY
<br />CAL SYSTEMS.
<br />K. THE ELECTRICAL CIRCUITS, COMPONENTS, AND CONTROLS FOR ALL EQUIPMENT ARE SELECTED AND SIZED,
<br />BASED ON THE EQUIPMENT SPECIFIED. IF SUBSTITUTIONS AND/OR EQUIVALENT EQUIPMENT ARE FURNISHED, IT
<br />IBILITY OF ALL PARTIES CONCERNED, INVOLVED IN, AND FURNISHING THE SUBSTITUTE
<br />AND/OR EQUIVALENT EQUIPMENT TO VERIFY AND COMPARE THE ELECTRICAL CHARACTERISTICS AND
<br />REQUIREMENTS OF THAT FURNISHED TO THAT SPECIFIED AND/OR SHOWN. IF GREATER CAPACITY OR MORE
<br />MATERIALS OR LABOR IS REQUIRED FOR THE ROUGH -IN, CIRCUITRY OR CONNECTIONS THAN FOR THE ITEM
<br />SPECIFIED AND PROVIDED FOR, THEN IT SHALL BE THE RESPONSIBIUTY OF THE PARTIES INVOLVED IN
<br />UTE AND/OR EQUIVALENT ITEMS OF EQUIPMENT TO PROVIDE ALL COMPENSATION FOR
<br />ADDITIONAL CHARGES MADE FOR THE PROPER ROUGH -IN, CIRCUITRY AND CONNECTIONS FOR THE EQUIPMENT
<br />FURNISHED. NO ADDITIONAL CHARGES ABOVE THE BASE BID SHALL BE ALLOWED FOR SUCH REVISIONS.
<br />BEFORE ROUGH -IN OF CIRCUITRY OR CONNECTING TO EQUIPMENT, FURNISHED UNDER THIS DIVISION, ANY OTHER
<br />DIVISION, OR BY THE OWNER, THE CONTRACTOR SHALL VERIFY THE ELECTRICAL CHARACTERISTICS AND
<br />REQUIREMENTS OF THE EQUIPMENT BEING FURNISHED AND FOR THAT SPECIFIED AND SHOWN ON THE
<br />DRAWINGS AND PROVIDE FOR PROPER ROUGH -IN AND CONNECTION.
<br />M. EX UND ELECTRICAL STRUCTURES: CONFORM TO ELEVATIONS AND DIMENSIONS
<br />SHOWN WITHIN A TOLERANCE OF PWS OR MINUS 0.10% PWS A SUFFICIENT DISTANCE TO PERMIT PLACING AND
<br />REMOVAL OF CONCRETE FORMWORK, INSTALLATION OF SERVICES, OTHER CONSTRUCTION, AND FOR
<br />INSPECTION.
<br />N. TRENCHING: EXCAVATE TRENCHES FOR ELECTRICAL INSTALLATIONS AS FOLLOWS:
<br />1. EXCAVATE TRENCHES TO THE UNIFORM WIDTH, SUFFICIENTLY WIDE TO PROVIDE AMPLE
<br />WORKING ROOM AND A MINIMUM OF 6" TO 9* CLEARANCE ON BOTH SIDES OF
<br />RACEWAYS AND EQUIPMENT.
<br />2. EXCAVATE TRENCHES TO DEPTH INDICATED OR REQUIRED.
<br />3. LIMIT THE LENGTH OF OPEN TRENCH TO THAT IN WHICH INSTALLATIONS CAN BE MADE AND THE
<br />TRENCH BACKFILLED WITHIN THE SAME DAY.
<br />4. WHERE ROCK IS ENCOUNTERED, CARRY EXCAVATION BELOW REQUIRED ELEVATION AND
<br />BACKFILL WITH A LAYER OF CRUSHED STONE OR GRAVEL PRIOR TO INSTALLATION OF RACEWAYS
<br />AND EQUIPMENT. PROVIDE A MINIMUM OF 6" OF STONE OR GRAVEL CUSHION BETWEEN ROCK BEARING
<br />SURFACE AND ELECTRICAL INSTALLATIONS.
<br />0. DE ALL INSERTS FOR THE SUPPORT OF DIVISION 26 EQUIPMENT
<br />TO BE PLACED IN CONCRETE OR THROUGH CONCRETE SLABS AS CONSTRUCTION PROGRESSES. HE
<br />SHALL PROVIDE ALL MISCELLANEOUS HANGING AND SUPPORTING HARDWARE. ALL ELECTRICAL WORK
<br />IS TO BE CONCEALED IN OR BUILT INTO GENERAL CONSTRUCTION SHALL BE PLACED AS
<br />CONSTRUCTION PROGRESSES. FAILURE OF THE CONTRACTOR TO COORDINATE WORK WITH OTHER
<br />TRADES AND THE PROJECT CONSTRUCTION PROGRESS SHALL MAKE HIM RESPONSIBLE FOR ALL COST
<br />OF CUTTING AND PATCHING, AS REQUIRED TO INSTALL WORK. NO STRUCTURAL MEMBER, MASONRY
<br />CONSTRUCTION OR
<br />FINISHED WORK SHALL BE CUT OR ALTERED WITHOUT PRIOR WRITTEN APPROVAL BY THE
<br />CONTRACTOR SHALL FIRE RATE ALL PENETRATIONS THROUGH ALL FIRE RATED
<br />SLABS OR WALLS PER THE INTENDED RATING.
<br />P. PLY AND SET INTO PLACE ALL WALL SLEEVES FOR CONDUITS
<br />AND COUNG INSERTS FOR HANGERS IN AREAS OF NEW CONSTRUCTION AS BUILDING CONSTRUCTION
<br />PROGRESSES. INSTALL EQUIPMENT NOTED TO BE CONCEALED IN WALLS BEFORE WALLS ARE
<br />CONSTRUCTED IN ORDER THAT WALLS MAY BE CONSTRUCTED AROUND CONDUITS, ENCLOSURES, ETC.
<br />Q. METAWC MATERIALS SHALL BE PROTECTED AGAINST CORROSION. EQUIPMENT ENCLOSURES
<br />SHALL BE GIVEN RUST -INHIBITING TREATMENT AND STANDARD FINISH BY MANUFACTURER. ALUMINUM
<br />ONTACT WITH EARTH, AND, WHERE CONNECTED TO DISSIMILAR METAL,
<br />SHALL BE PROTECTED BY SUITABLE FITTINGS AND TREATMENT. ALL FERROUS METALS SUCH AS
<br />ANCHORS, BOLTS, BRACES, BOXES, BODIES, CLAMPS, FITTINGS, GUARDS, NUTS, PINS, RODS, SHIMS,
<br />THIMBLES, WASHERS, AND MISCELLANEOUS PARTS, NOT OF STAINLESS STEEL OR NONFERROUS
<br />MATERIALS, SHALL BE
<br />HOT -DIPPED GALVANIZED.
<br />R. ALL CONDUITS STUBBED OUT FOR FUTURE USE SHALL HAVE A PULL WIRE INSTALLED, A
<br />PLASTIC CAP INSTALLED AND BE IDENTIFIED AS TO THE CONDUIT ORIGIN.
<br />S. THE RESPONSIBILITY FOR ANY CUTTING OF CONSTRUCTION WHICH IS REQUIRED FOR THE
<br />INSTALLATION OF DIVISION 16 WORK, SHALL BE BY THE CONTRACTOR. THE CONTRACTOR SHALL
<br />COORDINATE WITH ALL OTHER TRADES AND THE OWNER BEFORE ANY CUTTING AND OBTAIN
<br />HITECT/ENGINEER PRIOR TO ANY CUTTING. ALL PATCHING AND FINISHING
<br />SHALL BE BY THE CONTRACTOR.
<br />T. WHERE OPENINGS OR HOLES ARE CUT IN CONSTRUCTION AND THE CUTTING BREAKS
<br />ELECTRICAL CIRCUITRY OR CONTROL CIRCUITRY CONDUIT AND WIRING, THEN IT SHALL BE THE
<br />RESPONSIBILITY OF THE CONTRACTOR TO REROUTE THE CIRCUITRY CONDUIT AND RMRING AND TO
<br />COMPLETE THE CIRCUITRY AS REQUIRED AND AS APPROVED BY THE ARCHITECT/ENGINEER.
<br />TEMPORARY COMPLETION SHALL BE PROVIDED WHERE NECESSARY BEFORE THE PERMANENT
<br />REROUTING AND COMPLETION WORK IS FINISHED.
<br />U. ANY PENETRATIONS OF FIRE OR SMOKE RATED ASSEMBUES MADE BY THIS CONTRACTOR IN
<br />VERTICAL OR HORIZONTAL CONSTRUCTION SHALL BE SEALED AND PROTECTED BY THIS CONTRACTOR
<br />IN ORDER TO MAINTAIN THE ESTABUSHED FIRE RATING WITH METHODS AS APPROVED BY THE
<br />AUTHORITY HAVING JURISDICTION AND U.L.
<br />A. IDENTIFICATION NAMEPLATES SHALL BE LAMINATED PLASTIC, SECURED TO EQUIPMENT WITH
<br />TWO STAINLESS STEEL SCREWS.
<br />B. EACH PANELBOARD AND METER CENTER SHALL BE EQUIPPED WITH A PERMANENT PLASTIC
<br />IMUM LETTERS, SECURELY FASTENED TO THE DEVICE.
<br />C. EACH INDIVIDUALLY MOUNTED CIRCUIT BREAKER, SWITCH, MOTOR STARTER, RELAY PANEL,
<br />LIGHTING CONTACTOR, TRANSFORMER AND/OR ANY OTHER CONTROL OR PROTECTIVE DEVICE
<br />INCLUDING EQUIPMENT DISCONNECT SWITCHES SHALL BE EQUIPPED WITH A PERMANENT PLASTIC
<br />NAMEPLATE WITH 1/2- MINIMUM LETTERS.
<br />D. PANELBOARDS SHALL HAVE TYPEWRITTEN DIRECTORIES. ALL CIRCUITS TO BE IDEN11FIED BY
<br />DEVICES SERVED AND ROOM NUMBERS (I.E., LIGHTING ROOM 216). HANDWRITTEN DIRECTORIES WILL
<br />NOT BE ALLOWED.
<br />E. EACH JUNCTION BOX CABINET OR WIREWAY LARGER THAN 6" X 6" SHALL BE EQUIPPED WITH A
<br />PERMANENT PLASTIC NAMEPLATE WITH 1/2- MINIMUM LEITERS INDICATING THE SYSTEM ENCLOSED.
<br />F. ALL SYSTEMS JUNCTION BOXES AND CONDUIT SHALL BE COLOR CODED INSIDE AND OUTSIDE OF
<br />THE BOX PRIOR TO THE INSTALLATION OF CONDUCTORS PER THE FOLLOWING:
<br />1. CCTV SYSTEM: VIOLET
<br />2. TELEPHONE DATA SYSTEM: BLUE
<br />G. ENTIRE BOX INSIDE AND OUT , INCLUDING COVER, SHALL BE PAINTED PRIOR TO INSTALUNG
<br />CONDUCTORS.
<br />IV. WIRING DEVICES:
<br />A. SWITCHES SHALL BE 20 AMP COMMERCIAL GRADE 125 VAC. WHITE IN COLOR WITH NYLON
<br />COVER PLATES FOR COMMON AREAS.
<br />B. AMP SPECIFICATION GRADE 125 VAC. WHITE IN COLOR WITH NYLON
<br />COVER PLATES FOR COMMON AREAS.
<br />C. SWITCHES AND OUTLETS FOR HOTEL UNITS SHALL BE RESIDENTIAL UNE SILENT OPERATION
<br />TYPE RATED FOR 20AMPS, 120VOLTS. ALL DEVICES AND COVER PLATES SHALL BE WHITE.
<br />D. WITH GASKETED STAINLESS STEEL KEY
<br />LOCKABLE FUP COVER TYPE COVER PLATES. SURGE SUPPRESSION TYPE OUTLETS IN MDFS AND IDFS
<br />E. RECEPTACLES PROVIDED FOR ATTACHMENT OF CORD AND PLUG EQUIPMENT SHALL BE HEAVY
<br />DUTY, SPECIFICATION GRADE, NON -INTERCHANGEABLE, FLUSH MOUNTED TYPES OF THE PROPER NEMA
<br />CONFIGURATION TO SERVE THE EQUIPMENT. NEMA CONFIGURATIONS SHALL BE VERIFIED PRIOR TO
<br />INSTALLATION OF CIRCUIT CONDUCTORS. PROVIDE ALL FINAL FLEXIBLE. CONDUIT CONNECTIONS, TO
<br />HER, RANGE, MICROWAVES AND HVAC EQUIPMENT.
<br />F. ALL DEVICES SHALL HAVE PROPER PLATES, CARPET FLANGES, TRIMS, RINGS, ESCUTCHEONS,
<br />ETC., AS MANUFACTURED BY SAME MANUFACTURER AS DEVICES. ANY TELEPHONE OR OTHER OUTLET
<br />WHICH IS NOT EQUIPPED WITH A PLATE FURNISHED BY OTHERS SHALL HAVE ONE PROVIDED BY THIS
<br />CONTRACTOR.
<br />G. MOUNTING HEIGHTS ARE APPROXIMATE. THE EXACT LOCATIONS AND MOUNTING HEIGHTS SHALL
<br />BE DETERMINED ON THE JOB AND PER ARCHITECTURAL DRAWINGS AND IT SHALL BE THE
<br />CONTRACTOR'S RESPONSIBIUTY TO COORDINATE WITH ALL TRADES TO INSURE CORRECT
<br />INSTALLATION, I.E., OVER COUNTERS IN OR ABOVE BACK -SPLASHES, IN BLOCK WALLS, TILE, AND
<br />STRUCTION FEATURES. LOCATION OF OUTLETS MOUNTED IN BUILT-INS,
<br />MILLWORK, AND CABINETRY SHALL BE VERIFIED. OUTLETS MOUNTED IN KICK OR TOE SPACES SHALL
<br />BE MOUNTED HORIZONTALLY. OUTLET BOXES SHALL BE MOUNTED TO PREVENT DEVICE PLATE FROM
<br />OVERLAPPING BACKSPLASH, TRIM, TILE, ETC. LOCATE SO DEVICE PLATE WILL LAY FLAT AGAINST
<br />H. OUTLETS, OTHER THAN THOSE COORDINATED WITH COUNTER TOPS, SHELVES, AND CABINETS,
<br />SHALL BE LOCATED WITH THE CENTER LINE OF OUTLET BOXES THE FOLLOWING DISTANCE ABOVE THE
<br />FINISHED FLOOR, UNLESS OTHERWISE INDICATED:
<br />1. RECEPTACLES, GENERAL: V-6" AFF
<br />2. TELEPHONE OUTLETS: V-6* AFF
<br />3. SWITCHES, GENERAL: 4'-O" AFF
<br />V. RAC
<br />A. SHALL BE GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING. E.M.T. SHALL BE
<br />ELECTRO-GALVANIZED. CONDUITS SHALL BE AS MANUFACTURED BY REPUBUC, PITTSBURGH
<br />STANDARD, WHEATLAND, TRIANGLE, ALUED, OR YOUNGSTOWN.
<br />B. SHALL BE STANDARD THREADED TYPE, GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING.
<br />THREADLESS AND CLAMP TYPE NOT ACCEPTABLE. SHALL BE AS MANUFACTURED BY RACO, EFCOR,
<br />OR APPLETON.
<br />C. SHALL BE STEEL THREADED COMPRESSION TYPE. ALL COUPLINGS AND CONNECTORS SHALL BE
<br />EFCOR OR RACO. PRESSURE INDENTED TYPE CONNECTORS OR CAST METAL WILL NOT BE APPROVED
<br />FOR ANY LOCATION.
<br />D. LASTIC INSULATED THROAT INSERTS.
<br />E. THE USE OF METAL CLAD CABLE IS ACCEPTABLE IN LOCATIONS AS ACCEPTED BY THE NEC
<br />AND ALL LOCAL JURISDICTIONAL CODES.
<br />F. STEEL METAL CLAD CABLE, TYPE MC, EMPLOYING CIRCUIT CONDUCTORS #12 SOuD TO #2
<br />AWG, SOLID OR STRANDED COPPER WITH THHN INSULATION, AN INSULATED GREEN
<br />GROUNDING CONDUCTOR AND GALVANIZED STEEL INTERLOCKED ARMOR CLADDING. THE CABLES
<br />SHALL BE SUITABLE FOR USE IN CONCEALED DRY LOCATIONS AT TEMPERATURES NOT EXCEEDING
<br />90' C ON AD CIRCUITS UP TO 600 VOLTS IN ACCORDANCE WITH N.E.C., ARTICLE 334. THE CABLE
<br />R FIRE RATED PER ANSI/UL 1479 FOR USE CONCEALED IN WALL,
<br />COUNG AND FLOOR ASSEMBUES.
<br />G. FLEXIBLE METALUC CONDUIT RACEWAYS MAY BE USED TO CONNECT HVAC UNITS LOCATED IN
<br />INTERIOR MECHANICAL AREAS. MINIMUM SIZE 3/4-.
<br />H. CONDUIT SHALL BE SIZED IN ACCORDANCE WITH THE LATEST NATIONAL ELECTRICAL CODE
<br />IT SHALL BE SMALLER THAN 3/4- UNI ESS OTHERWISE NOTED. CONDUIT
<br />HAN REQUIRED ABOVE WHEN SO SHOWN ON THE DRAWINGS OR WHEN
<br />REQUIRED BY LOCAL CODE.
<br />1. UT FOR FUTURE SHALL BE CAPPED WITH A PLASTIC CAP AND
<br />MARKED WITH A 2" MINIMUM RED METAL TAG WHICH IDENTIFIES CONDUIT ORIGIN. CONDUITS STUBBED
<br />DUIT. CONDUIT STUBBED OUT BELOW
<br />GRADE SHALL BE TAGGED ON NEAREST BUILDING WALL, CURB, ETC., DIRECTLY OVER THE CONDUIT
<br />ALL EMPTY CONDUITS SHALL HAVE PULL WIRES.
<br />A. SCHEDULE 40 RIGID PVC
<br />A. CONDUIT SHALL BE COMPOSED OF POLYVINYLCHLORIDE (PVC) AND SHALL BE UL RATED TYPE
<br />40 FOR USE WITH 9O*C RATED CONDUCTORS. CONDUIT SHALL CONFORM TO NEMA STANDARDS AND
<br />APPUCABLE SECTIONS OF NEC.
<br />B. INSTALLA11ON OF RIGID NON-METALLIC CONDUIT SHALL COMPLY WITH ARTICLE 347 OF THE
<br />NATIONAL ELECTRICAL CODE (NFPA 70) AND THESE SPECIFICATIONS.
<br />C. PROVIDE A CONTINUOUS, INSULATED, GROUNDING CONDUCTOR IN EVERY RIGID, NON-METALLIC
<br />RACEWAY EVEN IF NOT SHOWN ON THE DRAWINGS. THE GROUNDING CONDUCTOR SHALL BE
<br />H END OF THE RACEWAY IN ACCORDANCE WITH ARTICLE 250 OF
<br />THE NATIONAL ELECTRICAL CODE (NFPA 70).
<br />D. WHERE RIGID NON-METALUC CONDUIT TRANSITIONS TO METALLIC CONDUIT, THE LOCATION OF
<br />THE TRANSITION SHALL BE UNDERGROUND.
<br />E RUN EXPOSED, OR ABOVE GRADE.
<br />VII. WIRE AND CABLE 600 VOLT:
<br />A. CONDUCTORS SHALL HAVE CURRENT CARRYING CAPACITIES AS PER NEC AND WITH 600 VOLT
<br />INSULATION, #12 AVERAGE MINIMUM FOR 20 AMP CIRCUITS. CONDUCTORS SHALL BE COPPER.
<br />B. OUD, TYPE THWN/THHN INSULATION.
<br />C. 18 AND LARGER, AND ANY SIZE TO MOTORS SHALL BE STRANDED TYPE THHN.
<br />D. SHALL BE MADE WITH T & B STA-KON WIRE JOINTS, PT SERIES, COMPLETE WITH INSULATING
<br />CAPS AND INSTALLED WITH WT161 TOOL OR WT2OOO TOOL, IDEAL SUPER -NUTS (NOT WIRE IDEAL
<br />WING NUTS, OR BUCHANAN ELEC. PRODUCTS B CAP OR SERIES 2000 PRESSURE CONNECTORS
<br />IT N INSULATORS AND INSTALLED WITH C24 PRESSURE TOOL.
<br />E. ALL JOINTS AND SPLICES IN WIRE SHALL BE MADE WITH APPROVED SOLDERUESS
<br />RED SO THAT INSULATION IS OWNER APPROVED EQUAL TO CONDUCTOR
<br />INSULATION. SPUCES SHALL NOT BE PERMITTED IN CONTROL, SECURITY, FIRE ALARM, TELEVISION OR
<br />COMMUNICA11ONS SYSTEMS, OR WHERE OTHERWISE NOTED. SPUCING OF WIRE OR CABLES WILL
<br />NOT BE ALLOWED BELOW GRADE, INCLUDING IN BOXES BELOW GRADE.
<br />F. DUITS SHALL BE CONTINUOUS FROM OUTLET TO OUTLET.
<br />G. IN INSTALUNG THE MAIN ELECTRICAL SERVICE, ADDITIONAL SLACK CONDUCTORS SHALL BE
<br />PROVIDED AND TERMINATED AS REQUIRED BY ELECTRIC UTILITY FOR CONNECTION TO THEIR
<br />EQUIPMENT. FIELD COORDINATE WITH UTILITY PRIOR TO INSTALUNG CONDUCTORS.
<br />H. IN INSTAILLING PARALLEL CONDUCTORS IT IS MANDATORY THAT ALL CONDUCTORS MAKING UP
<br />SAME LENGTH, THE SAME SIZE AND THE SAME TYPE OF CONDUCTOR
<br />WITH THE SAME INSULATION. FURTHER, EACH GROUP OF CONDUCTORS MAKING UP A PHASE OR
<br />BOTH ENDS IN AN APPROVED MANNER.
<br />1. CONDUCTOR SIZES INDICATED ON CIRCUIT HOMERUNS OR IN PANELBOARD SCHEDULES SHALL
<br />BE INSTALLED OVER THE ENTIRE LENGTH OF THE CIRCUIT UNLESS NOTED OTHERWISE ON THE
<br />DRAWINGS.
<br />J. TINUOUS AND UNSPUCED WHERE INSTALLED IN CONDUIT. SPUCES
<br />SHALL OCCUR ONLY WITHIN WIRING TROUGHS, WIREWAYS, JUNCTION BOXES, OUTLET BOXES, OR
<br />EQUIPMENT ENCLOSURES WHERE SUFFICIENT ADD11IONAL ROOM IS PROVIDED FOR ALL SPUCES.
<br />K.
<br />SIZES THRU NO. 6 AWG, THE INSULATION SHALL BE OF THE COLOR AS INDICATED BELOW. COLOR
<br />SIZES NO. 4 AWG AND LARGER, COLOR
<br />OUND THE CONDUCTOR INSULATION WITHIN 8"
<br />UCTOR AND IN EACH PULL OR JUNCTION BOX OR WHENEVER
<br />CALLY EXPOSED TO VIEW. GROUNDING CONDUCTORS AND GROUNDED
<br />CONDUCTORS SHALL HAVE INSULATION COLOR AS INDICATED FOR SIZES THROUGH #6 AWG.
<br />120/208 V, 3PHASE,4W
<br />PHASE A, COLOR: BLACK
<br />PHASE B, COLOR: RED
<br />PHASE C, COLOR: BLUE
<br />NEUTRAL, COLOR: WHITE
<br />GROUND, COLOR: GREEN
<br />L. PRIOR AUTHORIZATION FROM THE ARCHITECT/ENGINEER IF CONDUCTORS ARE SUBSTITUTED TO
<br />ALUMINUM CONDUCTORS. CONDUCTORS MUST HAVE THE EQUIVALENT OR GREATER AMPACITY VALUE
<br />D COPPER, SHALL PHYSICALLY FIT BELOW THE CONNECTION UJG AND SHALL
<br />BE SUBMITTED TO THE ENGINEER FOR APPROVAL ALL LUGS SHALL BE RATED FOR COPPER AND 1
<br />ALUMINUM CONDUCTORS. CONDUCTORS SHALL BE INSTAU_ED UTIUZING "NO -LOX" ANTI -OXIDATION
<br />D AS "COMPACT ALUMINUM". A
<br />V1 1. GROUNDING:
<br />A. THIS SECTION DEALS WITH THE GROUNDING OF SERVICE EQUIPMENT, TRANSFORMERS,
<br />NON -CURRENT CARRYING CONDUCTIVE SURFACES OF EQUIPMENT, METAL BUILDING, STRUCTURES AND B
<br />OTHER EQUIPMENT. MAXIMUM RESISTANCE SHALL NOT EXCEED 10 OHMS
<br />B. ALL GROUNDING CONNECTIONS SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL C
<br />ELECTRICAL CODE AND ALL LOCAL CODES AND REQUIREMENTS. SUCH CODES SHALL BE CONSIDERED
<br />MINIMUM REQUIREMENTS AND THE INSTALLATION OF THE GROUNDING SYSTEM SHALL INSURE
<br />AND SHALL PROVIDE A LOW IMPEDANCE GROUND D
<br />ION OF OVERCURRENT AND GROUND FAULT PROTECTIVE DEVICES.
<br />C. ALL SERVICE AND EQUIPMENT GROUNDING CONDUCTORS, AND BONDING JUMPERS SHALL BE
<br />INSULATED COPPER, TYPE THHN, THWN, OR THW CONDUCTORS (UNLESS NOTED OTHERWISE) AND
<br />SHALL BE SIZED IN ACCORDANCE WITH THE APPUCABLE PORTIONS OF ARTICLES 250 AND 517 OF
<br />THE NATIONAL ELECTRICAL CODE. GROUNDING CONDUCTORS #6 AWG AND SMALLER SHALL HAVE A
<br />GREEN COLOR INSULATION. ALL GROUNDING CONDUCTORS #4 AWG AND LARGER SHALL BE
<br />ADEQUATELY IDENTIFIED WITH A GREEN TRACER AND/OR GREEN COLORED TAPE AT EACH END OF E
<br />THE GROUNDING CONDUCTOR AND AT EACH PULLBOX OR OTHER ACCESSIBLE LOCATION.
<br />D. THE MAIN SERVICE GROUNDING ELECTRODE SYSTEM SHALL CONSIST OF THE FOLLOWING ITEMS
<br />BONDED TOGETHER BY THE GROUNDING ELECTRODE CONDUCTORS IN ACCORDANCE WITH NEC
<br />ARTICLE 250:
<br />1. COLD WATER PIPE, NEC 250 I
<br />2. METAL FRAME OF BUILDING WHERE AVAILABLE, NEC 250 F
<br />3. ODE, NEC 250-81(C)
<br />E. THE NEUTRAL CONDUCTOR SHALL BE GROUNDED AT THE SERVICE ENTRANCE MAIN
<br />DISCONNECT, AND AT EACH SEPARATELY DERIVED SYSTEM ONLY PER NEC ARTICLE 250.
<br />F. A #4 INSULATED COPPER CONDUCTOR INSTALLED IN 3/4- CONCEALED CONDUIT SHALL BE
<br />UILDING GROUNDING ELECTRODE SYSTEM TO EACH BUILDING FIRE ALARM
<br />CONTROL CABINETS, CCTV SYSTEM CABINETS, EMS CABINETS, RELAY CABINETS, AND SECURITY
<br />SYSTEM CABINETS. TERMINATE ON AN APPROPRIATELY SIZED (8) TERMINAL MULTI -CONDUCTOR
<br />G LUG LOCATED WITHIN CABINET OR ON TERMINAL BOARDS.
<br />IX. PANELBOARDS:
<br />A. PANELBOARDS SHALL BE DEAD FRONT TYPE AND SHALL BE IN ACCORDANCE WITH UNDERWRITERS'
<br />LABORATORIES, INC., STANDARD FOR PANELBOARDS AND ENCLOSING CABINETS AND SO LABELED.
<br />B. PANELBOARDS SHALL BE FACTORY ASSEMBLED WITH BRANCH BREAKERS ARRANGED AS SHOWN IN
<br />SCHEDULES. BREAKERS SHALL BE NUMBERED VERTICALLY BEGINNING TOP LEFT. BREAKER NUMBERS
<br />THED TO TRIM. PANEL SHALL BE MINIMUM 20* WIDE, UNLESS SPECIFICALLY
<br />NOTED OTHERWISE.
<br />D. ANY SPECIAL REQUIREMENTS ON THE DRAWINGS OR SCHEDULES, SUCH AS GROUND FAULT
<br />PROTECTION, INCREASED INTERRUPTING CAPACITY, ARC -FAULT CIRCUIT BREAKERS SHUNT TRIP TYPE
<br />CIRCUIT BREAKER, FEED THRU PANELBOARDS, ETC., SHALL SUPERSEDE THESE SPECIFICATIONS, BUT ONLY
<br />INSOFAR AS THAT PAR11CULAR REQUIREMENT IS CONCERNED AND AS INDICATED.
<br />E. WIRING IN PANELBOARD GUTTERS SHALL BE PERFORMED IN A NEAT AND WORKMAN UKE MANNER.
<br />WIRING SHALL BE GROUPED INTO NEAT BUNDLES AND SECURED WITH NYLON 11E WRAPS.
<br />F, PROVIDE TYPE WRITTEN DIRECTORIES FOR EACH PANELBOARD INDICATING THE LOAD SERVED.
<br />G. METERING
<br />A. GANGABLE AND WEATHERPROOF NEMA 3R METERING SHALL BE COMPLETE WITH: ALUMINUM CROSS
<br />BUSSING AND METER STACKS.
<br />B. MINIMUM SHORT CIRCUIT RATING OR INTEGRATED ASSEMBLY SHALL NOT BE LESS THAN 22,000
<br />C. METER BASES SHALL CONFORM TO U.L. STANDARD 175, AND BE CONFIGURED TO CONFORM TO THE
<br />SERVING UTILITY REQUIREMENTS.
<br />E. PHASE SEQUENCED BUSSING SHALL BE USED THROUGHOUT, WITH LOAD BALANCE AS EQUAL AS
<br />POSSIBLE. ALL SINGLE PHASE CIRCUITS SHALL HAVE A DEDICATED NEUTRAL PER NEC.
<br />X. LIGHTING FIXTURES:
<br />A. UGHTING FIXTURES SHALL BE FURNISHED AS SHOWN ON DRAWINGS AND IN THE LIGHTING
<br />HALL SPECIFICALLY BE THE RESPONSIBILITY OF THE CONTRACTOR TO
<br />VERIFY EXACT TYPE COUNG AND RECESSING DEPTH OF ALL RECESSED FIXTURES AND TO FURNISH THE
<br />MOUNTING TRIMS AND ACCESSORIES OF THE SPECIFIED AND/OR APPROVED FIXTURES FOR THE COUNG
<br />TO BE INSTALLED. UGHTING FIXTURES SHALL BE PROVIDED WITH JOINER PLATES, END CAPS, RETAINING
<br />CUPS, PLASTER FRAMES, HOUSINGS, AND ALL OTHER ACCESSORIES REQUIRED FOR A COMPLETE
<br />INSTALLATION.
<br />B. ALL FIXTURES SHALL BE EQUIPPED WITH LAMPS UNLESS OTHERWISE NOTED. LAMPS SHALL BE
<br />INSTALLED NEW, IMMEDIATELY PRIOR TO FINAL INSPECTION, AND SHALL NOT BE USED FOR
<br />CONSTRUCTION.
<br />C. FIXTURE CATALOG NUMBER REPRESENTS BASIC LUMINARY SIZE, TYPE, QUAUTY AND
<br />CONFIGURATION. ACCESSORIES SHALL BE FURNISHED WITH EACH UNIT As REQUIRED FOR A
<br />COMPLETE FINISHED INSTALLATION. BASIC ACCESSORIES SHALL INCLUDE, BUT ARE NOT UMITED
<br />TO, THE FOLLOWING:
<br />1. JOINING PLATES, END CAPS, RETAINING CLIPS, DRYWALL FLANGES, ETC.
<br />2. TRIMS FOR RECESSED FIXTURES.
<br />3. FIXTURE STEMS AND CANOPIES FINISHED TO MATCH FIXTURES.
<br />4. SPECIAL MOUNTING BRACKETS, TENONS, SUP FILTERS, CONCRETE BASES, POLES, ANCHOR BOLTS,
<br />JUNCTION BOXES, AND STANCHIONS FOR ALL EXTERIOR UGHTING FIXTURES. PROVIDE ALL
<br />WEATHERPROOFING FOR ALL LIGHTING FIXTURES TO BE INSTALLED IN EXTERIOR LOCATIONS.
<br />D. STRUCTURAL SUPPORT OF ALL FIXTURES SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
<br />E. RED TO EACH FIXTURE BODY BY MEANS OF A
<br />BONDING SCREW.
<br />F. OWNER WILL HAVE RIGHT TO RELOCATE LIGHTING FIXTURES OR UGHTING SWITCHES WITHIN 72" OF
<br />COORDINATE THE
<br />WALK-THROUGH PRIOR TO THE INSTALLATION OF THE WIRING.
<br />3EC11ON 283000 DIGITAL ADDRESSABLE FIRE -ALARM SYSTEM
<br />T1 - GENERAL
<br />DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND
<br />SUPPLEMENTARY CONDITIONS, DIVISION 1, AND DIVISION 26 SPECIFICATION SECTIONS, APPLY
<br />TO THIS SECTION.
<br />SUMMARY
<br />THIS SECTION INCLUDES AUTOMATIC NETWORKED FIRE ALARM SYSTEMS, INCLUDING FIRE
<br />ALARM CONTROL PANEL, REMOTE ANNUNCIATOR, DOOR HOLD OPEN DEVICES, MANUAL PULL
<br />DETECTORS, FIRE ALARM HORNS, VISUAL SIGNAL EQUIPMENT,
<br />OKE DAMPER CONNECTIONS, AND SURGE PROTECTION DEVICES.
<br />COORDINATE ALL WIRING AND DEVICE INTERFACES WITH OWNER'S REPRESENTATIVE.
<br />THE FIRE ALARM SYSTEM SHALL MEET THE LATEST ADOPTED EDITION OF ALL LOCAL,
<br />STATE OF FLORIDA AND ALL LOCAL CITY AND COUNTY CODE AMENDMENTS, NFPA 72, UL
<br />864-9THEDITION ALL FEDERAL "ADAG" REQUIREMENTS AND THE 2020 FLORIDA BUILDING
<br />CODE
<br />ALL DEVICES Mi" BE TM` N COLOR WITH 'INHW LETrHM
<br />.3 DEFINITIONS
<br />. ADDRESSABLE: COMBINED HARDWARE AND SOFTWARE SYSTEMS ASSOCIATED WITH THE
<br />EL AND FIELD DEVICES WHICH WILL PERMIT IDENTIFICATION OR
<br />CONTROL OF AN INDIVIDUAL DEVICE (INITIATING OR SIGNAL/CONTROL CIRCUIT).
<br />. ALARM -INITIATING DEVICE: A MANUAL STATION, SMOKE DETECTOR OR HEAT DETECTOR.
<br />. ALARM SIGNAL: SIGNIFIES A STATE OF EMERGENCY REQUIRING IMMEDIATE ACTION.
<br />PERTAINS TO SIGNALS SUCH AS THE OPERATION OF A MANUAL STATION AND THE
<br />OPERATION OF A SPRINKLER SYSTEM FLOW SWITCH.
<br />. STYLE "4" INITIATING CIRCUITS: CIRCUITS ARRANGED AND ELECTRICALLY SUPERVISED SO A
<br />SINGLE BREAK OR SINGLE GROUND FAULT CONDITION WILL BE INDICATED BY A TROUBLE
<br />NTROL PANEL (FACP) AND THE CIRCUIT WILL CONTINUE TO
<br />BE CAPABLE OF OPERATION FOR ITS INTENDED SERVICE IN THE FAULTED CONDITION NO
<br />T GROUND FAULT CONDITION OCCURS. (2-WIRE CLASS B
<br />CIRCUIT).
<br />. STYLE 'Y" INDICATING CIRCUIT: CIRCUITS ELECTRICALLY SUPERVISED SUCH THAT A SINGLE
<br />BREAK OR A SINGLE GROUND FAULT CONDITION WILL BE INDICATED BY A TROUBLE SIGNAL
<br />AT THE FACP AND THE CIRCUIT WILL CONTINUE TO BE CAPABLE OF OPERATION FOR ITS
<br />INTENDED SERVICE IN THE FAULTED CONDITION NO MATTER WHERE THE BREAK OR GROUND
<br />RS. (2-WIRE CLASS B).
<br />. MULTIPLEX SYSTEM: ONE USING SIGNALING METHOD CHARACTERIZED BY THE
<br />UENTIAL TRANSMISSION, OR BOTH, AND THE RECEPTION OF
<br />MUL11PLE SIGNALS IN A COMMUNICATION CHANNEL, INCLUDING MEANS FOR POSITIVELY
<br />IDENTIFYING EACH SIGNAL
<br />1.5 SYSTEM DESCRIPTION
<br />A. GENERAL: COMPLETE, ZONED, NONCODED, ADDRESSABLE, MICROPROCESSOR BASED FIRE
<br />DEFECTION AND ALARM SYSTEM WITH MANUAL AND AUTOMATIC ALARM INITIATION DEVICES
<br />LOCATED OUTDOORS SHALL BE SPECIFICALLY DESIGNED FOR EXTERIOR SERVICE. PROVIDE
<br />BATTERY BACK-UP BASED UPON TOTAL LOAD PER NFPA 72. ALARM SHALL ACHIEVE A
<br />MINIMUM OF 80 DB THROUGHOUT OCCUPIABLE SPACES AND MEET ADA REQUIREMENTS.
<br />B. SIGNAL TRANSMISSION: MULTIPLEX SIGNAL TRANSMISSION DEDICATED TO FIRE ALARM
<br />SERVICE ONLY.
<br />C. ALARM INDICATION: BY TRANSMITTING EMERGENCY ALARMS, SOUNDING INTERNAL AND
<br />WEATHERPROOF HORNS, AND ILLUMINATION OF ADA STROBES.
<br />D. ALLOW FOR LOADING AND EDITING SPECIAL INSTRUCTIONS
<br />ES AS REQUIRED. THE SYSTEM SHALL BE CAPABLE OF ON -SITE
<br />PROGRAMMING TO ACCOMMODATE SYSTEM EXPANSION AND FACILITATE CHANGES IN
<br />OPERATION. ALL SOFTWARE OPERATIONS SHALL BE STORED IN A NON-VOLATILE
<br />PROGRAMMABLE MEMORY WITHIN THE FIRE ALARM CONTROL UNIT. LOSS OF PRIMARY AND
<br />SECONDARY POWER SHALL NOT ERASE THE INSTRUCTIONS STORED IN MEMORY.
<br />E. THE SYSTEM SHALL HAVE THE CAPABIUTY OF LOADING SOFTWARE OPERATIONS FROM A
<br />SINGLE NODE TO ALL OTHER NODES ON THE NETWORK.
<br />F. RESIDENT SOFTWARE SHALL ALLOW FOR FULL CONFIGURATION OF INITIATING CIRCUITS SO
<br />THAT ADDITIONAL HARDWARE SHALL NOT BE NECESSARY TO ACCOMMODATE FUTURE
<br />CHANGES. FOR EXAMPLE, MONITORING OF NORMALLY OPEN CONTACT DEVICES TO
<br />MONITORING OF NORMALLY CLOSED CONTACT DEVICES, OR FROM SENSING OF NORMALLY
<br />OPEN CONTACT DEVICES TO SENSING A COMBINATION CIRCUIT AND BEING ABLE TO
<br />DIFFERENTIATE BETWEEN THE TWO.
<br />S. LL ALLOW FOR CONFIGURATION OF NOTIFICATION APPUANCE AND
<br />CONTROL CIRCUITS SO THAT ADDITIONAL HARDWARE SHALL NOT BE NECESSARY TO
<br />ACCOMMODATE CHANGES. FOR EXAMPLE, CHANGING A NON -CODED NOTIFICATION APPLICANT
<br />CIRCUIT TO A CODED CIRCUIT; OR FROM A SLOW MARCH TIME (20 BPM) TO FAST MARCH
<br />TIME (120 BPM) CODING.
<br />H. THE SYSTEM SHALL HAVE THE CAPABIUTY OF RECALUNG ALARMS AND TROUBLE
<br />CONDITIONS IN CHRONOLOGICAL ORDER FOR THE PURPOSE OF RECREATING AN EVENT
<br />HISTORY.
<br />1. SYSTEM CONNECTIONS AND CONDUIT AND WIRING FOR ALARM INDICATING CIRCUITS: STYLE
<br />"Y" WIRING.
<br />J. SYSTEM CONNECTIONS AND CONDUIT AND WIRING FOR ALARM -INITIATION CIRCUITS: STYLE *4
<br />WIRING.
<br />1. TRANSMISSION TO REMOTE CENTRAL STATION: PROVIDE WIRING AND EQUIPMENT TO
<br />AUTOMATICALLY ROUTE AN ALARM, SUPERVISORY, AND TROUBLE SIGNALS TO THE
<br />UNIVERSAL STUDIOS CENTRAL STATION SERVICE TRANSMITTER LOCATED WITHIN MAIN
<br />FIRE ALARM CONTROL PANEL USING USTED AND APPROVED DIALING EQUIPMENT.
<br />PROVIDE ALL NECESSARY AND REQUIRED DIALER EQUIPMENT, WIRING AND CONNECTIONS
<br />BY THIS CONTRACTOR.
<br />2. GENERAL ALARM: A SYSTEM GENERAL ALARM INCLUDES:
<br />a. INDICATING THE GENERAL ALARM CONDITION AT THE FACP AND THE INTEGRAL ANNUNCIATOR.
<br />b. IDENTIFYING THE DEVICE THAT IS THE SOURCE OF THE ALARM AT THE FACP, AND ANNUNCIATOR.
<br />C. INITIATING AUDIBLE AND VISIBLE ALARM SIGNALS THROUGHOUT THE BUILDING.
<br />d. STOPPING HVAC SUPPLY AND RETURN FANS.
<br />e. INITIATING TRANSMISSION OF ALARM SIGNAL TO REMOTE CENTRAL REPORTING STATION.
<br />f. OORS.
<br />g. CLOSE FIRE/SMOKE DAMPERS.
<br />h. CLOSE GAS SOLENOID VALVES AS REQUIRED
<br />3. MANUAL STATION ALARM OPERATION INITIATES A GENERAL ALARM.
<br />4. WATER -FLOW ALARM SWITCH OPERATION: INITIATES A GENERAL ALARM.
<br />5. SMOKE OR HEAT DEFECTION INITIATES A GENERAL ALARM.
<br />2.9 WIRE/CABLE
<br />A. LINE -VOLTAGE: UNE VOLTAGE CONDUCTORS SHALL BE SOUD COPPER CONDUCTORS WITH
<br />600 V_RATED INSULATION. #10 GAUGE, MINIMUM ADJUSTED FOR LARGER GAUGE LONG RUNS.
<br />B. INITIATION CIRCUITS (LOOP): INITIATION LOOP CONDUCTORS SHALL BE WEST PENN #D991 FOR
<br />3000'-O* IN LENGTH AND LESS. WEST PENN #D995 SHALL BE USED FOR CIRCUITS OVER
<br />3000'-O" IN LENGTH. BELOW GRADE, WET OR DAMP LOCATION INSTALLED CABLE, INCLUDING
<br />CABLE INSTALLED ON THE TOP OF EXTERIOR WALKWAYS, SHALL BE WEST PENN AQUASEAL
<br />MULTI -CONDUCTOR FLOODED CABLE (14 GAUGE), UNLESS NOTED OTHERWISE, AND SHALL BE
<br />INSTALLED IN CONDUIT.
<br />C. SIGNAL CIRCUITS: SIGNAL CIRCUITS SHALL BE #12 AWG THWN 19 STRAND COPPER.
<br />D. I PPER.
<br />E. COLOR CODE: STRICTLY ADHERED jg-
<br />POSMVE NEWIVE
<br />AUDIO/VISUAL* 112 AWG (THWN�. +ORANGE -WHITE
<br />E RELAY CIRCUIT 14 AWG (TH'WN +PINK -BLACK
<br />114 AWG (THWN +GRAY -BLACK
<br />GAS SHUTOFF 14 AWG (�THWN) +GRAY -BLACK
<br />24 VDC /1 4 AWG HWN) +RED -BLACK
<br />AUTOMATIC (NON ADDRESSABLE) # 1 4 AWG (THWN) +YELLOW -BROWN
<br />MANUAL (NON ADDRESSABLE) #14 AWG (THWN) +BLUE -PURPLE
<br />F. ALL WIRE SHALL BE INSTALLED IN NEW CONCEALED CONDUIT, MINIMUM 1.5" CONDUIT.
<br />3.7 DEMONSTRATION
<br />A. PROVIDE THE SERVICES OF A FACTORY -AUTHORIZED SERVICE REPRESENTATIVE TO
<br />TRAIN OWNER'S MAINTENANCE PERSONNEL AS SPECIFIED
<br />BELOW.
<br />1. TRAIN OWNER'S MAINTENANCE PERSONNEL IN THE LOCATION OF DEVICES, BOXES,
<br />EDULES INVOLVED IN OPERATING, TROUBLESHOOTING, SERVICING,
<br />AND PREVENTIVE MAINTAINING OF THE SYSTEM. PROVIDE A MINIMUM OF 4 HOURS'
<br />TRAINING. TRAINING SHALL INCLUDE A COMPLETE PROJECT WALK DOWN WITH OWNER'S
<br />AUTHORIZED REPRESENTATIVE TO IDENTIFY DEVICE LOCATIONS, JUNCTION BOX
<br />PPRESSION MODULE LOCATIONS.
<br />2. SCHEDULE TRAINING WITH THE OWNER AT LEAST SEVEN WORKING DAYS IN ADVANCE.
<br />END OF SECTION 283000
<br />LO �
<br />(D ;: I
<br />I Z c') N- I
<br />o !�
<br />,`� �, - M
<br />,
<br />,�,,' k� ,�, 0
<br />� 1�� �, z (D 11 -
<br />�; �� ;,�.� (14 ilk �1
<br />�
<br />�� , , .
<br />,�i, M I
<br />I z * .
<br />�
<br />,4,�io, j
<br />.W
<br />,�� ",
<br />"
<br />�.� 1 ,' < ____
<br />.1 __
<br />�, ` , I _j -
<br />.� 11 ��. ` - "I ,
<br />�:, �
<br />.1 � !I� "� 12- ` �
<br />,I 4" - � ; ;
<br />I
<br />, .
<br />. , �� , - �_' , I �
<br />11 I , -
<br />, , �� t, 11� z I
<br />, , ,
<br />11 1� I
<br />"L , , ,�
<br />I", !A ,�, (D
<br />I
<br />1,,�, ,�'. - =1
<br />, ;
<br />�!, � ',-,, "") (1)
<br />�� ,
<br />��, __ Lu
<br />11, .� �,,� -
<br />k��,��Ui � 1q Q
<br />,,,��: L- I
<br />11 , -
<br />.1 ,-� �i, ., �
<br />,� � �, -_ Uj
<br />El", � -, 1'1� - I
<br />lk�:''_ 11 ,,;,� I I 0�
<br />]� I I'. (D
<br />, _�� " , 0
<br />"" -, 11
<br />_ - Z)
<br />,�, ,�;, , � "
<br />,',�, - ." I I �_ 91
<br />,�,"�.'k,"w'--a , �,,� .5
<br />0 (n
<br />7- -1.1-11 1_1 Uj 6-
<br />�: 1 ,
<br />"11���, , C �f)
<br />"''.- , (O
<br />� ��_,�;�:�,�� � ", I I-- E M r- M
<br />�,,. � - .
<br />� . I I � 0 .:� C-, n
<br />I- � � . , -r 0 Fz -, "
<br />I., �� " . I (1) -C LL C)
<br />, . V ,!�
<br />-, ... 1� I,,;,. � � , _;.,..: " I �
<br />, , 11�.. I" I 'Al (.) (1) E 00
<br />11
<br />, , , , � L,
<br />, " , -6
<br />. � . . . . . I -0 01 (1) ::3 00
<br />I
<br />...... ..... � I
<br />LLLLLL ..... (1) 0 C r--
<br />10� a) U) _T 0
<br />_�c �= 'IT
<br /><0 00
<br />0) Lj) CD 3
<br />I " 2E -
<br />P, I h I. I
<br />i
<br />4;L 0 -L ?'�_
<br />I.
<br />t
<br />, )
<br />E �L_v , Y .- , p t -
<br />THIS DOCUMENf AND/OR THE DESIGN CONCEPTS
<br />EXPRLSSED HEREIN ARE THE PROPERTY OF
<br />KEESEE ASSOCIATES AND ALL RIGH1 S OF
<br />OWNERSHIP, INCLUDING COPYRIGHT OF
<br />IN] ELLEC1 UAL PROPERTY, ARE RESERVED. I HE
<br />REPRODUCTIONS, COPYING, OR USE OF THIS
<br />DOCUMENT AND/OR THE DESIGN CONCEPT
<br />WITHOUT THE WRITTEN CONSENT OF KEESEE
<br />ASSOCIATES IS STRICTLY PROHIBITED AND
<br />PROTECTED BY UNITED STATES AND
<br />INTERNATIONAI I AW
<br />C�3
<br />LO
<br />C14
<br />� t I co
<br />�, �. t ; I � % I � : If ;1�
<br />- I LO
<br />, I " I'� �_ I i, � .1 I
<br />, � 1 , .
<br />11 11-1 � � 1 6
<br />- ,
<br />_j _': - e , ,", I I � I � I � I 2i Z
<br />< �, ` "', , ',,- � , �; " , O_ W
<br />W1 - I- IL �_ Q_
<br />U) -, � 11 I I I 1 4?
<br />1 ,� SI
<br />11 I
<br />�__ I , rt,
<br />C16 -
<br />Luil___� ��_ � '. , I I -; 11 0�
<br />0�--,- -,. , , " , z-, I-_
<br />D:,� , , - I , I I dz I , - W
<br />F-- , , 0_
<br />_ _ , , / 1: 1 114
<br />-, : v I r.)
<br />< ,-' �, , - " L I 1 -4 &
<br />z . I I I ,
<br />� I L 6 N
<br />0 , - � , �, I I I - C:
<br />" I I
<br />�5 I . -1 , I a Q)
<br />" , 11 , 11 �e
<br />I r I I - 0
<br />� �11 I 1. 11, 11 �"L 2i
<br />� : , I
<br />� ,,;� � � � � � , 0,� '' _0
<br />,
<br />-)
<br /><
<br />Z)
<br />(3
<br />U)
<br />0
<br />�
<br />>
<br /><
<br /><
<br />(D
<br />-
<br />U)
<br />_j
<br />_j <
<br />-
<br />_r 0
<br />0� of
<br />>- 0
<br />T_ _j
<br />0- LL
<br />-
<br />N
<br />PERMIT 01/26/2022
<br />REV. REV. REV.
<br />NO. DESC. I DATE
<br />REVISIONS
<br />Project Number:
<br />21-7431
<br />Date: 01/26/2022 1-30:00 PM
<br />Issue Date,
<br />01/26/22
<br />Reviewed By:
<br />KR
<br />Drawn By:
<br />im
<br />Scale:
<br />As indicated
<br />Sheet Name:
<br />ELECTRICAL
<br />SPECIFICATIONS
<br />CA# 26308 I21570.00
<br />Adlk I N G E N U I T Y Sheet No.
<br />ENGINEEMIN c- E002
<br />141F "PROACTIVE ENGINEERING SOLUTIONS"
<br />4798 NEW BROAD ST. SUITE 300 1 ORLANDO, FLORIDA 1 407,398.6007
<br />__ - I—- I- , - : -'-- ----7 '17 --:---- ' -.1 I— --,-,,..--,. . -i I -
<br />
|