ELECTRICAL LEGEND <br />SYMBOL <br />DESCRIPTION <br />41 LED LINEAR STRIP FIXTURE <br />O <br />h N <br />Y <br />WALL MOUNTED LIGHT FIXTURE <br />LETTER DENOTES MARK IN LIGHTING FIXTURE SCHEDULE <br />0 N <br />RECESSED CEILING MOUNTED CAN LIGHT FIXTURE <br />LETTER DENOTES MARK IN LIGHTING FIXTURE SCHEDULE <br />gN <br />WALLPACK FIXTURE <br />LETTER DENOTES MARK IN LIGHTING FIXTURE SCHEDULE <br />EMX <br />EMERGENCY/EXIT COMBO LIGHT FIXTURE <br />LETTER DENOTES MARK IN FIXTURE SCHEDULE <br />EX <br />e <br />EXIT LIGHT FIXTURE <br />LETTER DENOTES MARK IN FIXTURE SCHEDULE <br />1�>EM <br />EMERGENCY LIGHT FIXTURE <br />LETTER DENOTES MARK IN FIXTURE SCHEDULE <br />FLUSH MOUNTED SINGLE POLE WALL SWITCH <br />$3 <br />FLUSH MOUNTED 3-WAY WALL SWITCH, 20 AMP <br />FLUSH MOUNTED DUPLEX WALL RECEPTACLE, NEMA 5-15R, MOUNTED AT 1911 AFF UNLESS NOTED <br />OTHERWISE <br />-_ <br />ELECTRICAL DISCONNECT SWITCH; SEE ELECTRICAL NOTES <br />JUNCTION BOX WITH COVER SIZED FOR THE NUMBER OF CIRCUITS SHOWN TERMINATING AT THAT <br />LOCATION. <br />VOICE/DATA JACK WITH 2 RUNS CAT 6 WIRE TO VOICE DATA PANEL <br />PANEL <br />ELECTRICAL PANEL; LETTERING IDENTIFIES PANEL <br />CIRCUITING EXAMPLE KEY <br />C KT:& a <br />DENOTES LIGHTING SWITCH LEG <br />DENOTES PANEL NAME (BY ROOM). LIGHTING PLAN ONLY <br />DENOTES CIRCUIT NUMBER <br />DISCONNECT EXAMPLE KEY <br />3P 60 0 3R <br />NUMBER OF POLES NEMA WEATHER RATING <br />DISCONNECT RATING FUSE SIZE <br />("NF" DENOTES NON -FUSED ) <br />POWER RISER NOTES: <br />V NEW 120/208V, 3-PHASE, PAD MOUNTED TRANSFORMER. <br />ONEW SERVICE ENTRANCE FEEDER. COORDINATE UTILITY CONNECTION POINT WITH <br />LOCAL UTILITY PRIOR TO INSTALLATION. <br />O W-PHASE <br />ENEMETER CENTER H RON <br />SER�AED TENANTBREAKERSSHALLBE SIZEDASASSHOWN VICEERANCE <br />SHOWN ON THE RISER DIAGRAM. <br />OFURNISH AND INSTALL NEW 1200 AMP MAIN METER CENTER TERMINATION CABINET <br />WITH 1,200 AMP MAIN CIRCUIT BREAKER (NEMA3R RATED). <br />OFURNISH AND INSTALL NEW 3-PHASE BRANCH METER/CIRCUIT BREAKER SECTION <br />W/ (2) 200A METER SOCKETS AND BREAKERS FOR PANELS 'B' & 'C' AND (1) <br />200A METER SOCKET WITH IOOA BREAKER FOR PANEL 'H'. <br />OFURNISH AND INSTALL NEW 3-PHASE BRANCH METER/CIRCUIT BREAKER SECTION <br />W/ (2) 400A METER SOCKETS AND BREAKERS FOR PANEL 'A'. <br />O7 FURNISH AND INSTALL NEW 120/208V, 3-PHASE, IOOA. MLO, PANEL 'H', 30 CKT. <br />(NEMA3R). <br />80 FURNISH AND INSTALL NEW 120/208V, 3-PHASE, 200A. MLO, PANEL 'C', 42 CKT. <br />O9 FURNISH AND INSTALL NEW 120/208V, 3-PHASE, 200A, MLO, PANEL 'B', 42 CKT. <br />10 FURNISH AND INSTALL NEW 120/208V, 3-PHASE, 400A. MLO, PANEL 'A', 84 CKT. <br />11 NEW 208V, 3-PHASE SURGE PROTECTION DEVICE. <br />12 03/0 COPPER GROUNDING ELECTRODE CONDUCTOR. <br />13 NEW TIMECLOCK W/ PHOTOCELL (NEMA3R RATED). SEE TIMECLOCK DETAIL. <br />SEE SHEET EI.2. <br />SERVICE ENTRANCE FEEDER SCHEDULE <br />1200A SERVICE ENTRANCE FEEDER: 3 SETS OF - (3) 600 MCM CU <br />AND (1) 600 MCM CU NEUTRAL. EACH IN 4' PVC CONDUIT. <br />FEEDER SCHEDULE <br />CU-100 <br />IOOA PANEL FEEDER: (3) 03 CU (D 03 CU NEUTRAL & <br />08 <br />(D CU GROUND IN 2' CONDUIT. <br />CU-200 <br />200A PANEL FEEDER: (3) 3/0 CU (U 3/0 CU NEUTRAL <br />•6 <br />& (D CU GROUND IN 2' CONWIT. <br />400A PANEL FEEDER: (3) 600 MCM CU. (D 600 MCM CU NEUTRAL <br />CU-400 <br />& (D 03 CU GROUND IN 4' CONDUIT. <br />D GRADE <br />f- CONDUIT AS REQUIRED <br />SERVICE TRENCHING NOTE: <br />CONTRACTOR SHALL TRENCH AND INSTALL UNDERGROUND SERVICE <br />AS SHOWN, & AS REQUIRED BY UTILITY. CONTRACTOR SHALL HAVE <br />THE EXISTING UTILITIES LOCATED BY A LOCAL SERVICE, OR THE <br />UTILITY, PRIOR TO ANY DIGGING, ENTIRE TRENCH ROUTE AS <br />INTENDED. <br />_TYPICAL SERVICE TRENCH CONFIGURATION <br />sCALEs NONE <br />ELECTRICAL POWER KEYNOTES: <br />U NEW UNDERGROUND SERVICE ENTRANCE FEEDER FROM UTILITY TRANSFORMER. 120/208V, <br />3-PHASE. SEE POWER RISER. <br />O NEW 120/208V, 3-PHASE, 4-WIRE, 1200A MCB, NEMA3R METER CENTER. SEE POWER RISER. <br />O NEW UNDERGROUND PANEL FEEDER CONDUIT FROM METER CENTER. TO BE INSTALLED AND <br />STUBBED UP INSIDE AT PANEL LOCATION. SEE POWER RISER. <br />NEW UNDERGROUND SERVICE LATERAL CONDUIT FROM METER CENTER. TO BE INSTALLED AND <br />40 STUBBED UP INSIDE AT PANEL LOCATION. SEE POWER RISER. <br />ONEW RTU BY MECHANICAL CONTRACTOR. PROVIDE POWER WIRING AS SHOWN. CONFIRM 'MCA' <br />AND 'MOCP' WITH HVAC SUBMITTAL PRIOR TO ORDERING SWITCHGEAR AND BREAKERS. <br />OFURNISH AND INSTALL NEW (2) 2' CONDUIT FOR PHONE & DATA TO TENANT SPACE. <br />PENETRATE WALL AND STUB OUT AND CAP WITH PULL -STRING FOR EACH SPACE. RUN TO <br />SERVICE PROVIDER CONNECTION POINT. ASSUME 50FT OF CONDUIT AND TRENCH FOR EACH <br />CONDUIT IF THE SERVICE PROVIDER CONNECTION POINT IS NOT KNOWN. <br />ODESIGN INTENT IS FOR THESE CONDUITS TO BE EITHER: (D TURNED UP DIRECTLY TO LOW <br />VOLTAGE BOARD AT TIME OF BUILD -OUT, OR (2) EXTENDED TO LOW VOLTAGE BOARD AND <br />TURNED UP AT TIME OF BUILD -OUT. <br />OFURNISH AND INSTALL NEW OUTDOOR GFCl/WP RECEPTACLES W/COVER AS SHOWN AND <br />CIRCUIT TO PANEL 'H' (TYP.). <br />O NEW 120/208V, 3-PHASE, 400A, MLO, PANEL 'A' (NEMAD, 84CKT. <br />10 NEW 120/208V, 3-PHASE, 200A, MLO, PANEL 'B (NEMAD, 42CKT. <br />11 NEW 120/208V, 3-PHASE, 200A, MLO, PANEL 'C' (NEMAD, 42CKT. <br />12 NEW 120/208V, 3-PHASE, IOOA, MLO, PANEL 'H' (NEMA3R). 30CKT. <br />13 EXTERIOR TIMECLOCK. <br />ASSUMED O <br />AFC: 78,160 <br />00 <br />GRADE <br />SOCKET RATING BREAKER SIZE PROVIDED <br />A <br />08 <br />MID <br />LOAD SERVED <br />METER SOCKET DETAIL <br />SC" NONE <br />EXTERIOR I SUITE "C" <br />INTERIOR <br />KC, <br />CU-200 <br />SUITE "B" <br />INTERIOR <br />O <br />CU-200 <br />I. I 1 _.'.lilt I <br />XFMR - ~ a <br />__-__.-__----_-__-___--_-_-_--.______- _-- -_--- j � <br />O8 �� o <br />a <br />PHO /DATA 3 F (pit <br />13 12 I t <br />6 _-i- -- U3 - I Qom- - �1 1- -- <br />L4J I � c�rnOj O ® c�ln 1G O <br />4 m 4 <br />0 <br />U U <br />6 <br />BUILDING EXTERIOR (WEST) <br />3 <br />AFC, 45-89 O ® O <br />m <br />21m <br />MAMA <br />OB <br />OB <br />off PIK <br />mm A <br />120/208VO <br />3PH <br />B <br />MC8 <br />TOINII B <br />e <br />OB <br />TBm C <br />N <br />B <br />G <br />via <br />•3/0 CU <br />NEW 120/208 3-PHASE SERVICE <br />POWER RISER DIAGRAM <br />NOT TO SCALE <br />leg <br />�W <br />d <br />7.5 TON <br />5 TON <br />J O <br />® \ 3P/60/NF/N3R <br />3P/60/NF/N3R 1 3 <br />a <br />3 co <br />� <br />ao� <� <br />a CKT:A-2,4,6 <br />CKT:A-1,3,5 <br />v <br />PHOTOCELL <br />TENANT 'A' <br />100 EXPOSED CLG. <br />(ASSUMED) <br />SUITE "A" <br />INTERIOR <br />Ct: <br />CU-400 <br />1 A_L.i <br />ELECTRICAL TO AVOID AND CONFLICTS <br />WITH ROOF, DRAIN/DOWN SPOUTS AND <br />ROOF LADDER (NOT SHOWN). <br />4 O6 PHONE/DATA <br />----------�---------- --- ---^\ <br />c�ln 11 O <br />1 <br />U <br />Y <br />U <br />TAT 'B' <br />EXPOSED CLG. <br />(ASSUMED) <br />TENANT 'C' <br />00 EXPOSED CLG. <br />(ASSUMED) <br />ELECTRICAL POWER <br />FLOOR PLAN <br />SCALE „a 11-011 <br />GULF COAST <br />ELECTRICAL DESIGN <br />2111 Sunnydale Blvd. Suite D <br />Clearwater, FL 33765 <br />(727) 330-4937 1 www.GCElectricaiDesign.com <br />Florida Board of Professional Engineers #33905 <br />80 <br />i� AT O <br />10 <br />�•ID <br />........ <br />CORY A GLASS P.E. #80467 <br />I L I_ I ----Ll I _ L! I I <br />ONE <br />Revisions Date By <br />Mark A. Jonnatti <br />Florida AR 0070778 <br />Jonnatti Architecture, Inc. <br />Florida AA 0003377 <br />ONNATTI <br />ARCHITECTURE <br />INCORPORATED <br />21021 US Highway 19 N <br />Clearwater, FL 33765 <br />(727) 725-ARCH <br />(727) 725-2603 fx <br />wwzv. jarch. com <br />info@jarch.com <br />Jonnatti Architecture <br />Incorporated 2019 <br />ZEPHR <br />RETAIL <br />DEVELOPMENT <br />US HWY 301 <br />GALL BLVD <br />ZEPHYRHILLS <br />FLORIDA <br />33542 <br />ELECTRICAL <br />POWER PLAN <br />(Drawn <br />MAJ <br />Check <br />MAJ <br />Date <br />JULY 20, 2021 <br />Scale <br />AS -NOTED <br />Job No <br />ZEPHR RB <br />Sheet: <br />El 1 <br />