Laserfiche WebLink
GENERAL NOTES <br />1. ALL WORK IS TO COMPLY WITH THE 2017 NATIONAL ELECTRIC CODE AND THE 7TH EDITION, 2020 <br />FLORIDA BUILDING CODE, AND ALL LOCAL CODES OR REGULATIONS THAT MAY APPLY TO THE <br />PROJECT. <br />2. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MAKING A SITE VISIT IN ORDER TO IDENTIFY <br />EXISTING CONDITIONS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THAT ANY <br />ELECTRICAL SYSTEMS TO REMAIN ARE CODE COMPLIANT. <br />3. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING TEMPORARY POWER AND <br />TEMPORARY LIGHTING AS REQUIRED FOR THE DURATION OF THE PROJECT. <br />4. THE ELECTRICAL CONTRACTOR IS REQUIRED TO PROVIDE A WORKMANSHIP WARRANTY OVER THE <br />PERIOD OF ONE YEAR AFTER PROJECT COMPLETION THAT IS SUFFICIENT TO COMPLY WITH THE <br />PROJECT CONTRACT. <br />5. THE ELECTRICAL CONTRACTOR IS TO PROVIDE A COMPLETE SET OF MARKED UP ELECTRICAL "AS <br />BUILT" DRAWINGS TO THE GENERAL CONTRACTOR UPON COMPLETION OF THE PROJECT. <br />6. THE ELECTRICAL CONTRACTOR IS TO PROVIDE AN OPERATION AND MAINTENANCE MANUAL FOR <br />ALL EQUIPMENT REQUIRING MAINTENANCE ASSOCIATED WITH THE PROJECT. <br />7. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL WORK WITH OTHER <br />TRADES IN ORDER TO NOT INTERFERE WITH THE OVERALL PROJECT SCHEDULE. <br />8. IF A DISCREPANCY IS FOUND BETWEEN THE ELECTRICAL PLANS AND THE SPECIFICATIONS, THE <br />MOST STRINGENT REQUIREMENT SHALL GOVERN UNLESS WRITTEN APPROVAL IS GRANTED FROM <br />THE ARCHITECT OR ENGINEER. <br />9. ALL BREAKER, DISCONNECT AND WIRE SIZING MUST BE CONFIRMED BY THE ELECTRICAL <br />CONTRACTOR PRIOR TO ROUGHIN. <br />SUBMITTALS AND SHOP DRAWINGS <br />1. PRIOR TO PROCUREMENT, THE CONTRACTOR IS REQUIRED TO PROVIDE SUBMITTALS AND SHOP <br />DRAWINGS TO THE GENERAL CONTRACTOR, ENGINEER, AND ARCHITECT FOR APPROVALS. <br />2. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO ENSURE THE SUBMITTED <br />PRODUCTS WILL FORM A COMPLETE, FUNCTIONAL, AND CODE COMPLIANT ELECTRICAL SYSTEM. <br />WIRING AND RACEWAYS <br />1. NO WIRING IS TO BE SMALLER THAN #12 AWG UNLESS OTHERWISE NOTED. <br />2. EACH CIRCUIT IS TO BE INSTALLED WITH A DEDICATED NEUTRAL UNLESS OTHERWISE NOTED. <br />3. THE CONDUCTORS FOR FEEDERS AND BRANCH CIRCUITS COMBINED SHALL BE SIZED FOR A <br />MAXIMUM AT 5% VOLTAGE DROP TOTAL PER FBC C405.5.3. <br />4. TYPE MC CABLING IS ACCEPTABLE UNLESS PROHIBITED BY THE SPECIFICATIONS OF THE PROJECT, <br />OR THE NATIONAL ELECTRIC CODE DUE TO THE OCCUPANCY TYPE OF THE PROJECT. <br />5. NONMETALLIC CABLING (ROMEX) SHALL NOT BE USED. <br />6. ALL WIRING IS TO BE SIZED ACCORDING TO THE NEC. <br />7. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO UPSIZE ALL CONDUIT AND WIRING <br />WHEN REQUIRED DUE TO VOLTAGE DROP POSED BY ONSITE CONDITIONS. <br />8. PROVIDE COMPLETE RACEWAYS FOR ALL SYSTEMS AS REQUIRED BY THE NEC AND LOCAL CODES. <br />TYPE PVC, EMT, AND RMC ARE PERMITTED AS REQUIRED BY THE LOCAL CODE. <br />9. A GROUND CONDUCTOR IS TO BE SUPPLIED IN ALL RACEWAYS. SIZE THE GROUND CONDUCTOR <br />PER THE NEC, OR AS SHOWN ON THE PLAN, WHICHEVER IS LARGER. <br />10. RACEWAYS ARE TO BE CONCEALED AND EQUIPMENT IS TO BE FLUSH MOUNTED, UNLESS <br />OTHERWISE NOTED, OR WHEN ONSITE CONDITIONS MAKE CONCEALING OR FLUSH MOUNTING <br />IMPOSSIBLE. <br />11. WHEN A RACEWAY PENETRATES A FIRE WALL OR FLOOR, THE RACEWAY IS TO BE SEALED IN A <br />MANNER WHICH WILL MAINTAIN THE RATING OF THE WALL OR FLOOR. <br />12. MINIMUM CONDUIT SIZE IS TO BE 3/4 INCH, UNLESS OTHERWISE NOTED. <br />13. FLEXIBLE CONDUIT IS ALLOWABLE IN LENGTHS OF 6' OR LESS, WHEN IT IS MORE PRACTICAL TO <br />MAKE CONNECTIONS TO EQUIPMENT. <br />14. SEALTITE FLEXIBLE CONDUIT IS TO BE USED IN OUTDOOR APPLICATIONS. <br />15. THE RACEWAY SYSTEM AS A WHOLE IS REQUIRED TO COMPLY WITH ALL NEC AND LOCAL CODE <br />REQUIREMENTS. <br />GROUNDING <br />1. THE ELECTRICAL SYSTEM IS TO BE GROUNDED IN ITS ENTIRETY PER THE NEC. <br />2. THE TELEPHONE / NETWORK BOARD IS TO HAVE NO. 6 AWG GROUND WIRE TO THE MAIN SERVICE <br />GROUND. <br />3. ALL METALLIC EQUIPMENT INCLUDING RACEWAYS, PANELBOARDS, DISCONNECTS, BOXES, ARE TO <br />BE CONNECTED TO THE GROUNDING SYSTEM PER NEC REQUIREMENTS. <br />4. THE SERVICE GROUND IS TO BE SIZED ACCORDING TO NEC REQUIREMENTS AND IS TO BE <br />CONNECTED TO BUILDING STEEL, COLD WATER PIPING, CONCRETE ENCASED STEEL, AND GAS <br />PIPING IF REQUIRED. <br />DEVICES <br />1. LIGHT SWITCHES ARE TO BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO THE CENTERLINE OF <br />THE DEVICE, UNLESS OTHERWISE NOTED. <br />2. RECEPTACLES ARE TO BE MOUNTED 18 INCHES ABOVE FINISHED FLOOR TO THE CENTERLINE OF <br />THE DEVICE, UNLESS OTHERWISE NOTED. <br />3. THE COLOR AND STYLE OF OUTLETS AND SWITCHES ARE TO BE DETERMINED BY THE CLIENT. <br />4. RECEPTACLES ARE TO BE GFCI TYPE WHERE NOTED. <br />5. RECEPTACLES ARE TO BE SWITCHED TO COMPLY WITH FLORIDA BUILDING CODE ENERGY <br />REGULATIONS WHERE REQUIRED. <br />6. RECEPTACLES AND SWITCHES ARE TO BE FLUSH MOUNTED UNLESS OTHERWISE NOTED. <br />7. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO ENSURE COMPATIBILITY OF <br />SPECIAL RECEPTACLES WITH THE EQUIPMENT THEY ARE INTENDED TO SERVE. <br />8. ALL EXTERIOR RECEPTACLES AND RECEPTACLES SUBJECT TO MOISTURE MUST BE OF GFCI TYPE <br />REGARDLESS OF THE TYPE SHOWN ON THE ELECTRICAL PLANS. <br />9. ALL EXTERIOR RECEPTACLES AND SWITCHES ARE REQUIRED TO BE INSTALLED WITH <br />WEATHERPROOF "IN USE" TYPE COVERS. <br />10, DEVICES ARE SHOWN ON THE ELECTRICAL PLANS FOR A REFERENCE LOCATION ONLY. <br />COORDINATE EXACT LOCATION WITH ARCHITECTURAL PLANS AND OTHER TRADES. NOTE ANY <br />CHANGES ON THE "AS BUILT" SET OF ELECTRICAL PLANS. <br />SWITCHGEAR <br />1. PANELBOARDS AND LOAD CENTERS ARE TO BE SQUARE D OR APPROVED EQUAL. <br />2. PANELBOARDS AND LOAD CENTERS ARE TO BE PROVIDED WITH TRANSIENT VOLTAGE SURGE <br />SUPPRESSION AS DESCRIBED IN THE ELECTRICAL PLANS. <br />3. DISCONNECTS ARE TO BE HEAVY DUTY TYPE AND ARE TO BE FUSED WHERE THE EQUIPMENT IS <br />NOT SUPPLIED BY THE APPROPRIATE BREAKER. <br />4. ALL NEW BREAKERS ADDED TO EXISTING PANELS ARE TO MATCH THE EXISTING PANEL <br />MANUFACTURER AND AIC RATING OF THE EXISTING BREAKERS. <br />5. THE LOCATIONS OF ALL SWITCHGEAR, PANELS, DISCONNECTS, MCC'S, ETC. IS APPROXIMATE. <br />CONSULT OWNER PRIOR TO ROUGH IN OF EQUIPMENT. <br />6. PROVIDE TYPED PANEL SCHEDULES/DIRECTORIES FOR ALL PANELS UPON COMPLETION OF THE <br />PROJECT. ENSURE THAT THE SCHEDULES PROVIDED REFLECT THE "AS BUILT" CONDITION AND <br />ARE NOT SIMPLY COPIES OF THE PANEL SCHEDULES FROM THESE PLANS. IF AN EXISTING PANEL <br />IS MODIFIED, IT IS ACCEPTABLE TO ADD THE MODIFICATION TO THE EXISTING SCHEDULE IN THE <br />MANNER THE EXISTING SCHEDULE WAS ORIGINALLY CREATED. <br />7. PROVIDE ENGRAVED PLASTIC LAMINATE NAME TAGS ON THE FRONT OF ALL PANELS, <br />DISCONNECTS, TRANSFORMERS AND OTHER SWITCHGEAR. LABEL THE EQUIPMENT TO MATCH <br />THE AS BUILT DRAWINGS TO ENSURE MAINTENANCE PERSONNEL ARE PROVIDED THE <br />INFORMATION THEY NEED TO QUICKLY IDENTIFY THE ELECTRICAL SYSTEM. <br />8. PROVIDE ALL OTHER IDENTIFICATION AS REQUIRED PER ANSI, NEC, AND ANY OTHER APPLICABLE <br />STANDARDS / SPECIFICATIONS. <br />9. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO VERIFY ALL NEC CLEARANCE <br />REQUIREMENTS ARE MET BEFORE THE ROUGH -IN OF ANY EQUIPMENT. THE LAYOUT OF <br />SWITCHGEAR AND OTHER EQUIPMENT ON THE PLANS IS DIAGRAMMATICAL ONLY. <br />LIGHTING <br />1. CONNECT ALL EXIT SIGNS, EGRESS FIXTURES, AND NIGHT LIGHTS ON THE UNSWITCHED LEG OF A <br />LOCAL LIGHTING CIRCUIT. <br />2. MINIMUM EMERGENCY ILLUMINATION OF 1 FOOTCANDLE AT FLOOR LEVEL ALONG THE PATH OF <br />EGRESS FOR 90 MINUTES IS REQUIRED. EMERGENCY LIGHTING FIXTURES SHALL BE ARRANGED <br />BY THE CONTRACTOR TO ACCOMPLISH THIS REQUIREMENT. <br />3. REFER TO THE ARCHITECTURAL CEILING PLAN FOR EXACT FIXTURE LOCATIONS. <br />4. MULTIPLE FIXTURES MAY HAVE OPTIONS FOR MOUNTING IN GRID, OR DRYWALL CEILINGS. IT IS <br />THE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE THE PROPER MOUNTING HARDWARE AND <br />TRIM PIECES ARE ORDERED BASED ON THE CEILING TYPES SHOWN IN THE ARCHITECTURAL <br />PLANS. <br />5. ALL FIXTURES AND CONTROLS ARE FURNISHED AND INSTALLED BY THE ELECTRICAL <br />CONTRACTOR, UNLESS OTHERWISE NOTED. <br />PROFESSIONAL STATEMENT <br />-0 THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND <br />iPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING <br />;ODES AND THE APPLICABLE FIRE SAFETY STANDARDS AS DETERMINE[ <br />3Y THE LOCAL AUTHORITY IN ACCORDANCE WITH FLORIDA STATUTES. <br />".. .4 0.1 : �ifl/:r1to] ►w <br />AFC <br />- AVAILABLE FAULT CURRENT <br />AFF <br />- ABOVE FINISHED FLOOR <br />AHU <br />- AIR HANDLING UNIT <br />BFG <br />- BELOW FINISHED GRADE <br />C <br />- CONDUIT <br />CW <br />- COOL WHITE <br />CU <br />- CONDENSING UNIT <br />CKT <br />- CIRCUIT <br />DACP <br />- DOOR ALARM CONTROL PANEL <br />DN <br />-DOWN <br />EF <br />- EXHAUST FAN <br />EG <br />- EQUIPMENT GROUND <br />ENCL <br />-ENCLOSURE <br />EWC <br />- ELECTRIC WATER COOLER <br />EWH <br />- ELECTRIC WATER HEATER <br />ETR <br />- EXISTING TO REMAIN <br />PNL <br />-PANEL <br />EOP <br />- EDGE OF PAVEMENT <br />EXP <br />- EXPLOSION PROOF <br />FCU <br />- FAN COIL UNIT <br />FHP <br />- FRACTIONAL HORSE POWER <br />FLA <br />- FULL LOAD AMPERES <br />G <br />-GROUND <br />GFI <br />- GROUND FAULT INTERRUPTER <br />HID <br />- HIGH INTENSITY DISCHARGE <br />HORIZ <br />- HORIZONTAL <br />IG <br />- ISOLATED GROUND <br />LW <br />- LIGHT WHITE <br />HP <br />- HORSEPOWER / HEAT PUMP <br />HVAC <br />- HEATING, VENTILATING, AIR CONDITIONING <br />JB <br />- JUNCTION BOX <br />LRA <br />- LOCKED ROTOR AMPERES <br />MCB <br />- MAIN CIRCUIT BREAKER <br />MLO <br />- MAIN LUGS ONLY <br />N <br />-NEUTRAL <br />NL <br />- NIGHT LIGHT <br />OB <br />- OUTLET BOX <br />PB <br />- PULL BOX, PUSHBUTTON <br />PS <br />- PAY STATION <br />RECEPT <br />-RECEPTACLE <br />SF <br />SUPPLY FAN <br />SPEC <br />SPECIFICATIONS <br />SPD <br />- SURGE PROTECTION DEVICE <br />SWECS <br />- SMOKE WARNING EMERGENCY CALL SYSTEM <br />TL <br />- TWISTLOCK <br />TTB <br />- TELEPHONE TERMINAL BOARD <br />TVTB <br />- TELEVISION TERMINAL BOARD <br />VERT <br />- VERTICAL <br />WM <br />- WATT MISER <br />WP <br />-WEATHERPROOF <br />WW <br />- WARM WHITE <br />XFMR <br />-TRANSFORMER <br />UL SYSTEM No. WL1001 <br />(FORMERLY SYSTEM No. 147) <br />'IF" RATING - 1, 2, 3, AND 4 HR. (SEE ITEM 2 AND 3) <br />'T" RATING - 0, 1, 2, 3, AND 4 HR. (SEE ITEM 3) <br />A <br />3 <br />2 <br />A <br />1. WALL ASSEMBLY- THE 1, 2, 3, OR 4 HOUR FIRE -RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE <br />MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGN IN THE UL FIRE <br />RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES. <br />a. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS CONSIST OF NOMINAL 2" x 4" <br />LUMBER SPACED 16INCHES O.C. WITH NOMINAL 2" x 4" LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN. 3-6/8" WIDE <br />BY 1-3/8" DEEP CHANNELS SPACED MAX. 24" O.C. <br />b. WALLBOARD GYPSUM -X" OR W THICK, 4 FT WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, <br />NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES <br />DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAMETER OF OPENING IS 13Y2". <br />2. PIPE OR CONDUIT - NOMINAL 12" DIA. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL CONDUIT; NOM. 4" DIAMETER (OR SMALLER) STEEL <br />ELECTRICAL CONDUIT MECHANICAL OR TYPE L (OR HEAVIER) COPPER TUBING OR NOM. V DIA (OR SMALLER) FLEXIBLE STEEL CONDUIT. <br />3. FILL, VOID OR CAVITY MATERIALS - CAULK- CAULK FILL MATERIAL INSTALLED TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR <br />CONDUIT AND GYPSUM WALLBOARD AND W/ A MIN. X" DIA. BEAD OF CAULK APPLIED TO PERIMETER OF PIPE OR CONDUIT AT ITS EGRESS <br />FROM THE WALL. CAULK INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY. THE HOURLY "F" RATING OF THE FIRESTOP <br />SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED AS SHOWN IN THE FOLLOWING <br />TABLE. THE HOURLY "T" RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE <br />HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED AS TABULATED BELOW: <br />MAX PIPE OR CONDUIT (DIA IN.) ANNULAR SPACE "F" RATING "T" RATING <br />1 IN. 0 TO Ma IN. 1 OR 2 0+, 1 OR 2 <br />4 IN. 1/4 TO 1/2 3 OR 4 3 OR 4 <br />4 IN. 0 TO 1/4 1 OR 2 0 <br />4 IN. 1/4 TO 1/2 3 OR 4 0 <br />4 IN. 3/16 TO 3/8 1 OR 2 0 <br />+ WHEN COPPER IS USED, "T" RATING IS 0 H. <br />MINNESOTA MINING & MFG. CO. - TYPES CP-25 S/L, CP-25 N/S, CP-25 WB, CP-25 WB+ <br />• BEARING THE UL CLASSIFICATION MARKING <br />1, 2, 3, 4 HOUR FIRE RATED GYP. / STUD WALL ASSEMBLY <br />l 1 !1 SCALE = NONE <br />AWARNING_ <br />Arc Flash and Shock Hazard <br />Nomin.l Sy..m Vo g. InclEenl fin.rpy (ullcm') <br />me Fi..n Souna.ry wortmS ol•rmo• <br />Re•iricl•E A...•.. PPE Hm,,d C.I.pory <br />L11146 APPm¢h Nc N.nny or Clothing <br />O Long n-vOft.•. Shin Ow SmG oid oovual <br />H-,o oL..m•r P-S, <br />OH., <br />O FI..h Bu11 _.1 O Sa1c,N. o H.m NN Lin., <br />136-b11 Oop01n <br />OFI.•h Stu P.M• 13,31- 13 <br />OS-r-ry 01..... <br />13 B"II Mood 13 1-.1 1313 <br />-iny Pro hon <br />OP.na OP•d,. O <br />OHnvy Dory w..mo olov. <br />Equipment ID: Date: <br />NOTES: <br />PROVIDE ARC FLASH HAZARD LABELING AND FIELD MARK ALL ELECTRICAL EQUIPMENT AS PART OF <br />ARC FLASH RISK ASSESSMENT PER 2015 EDITION OF NFPA 70E 130.50). THE LABEL MUST CONTAIN <br />THE FOLLOWING INFORMATION: <br />1. KNOWN SYSTEM VOLTAGE. <br />2. ARC FLASH BOUNDARY. <br />3. AT LEAST ONE OF THE FOLLOWING: <br />a. AVAILABLE INCIDENT ENERGY AND THE CORRESPONDING DISTANCE, OR THE ARC <br />FLASH PPE CATEGORY IN TABLE 130.7(C)(15)(A)(b) OR 130.7(C)(15)(B) FOR THE <br />EQUIPMENT, BUT NOT BOTH. <br />b. MINIMUM ARC RATING OF CLOTHING. <br />c. SITE -SPECIFIC LEVEL OF PPE. <br />ARC FLASH WARNING LABEL <br />DETAIL <br />UL SYSTEM No. CAJ1012 <br />(FORMERLY SYSTEM No. 129) <br />"F" RATING - 1 HR. <br />'T' RATING - 0 HR. <br />"L" RATING AT AMBIENT - LESS THEN 1 CFM/SQ. FT. (SEE ITEM 4) <br />"L" RATING AT 400 F - LESS THEN 1 CFM/SQ. FT. (SEE ITEM 4) <br />SECTION A -A SECTION A -A <br />(FLOOR ASSEMBLY) (WALL ASSEMBLY7 <br />1. FLOOR OR WALL ASSEMBLY - MIN. 5" THICK REINFORCED NORMAL WEIGHT (100-150 pcf) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF <br />ANY UL CLASSIFIED CONCRETE BLOCKS". MAX. DIAMETER OF OPENING IS 6INCHES. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE <br />FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS. <br />2. THROUGH - PENETRANTS - ONE METALLIC PIPE OR CONDUIT TO BE CENTERED WITHIN FIRESTOP SYSTEM. A NOM ANNULAR SPACE OF 3/4" <br />IS REQUIRED WITHIN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE FLOOR OR WALL <br />ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES OR CONDUITS MAY BE USED: <br />a. STEEL PIPE - NOM 4" DIA (OR SMALLER) SCHEDULE 5 (OR HEAVIER) STEEL PIPE. <br />b. CONDUIT - NOM 4" DIA (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL CONDUIT. <br />3. PACKING MATERIAL - MIN 3" THICKNESS OF MIN 4 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT <br />FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR AS REQUIRED TO ACCOMMODATE THE REQUIRED <br />THICKNESS FILL MATERIAL. PACKING MATERIAL TO BE CENTERED IN WALLS MID -DEPTH AND RECESSED TO ALLOW FOR INSULATION OF <br />FILL MATERIAL. <br />4. FILL, VOID OR CAVITY MATERIAL-- SEALANT OR FOAM - MIN 1/2" THCKNESS OF FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP <br />SURFACE OF FLOOR. IN WALLS, FILL MATERIAL TO BE APPLIED ON EACH SIDE OF PACKING MATERIAL. FOAMED SILICONE TO BE INSTALLED <br />AS DESCRIBED IN THE MANUFACTURER'S APPLICATION INSTRUCTIONS AT A DENSITY OF 14 pcf MIN TO 21 pcf MAX. THE THICKNESS OF FILL <br />MATERIAL IS DEPENDANT UPON THE TYPE OF FILL MATERIAL AS SHOWN IN THE TABLE BELOW: <br />FILL MATERIAL IDENTIFICATION MIN. THK OF FILL MATERIAL, In. <br />TYPE FB-2001 1 <br />TYPE FB-2000 OR FB-2003 1/2 <br />MINNESOTA MINING & MFG Co. - TYPES FB-2000, FB-2000+, FB-2001, FB-2003 (FLOORS ONLY). (NOTE: L RATINGS APPLY ONLY WHEN FB-2000+ <br />IS USED.) <br />- BEARING THE UL CLASSIFICATION MARKING <br />I HOUR FIRE RATED MASONRY FLOOR / WALL <br />LETTER (FILL) COLOR SHALL <br />BE BLACK <br />LETTERING SHALL BE y" <br />HIGH <br />NHA <br />120/208V, 3PH, 4W <br />FED FROM MSB BKR. I I <br />PHASE A - BLACK WIRE <br />PHASE B - RED WIRE <br />PHASE C - BLUE WIRE <br />NEUTRAL - WHITE WIRE <br />GROUND - GREEN WIRE <br />12,345 AFC / DATE <br />INDICATED VOLTAGE, <br />NO. OF PHASES, <br />NO OF WIRES <br />INDICATES WHERE THIS EQUIPMENT <br />IS FED FROM (TRANSFER SWITCHES <br />WILL HAVE TWO LINES) <br />ATTACH NAMEPLATE WITH (2) <br />SCREWS (MIN.) <br />NAMEPLATE COLOR <br />LIFE SAFETY = YELLOW <br />EMERGENCY =ORANGE <br />NORMAL - WHITE <br />INCLUDE MAXIMUM AVAILABLE FAULT CURRENT PER NEC 110.24(A) <br />ELECTRICAL EQUIPMENT NAMEPLATE DETAIL <br />Cq <br />0 P N L-A <br />208Y/120V 30 4W <br />kF_ <br />FED FROM MDP <br />�E] <br />0 112179 AFC 0 <br />, /16"O PRE -DRILLED HOLES. SECURE TO PANEL <br />WITH %"0 SS RIVETS (TYP. 4) <br />-EQUIPMENT NAME AS SPECIFIED ON PLANS <br />SYSTEM VOLTAGE <br />UPSTREAM EQUIPMENT SUPPLYING POWER <br />AVAILABLE FAULT CURRENT AT EQUIPMENT <br />LABEL AT TOP OF ENCLOSURE <br />NOTES: <br />1. ALL DISTRIBUTION EQUIPMENT SUCH AS PANELBOARDS, SWITCHBOARDS, DISCONNECTS, TRANSFORMERS, ETC. SHALL BE <br />PROVIDED WITH AN EQUIPMENT LABEL PER THE REQUIREMENTS OF THIS DETAIL. <br />2. LABELS SHALL BE 2-PLY ENGRAVED PLASTIC LAMINATE WITH BLACK TYPEFACE LETTERS., LABEL BACKGROUND SHALL <br />FOLLOW THE BELOW COLOR SCHEME: <br />a. NORMAL POWER -WHITE <br />b. UPS POWER - BLUE <br />c. LIFE SAFETY POWER -YELLOW <br />3. LABEL MATERIAL SHALL BE DURABLE, UV STABLE, RATED FOR OUTDOOR USE, AND ABRASION RESISTANT. WHERE ATTACHED TO <br />NEMA 4X EQUIPMENT, LABELS SHALL IN ADDITION BE CHEMICAL RESISTANT. <br />4. LABELS SHALL BE PERMANENTLY ATTACHED TO ENCLOSURE COVER WITH RIVETS UNLESS DOING SO COMPROMISES ITS NEMA / IF <br />RATING. LABELS FOR ENCLOSURES WITH WELDED SEAMS AND GASKETED DOORS SUCH AS THOSE RATED NEMA 12 OR NEMA 4 <br />SHALL BE INSTALLED USING PERMANENT WEATHER-, UV-, AND TEMPERATURE -RESISTANT DOUBLE -SIDED MOUNTING TAPE ONLY. <br />5. A SUBMITTAL WITH A COMPLETE LIST OF EQUIPMENT LABELS SHALL BE PROVIDED FOR ENGINEER APPROVAL PRIOR TO ORDERING. <br />6. LABELS SHALL INDICATE NO LESS THAN THE FOLLOWING: <br />a. EQUIPMENT NAME. <br />b. THE NOMINAL SYSTEM VOLTAGE WHICH SAID EQUIPMENT IS CONNECTED TO. <br />c. THE EQUIPMENT NAME SUPPLYING POWER TO SAID EQUIPMENT. <br />d. THE AVAILABLE FAULT CURRENT AT SAID EQUIPMENT. <br />LABEL DETAIL <br />NOTES: <br />1. ALL CONDUCTOR CONNECTIONS ARE TO BE EXOTHERMIC <br />WELD TYPE. <br />2. UL LISTED WATER PIPE CLAMP SIZED ACCORDINGLY. <br />3. UL LISTED REBAR CLAMP SIZED ACCORDINGLY. <br />4. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A NEW <br />GROUND ROD AS INDICATED. <br />NOT ALL GROUNDING ELECTRODES SHOWN MAY BE <br />PRESENT AT SITE. PER N.E.C. ARTICLE 250.50, THE <br />ELECTRICAL CONTRACTOR SHALL BOND TOGETHER ALL <br />PRESENT GROUNDING ELECTRODES. <br />MAIN BONDING JUMPER <br />(SIZE PER NEC 250.102) <br />METAL FRAME OF THE <br />BUILDING OR STRUCTURE <br />(NEC 250,52 (A) (2)) G N <br />SERVICE ENTRANCE EQUIPMENT <br />PER BONDING JUMPER GROUNDING ELECTRODE CONDUCTOR <br />BONDING JUMPER (SIZE PER NEC 2 PER (SIZE PER NEC 250.66) (SIZE PER NEC 250.66) <br />- SEE NOTE 2 (TYP.) <br />BONDING JUMPER (SIZE PER NEC 250.66) <br />NON-METALLIC PROTECTIVE SLEEVE <br />SEE NOTE 3 (TYP.) <br />CONCRETE ENCASED REBAR <br />(NEC 250.52 (A) (3)) <br />METAL UNDERGROUND WATER PIPE <br />GROUND ROD (NEC (NEC 250.52 (A) (1)) <br />250.52 (A) (5)) <br />(S:) GROUNDING ELECTRODE SYSTEM DETAIL <br />- MnM17 I Tr 7 n I 'CAT R - <br />ALIGN HORN ONLY DEVICE WITH TOP OF DOOR <br />FRAME, STOBE OR HORN/STROBE DEVICE 80" <br />AFF TO BOTTOM OF STROBE LENS <br />FIRE ALARM HORN ONLY, <br />STROBE OR HORN/STROBE, LLLL���QJJJJ <br />PAINT TO MATCH WALL 2" ABOVE BACKSPLASH <br />ALIGN WHEN MOUNTED Q <br />ON SAME WALL ( Q <br />4" ABOVE COUNTER W <br />W/0 BACKSPLASH L <br />O <br />FIRE ALARM PULL STATION ° ° <br />1 ° <br />I Q CABINET - <br />o I* <br />' Y �.P (TYP.) <br />v <br />010010 <br />FINISHED FLOOR <br />NOTES: <br />1. MOUNTING HEIGHTS SHOWN ARE FROM FINISHED FLOOR (A.F.F.), UNLESS OTHERWISE NOTED. <br />2. LOCATIONS OF OUTLETS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL TAKE PRECEDENCE OVER <br />THESE MOUNTING HEIGHTS. FIELD LOCATE OUTLETS WITH ARCHITECT DURING ROUGH -IN. <br />3. INSTALL OUTLETS THAT ARE IN CLOSE PROXIMITY ON THE SAME CENTERLINE. OUTLETS THAT ARE <br />WITHIN T-0" HORIZONTALLY AND WITHIN 1'-0" VERTICALLY SHALL BE INSTALLED ON THE SAME <br />HORIZONTAL CENTERLINE LOCATED HALF WAY BETWEEN THE HEIGHTS SHOWN. OUTLETS THAT ARE <br />MORE THAN 1'-0" APART VERTICALLY SHALL BE INSTALLED ON THE SAME VERTICAL CENTERLINE. <br />4. VERIFY MOUNTING HEIGHT WITH LOCAL AUTHORITY. <br />5. ADA REQUIREMENTS SHALL SUPERCEDE STANDARD MOUNTING HEIGHTS WHEN THERE IS A <br />CONFLICT. <br />STANDARD MOUNTING HEIGHTS DETAIL <br />GULF COAST <br />ELECTRICAL DESIGN <br />2111 Sunnydale Blvd. Suite D <br />Clearwater, FL 33765 <br />(727) 330-4937 1 www.GCElectricalDesign.com <br />Florida Board of Professional Engineers #33905 <br />Loll <br />80 <br />:- S OF <br />•W♦ <br />S�ONAL ;% �13-/a1 <br />CORY A GLASS V.E. #80467 <br />Revisions Date By <br />Mark A. Jonnatti <br />Florida AR 0010778 <br />Jonnatti Architecture, Inc. <br />Florida AA 0003371 <br />JONNATTI <br />ARCHITECTURE <br />INCORPORATED <br />21021 US Highway 19 N <br />Clearwater, FL 33765 <br />(727) 725-ARCH <br />(72 7) 725-2 603 fx <br />IV717W.jarch.com <br />info@jarch.com <br />Jonnatti Architecture <br />Incorporated 2019 <br />ZEPHR <br />RETAIL <br />DEVELOPMENT <br />US HWY 301 <br />GALL BLVD <br />ZEPHYRHILLS <br />FLORIDA <br />33542 <br />ELECTRICAL <br />NOTES AND <br />DETAILS <br />(-Drawn <br />MAJ <br />Check <br />MAj <br />Date <br />JULY 20, 2021 <br />Scale <br />AS -NOTED <br />Job No <br />ZEPHR RB <br />Sheet: <br />E100 <br />