_L_ - _L L - __ - , ___ -1 I __ <br />-111 " i i � I - - 1, - - - I ,___L__L � 11 I <br />' GENERAL REQUIREMENTS - DIVISION 26 ELECTRICAL <br />A. PERFORM ALL WORK IN COMPUANCE WITH THE LATEST ADOPTED EDITION OF THE INTERNATIONAL BUILDING <br />CODE 2015, NFPA 70 (NEC-2017) AND NFPA 101 (UFE SAFETY CODE), ADA ANSI A117.1. INSTALL AND CONNECT <br />PER AND THE REGULATIONS OF THE LOCAL UTILITY TELEPHONE, CABLE TELEVISION AND POWER UTIUTY <br />COMPANIES. OBTAIN AND PAY FOR ANY AND ALL REQUIRED PERMITS, INSPECTIONS, CERTIFICATES OF <br />INSPECTIONS AND APPROVAL, AND THE LIKE, AND DELIVER SUCH CERTIFICATES TO THE OWNER. <br />B. THE CONTRACTOR SHALL FURNISH, PERFORM, OR OTHERWISE PROVIDE ALL LABOR (INCLUDING, BUT NOT <br />UMITED TO, ALL PLANNING, PURCHASING, PAINTING, TRANSPORTING, RIGGING, HOISTING, STORING, INSTAWNG, <br />TESTING, CHASING, CHANNEUNG, CUTTING, TRENCHING, EXCAVATING AND BACKFILLING), COORDINATION, FIELD <br />VERIFICATION, EQUIPMENT INSTALLATION, SUPPORT, AND SAFETY, SUPPLIES, AND MATERIALS NECESSARY FOR <br />THE CORRECT INSTALLATION OF COMPLETE AND FUNCTIONAL ELECTRICAL SYSTEMS (AS DESCRIBED OR <br />IMPUED BY THESE SPECIFICATIONS AND THE APPLICABLE DRAWINGS). <br />C. ALL DRAWINGS AND SPECIFICATIONS ON THE PROJECT ARE COMPLEMENTARY, EACH TO ALL OTHER <br />SETS, AND THEY SHALL BE USED IN COMBINATION FOR THE EXECUTION OF THIS WORK. DIVISION 26 WORK <br />DRAWINGS, INCLUDING ALL ARCHITECTURAL DRAWINGS, MECHANICAL, PLUMBING <br />AND FIRE PROTECTION DRAWINGS FOR GENERAL WORK AND EQUIPMENT, AND DIVISION 26 WORK CALLED FOR <br />UNDER ANY SECTION OF THE PROJECT SPECIFICATIONS, SHALL BE CONSIDERED AS INCLUDED IN THIS WORK <br />EXCLUDED BY INCLUSION IN SOME OTHER BRANCH OF THE WORK. THIS SHALL INCLUDE <br />ROUGHING -IN FOR CONNECTIONS AND EQUIPMENT AS CALLED FOR OR INFERRED. THE CONTRACTOR SHALL <br />CHECK ALL DRAWINGS AND SPECIFICATIONS FOR THE PROJECT AND SHALL BE RESPONSIBLE FOR THE <br />INSTALLATION OF ALL DIVISION 26 WORK. <br />D. INGS AND SPECIFICATIONS OF ALL OTHER <br />TRADES AND DIVISIONS BEFORE INSTALLING ANY OF HIS WORK. HE SHALL IN ALL CASES CONSIDER THE WORK <br />OF ALL OTHER TRADES, AND SHALL COORDINATE HIS WORK WITH THEM SO THAT THE BEST ARRANGEMENTS <br />OF ALL EQUIPMENT, PIPING, CONDUIT, DUCTS, ROUGH -IN, ETC., CAN BE OBTAINED. <br />E. R OUTLETS, SWITCHES, DEVICES, EQUIPMENT, ETC., ARE <br />RIFIED IN THE FIELD AND CHECKED WITH ARCHITECTURAL <br />AND ID DRAWINGS. CONTRACTOR SHALL LOCATE ALL DEVICES UP TO 5 FEET IN ANY DIRECTION AS DIRECTED <br />E. WHERE INSTRUCTIONS OR NOTES ARE INSUFFICIENT TO CONVEY THE INTENT OF <br />THE DESIGN, CONSULT THE OWNER PRIOR TO BIDDING AND INSTALLATION. <br />F. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING AND COORDINATING THE LOCATIONS OF DEVICES <br />TO BE USED AND COORDINATING THE FINAL LOCATIONS OF ELECTRICAL EQUIPMENT WITH MILLWORK, SINKS, <br />BENCHES, COUNTERS AND SHELVING PRIOR TO BIDDING AND INSTALLATION. ALL DISCREPANCIES SHALL BE <br />BROUGHT TO THE ATTENTION OF THE OWNER. <br />G. DIVISION 26 CONTRACTOR SHALL HAVE HAD EXPERIENCE OF AT LEAST THE SAME SIZE AND SCOPE AS <br />THIS PROJECT, ON AT LEAST TWO OTHER PROJECTS WITHIN THE LAST FIVE YEARS IN ORDER TO BE QUAILIFIED <br />TO BID THIS PROJECT. <br />H. CONTRACTOR SHALL AND DOES HEREBY WARRANT ALL MATERIALS AND EQUIPMENT FURNISHED UNDER <br />THIS SECTION OF THE SPECIFICATIONS TO BE FREE FROM DEFECTS AND TO FUNCTION OR OPERATE <br />SATISFACTORILY FOR ONE YEAR AFTER FINAL ACCEPTANCE OF THE WORK, AND THAT ANY ITEMS NOT <br />MEETING THIS REQUIREMENT WILL BE MADE GOOD BY HIM WITHOUT COST TO OWNER, PROVIDED SUCH DEFECTS <br />OR FAILURES ARE NOT DUE TO ABUSE, NEGLECT, OR LACK OF REASONABLE AND ORDINARY MAINTENANCE. <br />1. ALL WORK SHALL BE EXECUTED IN A WORKMANSHIP MANNER AND SHALL PRESENT A NEAT <br />MECHANICAL APPEARANCE UPON COMPLETION. I <br />J. BALANCE LOAD AS EQUALLY AS PRACTICABLE ON ALL FEEDERS, BRANCH CIRCUITS AND PANEL BUSES. <br />K. IDE ADEQUATE PROTECTION, WHEREVER WORK IS TO BE PERFORMED IN <br />FINISHED/OCCUPIED SPACES, TO PREVENT DAMAGE TO ADJACENT AREAS, EQUIPMENT, OR FURNISHINGS; TO <br />PREVENT ACCIDENTAL INJURY TO BUILDING OCCUPANTS AND THE PUBLIC; TO PREVENT THE SPREADING OF <br />DUST, DIRT, DEBRIS, AND MOISTURE FROM THE AREA WHERE WORK IS BEING PERFORMED; AND TO PREVENT <br />DUST, DIRT, DEBRIS, AND MOISTURE FROM GETTING ON OR IN THE BUILDING OCCUPANT'S FURNISHINGS OR <br />EQUIPMENT. <br />L. THE CONTRACTOR SHALL REPAIR, AT NO COST TO THE OWNER, ANY DAMAGE DONE BY HIMSELF <br />OR HIS EMPLOYEES. HE SHALL ALSO BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED TO <br />PROPERLY INSTALL HIS WORK. THIS SHALL ALSO INCLUDE THE PATCHING OF EXISTING ROADWAYS (PAVED OR <br />IMPROVED), PARKING AREAS, SIDEWALKS, WALLS, STAIRS, MECHANICAL WORK, CURBS, GUTTERS, ETC., CUT TO <br />INSTALL WORK PROVIDED BY THE CONTRACTOR. PATCH WORK SHALL COMPLY WITH THE APPUCABLE <br />SECTIONS OF THESE SPECIFICATIONS AND SHALL MATCH THE EXISTING FINISHES. <br />M. RK, THE EN11RE WIRING SYSTEM SHALL BE TESTED, AND SHALL BE <br />SHOWN TO BE IN PROPER WORKING CONDITION IN ACCORDANCE WITH INTENT OF SPECIFICATIONS AND <br />DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO HAVE ALL SYSTEMS READY FOR <br />OPERATION AND TO HAVE AN El ECTRICIAN AVAILABLE TO OPERATE SAME IN ACCORDANCE WITH AND UNDER <br />THE INSPECTION REPRESENTATIVE OF THE ENGINEER. THE CONTRACTOR SHALL BE <br />AVAILABLE TO ASSIST IN REMOVAL OF PANEL FRONTS, TO PERMIT INSPECTION AS REQUIRED. IN ACCORDANCE <br />WITH DIVISION 1 AND THE CONDITIONS OF THE CONTRACT, THE CONTRACTOR SHALL PROVIDE AND KEEP UP TO <br />D SET OF CONSTRUCTION "AS-BUILTS* BLUELINE PRINTS WHICH SHALL BE <br />CORRECTED DAILY, AND SHALL SHOW EVERY CHANGE FROM THE ORIGINAL CONTRACT DRAWINGS, INCLUDING <br />ADDENDA AND CHANGE ORDERS IN <br />ACCORDANCE WITH GENERAL REQUIREMENTS AND SPECIAL CONDITIONS. THIS SET OF PRINTS SHALL BE KEPT <br />ON THE JOB SITE, AND SHALL BE USED ONLY AS A RECORD SET. THIS SHALL NOT BE CONSTRUED AS <br />S IN THE LAYOUT WITHOUT DEFINITE INSTRUCTION <br />IN EACH CASE. <br />ELECTRICAL SCOPE: <br />A. FURNISHING AND INSTALLATION OF ELECTRIC UGHTING SYSTEMS, POWER SYSTEMS, AND AUXILIARY <br />EIN SPECIFIED. <br />B. CONNECTION OF ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTION, MENTIONED IN THIS DIVISION OR <br />SHOWN ON DRAWINGS, WHETHER FURNISHED BY DIVISION 26 OR UNDER OTHER DIVISIONS, OR FURNISHED BY <br />OWNER, INCWDING FIRE PROTECTION AND FIRE SPRINKLER SYSTEMS. <br />C. FURNISHING AND INSTALLATION OF OUTLET BOXES, CONDUIT RACEWAYS, TERMINAL BOARDS, POWER <br />OMPLETE TELEPHONE, TELEVISION AND DATA RACEWAY DISTRIBUTION SYSTEM. <br />RE, AS WELL AS SOFTWARE IS NOT INCWDED.) <br />D. ULLY RESPONSIBLE FOR CONTACTING THE OFFICES OF ALL LOCAL <br />AND/OR STATE AUTHORITIES HAVING JURISDICTION OVER THIS PROJECT IN ORDER TO SCHEDULE ALL REQUIRED <br />INSPECTIONS AND OBTAIN ALL NECESSARY PERMITS, ETC. THE CONTRACTOR SHALL NOTIFY THE <br />OF ALL SCHEDULED INSPECTIONS AT LEAST TWO WEEKS IN ADVANCE OF THE <br />SCHEDULED DATE. <br />E. LACE ANY DEFECTIVE MATERIALS, EQUIPMENT, OR WORKMANSHIP WITHOUT <br />COST TO THE OWNER WITHIN THE STIPULATED GUARANTEED PERIOD. <br />F. IT NSIBILITY OF THE DIVISION 26 CONTRACTOR TO HAVE ALL SYSTEMS READY FOR <br />OPERATION AND TO HAVE AN ELECTRICIAN AVAILABLE FOR ALL INSPECTIONS. THE CONTRACTOR SHALL <br />PROVIDE PERSONNEL TO ASSIST IN REMOVAL OF PANEL FRONTS, ETC. TO PERMIT INSPECTION AS REQUIRED. <br />G. SUBMIT TO THE ARCHITECT/ENGINEER PROMPTLY AFTER AWARD OF CONTRACT AND PRIOR TO <br />PURCHASING, SIX COPIES OF MANUFACTURER'S SHOP DRAWINGS IN ACCORDANCE WITH DIVISION 1, SUBMITTALS <br />IT ALL SHOP DRAWINGS OF A SPECIFIC ITEM OR SYSTEM SHALL BE MADE IN ONE <br />SUBMITTAL <br />AND WITHIN TEN DAYS AFTER AWARD OF CONTRACT. <br />1. PANELBOARDS 6. DISCONNECT SWITCHES 10. FIRE ALARM <br />2. LIGHTING FIXTURES 7. CONDUIT <br />3. 120V SMOKE/CO2 DETECTORS 8. CONDUCTORS <br />4. WIRING DEVICES 9. IVSS <br />J. COMPLETED WIRING SYSTEMS SHALL BE FREE FROM SHORT CIRCUITS AND AFTER COMPLETION, PERFORM <br />TESTS FOR INSULATION RESISTANCE IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL <br />CODE. ALL WIRING SYSTEMS SHALL BE COMPLETELY AND TOTALLY ISAFED?DURING CONSTRUCTION. ONLY <br />CAL SYSTEMS. <br />K. THE ELECTRICAL CIRCUITS, COMPONENTS, AND CONTROLS FOR ALL EQUIPMENT ARE SELECTED AND SIZED, <br />BASED ON THE EQUIPMENT SPECIFIED. IF SUBSTITUTIONS AND/OR EQUIVALENT EQUIPMENT ARE FURNISHED, IT <br />IBILITY OF ALL PARTIES CONCERNED, INVOLVED IN, AND FURNISHING THE SUBSTITUTE <br />AND/OR EQUIVALENT EQUIPMENT TO VERIFY AND COMPARE THE ELECTRICAL CHARACTERISTICS AND <br />REQUIREMENTS OF THAT FURNISHED TO THAT SPECIFIED AND/OR SHOWN. IF GREATER CAPACITY OR MORE <br />MATERIALS OR LABOR IS REQUIRED FOR THE ROUGH -IN, CIRCUITRY OR CONNECTIONS THAN FOR THE ITEM <br />SPECIFIED AND PROVIDED FOR, THEN IT SHALL BE THE RESPONSIBIUTY OF THE PARTIES INVOLVED IN <br />UTE AND/OR EQUIVALENT ITEMS OF EQUIPMENT TO PROVIDE ALL COMPENSATION FOR <br />ADDITIONAL CHARGES MADE FOR THE PROPER ROUGH -IN, CIRCUITRY AND CONNECTIONS FOR THE EQUIPMENT <br />FURNISHED. NO ADDITIONAL CHARGES ABOVE THE BASE BID SHALL BE ALLOWED FOR SUCH REVISIONS. <br />BEFORE ROUGH -IN OF CIRCUITRY OR CONNECTING TO EQUIPMENT, FURNISHED UNDER THIS DIVISION, ANY OTHER <br />DIVISION, OR BY THE OWNER, THE CONTRACTOR SHALL VERIFY THE ELECTRICAL CHARACTERISTICS AND <br />REQUIREMENTS OF THE EQUIPMENT BEING FURNISHED AND FOR THAT SPECIFIED AND SHOWN ON THE <br />DRAWINGS AND PROVIDE FOR PROPER ROUGH -IN AND CONNECTION. <br />M. EX UND ELECTRICAL STRUCTURES: CONFORM TO ELEVATIONS AND DIMENSIONS <br />SHOWN WITHIN A TOLERANCE OF PWS OR MINUS 0.10% PWS A SUFFICIENT DISTANCE TO PERMIT PLACING AND <br />REMOVAL OF CONCRETE FORMWORK, INSTALLATION OF SERVICES, OTHER CONSTRUCTION, AND FOR <br />INSPECTION. <br />N. TRENCHING: EXCAVATE TRENCHES FOR ELECTRICAL INSTALLATIONS AS FOLLOWS: <br />1. EXCAVATE TRENCHES TO THE UNIFORM WIDTH, SUFFICIENTLY WIDE TO PROVIDE AMPLE <br />WORKING ROOM AND A MINIMUM OF 6" TO 9* CLEARANCE ON BOTH SIDES OF <br />RACEWAYS AND EQUIPMENT. <br />2. EXCAVATE TRENCHES TO DEPTH INDICATED OR REQUIRED. <br />3. LIMIT THE LENGTH OF OPEN TRENCH TO THAT IN WHICH INSTALLATIONS CAN BE MADE AND THE <br />TRENCH BACKFILLED WITHIN THE SAME DAY. <br />4. WHERE ROCK IS ENCOUNTERED, CARRY EXCAVATION BELOW REQUIRED ELEVATION AND <br />BACKFILL WITH A LAYER OF CRUSHED STONE OR GRAVEL PRIOR TO INSTALLATION OF RACEWAYS <br />AND EQUIPMENT. PROVIDE A MINIMUM OF 6" OF STONE OR GRAVEL CUSHION BETWEEN ROCK BEARING <br />SURFACE AND ELECTRICAL INSTALLATIONS. <br />0. DE ALL INSERTS FOR THE SUPPORT OF DIVISION 26 EQUIPMENT <br />TO BE PLACED IN CONCRETE OR THROUGH CONCRETE SLABS AS CONSTRUCTION PROGRESSES. HE <br />SHALL PROVIDE ALL MISCELLANEOUS HANGING AND SUPPORTING HARDWARE. ALL ELECTRICAL WORK <br />IS TO BE CONCEALED IN OR BUILT INTO GENERAL CONSTRUCTION SHALL BE PLACED AS <br />CONSTRUCTION PROGRESSES. FAILURE OF THE CONTRACTOR TO COORDINATE WORK WITH OTHER <br />TRADES AND THE PROJECT CONSTRUCTION PROGRESS SHALL MAKE HIM RESPONSIBLE FOR ALL COST <br />OF CUTTING AND PATCHING, AS REQUIRED TO INSTALL WORK. NO STRUCTURAL MEMBER, MASONRY <br />CONSTRUCTION OR <br />FINISHED WORK SHALL BE CUT OR ALTERED WITHOUT PRIOR WRITTEN APPROVAL BY THE <br />CONTRACTOR SHALL FIRE RATE ALL PENETRATIONS THROUGH ALL FIRE RATED <br />SLABS OR WALLS PER THE INTENDED RATING. <br />P. PLY AND SET INTO PLACE ALL WALL SLEEVES FOR CONDUITS <br />AND COUNG INSERTS FOR HANGERS IN AREAS OF NEW CONSTRUCTION AS BUILDING CONSTRUCTION <br />PROGRESSES. INSTALL EQUIPMENT NOTED TO BE CONCEALED IN WALLS BEFORE WALLS ARE <br />CONSTRUCTED IN ORDER THAT WALLS MAY BE CONSTRUCTED AROUND CONDUITS, ENCLOSURES, ETC. <br />Q. METAWC MATERIALS SHALL BE PROTECTED AGAINST CORROSION. EQUIPMENT ENCLOSURES <br />SHALL BE GIVEN RUST -INHIBITING TREATMENT AND STANDARD FINISH BY MANUFACTURER. ALUMINUM <br />ONTACT WITH EARTH, AND, WHERE CONNECTED TO DISSIMILAR METAL, <br />SHALL BE PROTECTED BY SUITABLE FITTINGS AND TREATMENT. ALL FERROUS METALS SUCH AS <br />ANCHORS, BOLTS, BRACES, BOXES, BODIES, CLAMPS, FITTINGS, GUARDS, NUTS, PINS, RODS, SHIMS, <br />THIMBLES, WASHERS, AND MISCELLANEOUS PARTS, NOT OF STAINLESS STEEL OR NONFERROUS <br />MATERIALS, SHALL BE <br />HOT -DIPPED GALVANIZED. <br />R. ALL CONDUITS STUBBED OUT FOR FUTURE USE SHALL HAVE A PULL WIRE INSTALLED, A <br />PLASTIC CAP INSTALLED AND BE IDENTIFIED AS TO THE CONDUIT ORIGIN. <br />S. THE RESPONSIBILITY FOR ANY CUTTING OF CONSTRUCTION WHICH IS REQUIRED FOR THE <br />INSTALLATION OF DIVISION 16 WORK, SHALL BE BY THE CONTRACTOR. THE CONTRACTOR SHALL <br />COORDINATE WITH ALL OTHER TRADES AND THE OWNER BEFORE ANY CUTTING AND OBTAIN <br />HITECT/ENGINEER PRIOR TO ANY CUTTING. ALL PATCHING AND FINISHING <br />SHALL BE BY THE CONTRACTOR. <br />T. WHERE OPENINGS OR HOLES ARE CUT IN CONSTRUCTION AND THE CUTTING BREAKS <br />ELECTRICAL CIRCUITRY OR CONTROL CIRCUITRY CONDUIT AND WIRING, THEN IT SHALL BE THE <br />RESPONSIBILITY OF THE CONTRACTOR TO REROUTE THE CIRCUITRY CONDUIT AND RMRING AND TO <br />COMPLETE THE CIRCUITRY AS REQUIRED AND AS APPROVED BY THE ARCHITECT/ENGINEER. <br />TEMPORARY COMPLETION SHALL BE PROVIDED WHERE NECESSARY BEFORE THE PERMANENT <br />REROUTING AND COMPLETION WORK IS FINISHED. <br />U. ANY PENETRATIONS OF FIRE OR SMOKE RATED ASSEMBUES MADE BY THIS CONTRACTOR IN <br />VERTICAL OR HORIZONTAL CONSTRUCTION SHALL BE SEALED AND PROTECTED BY THIS CONTRACTOR <br />IN ORDER TO MAINTAIN THE ESTABUSHED FIRE RATING WITH METHODS AS APPROVED BY THE <br />AUTHORITY HAVING JURISDICTION AND U.L. <br />A. IDENTIFICATION NAMEPLATES SHALL BE LAMINATED PLASTIC, SECURED TO EQUIPMENT WITH <br />TWO STAINLESS STEEL SCREWS. <br />B. EACH PANELBOARD AND METER CENTER SHALL BE EQUIPPED WITH A PERMANENT PLASTIC <br />IMUM LETTERS, SECURELY FASTENED TO THE DEVICE. <br />C. EACH INDIVIDUALLY MOUNTED CIRCUIT BREAKER, SWITCH, MOTOR STARTER, RELAY PANEL, <br />LIGHTING CONTACTOR, TRANSFORMER AND/OR ANY OTHER CONTROL OR PROTECTIVE DEVICE <br />INCLUDING EQUIPMENT DISCONNECT SWITCHES SHALL BE EQUIPPED WITH A PERMANENT PLASTIC <br />NAMEPLATE WITH 1/2- MINIMUM LETTERS. <br />D. PANELBOARDS SHALL HAVE TYPEWRITTEN DIRECTORIES. ALL CIRCUITS TO BE IDEN11FIED BY <br />DEVICES SERVED AND ROOM NUMBERS (I.E., LIGHTING ROOM 216). HANDWRITTEN DIRECTORIES WILL <br />NOT BE ALLOWED. <br />E. EACH JUNCTION BOX CABINET OR WIREWAY LARGER THAN 6" X 6" SHALL BE EQUIPPED WITH A <br />PERMANENT PLASTIC NAMEPLATE WITH 1/2- MINIMUM LEITERS INDICATING THE SYSTEM ENCLOSED. <br />F. ALL SYSTEMS JUNCTION BOXES AND CONDUIT SHALL BE COLOR CODED INSIDE AND OUTSIDE OF <br />THE BOX PRIOR TO THE INSTALLATION OF CONDUCTORS PER THE FOLLOWING: <br />1. CCTV SYSTEM: VIOLET <br />2. TELEPHONE DATA SYSTEM: BLUE <br />G. ENTIRE BOX INSIDE AND OUT , INCLUDING COVER, SHALL BE PAINTED PRIOR TO INSTALUNG <br />CONDUCTORS. <br />IV. WIRING DEVICES: <br />A. SWITCHES SHALL BE 20 AMP COMMERCIAL GRADE 125 VAC. WHITE IN COLOR WITH NYLON <br />COVER PLATES FOR COMMON AREAS. <br />B. AMP SPECIFICATION GRADE 125 VAC. WHITE IN COLOR WITH NYLON <br />COVER PLATES FOR COMMON AREAS. <br />C. SWITCHES AND OUTLETS FOR HOTEL UNITS SHALL BE RESIDENTIAL UNE SILENT OPERATION <br />TYPE RATED FOR 20AMPS, 120VOLTS. ALL DEVICES AND COVER PLATES SHALL BE WHITE. <br />D. WITH GASKETED STAINLESS STEEL KEY <br />LOCKABLE FUP COVER TYPE COVER PLATES. SURGE SUPPRESSION TYPE OUTLETS IN MDFS AND IDFS <br />E. RECEPTACLES PROVIDED FOR ATTACHMENT OF CORD AND PLUG EQUIPMENT SHALL BE HEAVY <br />DUTY, SPECIFICATION GRADE, NON -INTERCHANGEABLE, FLUSH MOUNTED TYPES OF THE PROPER NEMA <br />CONFIGURATION TO SERVE THE EQUIPMENT. NEMA CONFIGURATIONS SHALL BE VERIFIED PRIOR TO <br />INSTALLATION OF CIRCUIT CONDUCTORS. PROVIDE ALL FINAL FLEXIBLE. CONDUIT CONNECTIONS, TO <br />HER, RANGE, MICROWAVES AND HVAC EQUIPMENT. <br />F. ALL DEVICES SHALL HAVE PROPER PLATES, CARPET FLANGES, TRIMS, RINGS, ESCUTCHEONS, <br />ETC., AS MANUFACTURED BY SAME MANUFACTURER AS DEVICES. ANY TELEPHONE OR OTHER OUTLET <br />WHICH IS NOT EQUIPPED WITH A PLATE FURNISHED BY OTHERS SHALL HAVE ONE PROVIDED BY THIS <br />CONTRACTOR. <br />G. MOUNTING HEIGHTS ARE APPROXIMATE. THE EXACT LOCATIONS AND MOUNTING HEIGHTS SHALL <br />BE DETERMINED ON THE JOB AND PER ARCHITECTURAL DRAWINGS AND IT SHALL BE THE <br />CONTRACTOR'S RESPONSIBIUTY TO COORDINATE WITH ALL TRADES TO INSURE CORRECT <br />INSTALLATION, I.E., OVER COUNTERS IN OR ABOVE BACK -SPLASHES, IN BLOCK WALLS, TILE, AND <br />STRUCTION FEATURES. LOCATION OF OUTLETS MOUNTED IN BUILT-INS, <br />MILLWORK, AND CABINETRY SHALL BE VERIFIED. OUTLETS MOUNTED IN KICK OR TOE SPACES SHALL <br />BE MOUNTED HORIZONTALLY. OUTLET BOXES SHALL BE MOUNTED TO PREVENT DEVICE PLATE FROM <br />OVERLAPPING BACKSPLASH, TRIM, TILE, ETC. LOCATE SO DEVICE PLATE WILL LAY FLAT AGAINST <br />H. OUTLETS, OTHER THAN THOSE COORDINATED WITH COUNTER TOPS, SHELVES, AND CABINETS, <br />SHALL BE LOCATED WITH THE CENTER LINE OF OUTLET BOXES THE FOLLOWING DISTANCE ABOVE THE <br />FINISHED FLOOR, UNLESS OTHERWISE INDICATED: <br />1. RECEPTACLES, GENERAL: V-6" AFF <br />2. TELEPHONE OUTLETS: V-6* AFF <br />3. SWITCHES, GENERAL: 4'-O" AFF <br />V. RAC <br />A. SHALL BE GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING. E.M.T. SHALL BE <br />ELECTRO-GALVANIZED. CONDUITS SHALL BE AS MANUFACTURED BY REPUBUC, PITTSBURGH <br />STANDARD, WHEATLAND, TRIANGLE, ALUED, OR YOUNGSTOWN. <br />B. SHALL BE STANDARD THREADED TYPE, GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING. <br />THREADLESS AND CLAMP TYPE NOT ACCEPTABLE. SHALL BE AS MANUFACTURED BY RACO, EFCOR, <br />OR APPLETON. <br />C. SHALL BE STEEL THREADED COMPRESSION TYPE. ALL COUPLINGS AND CONNECTORS SHALL BE <br />EFCOR OR RACO. PRESSURE INDENTED TYPE CONNECTORS OR CAST METAL WILL NOT BE APPROVED <br />FOR ANY LOCATION. <br />D. LASTIC INSULATED THROAT INSERTS. <br />E. THE USE OF METAL CLAD CABLE IS ACCEPTABLE IN LOCATIONS AS ACCEPTED BY THE NEC <br />AND ALL LOCAL JURISDICTIONAL CODES. <br />F. STEEL METAL CLAD CABLE, TYPE MC, EMPLOYING CIRCUIT CONDUCTORS #12 SOuD TO #2 <br />AWG, SOLID OR STRANDED COPPER WITH THHN INSULATION, AN INSULATED GREEN <br />GROUNDING CONDUCTOR AND GALVANIZED STEEL INTERLOCKED ARMOR CLADDING. THE CABLES <br />SHALL BE SUITABLE FOR USE IN CONCEALED DRY LOCATIONS AT TEMPERATURES NOT EXCEEDING <br />90' C ON AD CIRCUITS UP TO 600 VOLTS IN ACCORDANCE WITH N.E.C., ARTICLE 334. THE CABLE <br />R FIRE RATED PER ANSI/UL 1479 FOR USE CONCEALED IN WALL, <br />COUNG AND FLOOR ASSEMBUES. <br />G. FLEXIBLE METALUC CONDUIT RACEWAYS MAY BE USED TO CONNECT HVAC UNITS LOCATED IN <br />INTERIOR MECHANICAL AREAS. MINIMUM SIZE 3/4-. <br />H. CONDUIT SHALL BE SIZED IN ACCORDANCE WITH THE LATEST NATIONAL ELECTRICAL CODE <br />IT SHALL BE SMALLER THAN 3/4- UNI ESS OTHERWISE NOTED. CONDUIT <br />HAN REQUIRED ABOVE WHEN SO SHOWN ON THE DRAWINGS OR WHEN <br />REQUIRED BY LOCAL CODE. <br />1. UT FOR FUTURE SHALL BE CAPPED WITH A PLASTIC CAP AND <br />MARKED WITH A 2" MINIMUM RED METAL TAG WHICH IDENTIFIES CONDUIT ORIGIN. CONDUITS STUBBED <br />DUIT. CONDUIT STUBBED OUT BELOW <br />GRADE SHALL BE TAGGED ON NEAREST BUILDING WALL, CURB, ETC., DIRECTLY OVER THE CONDUIT <br />ALL EMPTY CONDUITS SHALL HAVE PULL WIRES. <br />A. SCHEDULE 40 RIGID PVC <br />A. CONDUIT SHALL BE COMPOSED OF POLYVINYLCHLORIDE (PVC) AND SHALL BE UL RATED TYPE <br />40 FOR USE WITH 9O*C RATED CONDUCTORS. CONDUIT SHALL CONFORM TO NEMA STANDARDS AND <br />APPUCABLE SECTIONS OF NEC. <br />B. INSTALLA11ON OF RIGID NON-METALLIC CONDUIT SHALL COMPLY WITH ARTICLE 347 OF THE <br />NATIONAL ELECTRICAL CODE (NFPA 70) AND THESE SPECIFICATIONS. <br />C. PROVIDE A CONTINUOUS, INSULATED, GROUNDING CONDUCTOR IN EVERY RIGID, NON-METALLIC <br />RACEWAY EVEN IF NOT SHOWN ON THE DRAWINGS. THE GROUNDING CONDUCTOR SHALL BE <br />H END OF THE RACEWAY IN ACCORDANCE WITH ARTICLE 250 OF <br />THE NATIONAL ELECTRICAL CODE (NFPA 70). <br />D. WHERE RIGID NON-METALUC CONDUIT TRANSITIONS TO METALLIC CONDUIT, THE LOCATION OF <br />THE TRANSITION SHALL BE UNDERGROUND. <br />E RUN EXPOSED, OR ABOVE GRADE. <br />VII. WIRE AND CABLE 600 VOLT: <br />A. CONDUCTORS SHALL HAVE CURRENT CARRYING CAPACITIES AS PER NEC AND WITH 600 VOLT <br />INSULATION, #12 AVERAGE MINIMUM FOR 20 AMP CIRCUITS. CONDUCTORS SHALL BE COPPER. <br />B. OUD, TYPE THWN/THHN INSULATION. <br />C. 18 AND LARGER, AND ANY SIZE TO MOTORS SHALL BE STRANDED TYPE THHN. <br />D. SHALL BE MADE WITH T & B STA-KON WIRE JOINTS, PT SERIES, COMPLETE WITH INSULATING <br />CAPS AND INSTALLED WITH WT161 TOOL OR WT2OOO TOOL, IDEAL SUPER -NUTS (NOT WIRE IDEAL <br />WING NUTS, OR BUCHANAN ELEC. PRODUCTS B CAP OR SERIES 2000 PRESSURE CONNECTORS <br />IT N INSULATORS AND INSTALLED WITH C24 PRESSURE TOOL. <br />E. ALL JOINTS AND SPLICES IN WIRE SHALL BE MADE WITH APPROVED SOLDERUESS <br />RED SO THAT INSULATION IS OWNER APPROVED EQUAL TO CONDUCTOR <br />INSULATION. SPUCES SHALL NOT BE PERMITTED IN CONTROL, SECURITY, FIRE ALARM, TELEVISION OR <br />COMMUNICA11ONS SYSTEMS, OR WHERE OTHERWISE NOTED. SPUCING OF WIRE OR CABLES WILL <br />NOT BE ALLOWED BELOW GRADE, INCLUDING IN BOXES BELOW GRADE. <br />F. DUITS SHALL BE CONTINUOUS FROM OUTLET TO OUTLET. <br />G. IN INSTALUNG THE MAIN ELECTRICAL SERVICE, ADDITIONAL SLACK CONDUCTORS SHALL BE <br />PROVIDED AND TERMINATED AS REQUIRED BY ELECTRIC UTILITY FOR CONNECTION TO THEIR <br />EQUIPMENT. FIELD COORDINATE WITH UTILITY PRIOR TO INSTALUNG CONDUCTORS. <br />H. IN INSTAILLING PARALLEL CONDUCTORS IT IS MANDATORY THAT ALL CONDUCTORS MAKING UP <br />SAME LENGTH, THE SAME SIZE AND THE SAME TYPE OF CONDUCTOR <br />WITH THE SAME INSULATION. FURTHER, EACH GROUP OF CONDUCTORS MAKING UP A PHASE OR <br />BOTH ENDS IN AN APPROVED MANNER. <br />1. CONDUCTOR SIZES INDICATED ON CIRCUIT HOMERUNS OR IN PANELBOARD SCHEDULES SHALL <br />BE INSTALLED OVER THE ENTIRE LENGTH OF THE CIRCUIT UNLESS NOTED OTHERWISE ON THE <br />DRAWINGS. <br />J. TINUOUS AND UNSPUCED WHERE INSTALLED IN CONDUIT. SPUCES <br />SHALL OCCUR ONLY WITHIN WIRING TROUGHS, WIREWAYS, JUNCTION BOXES, OUTLET BOXES, OR <br />EQUIPMENT ENCLOSURES WHERE SUFFICIENT ADD11IONAL ROOM IS PROVIDED FOR ALL SPUCES. <br />K. <br />SIZES THRU NO. 6 AWG, THE INSULATION SHALL BE OF THE COLOR AS INDICATED BELOW. COLOR <br />SIZES NO. 4 AWG AND LARGER, COLOR <br />OUND THE CONDUCTOR INSULATION WITHIN 8" <br />UCTOR AND IN EACH PULL OR JUNCTION BOX OR WHENEVER <br />CALLY EXPOSED TO VIEW. GROUNDING CONDUCTORS AND GROUNDED <br />CONDUCTORS SHALL HAVE INSULATION COLOR AS INDICATED FOR SIZES THROUGH #6 AWG. <br />120/208 V, 3PHASE,4W <br />PHASE A, COLOR: BLACK <br />PHASE B, COLOR: RED <br />PHASE C, COLOR: BLUE <br />NEUTRAL, COLOR: WHITE <br />GROUND, COLOR: GREEN <br />L. PRIOR AUTHORIZATION FROM THE ARCHITECT/ENGINEER IF CONDUCTORS ARE SUBSTITUTED TO <br />ALUMINUM CONDUCTORS. CONDUCTORS MUST HAVE THE EQUIVALENT OR GREATER AMPACITY VALUE <br />D COPPER, SHALL PHYSICALLY FIT BELOW THE CONNECTION UJG AND SHALL <br />BE SUBMITTED TO THE ENGINEER FOR APPROVAL ALL LUGS SHALL BE RATED FOR COPPER AND 1 <br />ALUMINUM CONDUCTORS. CONDUCTORS SHALL BE INSTAU_ED UTIUZING "NO -LOX" ANTI -OXIDATION <br />D AS "COMPACT ALUMINUM". A <br />V1 1. GROUNDING: <br />A. THIS SECTION DEALS WITH THE GROUNDING OF SERVICE EQUIPMENT, TRANSFORMERS, <br />NON -CURRENT CARRYING CONDUCTIVE SURFACES OF EQUIPMENT, METAL BUILDING, STRUCTURES AND B <br />OTHER EQUIPMENT. MAXIMUM RESISTANCE SHALL NOT EXCEED 10 OHMS <br />B. ALL GROUNDING CONNECTIONS SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL C <br />ELECTRICAL CODE AND ALL LOCAL CODES AND REQUIREMENTS. SUCH CODES SHALL BE CONSIDERED <br />MINIMUM REQUIREMENTS AND THE INSTALLATION OF THE GROUNDING SYSTEM SHALL INSURE <br />AND SHALL PROVIDE A LOW IMPEDANCE GROUND D <br />ION OF OVERCURRENT AND GROUND FAULT PROTECTIVE DEVICES. <br />C. ALL SERVICE AND EQUIPMENT GROUNDING CONDUCTORS, AND BONDING JUMPERS SHALL BE <br />INSULATED COPPER, TYPE THHN, THWN, OR THW CONDUCTORS (UNLESS NOTED OTHERWISE) AND <br />SHALL BE SIZED IN ACCORDANCE WITH THE APPUCABLE PORTIONS OF ARTICLES 250 AND 517 OF <br />THE NATIONAL ELECTRICAL CODE. GROUNDING CONDUCTORS #6 AWG AND SMALLER SHALL HAVE A <br />GREEN COLOR INSULATION. ALL GROUNDING CONDUCTORS #4 AWG AND LARGER SHALL BE <br />ADEQUATELY IDENTIFIED WITH A GREEN TRACER AND/OR GREEN COLORED TAPE AT EACH END OF E <br />THE GROUNDING CONDUCTOR AND AT EACH PULLBOX OR OTHER ACCESSIBLE LOCATION. <br />D. THE MAIN SERVICE GROUNDING ELECTRODE SYSTEM SHALL CONSIST OF THE FOLLOWING ITEMS <br />BONDED TOGETHER BY THE GROUNDING ELECTRODE CONDUCTORS IN ACCORDANCE WITH NEC <br />ARTICLE 250: <br />1. COLD WATER PIPE, NEC 250 I <br />2. METAL FRAME OF BUILDING WHERE AVAILABLE, NEC 250 F <br />3. ODE, NEC 250-81(C) <br />E. THE NEUTRAL CONDUCTOR SHALL BE GROUNDED AT THE SERVICE ENTRANCE MAIN <br />DISCONNECT, AND AT EACH SEPARATELY DERIVED SYSTEM ONLY PER NEC ARTICLE 250. <br />F. A #4 INSULATED COPPER CONDUCTOR INSTALLED IN 3/4- CONCEALED CONDUIT SHALL BE <br />UILDING GROUNDING ELECTRODE SYSTEM TO EACH BUILDING FIRE ALARM <br />CONTROL CABINETS, CCTV SYSTEM CABINETS, EMS CABINETS, RELAY CABINETS, AND SECURITY <br />SYSTEM CABINETS. TERMINATE ON AN APPROPRIATELY SIZED (8) TERMINAL MULTI -CONDUCTOR <br />G LUG LOCATED WITHIN CABINET OR ON TERMINAL BOARDS. <br />IX. PANELBOARDS: <br />A. PANELBOARDS SHALL BE DEAD FRONT TYPE AND SHALL BE IN ACCORDANCE WITH UNDERWRITERS' <br />LABORATORIES, INC., STANDARD FOR PANELBOARDS AND ENCLOSING CABINETS AND SO LABELED. <br />B. PANELBOARDS SHALL BE FACTORY ASSEMBLED WITH BRANCH BREAKERS ARRANGED AS SHOWN IN <br />SCHEDULES. BREAKERS SHALL BE NUMBERED VERTICALLY BEGINNING TOP LEFT. BREAKER NUMBERS <br />THED TO TRIM. PANEL SHALL BE MINIMUM 20* WIDE, UNLESS SPECIFICALLY <br />NOTED OTHERWISE. <br />D. ANY SPECIAL REQUIREMENTS ON THE DRAWINGS OR SCHEDULES, SUCH AS GROUND FAULT <br />PROTECTION, INCREASED INTERRUPTING CAPACITY, ARC -FAULT CIRCUIT BREAKERS SHUNT TRIP TYPE <br />CIRCUIT BREAKER, FEED THRU PANELBOARDS, ETC., SHALL SUPERSEDE THESE SPECIFICATIONS, BUT ONLY <br />INSOFAR AS THAT PAR11CULAR REQUIREMENT IS CONCERNED AND AS INDICATED. <br />E. WIRING IN PANELBOARD GUTTERS SHALL BE PERFORMED IN A NEAT AND WORKMAN UKE MANNER. <br />WIRING SHALL BE GROUPED INTO NEAT BUNDLES AND SECURED WITH NYLON 11E WRAPS. <br />F, PROVIDE TYPE WRITTEN DIRECTORIES FOR EACH PANELBOARD INDICATING THE LOAD SERVED. <br />G. METERING <br />A. GANGABLE AND WEATHERPROOF NEMA 3R METERING SHALL BE COMPLETE WITH: ALUMINUM CROSS <br />BUSSING AND METER STACKS. <br />B. MINIMUM SHORT CIRCUIT RATING OR INTEGRATED ASSEMBLY SHALL NOT BE LESS THAN 22,000 <br />C. METER BASES SHALL CONFORM TO U.L. STANDARD 175, AND BE CONFIGURED TO CONFORM TO THE <br />SERVING UTILITY REQUIREMENTS. <br />E. PHASE SEQUENCED BUSSING SHALL BE USED THROUGHOUT, WITH LOAD BALANCE AS EQUAL AS <br />POSSIBLE. ALL SINGLE PHASE CIRCUITS SHALL HAVE A DEDICATED NEUTRAL PER NEC. <br />X. LIGHTING FIXTURES: <br />A. UGHTING FIXTURES SHALL BE FURNISHED AS SHOWN ON DRAWINGS AND IN THE LIGHTING <br />HALL SPECIFICALLY BE THE RESPONSIBILITY OF THE CONTRACTOR TO <br />VERIFY EXACT TYPE COUNG AND RECESSING DEPTH OF ALL RECESSED FIXTURES AND TO FURNISH THE <br />MOUNTING TRIMS AND ACCESSORIES OF THE SPECIFIED AND/OR APPROVED FIXTURES FOR THE COUNG <br />TO BE INSTALLED. UGHTING FIXTURES SHALL BE PROVIDED WITH JOINER PLATES, END CAPS, RETAINING <br />CUPS, PLASTER FRAMES, HOUSINGS, AND ALL OTHER ACCESSORIES REQUIRED FOR A COMPLETE <br />INSTALLATION. <br />B. ALL FIXTURES SHALL BE EQUIPPED WITH LAMPS UNLESS OTHERWISE NOTED. LAMPS SHALL BE <br />INSTALLED NEW, IMMEDIATELY PRIOR TO FINAL INSPECTION, AND SHALL NOT BE USED FOR <br />CONSTRUCTION. <br />C. FIXTURE CATALOG NUMBER REPRESENTS BASIC LUMINARY SIZE, TYPE, QUAUTY AND <br />CONFIGURATION. ACCESSORIES SHALL BE FURNISHED WITH EACH UNIT As REQUIRED FOR A <br />COMPLETE FINISHED INSTALLATION. BASIC ACCESSORIES SHALL INCLUDE, BUT ARE NOT UMITED <br />TO, THE FOLLOWING: <br />1. JOINING PLATES, END CAPS, RETAINING CLIPS, DRYWALL FLANGES, ETC. <br />2. TRIMS FOR RECESSED FIXTURES. <br />3. FIXTURE STEMS AND CANOPIES FINISHED TO MATCH FIXTURES. <br />4. SPECIAL MOUNTING BRACKETS, TENONS, SUP FILTERS, CONCRETE BASES, POLES, ANCHOR BOLTS, <br />JUNCTION BOXES, AND STANCHIONS FOR ALL EXTERIOR UGHTING FIXTURES. PROVIDE ALL <br />WEATHERPROOFING FOR ALL LIGHTING FIXTURES TO BE INSTALLED IN EXTERIOR LOCATIONS. <br />D. STRUCTURAL SUPPORT OF ALL FIXTURES SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. <br />E. RED TO EACH FIXTURE BODY BY MEANS OF A <br />BONDING SCREW. <br />F. OWNER WILL HAVE RIGHT TO RELOCATE LIGHTING FIXTURES OR UGHTING SWITCHES WITHIN 72" OF <br />COORDINATE THE <br />WALK-THROUGH PRIOR TO THE INSTALLATION OF THE WIRING. <br />3EC11ON 283000 DIGITAL ADDRESSABLE FIRE -ALARM SYSTEM <br />T1 - GENERAL <br />DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND <br />SUPPLEMENTARY CONDITIONS, DIVISION 1, AND DIVISION 26 SPECIFICATION SECTIONS, APPLY <br />TO THIS SECTION. <br />SUMMARY <br />THIS SECTION INCLUDES AUTOMATIC NETWORKED FIRE ALARM SYSTEMS, INCLUDING FIRE <br />ALARM CONTROL PANEL, REMOTE ANNUNCIATOR, DOOR HOLD OPEN DEVICES, MANUAL PULL <br />DETECTORS, FIRE ALARM HORNS, VISUAL SIGNAL EQUIPMENT, <br />OKE DAMPER CONNECTIONS, AND SURGE PROTECTION DEVICES. <br />COORDINATE ALL WIRING AND DEVICE INTERFACES WITH OWNER'S REPRESENTATIVE. <br />THE FIRE ALARM SYSTEM SHALL MEET THE LATEST ADOPTED EDITION OF ALL LOCAL, <br />STATE OF FLORIDA AND ALL LOCAL CITY AND COUNTY CODE AMENDMENTS, NFPA 72, UL <br />864-9THEDITION ALL FEDERAL "ADAG" REQUIREMENTS AND THE 2020 FLORIDA BUILDING <br />CODE <br />ALL DEVICES Mi" BE TM` N COLOR WITH 'INHW LETrHM <br />.3 DEFINITIONS <br />. ADDRESSABLE: COMBINED HARDWARE AND SOFTWARE SYSTEMS ASSOCIATED WITH THE <br />EL AND FIELD DEVICES WHICH WILL PERMIT IDENTIFICATION OR <br />CONTROL OF AN INDIVIDUAL DEVICE (INITIATING OR SIGNAL/CONTROL CIRCUIT). <br />. ALARM -INITIATING DEVICE: A MANUAL STATION, SMOKE DETECTOR OR HEAT DETECTOR. <br />. ALARM SIGNAL: SIGNIFIES A STATE OF EMERGENCY REQUIRING IMMEDIATE ACTION. <br />PERTAINS TO SIGNALS SUCH AS THE OPERATION OF A MANUAL STATION AND THE <br />OPERATION OF A SPRINKLER SYSTEM FLOW SWITCH. <br />. STYLE "4" INITIATING CIRCUITS: CIRCUITS ARRANGED AND ELECTRICALLY SUPERVISED SO A <br />SINGLE BREAK OR SINGLE GROUND FAULT CONDITION WILL BE INDICATED BY A TROUBLE <br />NTROL PANEL (FACP) AND THE CIRCUIT WILL CONTINUE TO <br />BE CAPABLE OF OPERATION FOR ITS INTENDED SERVICE IN THE FAULTED CONDITION NO <br />T GROUND FAULT CONDITION OCCURS. (2-WIRE CLASS B <br />CIRCUIT). <br />. STYLE 'Y" INDICATING CIRCUIT: CIRCUITS ELECTRICALLY SUPERVISED SUCH THAT A SINGLE <br />BREAK OR A SINGLE GROUND FAULT CONDITION WILL BE INDICATED BY A TROUBLE SIGNAL <br />AT THE FACP AND THE CIRCUIT WILL CONTINUE TO BE CAPABLE OF OPERATION FOR ITS <br />INTENDED SERVICE IN THE FAULTED CONDITION NO MATTER WHERE THE BREAK OR GROUND <br />RS. (2-WIRE CLASS B). <br />. MULTIPLEX SYSTEM: ONE USING SIGNALING METHOD CHARACTERIZED BY THE <br />UENTIAL TRANSMISSION, OR BOTH, AND THE RECEPTION OF <br />MUL11PLE SIGNALS IN A COMMUNICATION CHANNEL, INCLUDING MEANS FOR POSITIVELY <br />IDENTIFYING EACH SIGNAL <br />1.5 SYSTEM DESCRIPTION <br />A. GENERAL: COMPLETE, ZONED, NONCODED, ADDRESSABLE, MICROPROCESSOR BASED FIRE <br />DEFECTION AND ALARM SYSTEM WITH MANUAL AND AUTOMATIC ALARM INITIATION DEVICES <br />LOCATED OUTDOORS SHALL BE SPECIFICALLY DESIGNED FOR EXTERIOR SERVICE. PROVIDE <br />BATTERY BACK-UP BASED UPON TOTAL LOAD PER NFPA 72. ALARM SHALL ACHIEVE A <br />MINIMUM OF 80 DB THROUGHOUT OCCUPIABLE SPACES AND MEET ADA REQUIREMENTS. <br />B. SIGNAL TRANSMISSION: MULTIPLEX SIGNAL TRANSMISSION DEDICATED TO FIRE ALARM <br />SERVICE ONLY. <br />C. ALARM INDICATION: BY TRANSMITTING EMERGENCY ALARMS, SOUNDING INTERNAL AND <br />WEATHERPROOF HORNS, AND ILLUMINATION OF ADA STROBES. <br />D. ALLOW FOR LOADING AND EDITING SPECIAL INSTRUCTIONS <br />ES AS REQUIRED. THE SYSTEM SHALL BE CAPABLE OF ON -SITE <br />PROGRAMMING TO ACCOMMODATE SYSTEM EXPANSION AND FACILITATE CHANGES IN <br />OPERATION. ALL SOFTWARE OPERATIONS SHALL BE STORED IN A NON-VOLATILE <br />PROGRAMMABLE MEMORY WITHIN THE FIRE ALARM CONTROL UNIT. LOSS OF PRIMARY AND <br />SECONDARY POWER SHALL NOT ERASE THE INSTRUCTIONS STORED IN MEMORY. <br />E. THE SYSTEM SHALL HAVE THE CAPABIUTY OF LOADING SOFTWARE OPERATIONS FROM A <br />SINGLE NODE TO ALL OTHER NODES ON THE NETWORK. <br />F. RESIDENT SOFTWARE SHALL ALLOW FOR FULL CONFIGURATION OF INITIATING CIRCUITS SO <br />THAT ADDITIONAL HARDWARE SHALL NOT BE NECESSARY TO ACCOMMODATE FUTURE <br />CHANGES. FOR EXAMPLE, MONITORING OF NORMALLY OPEN CONTACT DEVICES TO <br />MONITORING OF NORMALLY CLOSED CONTACT DEVICES, OR FROM SENSING OF NORMALLY <br />OPEN CONTACT DEVICES TO SENSING A COMBINATION CIRCUIT AND BEING ABLE TO <br />DIFFERENTIATE BETWEEN THE TWO. <br />S. LL ALLOW FOR CONFIGURATION OF NOTIFICATION APPUANCE AND <br />CONTROL CIRCUITS SO THAT ADDITIONAL HARDWARE SHALL NOT BE NECESSARY TO <br />ACCOMMODATE CHANGES. FOR EXAMPLE, CHANGING A NON -CODED NOTIFICATION APPLICANT <br />CIRCUIT TO A CODED CIRCUIT; OR FROM A SLOW MARCH TIME (20 BPM) TO FAST MARCH <br />TIME (120 BPM) CODING. <br />H. THE SYSTEM SHALL HAVE THE CAPABIUTY OF RECALUNG ALARMS AND TROUBLE <br />CONDITIONS IN CHRONOLOGICAL ORDER FOR THE PURPOSE OF RECREATING AN EVENT <br />HISTORY. <br />1. SYSTEM CONNECTIONS AND CONDUIT AND WIRING FOR ALARM INDICATING CIRCUITS: STYLE <br />"Y" WIRING. <br />J. SYSTEM CONNECTIONS AND CONDUIT AND WIRING FOR ALARM -INITIATION CIRCUITS: STYLE *4 <br />WIRING. <br />1. TRANSMISSION TO REMOTE CENTRAL STATION: PROVIDE WIRING AND EQUIPMENT TO <br />AUTOMATICALLY ROUTE AN ALARM, SUPERVISORY, AND TROUBLE SIGNALS TO THE <br />UNIVERSAL STUDIOS CENTRAL STATION SERVICE TRANSMITTER LOCATED WITHIN MAIN <br />FIRE ALARM CONTROL PANEL USING USTED AND APPROVED DIALING EQUIPMENT. <br />PROVIDE ALL NECESSARY AND REQUIRED DIALER EQUIPMENT, WIRING AND CONNECTIONS <br />BY THIS CONTRACTOR. <br />2. GENERAL ALARM: A SYSTEM GENERAL ALARM INCLUDES: <br />a. INDICATING THE GENERAL ALARM CONDITION AT THE FACP AND THE INTEGRAL ANNUNCIATOR. <br />b. IDENTIFYING THE DEVICE THAT IS THE SOURCE OF THE ALARM AT THE FACP, AND ANNUNCIATOR. <br />C. INITIATING AUDIBLE AND VISIBLE ALARM SIGNALS THROUGHOUT THE BUILDING. <br />d. STOPPING HVAC SUPPLY AND RETURN FANS. <br />e. INITIATING TRANSMISSION OF ALARM SIGNAL TO REMOTE CENTRAL REPORTING STATION. <br />f. OORS. <br />g. CLOSE FIRE/SMOKE DAMPERS. <br />h. CLOSE GAS SOLENOID VALVES AS REQUIRED <br />3. MANUAL STATION ALARM OPERATION INITIATES A GENERAL ALARM. <br />4. WATER -FLOW ALARM SWITCH OPERATION: INITIATES A GENERAL ALARM. <br />5. SMOKE OR HEAT DEFECTION INITIATES A GENERAL ALARM. <br />2.9 WIRE/CABLE <br />A. LINE -VOLTAGE: UNE VOLTAGE CONDUCTORS SHALL BE SOUD COPPER CONDUCTORS WITH <br />600 V_RATED INSULATION. #10 GAUGE, MINIMUM ADJUSTED FOR LARGER GAUGE LONG RUNS. <br />B. INITIATION CIRCUITS (LOOP): INITIATION LOOP CONDUCTORS SHALL BE WEST PENN #D991 FOR <br />3000'-O* IN LENGTH AND LESS. WEST PENN #D995 SHALL BE USED FOR CIRCUITS OVER <br />3000'-O" IN LENGTH. BELOW GRADE, WET OR DAMP LOCATION INSTALLED CABLE, INCLUDING <br />CABLE INSTALLED ON THE TOP OF EXTERIOR WALKWAYS, SHALL BE WEST PENN AQUASEAL <br />MULTI -CONDUCTOR FLOODED CABLE (14 GAUGE), UNLESS NOTED OTHERWISE, AND SHALL BE <br />INSTALLED IN CONDUIT. <br />C. SIGNAL CIRCUITS: SIGNAL CIRCUITS SHALL BE #12 AWG THWN 19 STRAND COPPER. <br />D. I PPER. <br />E. COLOR CODE: STRICTLY ADHERED jg- <br />POSMVE NEWIVE <br />AUDIO/VISUAL* 112 AWG (THWN�. +ORANGE -WHITE <br />E RELAY CIRCUIT 14 AWG (TH'WN +PINK -BLACK <br />114 AWG (THWN +GRAY -BLACK <br />GAS SHUTOFF 14 AWG (�THWN) +GRAY -BLACK <br />24 VDC /1 4 AWG HWN) +RED -BLACK <br />AUTOMATIC (NON ADDRESSABLE) # 1 4 AWG (THWN) +YELLOW -BROWN <br />MANUAL (NON ADDRESSABLE) #14 AWG (THWN) +BLUE -PURPLE <br />F. ALL WIRE SHALL BE INSTALLED IN NEW CONCEALED CONDUIT, MINIMUM 1.5" CONDUIT. <br />3.7 DEMONSTRATION <br />A. PROVIDE THE SERVICES OF A FACTORY -AUTHORIZED SERVICE REPRESENTATIVE TO <br />TRAIN OWNER'S MAINTENANCE PERSONNEL AS SPECIFIED <br />BELOW. <br />1. TRAIN OWNER'S MAINTENANCE PERSONNEL IN THE LOCATION OF DEVICES, BOXES, <br />EDULES INVOLVED IN OPERATING, TROUBLESHOOTING, SERVICING, <br />AND PREVENTIVE MAINTAINING OF THE SYSTEM. PROVIDE A MINIMUM OF 4 HOURS' <br />TRAINING. TRAINING SHALL INCLUDE A COMPLETE PROJECT WALK DOWN WITH OWNER'S <br />AUTHORIZED REPRESENTATIVE TO IDENTIFY DEVICE LOCATIONS, JUNCTION BOX <br />PPRESSION MODULE LOCATIONS. <br />2. SCHEDULE TRAINING WITH THE OWNER AT LEAST SEVEN WORKING DAYS IN ADVANCE. <br />END OF SECTION 283000 <br />LO � <br />(D ;: I <br />I Z c') N- I <br />o !� <br />,`­� �, - M <br />, <br />,�,,' k� ,�, 0 <br />�­ 1�� �, z (D 11 - <br />�; �� ;,�.� (14 ilk �1 <br />� <br />�� , , . <br />,�i, M I <br />I z * . <br />� <br />,4,�io, j <br />.W <br />,�� ", <br />" <br />�.� 1 ,' < ____ <br />.1 __ <br />�, ` , I _j - <br />.� 11 ��. ` - "I , <br />�:, � <br />.1 � !I� "� 12- ` � <br />,I 4" - � ; ; <br />I <br />, . <br />. , �� , - �_' , I � <br />11 I , - <br />, , �� t, 11� z I <br />, , , <br />11 1� I <br />"L , , ,� <br />I", !A ,�, (D <br />I <br />1,,�, ,�'. - =1 <br />, ; <br />�!, � ',-,, "") (1) <br />�� , <br />��, __ Lu <br />11, .� �,,� - <br />k��,��Ui � 1­q Q <br />,,,��: L- I <br />11 , - <br />.1 ,-� �i, ., � <br />,� � �, -_ Uj <br />El", � -, 1'1� - I <br />lk�:''_ 11 ,,;,� I I 0� <br />]� I I'. (D <br />, _�� " , 0 <br />"" -, 11 <br />_ - Z) <br />,�, ,�;, , � " <br />,',�, - ." I I �_ 91 <br />,�,"�.'k,"w'--a , �,,� .5 <br />0 (n <br />7- -1.1-11­ 1_­­1 Uj 6- <br />�: 1 , <br />"11���, , C �f) <br />"''.- , (O <br />� ��_,�;�:�,�� � ", I I-- E M r- M <br />�,,. � - . <br />� . I I � 0 .:� C-, n <br />I- � � . , -r 0 Fz -, " <br />I., �� " . I (1) -C LL C) <br />, . V ,!� <br />-, ... 1� I,,;,. � � , _;.,..: " I � <br />, , 11�.. I" I 'Al (.) (1) E 00 <br />1­1 <br />, , , , � L, <br />, " , -6 <br />. � . . . . . I -0 01 (1) ::3 00 <br />I <br />...... ..... � I <br />LLLLLL ..... (1) 0 C r-- <br />10� a) U) _T 0 <br />_�c �= 'IT <br /><0 00 <br />0) Lj) CD 3 <br />I " 2E - <br />P, I h I. I <br />i <br />4;L 0 -L ?'�_ <br />I. <br />t <br />, ) <br />E �L_v , Y .- , p t - <br />THIS DOCUMENf AND/OR THE DESIGN CONCEPTS <br />EXPRLSSED HEREIN ARE THE PROPERTY OF <br />KEESEE ASSOCIATES AND ALL RIGH1 S OF <br />OWNERSHIP, INCLUDING COPYRIGHT OF <br />IN] ELLEC1 UAL PROPERTY, ARE RESERVED. I HE <br />REPRODUCTIONS, COPYING, OR USE OF THIS <br />DOCUMENT AND/OR THE DESIGN CONCEPT <br />WITHOUT THE WRITTEN CONSENT OF KEESEE <br />ASSOCIATES IS STRICTLY PROHIBITED AND <br />PROTECTED BY UNITED STATES AND <br />INTERNATIONAI I AW <br />C�3 <br />LO <br />C14 <br />� t I co <br />�, �. t ; I � % I � : If ;1� <br />- I LO <br />, I " I'� �_ I i, � .1 I <br />, � 1 , . <br />11 11-1 � � 1 6 <br />- , <br />_j _': - e , ,", I I � I � I � I 2i Z <br />< �, `­ "', , ',,- � , �; " , O_ W <br />W1 - I- IL �_ Q_ <br />U) -, � 11 I I I 1 4? <br />1 ,� SI <br />11 I <br />�__ I , rt, <br />C16 - <br />Luil___� ��_ � '. , I I -; 11 0� <br />0�--,- -,. , , " , z-, I-_ <br />D:,� , , - I , I I dz I , - W <br />F-- , , 0_ <br />_ _ , , / 1: 1 114 <br />-, : v I r.) <br />< ,-' �, , - " L I 1 -4 & <br />z . I I I , <br />� I L 6 N <br />0 , - � , �, I I I - C: <br />" I I <br />�5 I . -1 , I a Q) <br />" , 11 , 11 �e <br />I r I I - 0 <br />� �11 I 1. 11, 11 �"L 2i <br />� : , I <br />� ,,;� � � � � � , 0,� '' _0 <br />, <br />-) <br />< <br />Z) <br />(3 <br />U) <br />0 <br />� <br />> <br />< <br />< <br />(D <br />- <br />U) <br />_j <br />_j < <br />- <br />_r 0 <br />0� of <br />>- 0 <br />T_ _j <br />0- LL <br />- <br />N <br />PERMIT 01/26/2022 <br />REV. REV. REV. <br />NO. DESC. I DATE <br />REVISIONS <br />Project Number: <br />21-7431 <br />Date: 01/26/2022 1-30:00 PM <br />Issue Date, <br />01/26/22 <br />Reviewed By: <br />KR <br />Drawn By: <br />im <br />Scale: <br />As indicated <br />Sheet Name: <br />ELECTRICAL <br />SPECIFICATIONS <br />CA# 26308 I21570.00 <br />Adlk I N G E N U I T Y Sheet No. <br />ENGINEEMIN c- E002 <br />141F "PROACTIVE ENGINEERING SOLUTIONS" <br />4798 NEW BROAD ST. SUITE 300 1 ORLANDO, FLORIDA 1 407,398.6007 <br />__ - I—- I- , - : -'-- ----7 ­ '17­ --:---- ­' -.1 I— --,-,,..--,. . -i I - <br />