GENERAL NOTES
<br />1. ALL WORK IS TO COMPLY WITH THE 2017 NATIONAL ELECTRIC CODE AND THE 7TH EDITION, 2020
<br />FLORIDA BUILDING CODE, AND ALL LOCAL CODES OR REGULATIONS THAT MAY APPLY TO THE
<br />PROJECT.
<br />2. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MAKING A SITE VISIT IN ORDER TO IDENTIFY
<br />EXISTING CONDITIONS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THAT ANY
<br />ELECTRICAL SYSTEMS TO REMAIN ARE CODE COMPLIANT.
<br />3. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING TEMPORARY POWER AND
<br />TEMPORARY LIGHTING AS REQUIRED FOR THE DURATION OF THE PROJECT.
<br />4. THE ELECTRICAL CONTRACTOR IS REQUIRED TO PROVIDE A WORKMANSHIP WARRANTY OVER THE
<br />PERIOD OF ONE YEAR AFTER PROJECT COMPLETION THAT IS SUFFICIENT TO COMPLY WITH THE
<br />PROJECT CONTRACT.
<br />5. THE ELECTRICAL CONTRACTOR IS TO PROVIDE A COMPLETE SET OF MARKED UP ELECTRICAL "AS
<br />BUILT" DRAWINGS TO THE GENERAL CONTRACTOR UPON COMPLETION OF THE PROJECT.
<br />6. THE ELECTRICAL CONTRACTOR IS TO PROVIDE AN OPERATION AND MAINTENANCE MANUAL FOR
<br />ALL EQUIPMENT REQUIRING MAINTENANCE ASSOCIATED WITH THE PROJECT.
<br />7. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL WORK WITH OTHER
<br />TRADES IN ORDER TO NOT INTERFERE WITH THE OVERALL PROJECT SCHEDULE.
<br />8. IF A DISCREPANCY IS FOUND BETWEEN THE ELECTRICAL PLANS AND THE SPECIFICATIONS, THE
<br />MOST STRINGENT REQUIREMENT SHALL GOVERN UNLESS WRITTEN APPROVAL IS GRANTED FROM
<br />THE ARCHITECT OR ENGINEER.
<br />9. ALL BREAKER, DISCONNECT AND WIRE SIZING MUST BE CONFIRMED BY THE ELECTRICAL
<br />CONTRACTOR PRIOR TO ROUGHIN.
<br />SUBMITTALS AND SHOP DRAWINGS
<br />1. PRIOR TO PROCUREMENT, THE CONTRACTOR IS REQUIRED TO PROVIDE SUBMITTALS AND SHOP
<br />DRAWINGS TO THE GENERAL CONTRACTOR, ENGINEER, AND ARCHITECT FOR APPROVALS.
<br />2. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO ENSURE THE SUBMITTED
<br />PRODUCTS WILL FORM A COMPLETE, FUNCTIONAL, AND CODE COMPLIANT ELECTRICAL SYSTEM.
<br />WIRING AND RACEWAYS
<br />1. NO WIRING IS TO BE SMALLER THAN #12 AWG UNLESS OTHERWISE NOTED.
<br />2. EACH CIRCUIT IS TO BE INSTALLED WITH A DEDICATED NEUTRAL UNLESS OTHERWISE NOTED.
<br />3. THE CONDUCTORS FOR FEEDERS AND BRANCH CIRCUITS COMBINED SHALL BE SIZED FOR A
<br />MAXIMUM AT 5% VOLTAGE DROP TOTAL PER FBC C405.5.3.
<br />4. TYPE MC CABLING IS ACCEPTABLE UNLESS PROHIBITED BY THE SPECIFICATIONS OF THE PROJECT,
<br />OR THE NATIONAL ELECTRIC CODE DUE TO THE OCCUPANCY TYPE OF THE PROJECT.
<br />5. NONMETALLIC CABLING (ROMEX) SHALL NOT BE USED.
<br />6. ALL WIRING IS TO BE SIZED ACCORDING TO THE NEC.
<br />7. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO UPSIZE ALL CONDUIT AND WIRING
<br />WHEN REQUIRED DUE TO VOLTAGE DROP POSED BY ONSITE CONDITIONS.
<br />8. PROVIDE COMPLETE RACEWAYS FOR ALL SYSTEMS AS REQUIRED BY THE NEC AND LOCAL CODES.
<br />TYPE PVC, EMT, AND RMC ARE PERMITTED AS REQUIRED BY THE LOCAL CODE.
<br />9. A GROUND CONDUCTOR IS TO BE SUPPLIED IN ALL RACEWAYS. SIZE THE GROUND CONDUCTOR
<br />PER THE NEC, OR AS SHOWN ON THE PLAN, WHICHEVER IS LARGER.
<br />10. RACEWAYS ARE TO BE CONCEALED AND EQUIPMENT IS TO BE FLUSH MOUNTED, UNLESS
<br />OTHERWISE NOTED, OR WHEN ONSITE CONDITIONS MAKE CONCEALING OR FLUSH MOUNTING
<br />IMPOSSIBLE.
<br />11. WHEN A RACEWAY PENETRATES A FIRE WALL OR FLOOR, THE RACEWAY IS TO BE SEALED IN A
<br />MANNER WHICH WILL MAINTAIN THE RATING OF THE WALL OR FLOOR.
<br />12. MINIMUM CONDUIT SIZE IS TO BE 3/4 INCH, UNLESS OTHERWISE NOTED.
<br />13. FLEXIBLE CONDUIT IS ALLOWABLE IN LENGTHS OF 6' OR LESS, WHEN IT IS MORE PRACTICAL TO
<br />MAKE CONNECTIONS TO EQUIPMENT.
<br />14. SEALTITE FLEXIBLE CONDUIT IS TO BE USED IN OUTDOOR APPLICATIONS.
<br />15. THE RACEWAY SYSTEM AS A WHOLE IS REQUIRED TO COMPLY WITH ALL NEC AND LOCAL CODE
<br />REQUIREMENTS.
<br />GROUNDING
<br />1. THE ELECTRICAL SYSTEM IS TO BE GROUNDED IN ITS ENTIRETY PER THE NEC.
<br />2. THE TELEPHONE / NETWORK BOARD IS TO HAVE NO. 6 AWG GROUND WIRE TO THE MAIN SERVICE
<br />GROUND.
<br />3. ALL METALLIC EQUIPMENT INCLUDING RACEWAYS, PANELBOARDS, DISCONNECTS, BOXES, ARE TO
<br />BE CONNECTED TO THE GROUNDING SYSTEM PER NEC REQUIREMENTS.
<br />4. THE SERVICE GROUND IS TO BE SIZED ACCORDING TO NEC REQUIREMENTS AND IS TO BE
<br />CONNECTED TO BUILDING STEEL, COLD WATER PIPING, CONCRETE ENCASED STEEL, AND GAS
<br />PIPING IF REQUIRED.
<br />DEVICES
<br />1. LIGHT SWITCHES ARE TO BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO THE CENTERLINE OF
<br />THE DEVICE, UNLESS OTHERWISE NOTED.
<br />2. RECEPTACLES ARE TO BE MOUNTED 18 INCHES ABOVE FINISHED FLOOR TO THE CENTERLINE OF
<br />THE DEVICE, UNLESS OTHERWISE NOTED.
<br />3. THE COLOR AND STYLE OF OUTLETS AND SWITCHES ARE TO BE DETERMINED BY THE CLIENT.
<br />4. RECEPTACLES ARE TO BE GFCI TYPE WHERE NOTED.
<br />5. RECEPTACLES ARE TO BE SWITCHED TO COMPLY WITH FLORIDA BUILDING CODE ENERGY
<br />REGULATIONS WHERE REQUIRED.
<br />6. RECEPTACLES AND SWITCHES ARE TO BE FLUSH MOUNTED UNLESS OTHERWISE NOTED.
<br />7. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO ENSURE COMPATIBILITY OF
<br />SPECIAL RECEPTACLES WITH THE EQUIPMENT THEY ARE INTENDED TO SERVE.
<br />8. ALL EXTERIOR RECEPTACLES AND RECEPTACLES SUBJECT TO MOISTURE MUST BE OF GFCI TYPE
<br />REGARDLESS OF THE TYPE SHOWN ON THE ELECTRICAL PLANS.
<br />9. ALL EXTERIOR RECEPTACLES AND SWITCHES ARE REQUIRED TO BE INSTALLED WITH
<br />WEATHERPROOF "IN USE" TYPE COVERS.
<br />10, DEVICES ARE SHOWN ON THE ELECTRICAL PLANS FOR A REFERENCE LOCATION ONLY.
<br />COORDINATE EXACT LOCATION WITH ARCHITECTURAL PLANS AND OTHER TRADES. NOTE ANY
<br />CHANGES ON THE "AS BUILT" SET OF ELECTRICAL PLANS.
<br />SWITCHGEAR
<br />1. PANELBOARDS AND LOAD CENTERS ARE TO BE SQUARE D OR APPROVED EQUAL.
<br />2. PANELBOARDS AND LOAD CENTERS ARE TO BE PROVIDED WITH TRANSIENT VOLTAGE SURGE
<br />SUPPRESSION AS DESCRIBED IN THE ELECTRICAL PLANS.
<br />3. DISCONNECTS ARE TO BE HEAVY DUTY TYPE AND ARE TO BE FUSED WHERE THE EQUIPMENT IS
<br />NOT SUPPLIED BY THE APPROPRIATE BREAKER.
<br />4. ALL NEW BREAKERS ADDED TO EXISTING PANELS ARE TO MATCH THE EXISTING PANEL
<br />MANUFACTURER AND AIC RATING OF THE EXISTING BREAKERS.
<br />5. THE LOCATIONS OF ALL SWITCHGEAR, PANELS, DISCONNECTS, MCC'S, ETC. IS APPROXIMATE.
<br />CONSULT OWNER PRIOR TO ROUGH IN OF EQUIPMENT.
<br />6. PROVIDE TYPED PANEL SCHEDULES/DIRECTORIES FOR ALL PANELS UPON COMPLETION OF THE
<br />PROJECT. ENSURE THAT THE SCHEDULES PROVIDED REFLECT THE "AS BUILT" CONDITION AND
<br />ARE NOT SIMPLY COPIES OF THE PANEL SCHEDULES FROM THESE PLANS. IF AN EXISTING PANEL
<br />IS MODIFIED, IT IS ACCEPTABLE TO ADD THE MODIFICATION TO THE EXISTING SCHEDULE IN THE
<br />MANNER THE EXISTING SCHEDULE WAS ORIGINALLY CREATED.
<br />7. PROVIDE ENGRAVED PLASTIC LAMINATE NAME TAGS ON THE FRONT OF ALL PANELS,
<br />DISCONNECTS, TRANSFORMERS AND OTHER SWITCHGEAR. LABEL THE EQUIPMENT TO MATCH
<br />THE AS BUILT DRAWINGS TO ENSURE MAINTENANCE PERSONNEL ARE PROVIDED THE
<br />INFORMATION THEY NEED TO QUICKLY IDENTIFY THE ELECTRICAL SYSTEM.
<br />8. PROVIDE ALL OTHER IDENTIFICATION AS REQUIRED PER ANSI, NEC, AND ANY OTHER APPLICABLE
<br />STANDARDS / SPECIFICATIONS.
<br />9. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO VERIFY ALL NEC CLEARANCE
<br />REQUIREMENTS ARE MET BEFORE THE ROUGH -IN OF ANY EQUIPMENT. THE LAYOUT OF
<br />SWITCHGEAR AND OTHER EQUIPMENT ON THE PLANS IS DIAGRAMMATICAL ONLY.
<br />LIGHTING
<br />1. CONNECT ALL EXIT SIGNS, EGRESS FIXTURES, AND NIGHT LIGHTS ON THE UNSWITCHED LEG OF A
<br />LOCAL LIGHTING CIRCUIT.
<br />2. MINIMUM EMERGENCY ILLUMINATION OF 1 FOOTCANDLE AT FLOOR LEVEL ALONG THE PATH OF
<br />EGRESS FOR 90 MINUTES IS REQUIRED. EMERGENCY LIGHTING FIXTURES SHALL BE ARRANGED
<br />BY THE CONTRACTOR TO ACCOMPLISH THIS REQUIREMENT.
<br />3. REFER TO THE ARCHITECTURAL CEILING PLAN FOR EXACT FIXTURE LOCATIONS.
<br />4. MULTIPLE FIXTURES MAY HAVE OPTIONS FOR MOUNTING IN GRID, OR DRYWALL CEILINGS. IT IS
<br />THE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE THE PROPER MOUNTING HARDWARE AND
<br />TRIM PIECES ARE ORDERED BASED ON THE CEILING TYPES SHOWN IN THE ARCHITECTURAL
<br />PLANS.
<br />5. ALL FIXTURES AND CONTROLS ARE FURNISHED AND INSTALLED BY THE ELECTRICAL
<br />CONTRACTOR, UNLESS OTHERWISE NOTED.
<br />PROFESSIONAL STATEMENT
<br />-0 THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND
<br />iPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING
<br />;ODES AND THE APPLICABLE FIRE SAFETY STANDARDS AS DETERMINE[
<br />3Y THE LOCAL AUTHORITY IN ACCORDANCE WITH FLORIDA STATUTES.
<br />".. .4 0.1 : �ifl/:r1to] ►w
<br />AFC
<br />- AVAILABLE FAULT CURRENT
<br />AFF
<br />- ABOVE FINISHED FLOOR
<br />AHU
<br />- AIR HANDLING UNIT
<br />BFG
<br />- BELOW FINISHED GRADE
<br />C
<br />- CONDUIT
<br />CW
<br />- COOL WHITE
<br />CU
<br />- CONDENSING UNIT
<br />CKT
<br />- CIRCUIT
<br />DACP
<br />- DOOR ALARM CONTROL PANEL
<br />DN
<br />-DOWN
<br />EF
<br />- EXHAUST FAN
<br />EG
<br />- EQUIPMENT GROUND
<br />ENCL
<br />-ENCLOSURE
<br />EWC
<br />- ELECTRIC WATER COOLER
<br />EWH
<br />- ELECTRIC WATER HEATER
<br />ETR
<br />- EXISTING TO REMAIN
<br />PNL
<br />-PANEL
<br />EOP
<br />- EDGE OF PAVEMENT
<br />EXP
<br />- EXPLOSION PROOF
<br />FCU
<br />- FAN COIL UNIT
<br />FHP
<br />- FRACTIONAL HORSE POWER
<br />FLA
<br />- FULL LOAD AMPERES
<br />G
<br />-GROUND
<br />GFI
<br />- GROUND FAULT INTERRUPTER
<br />HID
<br />- HIGH INTENSITY DISCHARGE
<br />HORIZ
<br />- HORIZONTAL
<br />IG
<br />- ISOLATED GROUND
<br />LW
<br />- LIGHT WHITE
<br />HP
<br />- HORSEPOWER / HEAT PUMP
<br />HVAC
<br />- HEATING, VENTILATING, AIR CONDITIONING
<br />JB
<br />- JUNCTION BOX
<br />LRA
<br />- LOCKED ROTOR AMPERES
<br />MCB
<br />- MAIN CIRCUIT BREAKER
<br />MLO
<br />- MAIN LUGS ONLY
<br />N
<br />-NEUTRAL
<br />NL
<br />- NIGHT LIGHT
<br />OB
<br />- OUTLET BOX
<br />PB
<br />- PULL BOX, PUSHBUTTON
<br />PS
<br />- PAY STATION
<br />RECEPT
<br />-RECEPTACLE
<br />SF
<br />SUPPLY FAN
<br />SPEC
<br />SPECIFICATIONS
<br />SPD
<br />- SURGE PROTECTION DEVICE
<br />SWECS
<br />- SMOKE WARNING EMERGENCY CALL SYSTEM
<br />TL
<br />- TWISTLOCK
<br />TTB
<br />- TELEPHONE TERMINAL BOARD
<br />TVTB
<br />- TELEVISION TERMINAL BOARD
<br />VERT
<br />- VERTICAL
<br />WM
<br />- WATT MISER
<br />WP
<br />-WEATHERPROOF
<br />WW
<br />- WARM WHITE
<br />XFMR
<br />-TRANSFORMER
<br />UL SYSTEM No. WL1001
<br />(FORMERLY SYSTEM No. 147)
<br />'IF" RATING - 1, 2, 3, AND 4 HR. (SEE ITEM 2 AND 3)
<br />'T" RATING - 0, 1, 2, 3, AND 4 HR. (SEE ITEM 3)
<br />A
<br />3
<br />2
<br />A
<br />1. WALL ASSEMBLY- THE 1, 2, 3, OR 4 HOUR FIRE -RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE
<br />MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGN IN THE UL FIRE
<br />RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES.
<br />a. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS CONSIST OF NOMINAL 2" x 4"
<br />LUMBER SPACED 16INCHES O.C. WITH NOMINAL 2" x 4" LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN. 3-6/8" WIDE
<br />BY 1-3/8" DEEP CHANNELS SPACED MAX. 24" O.C.
<br />b. WALLBOARD GYPSUM -X" OR W THICK, 4 FT WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS,
<br />NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES
<br />DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAMETER OF OPENING IS 13Y2".
<br />2. PIPE OR CONDUIT - NOMINAL 12" DIA. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL CONDUIT; NOM. 4" DIAMETER (OR SMALLER) STEEL
<br />ELECTRICAL CONDUIT MECHANICAL OR TYPE L (OR HEAVIER) COPPER TUBING OR NOM. V DIA (OR SMALLER) FLEXIBLE STEEL CONDUIT.
<br />3. FILL, VOID OR CAVITY MATERIALS - CAULK- CAULK FILL MATERIAL INSTALLED TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR
<br />CONDUIT AND GYPSUM WALLBOARD AND W/ A MIN. X" DIA. BEAD OF CAULK APPLIED TO PERIMETER OF PIPE OR CONDUIT AT ITS EGRESS
<br />FROM THE WALL. CAULK INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY. THE HOURLY "F" RATING OF THE FIRESTOP
<br />SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED AS SHOWN IN THE FOLLOWING
<br />TABLE. THE HOURLY "T" RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE
<br />HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED AS TABULATED BELOW:
<br />MAX PIPE OR CONDUIT (DIA IN.) ANNULAR SPACE "F" RATING "T" RATING
<br />1 IN. 0 TO Ma IN. 1 OR 2 0+, 1 OR 2
<br />4 IN. 1/4 TO 1/2 3 OR 4 3 OR 4
<br />4 IN. 0 TO 1/4 1 OR 2 0
<br />4 IN. 1/4 TO 1/2 3 OR 4 0
<br />4 IN. 3/16 TO 3/8 1 OR 2 0
<br />+ WHEN COPPER IS USED, "T" RATING IS 0 H.
<br />MINNESOTA MINING & MFG. CO. - TYPES CP-25 S/L, CP-25 N/S, CP-25 WB, CP-25 WB+
<br />• BEARING THE UL CLASSIFICATION MARKING
<br />1, 2, 3, 4 HOUR FIRE RATED GYP. / STUD WALL ASSEMBLY
<br />l 1 !1 SCALE = NONE
<br />AWARNING_
<br />Arc Flash and Shock Hazard
<br />Nomin.l Sy..m Vo g. InclEenl fin.rpy (ullcm')
<br />me Fi..n Souna.ry wortmS ol•rmo•
<br />Re•iricl•E A...•.. PPE Hm,,d C.I.pory
<br />L11146 APPm¢h Nc N.nny or Clothing
<br />O Long n-vOft.•. Shin Ow SmG oid oovual
<br />H-,o oL..m•r P-S,
<br />OH.,
<br />O FI..h Bu11 _.1 O Sa1c,N. o H.m NN Lin.,
<br />136-b11 Oop01n
<br />OFI.•h Stu P.M• 13,31- 13
<br />OS-r-ry 01.....
<br />13 B"II Mood 13 1-.1 1313
<br />-iny Pro hon
<br />OP.na OP•d,. O
<br />OHnvy Dory w..mo olov.
<br />Equipment ID: Date:
<br />NOTES:
<br />PROVIDE ARC FLASH HAZARD LABELING AND FIELD MARK ALL ELECTRICAL EQUIPMENT AS PART OF
<br />ARC FLASH RISK ASSESSMENT PER 2015 EDITION OF NFPA 70E 130.50). THE LABEL MUST CONTAIN
<br />THE FOLLOWING INFORMATION:
<br />1. KNOWN SYSTEM VOLTAGE.
<br />2. ARC FLASH BOUNDARY.
<br />3. AT LEAST ONE OF THE FOLLOWING:
<br />a. AVAILABLE INCIDENT ENERGY AND THE CORRESPONDING DISTANCE, OR THE ARC
<br />FLASH PPE CATEGORY IN TABLE 130.7(C)(15)(A)(b) OR 130.7(C)(15)(B) FOR THE
<br />EQUIPMENT, BUT NOT BOTH.
<br />b. MINIMUM ARC RATING OF CLOTHING.
<br />c. SITE -SPECIFIC LEVEL OF PPE.
<br />ARC FLASH WARNING LABEL
<br />DETAIL
<br />UL SYSTEM No. CAJ1012
<br />(FORMERLY SYSTEM No. 129)
<br />"F" RATING - 1 HR.
<br />'T' RATING - 0 HR.
<br />"L" RATING AT AMBIENT - LESS THEN 1 CFM/SQ. FT. (SEE ITEM 4)
<br />"L" RATING AT 400 F - LESS THEN 1 CFM/SQ. FT. (SEE ITEM 4)
<br />SECTION A -A SECTION A -A
<br />(FLOOR ASSEMBLY) (WALL ASSEMBLY7
<br />1. FLOOR OR WALL ASSEMBLY - MIN. 5" THICK REINFORCED NORMAL WEIGHT (100-150 pcf) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF
<br />ANY UL CLASSIFIED CONCRETE BLOCKS". MAX. DIAMETER OF OPENING IS 6INCHES. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE
<br />FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
<br />2. THROUGH - PENETRANTS - ONE METALLIC PIPE OR CONDUIT TO BE CENTERED WITHIN FIRESTOP SYSTEM. A NOM ANNULAR SPACE OF 3/4"
<br />IS REQUIRED WITHIN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE FLOOR OR WALL
<br />ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES OR CONDUITS MAY BE USED:
<br />a. STEEL PIPE - NOM 4" DIA (OR SMALLER) SCHEDULE 5 (OR HEAVIER) STEEL PIPE.
<br />b. CONDUIT - NOM 4" DIA (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL CONDUIT.
<br />3. PACKING MATERIAL - MIN 3" THICKNESS OF MIN 4 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT
<br />FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR AS REQUIRED TO ACCOMMODATE THE REQUIRED
<br />THICKNESS FILL MATERIAL. PACKING MATERIAL TO BE CENTERED IN WALLS MID -DEPTH AND RECESSED TO ALLOW FOR INSULATION OF
<br />FILL MATERIAL.
<br />4. FILL, VOID OR CAVITY MATERIAL-- SEALANT OR FOAM - MIN 1/2" THCKNESS OF FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP
<br />SURFACE OF FLOOR. IN WALLS, FILL MATERIAL TO BE APPLIED ON EACH SIDE OF PACKING MATERIAL. FOAMED SILICONE TO BE INSTALLED
<br />AS DESCRIBED IN THE MANUFACTURER'S APPLICATION INSTRUCTIONS AT A DENSITY OF 14 pcf MIN TO 21 pcf MAX. THE THICKNESS OF FILL
<br />MATERIAL IS DEPENDANT UPON THE TYPE OF FILL MATERIAL AS SHOWN IN THE TABLE BELOW:
<br />FILL MATERIAL IDENTIFICATION MIN. THK OF FILL MATERIAL, In.
<br />TYPE FB-2001 1
<br />TYPE FB-2000 OR FB-2003 1/2
<br />MINNESOTA MINING & MFG Co. - TYPES FB-2000, FB-2000+, FB-2001, FB-2003 (FLOORS ONLY). (NOTE: L RATINGS APPLY ONLY WHEN FB-2000+
<br />IS USED.)
<br />- BEARING THE UL CLASSIFICATION MARKING
<br />I HOUR FIRE RATED MASONRY FLOOR / WALL
<br />LETTER (FILL) COLOR SHALL
<br />BE BLACK
<br />LETTERING SHALL BE y"
<br />HIGH
<br />NHA
<br />120/208V, 3PH, 4W
<br />FED FROM MSB BKR. I I
<br />PHASE A - BLACK WIRE
<br />PHASE B - RED WIRE
<br />PHASE C - BLUE WIRE
<br />NEUTRAL - WHITE WIRE
<br />GROUND - GREEN WIRE
<br />12,345 AFC / DATE
<br />INDICATED VOLTAGE,
<br />NO. OF PHASES,
<br />NO OF WIRES
<br />INDICATES WHERE THIS EQUIPMENT
<br />IS FED FROM (TRANSFER SWITCHES
<br />WILL HAVE TWO LINES)
<br />ATTACH NAMEPLATE WITH (2)
<br />SCREWS (MIN.)
<br />NAMEPLATE COLOR
<br />LIFE SAFETY = YELLOW
<br />EMERGENCY =ORANGE
<br />NORMAL - WHITE
<br />INCLUDE MAXIMUM AVAILABLE FAULT CURRENT PER NEC 110.24(A)
<br />ELECTRICAL EQUIPMENT NAMEPLATE DETAIL
<br />Cq
<br />0 P N L-A
<br />208Y/120V 30 4W
<br />kF_
<br />FED FROM MDP
<br />�E]
<br />0 112179 AFC 0
<br />, /16"O PRE -DRILLED HOLES. SECURE TO PANEL
<br />WITH %"0 SS RIVETS (TYP. 4)
<br />-EQUIPMENT NAME AS SPECIFIED ON PLANS
<br />SYSTEM VOLTAGE
<br />UPSTREAM EQUIPMENT SUPPLYING POWER
<br />AVAILABLE FAULT CURRENT AT EQUIPMENT
<br />LABEL AT TOP OF ENCLOSURE
<br />NOTES:
<br />1. ALL DISTRIBUTION EQUIPMENT SUCH AS PANELBOARDS, SWITCHBOARDS, DISCONNECTS, TRANSFORMERS, ETC. SHALL BE
<br />PROVIDED WITH AN EQUIPMENT LABEL PER THE REQUIREMENTS OF THIS DETAIL.
<br />2. LABELS SHALL BE 2-PLY ENGRAVED PLASTIC LAMINATE WITH BLACK TYPEFACE LETTERS., LABEL BACKGROUND SHALL
<br />FOLLOW THE BELOW COLOR SCHEME:
<br />a. NORMAL POWER -WHITE
<br />b. UPS POWER - BLUE
<br />c. LIFE SAFETY POWER -YELLOW
<br />3. LABEL MATERIAL SHALL BE DURABLE, UV STABLE, RATED FOR OUTDOOR USE, AND ABRASION RESISTANT. WHERE ATTACHED TO
<br />NEMA 4X EQUIPMENT, LABELS SHALL IN ADDITION BE CHEMICAL RESISTANT.
<br />4. LABELS SHALL BE PERMANENTLY ATTACHED TO ENCLOSURE COVER WITH RIVETS UNLESS DOING SO COMPROMISES ITS NEMA / IF
<br />RATING. LABELS FOR ENCLOSURES WITH WELDED SEAMS AND GASKETED DOORS SUCH AS THOSE RATED NEMA 12 OR NEMA 4
<br />SHALL BE INSTALLED USING PERMANENT WEATHER-, UV-, AND TEMPERATURE -RESISTANT DOUBLE -SIDED MOUNTING TAPE ONLY.
<br />5. A SUBMITTAL WITH A COMPLETE LIST OF EQUIPMENT LABELS SHALL BE PROVIDED FOR ENGINEER APPROVAL PRIOR TO ORDERING.
<br />6. LABELS SHALL INDICATE NO LESS THAN THE FOLLOWING:
<br />a. EQUIPMENT NAME.
<br />b. THE NOMINAL SYSTEM VOLTAGE WHICH SAID EQUIPMENT IS CONNECTED TO.
<br />c. THE EQUIPMENT NAME SUPPLYING POWER TO SAID EQUIPMENT.
<br />d. THE AVAILABLE FAULT CURRENT AT SAID EQUIPMENT.
<br />LABEL DETAIL
<br />NOTES:
<br />1. ALL CONDUCTOR CONNECTIONS ARE TO BE EXOTHERMIC
<br />WELD TYPE.
<br />2. UL LISTED WATER PIPE CLAMP SIZED ACCORDINGLY.
<br />3. UL LISTED REBAR CLAMP SIZED ACCORDINGLY.
<br />4. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A NEW
<br />GROUND ROD AS INDICATED.
<br />NOT ALL GROUNDING ELECTRODES SHOWN MAY BE
<br />PRESENT AT SITE. PER N.E.C. ARTICLE 250.50, THE
<br />ELECTRICAL CONTRACTOR SHALL BOND TOGETHER ALL
<br />PRESENT GROUNDING ELECTRODES.
<br />MAIN BONDING JUMPER
<br />(SIZE PER NEC 250.102)
<br />METAL FRAME OF THE
<br />BUILDING OR STRUCTURE
<br />(NEC 250,52 (A) (2)) G N
<br />SERVICE ENTRANCE EQUIPMENT
<br />PER BONDING JUMPER GROUNDING ELECTRODE CONDUCTOR
<br />BONDING JUMPER (SIZE PER NEC 2 PER (SIZE PER NEC 250.66) (SIZE PER NEC 250.66)
<br />- SEE NOTE 2 (TYP.)
<br />BONDING JUMPER (SIZE PER NEC 250.66)
<br />NON-METALLIC PROTECTIVE SLEEVE
<br />SEE NOTE 3 (TYP.)
<br />CONCRETE ENCASED REBAR
<br />(NEC 250.52 (A) (3))
<br />METAL UNDERGROUND WATER PIPE
<br />GROUND ROD (NEC (NEC 250.52 (A) (1))
<br />250.52 (A) (5))
<br />(S:) GROUNDING ELECTRODE SYSTEM DETAIL
<br />- MnM17 I Tr 7 n I 'CAT R -
<br />ALIGN HORN ONLY DEVICE WITH TOP OF DOOR
<br />FRAME, STOBE OR HORN/STROBE DEVICE 80"
<br />AFF TO BOTTOM OF STROBE LENS
<br />FIRE ALARM HORN ONLY,
<br />STROBE OR HORN/STROBE, LLLL���QJJJJ
<br />PAINT TO MATCH WALL 2" ABOVE BACKSPLASH
<br />ALIGN WHEN MOUNTED Q
<br />ON SAME WALL ( Q
<br />4" ABOVE COUNTER W
<br />W/0 BACKSPLASH L
<br />O
<br />FIRE ALARM PULL STATION ° °
<br />1 °
<br />I Q CABINET -
<br />o I*
<br />' Y �.P (TYP.)
<br />v
<br />010010
<br />FINISHED FLOOR
<br />NOTES:
<br />1. MOUNTING HEIGHTS SHOWN ARE FROM FINISHED FLOOR (A.F.F.), UNLESS OTHERWISE NOTED.
<br />2. LOCATIONS OF OUTLETS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL TAKE PRECEDENCE OVER
<br />THESE MOUNTING HEIGHTS. FIELD LOCATE OUTLETS WITH ARCHITECT DURING ROUGH -IN.
<br />3. INSTALL OUTLETS THAT ARE IN CLOSE PROXIMITY ON THE SAME CENTERLINE. OUTLETS THAT ARE
<br />WITHIN T-0" HORIZONTALLY AND WITHIN 1'-0" VERTICALLY SHALL BE INSTALLED ON THE SAME
<br />HORIZONTAL CENTERLINE LOCATED HALF WAY BETWEEN THE HEIGHTS SHOWN. OUTLETS THAT ARE
<br />MORE THAN 1'-0" APART VERTICALLY SHALL BE INSTALLED ON THE SAME VERTICAL CENTERLINE.
<br />4. VERIFY MOUNTING HEIGHT WITH LOCAL AUTHORITY.
<br />5. ADA REQUIREMENTS SHALL SUPERCEDE STANDARD MOUNTING HEIGHTS WHEN THERE IS A
<br />CONFLICT.
<br />STANDARD MOUNTING HEIGHTS DETAIL
<br />GULF COAST
<br />ELECTRICAL DESIGN
<br />2111 Sunnydale Blvd. Suite D
<br />Clearwater, FL 33765
<br />(727) 330-4937 1 www.GCElectricalDesign.com
<br />Florida Board of Professional Engineers #33905
<br />Loll
<br />80
<br />:- S OF
<br />•W♦
<br />S�ONAL ;% �13-/a1
<br />CORY A GLASS V.E. #80467
<br />Revisions Date By
<br />Mark A. Jonnatti
<br />Florida AR 0010778
<br />Jonnatti Architecture, Inc.
<br />Florida AA 0003371
<br />JONNATTI
<br />ARCHITECTURE
<br />INCORPORATED
<br />21021 US Highway 19 N
<br />Clearwater, FL 33765
<br />(727) 725-ARCH
<br />(72 7) 725-2 603 fx
<br />IV717W.jarch.com
<br />info@jarch.com
<br />Jonnatti Architecture
<br />Incorporated 2019
<br />ZEPHR
<br />RETAIL
<br />DEVELOPMENT
<br />US HWY 301
<br />GALL BLVD
<br />ZEPHYRHILLS
<br />FLORIDA
<br />33542
<br />ELECTRICAL
<br />NOTES AND
<br />DETAILS