PIPING SYSTEM LABELS
<br />WATER WASTE OR STORM
<br />DCW DOMESTIC COLD WATER -SAN- WASTE OR SOIL
<br />DHW DOMESTIC HOT WATER SD SUBSOIL DRAIN
<br />DHR DOMESTIC HOT WATER RETURN S STORM
<br />CSW COLD SOFT WATER OD- OVERFLOW DRAIN
<br />HT HEAT TRACE HOT WATER FM FORCE MAIN
<br />NPW NON -POTABLE WATER -CWW CLEARWATER WASTE
<br />DI DEIONIZED WATER IW INDIRECT WASTE
<br />RO- REVERSE OSMOSIS WATER -GIN GREASE WASTE
<br />PW PURE WATER CRW CORROSION RESISTANT
<br />PCW PROCESS COLD WATER WASTE
<br />PHW PROCESS HOT WATER - - - - - UNDERFLOOR WASTE OR
<br />SOIL, SUBSOIL, STORM &
<br />PHR PROCESS HOT WATER RETURN FORCE MAIN
<br />LCW LAB COLD WATER
<br />LHW LAB HOT WATER
<br />LHR LAB HOT WATER RETURN VENT
<br />TF TRAP FILLER LINE - - -V- - - VENT
<br />TW TEMPERED WATER - -CWV- - CLEARWATER VENT
<br />C
<br />0 ■
<br />0
<br />-CRV- - CORROSION RESISTANT VENT
<br />ABBREVIATIONS
<br />AFF ABOVE FINISHED FLOOR
<br />ASME AMERICAN SOCIETY OF MECHANICAL
<br />ENGINEERS
<br />CO
<br />CLEAN OUT
<br />CW
<br />COLD WATER (POTABLE)
<br />ETR
<br />EXISTING TO REMAIN
<br />ETD
<br />EXISTING TO DEMO
<br />FCO
<br />FLUSH CLEAN OUT
<br />FPM
<br />FEET PER MINUTE
<br />FPS
<br />FEET PER SECOND
<br />HB
<br />HOSE BIBB
<br />HW
<br />HOT WATER
<br />ID
<br />INSIDE DIAMETER
<br />IN
<br />INCHES
<br />MAX
<br />MAXIMUM
<br />MH
<br />MANHOLE
<br />MIN
<br />MINIMUM
<br />N/A
<br />NOT APPLICABLE
<br />NTS
<br />NOT TO SCALE
<br />SQ.FT
<br />SQUARE FOOT (FEET)
<br />SS
<br />STAINLESS STEEL
<br />TAB
<br />TESTING, ADJUSTING, BALANCE
<br />UL
<br />UNDERWRITERS LABORATORY
<br />VTR
<br />VENT THRU ROOF
<br />WCO
<br />WALL CLEAN OUT
<br />YCO
<br />YARD CLEAN OUT
<br />PLUMBING SYMBOLS AND ABBREVIATIONS
<br />PIPING SYMBOLS VALVE & GENERAL SYMBOLS DRAWING SYMBOLS DRAINS AND CLEANOUTS
<br />SINGLE DOUBLE SINGLE DOUBLE GATE EXISTING PIPING TO REMAIN X }-- VALVE ® ® FLOOR DRAIN/FLOOR SINK 106 WEST NORTH BAY STREET 1 TAMPA, FL 33603
<br />ELBOW DOWN - CIRCUIT SETTER OR 2 DETAIL NUMBER www.cjaegroup.com
<br />EXISTING -ill-
<br />GLOBE VALVE BALANCING VALVE ( ROOF DRAIN
<br />� H4 DRAWING NUMBER
<br />O ELBOW UP -� LINE CONTINUATION BREAK CHECK VALVE PLUG VALVE WHERE DRAWN 0 HUB DRAIN
<br />PRESSURE REDUCING
<br />WYE STRAINER WITH VALVE (PRV)
<br />-►-- FLOW DIRECTION row DRAIN VALVE SECTION LETTER
<br />I BOTTOM CONNECTION WATER LEVEL CONTROLLER A (}--) FIXTURE WASTE TRAP
<br />.l t (45° OR 90°) um FLEXIBLE CONNECTION H7
<br />v � � FLOW METER DRAWING NUMBER 0�� CLEANOUT
<br />N/A CONNECTION POINT
<br />ANGLE GLOBE VALVE WHERE SHOWN -_ Lm
<br />TOP CONNECTION h --���- BUTTERFLY VALVE xT__4 DRAIN FCO 13
<br />Q FLOOR CLEANOUT
<br />-- (45° OR 90°) OR ECCENTRIC REDUCER SHUTOFF VALVE
<br />-��-- BALL VALVE P NDIIIPMENT CATED) {PUMP ENGIN t E R I N GO'
<br />--► D 45° PIPE RISE(R) /DROP(D) - THERMOMETER
<br />--
<br />CONCENTRIC REDUCER CONTROL VALVE MECHANICAL •ELECTRICAL -PLUMBING
<br />TEE (REFER TO (fi�--�J PRESSURE GAUGE REVISION REFERENCE
<br />_ SPECIFICATION FOR SIDE, --- PRESSURE REGULATING `' L 1 800 HIGHLAND AVE. STE 102
<br />TOP OR BOTTOM TEE) VALVE
<br />VACUUM BREAKER GENERAL OR SPECIAL ORLANDO, FL 32803
<br />PRESSURE SAFETY NOTES REFERENCE CA LIC. NO.: 31963
<br />VALVE PHONE: (407) 250-8485
<br />WWW.DCL-ENG.COM
<br />PLUMBING SPECIFICATIONS
<br />APPLICABLE CODES AND STANDARDS:
<br />1. FLORIDA BUILDING CODE 7TH EDITION (2020) - BUILDING, MECHANICAL, PLUMBING AND ENERGY CONSERVATION
<br />2. NFPA-1 UNIFORM FIRE CODE (2015)
<br />3. NFPA-70 NATIONAL ELECTRICAL CODE (2017)
<br />4. NFPA-72 NATIONAL FIRE ALARM CODE (2016)
<br />5. NFPA-99 HEALTH CARE FACILITIES CODE (2015)
<br />6. NFPA-101 LIFE SAFETY CODE (2018)
<br />7. LATEST EDITION OF ALL OTHER NFPA ARTICLES NOT LISTED, AS ADOPTED BY THE STATE FIRE MARSHAL
<br />8. UNDERWRITERS LABORATORIES, INC. PUBLICATIONS
<br />9. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
<br />10. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
<br />11. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
<br />12. NATIONAL ELECTRICAL SAFETY CODE
<br />13. REQUIREMENTS OF LOCAL POWER CORPORATION
<br />14. ADA STANDARDS FOR ACCESSIBLE DESIGN (2010)
<br />15. AMERICAN SOCIETY FOR TESTING AND MATERIAL (ASTM)
<br />16. THE OCCUPATION SAFETY AND HEALTH ACT (OSHA)
<br />17. FLORIDA ADMINISTRATIVE CODE 69A3.012
<br />18. THE FACILITY GUIDELINES INSTITUTE - GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES (FGI - 2018)
<br />19. ASTM LATEST STANDARDS.
<br />GENERAL:
<br />1, CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIAL, EQUIPMENT, ACCESS PANELS, CONTROL SYSTEMS, DEVICES, PERMITS AND SERVICES NECESSARY FOR FURNISHING AN INSTALLATION OF A COMPLETE SERVICEABLE MECHANICAL SYSTEM AS
<br />OUTLINED IN THE CONTRACT DRAWINGS AND SPECIFICATIONS. THE SYSTEMS, EQUIPMENT, DEVICES AND ACCESSORIES SHALL BE INSTALLED, FINISHED AND ADJUSTED FOR CONTINUOUS AND PROPER OPERATION.
<br />2. ALL MECHANICAL SYSTEMS ARE TO BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE SECTIONS OF THE NFPA STANDARDS, ANSI STANDARDS, LOCAL CODES, LOCAL ORDINANCES, AMENDMENTS AND MANUFACTURER RECOMMENDATIONS.
<br />3. ALL MATERIALS SHALL BE NEW (UNLESS OTHERWISE INDICATED) ANY DAMAGE EQUIPMENT SHALL BE REPLACE AT NOT COST TO THE OWNER. ALL EQUIPMENT SHALL BE STORED IN A SAFE, DRY PLACE IN THE MANUFACTUREROS ORIGINAL PACKAGING
<br />UNTIL READY FOR USE. THE OWNER SHALL NOT BE RESPONSIBLE FOR PROVIDING ANY PART OF THE PROJECT, UNLESS SPECIFICALLY NOTED.
<br />4. CONTRACTOR SHALL WARRANTY ALL MECHANICAL SYSTEMS, EQUIPMENT, PARTS AND LABOR FOR A PERIOD OF ONE (1) YEAR. ONE YEAR PERIOD SHALL NOT START UNTIL PROJECT IS COMPLETED AND CONTRACTOR HAD RECEIVED CERTIFICATED OF
<br />COMPLETION. ALL EQUIPMENT AND WORK (LABOR + PARTS) SHALL BE FULLY GUARANTEED. ALL REPAIRED MADE DURING THE GUARANTEE SHALL BE GUARANTEE FOR AN ADDITIONAL YEAR FROM THE TIME THE REPAIR IS COMPLETED.
<br />CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR ANY DAMAGE TO THE BUILDING, ITS COMPONENTS, OTHER EQUIPMENT OR ANY PROCESS, CAUSED BY DEFECTS OR IMPROPER INSTALLATIONS OF ITS EQUIPMENT.
<br />5. ALL WORK ON THIS PROJECT SHALL BE COORDINATED WITH THE OWNER AND ALL OTHER TRADES PRIOR TO BEGINNING ANY WORK OR ORDERING ANY MATERIALS. COORDINATE ALL WORK FOR SIZE, LOCATION, CLEARANCE, ACCESS AND ELECTRICAL
<br />CONNECTIONS WITH ALL THE TRADES. CONTRACTOR SHALL NOTIFY THE ARCHITECT THE ARCHITECT IN WRITING OF ANY CONFLICTS, CODE OR SAFETY ISSUES THAT MAY EXIST PRIOR TO ANY FABRICATION OR ORDERING OF EQUIPMENT. RESOLUTION
<br />OF SUCH CONFLICTS WHICH ARE NOT REPORTED PRIOR TO CONSTRUCTION SHALL REMAIN RESPONSIBILITY OF THE CONTRACTOR AND CHANGE ORDER PROPOSALS FOR SUCH WORK WILL NOT BE ACCEPTED.
<br />6. THESE DRAWINGS AND SPECIFICATIONS REPRESENT THE DESIGN INTENT BASED ON INFORMATION AVAILABLE AT THE TIME OF DESIGN. ANY SUBSTANTIAL MODIFICATIONS OR ALTERATIONS MADE DURING THE CONSTRUCTION PHASE SHALL BE
<br />REPORTED TO THE ENGINEER PRIOR TO WORK. MODIFICATIONS MADE WITHOUT THE ENGINEER'S WRITTEN APPROVAL SHALL REMAIN THE RESPONSIBILITY OF THE CONTRACTOR
<br />7. CONTRACTOR TO FIELD ROUTE PIPING AS REQUIRED. FOR CLARITY, PIPING RISERS AND DROPS ARE NOT SHOWN, CONTRACTOR TO PROVIDE AT NO ADDITIONAL COST TO THE OWNER ALL PIPING OFFSETS, BENDS AND TRANSITIONS REQUIRED FOR
<br />COMPLETE FUNCTIONAL SYSTEM. PAINT ALL EXPOSED PIPING BLACK EXCEPT FOR GAS PIPING.
<br />8. WALL, ROOF AND CEILING OPENINGS INDICATED ON DRAWINGS ARE NOMINAL DIMENSIONS ONLY, ADJUST OPENING AS REQUIRED. ALL PIPING AND/OR EQUIPMENT PENETRATIONS SHALL BE SLEEVED AND FIRE RATED AS REQUIRED. CONTRACTOR TO
<br />PATCH ALL FLOOR PENETRATIONS.
<br />9. HANG PIPING FROM STRUCTURE AS NECESSARY. COORDINATE WITH STRUCTURAL/ARCHITECT. PROVIDE SUPPORTING AS REQUIRED FOR INSTALLATION OF EQUIPMENT.
<br />10. MECHANICAL PLANS ARE IN GENERAL DIAGRAMMATIC IN NATURE SHALL BE READ IN CONJUNCTION WITH THE ARCHITECTURAL, PLUMBING, ELECTRICAL AND STRUCTURAL PLANS. INFORMATION GIVEN HEREIN AND ON DRAWINGS IS AS EXACT AS COULD
<br />BE SECURED BUT IS NOT GUARANTEED. DO NOT SCALE DRAWINGS FOR EXACT DIMENSIONS.
<br />11. PROVIDE A MINIMUM OF T CLEARANCE IN FRONT OF ANY 120-240 VOLTS RATED PANELS AND DISCONNECTS AND 4' CLEARANCE IN FRONT OF ANY 480 VOLTS RATED PANELS OR DISCONNECTS, PROVIDE ADEQUATE SIDE CLEARANCE PER NEC.
<br />12. PROVIDE A MINIMUM OF 10' CLEARANCE BETWEEN OUTSIDE AIR INTAKES AND ANY VENTS OR EXHAUST OPENINGS. COORDINATE NEW OPENING OR VENTS WITH EXISTING EQUIPMENT, INTAKES AND VENTS.
<br />PLUMBING GENERAL:
<br />1. ALL PLUMBING SERVICES TERMINATE 5'-0" FROM THE BUILDING EXTERIOR WALLS.
<br />2. NO LEAD OR ASBESTOS CONTAINING MATERIALS OF ANY KIND SHALL BE USED IN THE FABRICATION OF POTABLE WATER SUPPLY SYSTEMS. GALVANIZED STEEL PIPING SHALL NOT BE USED FOR POTABLE WATER SUPPLY PIPING.
<br />3. INSTALL ALL WORK IN COMPLIANCE WITH ADA REQUIREMENTS.
<br />4. PROVIDE "P" TRAPS WITH CLEANOUTS IN THE DRAINS OF ALL FIXTURES EXCEPT THOSE WITH INTERNAL TRAPS OR AS SPECIFICALLY NOTED ON PLANS.
<br />5. PROVIDE FLOOR DRAINS WITH TRAP PRIMERS IN ALL PUBLIC BATHROOMS.
<br />6. ALL PIPING SHALL BE CONCEALED IN WALLS, CHASES, CEILINGS, ETC. UNLESS SPECIFICALLY NOTED ON DRAWINGS. ANY PIPING OR ACCESSORIES THAT MUST BE EXPOSED SHALL HAVE A POLISHED CHROME FINISH.
<br />7. INSTALL ALL VALVES AND CONTROLS IN ACCESSIBLE LOCATIONS, EXCEPT AS SPECIFICALLY NOTED ON PLANS OR PROHIBITED BY CODE.
<br />8. ALL PIPE SIZES ARE CLEAR INSIDE DIMENSIONS, COORDINATE PIPING ROUTING, DIMENSION AND ELEVATION WITH ARCHITECT/OWNER. MAKE ALLOWANCES FOR BEAMS, PIPING AND OTHER OBSTRUCTIONS
<br />9. PROVIDE MIN. 6x6 INCH PAINTED ALUMINUM ACCESS DOORS WITH FULL HINGE AND KEY, FOR ACCESS TO ALL VALVES, CONTROLS, AND ACCESSORIES CONCEALED IN PLASTER, TILE, DRYWALL, OR INACCESSIBLE CEILINGS, OR IN WALLS. GROUP DEVICES
<br />AT A SINGLE LOCATION, AS AVAILABLE.
<br />10. COORDINATE THE ELECTRICAL CHARACTERISTICS OF ALL ELECTRICAL EQUIPMENT WITH THE ELECTRICAL CONTRACTOR PRIOR TO ORDERING.
<br />11. PIPING SHALL NOT PASS THROUGH 'WORK OF ANY KIND UNLESS APPROVED BY THE ENGINEER.
<br />12. PIPING SHALL NOT BE RUN ABOVE ELECTRICAL PANELS, THROUGH ELECTRICAL ROOMS OR ANY OTHER WATER SENSITIVE AREAS, EXCEPT AS SPECIFICALLY NOTED ON PLANS.
<br />13. INSULATE ALL PIPING FROM CONCRETE WITH INSULATION MATERIAL. INSULATION SHALL HAVE A FIRE/SMOKE RATING LESS THAN 25/50.
<br />14. INSULATE ALL HOT WATER LINES IN ACCORDANCE WITH THE ENERGY EFFICIENCY CODE.
<br />15. INSTALL METALLIC PIPING AS REQUIRED BY CODE IN THE FIRE RATE WALLS,
<br />16. PROVIDE DIELECTRIC UNIONS FOR CONNECTION BETWEEN DISSIMILAR PIPES.
<br />17. INSTALL ALL EXTERIOR HOSE BIBBS 20" AFF.
<br />18. WATER SERVICE UNDERGROUND SHALL BE SEPARATED FROM SEWER LINES BY A MINIMUM OF 5 FEET OF UNDISTURBED OR COMPACTED EARTH.
<br />19. REFER TO SITE PLANS FOR METERS AND SITE UTILITIES.
<br />20. COLD AND HOT WATER SUPPLY PIPING TO EACH ROOM SHALL BE PROVIDED WITH SHUTOFF VALVES ABOVE CEILING TO ISOLATE ALL FIXTURES INSIDE THE ROOM WITHOUT INTERRUPTING MAIN SERVICE TO ALL OTHER AREAS/ROOMS.
<br />SHOP DRAWINGS AND SUBMITTALS:
<br />1. SUBMIT SHOP DRAWINGS AND MANUFACTURER'S DATA FOR ALL NEW EQUIPMENT TO ENGINEER FOR APPROVAL PRIOR TO PURCHASING AND/OR FABRICATION. SHOP DRAWINGS FOR EQUIPMENT REQUIRING ELECTRIC POWER AND/OR CONTROL WIRING
<br />SHALL INCLUDE COMPLETE WIRING DIAGRAMS.
<br />2. CONTRACTOR SHALL SUBMIT COMPLETE PLUMBING SHOP DRAWINGS FOR REVIEW BY THE ENGINEER. SHOP DRAWINGS SHALL INCLUDE COORDINATION WITH OTHER DISCIPLINES AND EXACT OPENINGS REQUIRED IN EXTERIOR WALLS AND ALL DEVICES
<br />WITH THEIR RESPECTIVE SERVICE CLEARANCES.
<br />3. SPECIFICALLY MARK GENERAL CATALOG SHEETS AND DRAWINGS TO INDICATE SPECIFIC ITEMS SUBMITTED AND ITS CORRELATION TO SPECIFIC DESIGNATION FOR PRODUCT IN DRAWINGS.
<br />4. SPECIFICALLY INDICATE PROPER IDENTIFICATION OF EQUIPMENT BY NAME AND/OR NUMBER, AS INDICATED IN SPECIFICATION AND SHOWN ON DRAWINGS.
<br />5. WHEN MANUFACTURER'S REFERENCE NUMBERS ARE DIFFERENT FROM THOSE SPECIFIED, PROVIDE CORRECT CROSS-REFERENCE NUMBERS FOR EACH ITEM. CLEARLY MARK AND NOTE SUBMITTALS ACCORDINGLY.
<br />6. SUBMITTALS THAT ARE NOT COMPLETE, NOT PERMANENT OR NOT PROPERLY CHECKED BY CONTRACTOR WILL BE RETURN WITHOUT REVIEW. IF PROJECT SITE CONTAINS MULTIPLE BUILDINGS, CONTRACTOR SHALL SUBMIT SHOP DRAWINGS
<br />INDIVIDUALLY PER DISCIPLINE.
<br />7. PLUMBING SHOP DRAWINGS WILL ONLY BE REVIEWED FOR COMPLIANCE WITH DESIGN DRAWINGS AND SPECIFICATIONS. DRAWINGS WILL NOT BE CHECKED FOR COORDINATION WITH OTHER TRADES OR BUILDINGS STRUCTURE. IT IS THE RESPONSIBILITY
<br />OF THE CONTRACTORS TO COORDINATE AND VERIFY ROUTING AND EXACT LOCATION OF SYSTEM COMPONENTS.
<br />SANITARY WASTE & VENT PIPING:
<br />1. ALL SANITARY WASTE PIPING SHALL MATCH EXISTING MATERIALS.
<br />2. ALL SANITARY WASTE PIPING 3" TO 6" SHALL BE SLOPED AT NO LESS THAN 1/8" PER FOOT. ALL SANITARY WASTE 2 1/2" AND SMALLER SHALL BE SLOPED AT NO LESS THAN 1/4" PER FOOT
<br />3. ALL SANITARY PIPING SHALL BE INSTALLED PER FBC AND APPROVED BY THE AUTHORITY HAVING JURISDICTION.
<br />4. THE MINIMUM SANITARY WASTE & VENT PIPE SIZE SHALL BE 1 1/2".
<br />5. VERIFY LOCATIONS AND INVERT ELEVATIONS OF ANY AND ALL EXISTING WASTE, VENT, AND STORM DRAIN PIPING PRIOR TO BEGINNING ANY WORK,
<br />IMAGING EQUIPMENT NOTES
<br />THESE DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE IMAGING EQUIPMENT VENDOR
<br />PLANS AND/OR DETAILS; AND THEY ARE INTENDED TO GIVE THE CONTRACTOR A GENERAL
<br />KNOWLEDGE OF THE WORK ASSOCIATED WITH THE INSTALLATION OF THE IMAGING
<br />EQUIPMENT. IT IS NOT INTENDED TO INDICATE ALL WIRING, CONNECTIONS, J-BOXES,
<br />SWITCHES, ETC, OR ANCILLARY COMPONENTS REQUIRED FOR INSTALLATION. ALL
<br />EQUIPMENT SHALL BE INSTALLED PER THE OWNER APPROVED MANUFACTURER'S
<br />INSTALLATION DRAWINGS. INSTALLATION SHALL BE COORDINATED IN FIELD WITH IMAGING
<br />EQUIPMENT MANUFACTURER.
<br />IT IS THE INTENTION OF THESE DRAWINGS THAT ALL WORK (LABOR, MATERIALS, ETC.)
<br />REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM SHALL BE PROVIDED.
<br />EQUIPMENT MANUFACTURER SHALL SUPPLY FIXED LENGTH CABLES, WHEREBY ALL
<br />MEASUREMENTS SHALL BE DETERMINED FROM ELECTRICAL TROUGH RUNS INDICATED ON
<br />THE DRAWINGS. ANY CHANGES TO EQUIPMENT PLACEMENT OR TROUGH ROUTINGS AT JOB
<br />SITE WILL CAUSE THE DELIVERY OF INACCURATE AND ERRONEOUS CABLE LENGTHS. THIS
<br />MAY RESULT IN ADDITIONAL COST FOR REPLACEMENT CABLES AND DELAY EQUIPMENT
<br />INSTALLATION. COORDINATE PLACEMENT OF ALL EQUIPMENT WITH EQUIPMENT INSTALLER
<br />PRIOR TO ROUGH -IN.
<br />ALL RADIOLOGY EQUIPMENT SHALL BE TESTED AND RECORDED FOR CHASSIS LEAKAGE IN
<br />ACCORDANCE WITH NFPA 99, SECTION 8-4.1.3.4. PROVIDE A WRITTEN REPORT, SIGNED,
<br />SEALED AND DATED BY THE PERSON SUPERVISING THE TEST FOR EACH PIECE OF
<br />EQUIPMENT TABULATION PERMITTED AND RECOMMENDED.
<br />DOMESTIC WATER PIPING:
<br />1. ALL DOMESTIC WATER PIPING SHALL MATCH EXISTING.
<br />2. ALL DOMESTIC WATER PIPING ABOVE GROUND SHALL BE TYPE "L" COPPER WITH WROUGHT COPPER FITTINGS AND LEAD FREE SOLDER JOINTS.
<br />3. ALL NEW WATER SUPPLY PIPING SHALL BE RUN OVERHEAD (DO NOT RUN WATER SUPPLY PIPING BELOW CONCRETE FLOOR SLABS) UNLESS SPECIFICALLY STATED ON PLANS OR AS ABSOLUTELY NECESSARY TO MATCH AN
<br />EXISTING INSTALLATION.
<br />4. THE MINIMUM DOMESTIC WATER PIPE SIZE SHALL BE1/2".
<br />5. ALL HOT WATER SUPPLY AND HOT WATER RECIRCULATING LOOP PIPING SHALL BE INSULATED WITH 1" THICK, MIN. R-6, CLOSED CELL FOAM INSULATION (ARMAFLEX OR EQUIVALENT).
<br />6. ALL NEW DOMESTIC WATER PIPING SHALL BE DISINFECTED BY INTRODUCING A SOLUTION OF CALCIUM HYPOCHLORITE OF 50 PARTS PER MILLION OF CHLORIDE AND AS PER AWWA STANDARDS.
<br />VENTS:
<br />1. VENT PIPING SHALL BE DWV PVC, SCHEDULE 40.
<br />2. ALL TRAPS OR TRAPPED FIXTURES SHALL BE PROVIDED WITH AN INDIVIDUAL VENT UNLESS OTHERWISE NOTED.
<br />3. CONNECT ALL VENT PIPING SHOWN TO EXISTING BUILDING MAIN VENT IN LOCATION INDICATED ON PLAN.
<br />4. SLOPE ALL HORIZONTAL VENTS SUCH THAT WATER MAY DRAIN BACK INTO THE SANITARY SYSTEM,
<br />5. SINK/FAUCET VENTS THRU ROOF WITH WEATHERPROOF RAIN CAP. COORDINATE LOCATIONS WITH EXISTING EQUIPMENT AND ARCHITECT. SEAL ROOF PENETRATION AS NECESSARY.
<br />VALVES & ACCESSORIES:
<br />1. PROVIDE WATER HAMMER ARRESTORS OR AIR CHAMBERS AS REQUIRED TO ELIMINATE WATER HAMMER AND COMPLY WITH LOCAL REGULATIONS, PARTICULARLY AT ALL APPLIANCES OR DEVICES WITH QUICK -CLOSING VALVES.
<br />ARRESTORS SHALL BE FACTORY FABRICATED, INSTALL ARRESTORS AND SIZE PER PLUMBING AND DRAINAGE INSTITUTE STANDARD PDIWH-201. HAMMER ARRESTORS SHALL BE EQUAL TO PRECISION PLUMBING PRODUCTS,
<br />PISTON TYPE.
<br />2. AIR CHAMBERS SHALL NOT BE CONSIDERED AN EQUAL TO WATER ARRESTOR AS SPECIFIED.
<br />3. PROVIDE A MAIN SHUTOFF VALVE AT THE BUILDING'S DOMESTIC WATER SERVICE ENTRANCE.
<br />4. ALL DOMESTIC WATER VALVES SHALL BE OF BRONZE BODY, TWO PIECE CONSTRUCTION, FULL PORT AND STAINLESS STEEL TRIM EQUAL TO NIBCO-585-70-68 OR APPROVED EQUAL. IF PVC OR CPVC PIPING IS UTILIZED, BALL
<br />PATTERN WITH TRUE CPVC UNION, NFS 61 EQUAL TO APEX VX SERIES OR APPROVED EQUAL, ARE ACCEPTABLE.
<br />5. PROVIDE VACUUM BREAKERS FOR ALL SILLCOCKS, HOSE BIBBS, AND WALL HYDRANTS.
<br />6. PROVIDE CLEANOUTS AT ALL CHANGES OF DIRECTION OF MORE THAN 45 DEGREES OR EVERY 50 FEET OF STRAIGHT PIPE FOR ALL SANITARY WASTE AND STORM DRAIN PIPING.
<br />7. PROVIDE CLEANOUTS AT THE BASE OF ALL STACKS. PROVIDE A YARD CLEANOUT FLUSH WITH FINISHED GRADE WITHIN 5 FEET OF THE BUILDING SEWER EXITING THE BUILDING. COORDINATE ALL CLEANOUT LOCATIONS WITH THE
<br />ARCHITECT PRIOR TO INSTALLATION.
<br />8. PROVIDE DIELECTRIC UNIONS AT ALL POINTS OF CONNECTION BETWEEN PIPES OF DISSIMILAR METALS.
<br />9. APPLY MIN. 20 MILS THICK SCOTCHWRAP (OR EQUIVALENT) VINYL TAPE COVERING OVER ALL STEEL OR COPPER WATER PIPING IN CONTACT WITH MASONRY OR CONCRETE.
<br />10. PROVIDE CHROME PLATED ESCUTCHEONS WHERE PIPES PENETRATE ANY EXPOSED WALLS, PARTITIONS, ETC. TO COVER THE PENETRATION.
<br />11. DOMESTIC WATER SUPPLY ASSEMBLY: CHROME FINISH TUBING WITH ANGLE SHUT OFF VALVES.
<br />12. PROVIDE THERMOSTATIC MIXING VALVE FOR ALL SINKS. WATER TEMPERATURE LIMITING DEVICES SHALL CONFORM TO ASSE 1070 OR CSA B125-3. MIXING VALVE SHALL BE EQUAL TO WATT USG-B LAVATORY OR APPROVED EQUAL.
<br />13. PROVIDE SHUT OFF VALVE ON THE BASE OF EVERY WATER RISER. -
<br />FIXTURES:
<br />1. ALL PLUMBING FIXTURES SHALL BE SELECTED BY OWNER AND SHALL BE FURNISHED AND INSTALLED BY CONTRACTOR. FIXTURES SHALL BE COMPLETED WITH DRAINS, TRAPS, SUPPLIES AND ANY OTHER ACCESSORIES
<br />REQUIRED. ALL FIXTURES AND FAUCETS SHALL COMPLY WITH THE FLORIDA BUILDING CODE WATER SAVING STANDARD. FIXTURES HAVE BEEN SELECTED TO ESTABLISH A STANDARD OF QUALITY AND SUBSTITUTIONS ARE NOT
<br />PERMITTED UNLESS SUBMITTED AND APPROVED PRIOR TO USE.
<br />2. ALL VITREOUS CHINA FIXTURES SHALL BE WHITE UNLESS OTHERWISE NOTED.
<br />3. SEE ARCHITECTURAL PLANS FOR EXACT FIXTURE LOCATIONS AND MOUNTING HEIGHTS.
<br />4. ALL FIXTURES IN THE SAME BUILDING OR AREA SHALL HAVE IDENTICAL FAUCETS, ESCUTCHEONS, AND TRIM KITS, UNLESS SPECIFICALLY NOTED ON PLANS. INSTALL HOT WATER SUPPLY ON THE LEFT SIDE OF ALL FIXTURES.
<br />5. ALL LAVATORIES IN PUBLIC RESTROOMS SHALL HAVE 0.5 GPM FLOW RESTRICTING AERATORS.
<br />6. FLUSH CONTROLS SHALL BE INSTALLED ON THE WIDE SIDE OF ALL WATER CLOSET STALLS,
<br />7. PROVIDE CONCEALED ARM CARRIERS OR 2X10 PT BLOCKING WITH ALL WALL MOUNTED LAVATORIES, URINALS, WATER CLOSETS, AND WATER COOLERS. CARRIERS OR BLOCKING SHALL WITHSTAND A MINIMUM VERTICAL LOAD OF
<br />250 POUNDS ON THE FRONT OF THE FIXTURE.
<br />8. PROVIDE PROTECTIVE ANTI -MICROBIAL INSULATION ON THE SUPPLY SET AND WASTE DRAIN AND TRAP OF ALL HANDICAPPED LAVATORIES.
<br />9. ALL WATER CLOSETS SHALL BE THE ELONGATED TYPE WITH OPEN FRONT SEATS.
<br />SUPPORTS & PENETRATIONS:
<br />1. PROVIDE MANUFACTURED PIPE HANGERS, RODS, AND INSERTS OR CLAMPS FOR THE PROPER SUPPORT OF ALL PIPING. BAND IRON, TIE WIRE, OR WIRE STRAPPING ARE NOT ACCEPTABLE. ALL PIPES SHALL BE SUPPORTED AT
<br />REGULAR INTERVALS. PIPE SWAY AND/OR VIBRATION SHALL NOT BE ACCEPTABLE. DO NOT HANG PIPING FROM ANYTHING OTHER THAN THE BUILDING STRUCTURE.
<br />2. ALL SUPPORT FOR PIPING SHALL BE IN ACCORDANCE WITH FLORIDA BUILDING CODE - PLUMBING (SECTION 308). UNLESS NOTED OTHERWISE IN FLORIDA BUILDING CODE - PLUMBING, SUPPORT ALL PIPING ACCORDING TO THE
<br />FOLLOWING SPACING CRITERIA:
<br />HORIZONTAL (FT) VERTICAL (FT)
<br />CAST IRON 5 15
<br />COPPER 6 10
<br />CPVC 3 10
<br />PVC 4 10
<br />STEEL 8 10
<br />3. PROVIDE PLASTIC OR RUBBER COATED ISOLATORS WHERE COPPER PIPING IS IN DIRECT CONTACT WITH OR SUPPORTED BY STEEL PIPE HANGERS.
<br />WARRANTIES AND MAINTENANCE:
<br />1. ALL FIXTURES SHALL BE TESTED, CLEANED, AND PLACED IN GOOD OPERATING CONDITION BY THE CONTRACTOR. CONTRACTOR SHALL GUARANTEE ALL EQUIPMENT, MATERIALS, AND WORKMANSHIP TO BE FREE OF DEFECTS FOR
<br />A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE BY THE OWNER AND THE CONTRACTOR SHALL REPAIR ANY SUCH DEFECTS AT NO COST TO THE OWNER. ALL EQUIPMENT INCLUDED IN THE PROJECT SHALL BE COVERED
<br />BY THE MANUFACTURER'S WARRANTY FOR THE DURATION OF THAT WARRANTY. COPIES OF ALL MANUFACTURER'S WARRANTIES AND CONTRACTOR WARRANTIES SHALL BE PROVIDED TO THE OWNER AT FINAL ACCEPTANCE.
<br />2. CONTRACTOR SHALL MEET WITH THE OWNER'S REPRESENTATIVE AND REVIEW ALL OPERATIONS AND MAINTENANCE OF ALL SYSTEMS. CONTRACTOR SHALL PROVIDE THE OWNER WITH BOUND COPIES OF ALL OPERATION AND
<br />MAINTENANCE MANUALS INCLUDING PARTS LISTS, MAINTENANCE SCHEDULES, ETC.
<br />3. THE CONTRACTOR SHALL CONTINUALLY RECORD ANY AND ALL DEVIATIONS TO THE CONTRACT DOCUMENTS MADE DURING CONSTRUCTION AND PROVIDE A COMPLETE SET OF THESE RECORD DRAWINGS TO THE OWNER WITHIN
<br />30 DAYS OF COMPLETION OF CONSTRUCTION. IF REQUIRED BY THE AUTHORITY HAVING JURISDICTION, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO SECURE THE SERVICES OF A LICENSED PROFESSIONAL ENGINEER
<br />TO PROVIDE SIGNED AND SEALED RECORD DRAWINGS.
<br />TESTING:
<br />1. AT THE COMPLETION OF THE PROJECT, TEST ALL PLUMBING SYSTEMS AND FIXTURES FOR PROPER OPERATION. TEST ALL PIPING FOR LEAKS ACCORDING TO FLORIDA BUILDING CODE - PLUMBING (SECTION 312). REPORT ALL
<br />RESULTS TO THE ARCHITECT/ENGINEER IN WRITING. REPLACE ANY DEFECTIVE DEVICES OR EQUIPMENT.
<br />2. ALL NEW SANITARY AND DOMESTIC WATER PIPING SHALL BE TESTED FOR LEAKS BEFORE PIPING IS CONCEALED OR CONNECTED TO EQUIPMENT AND/OR PLUMING FIXTURES.
<br />PLUMBING FIXTURE/EQUIPMENT SCHEDULE
<br />SOIL/
<br />VENT
<br />COLD
<br />HOT
<br />DESCRIPTION
<br />MARK
<br />FIXTURE
<br />WASTE
<br />WATER
<br />WATER
<br />(IN)
<br />(IN)
<br />(IN)
<br />(IN)
<br />SINK: TYPE 302, 18-8" STAINLESS STEEL, SELF -RIMMING, SINGLE COMPARTMENT, 17"x19"x6-1/8" DEEP. TAILPIECE AND
<br />STAINLESS STEEL CUP STRAINER. PROVIDE WITH CENTERSET FAUCET. EQUAL TO ELKAY MODEL LR2219.
<br />FAUCET: EQUAL TO CHICAGO FAUCET MODEL 786-GN2A-317. 4" WRIST BLADE HANDLE WITH 1.6 GPM FLOW CONTROL.
<br />FINISHED/TYPE SELECTED BY OWNER/ARCHITECT.
<br />S-1
<br />SINK
<br />2"
<br />1-1/2"
<br />1/2"
<br />1/2"
<br />TRAP: KOHLER K-9000, 1-1/2" X 1-1/2" P-TRAP, CLEANOUT PLUG, ADJUSTABLE WITH CONNECTED ELBOW AND NIPPLE
<br />TO WALL, CHROME PLATED.
<br />STOPS AND SUPPLIES: CHICAGO FAUCET #1006, ANGLE PATTERN, LOCK SHIELD CAP, LOOSE KEY HANDLE, WITH
<br />COPPER ALLOY CONTROL VALVE BODIES, STEMS, AND GLAND NUTS, 1/2" NPT INLET X 1/2" COMPRESSION OUTLET.
<br />PROVIDE THERMOSTATIC MIXING VALVE FOR ALL SINKS. WATER -TEMPERATURE LIMITING DEVICE SHALL CONFORM TO
<br />ASSE 1070 OR CSA B125.3. MIXING VALVE SHALL BE EQUAL TO WATT USG-B LAVATORY VALVE OR APPROVED EQUAL
<br />NOTES:
<br />1. ALL FIXTURES SHALL COMPLIED WITH THE FLORIDA BUILDING CODE WATER CONSERVATION TABLE.
<br />2. PROVIDE INSULATION KID FOR DRAIN, TRAP AND SUPPLY TO ALL SINKS AND LAVATORIES.
<br />3. ALL SUPPLIES SHALL BE CHROME PLATED LP.S. BRASS. PLASTIC SUPPLIERS ARE NOT ACCEPTABLE.
<br />4. PROVIDE ALL BOLTS, CAPS, STRAINERS, STOPS, SUPPLIES, TRAPS, ETC. FOR A COMPLETE INSTALLATION.
<br />STAMPS AND APPROVALS
<br />I HEREBY CERTIFY THAT THIS PLAN, SPECIFICATION OR REPORT WAS
<br />PREPARED BY ME OR UNDER MY DIRECT SUPERVISION, AND THAT I AM A
<br />DULY LICENSED ENGINEER UNDER THE LAWS OF THE STATE OF FLORIDA,
<br />TO THE BEST OF MY KNOWLEDGE THESE PLANS AND SPECIFICATIONS
<br />COMPLY WITH THE APPLICABLE BUILDING CODES.
<br />DANIEL CESAR, PE; LICENSE NO: 68670
<br />PROJECT NAME
<br />ADVENT HEALTH ZEPHYRHILLS ROOM 6
<br />X-RAY REPLACEMNET
<br />PROJECT LOCATION
<br />7050 GALL BOULEVARD
<br />ZEPHYRHILLS, FL 33541
<br />PROJECT NUMBER
<br />2021-009
<br />PROJECT PHASE
<br />100% CONSTRUCTION DOCUMENTS
<br />ISSUE DATE
<br />August 18, 2021
<br />REVISIONS LIST
<br />NO. I DATE I DESCRIPTION
<br />SHEET TITLE
<br />PLUMBING LEGEND
<br />AND
<br />SPECIFICATIONS
<br />SHEET NO.