s_...sswrwv.l:uulua..uL 1. .L. l�{..v` �w..i:.�_. w.J� 1:. ... ue_.:...w.:luu.t�n::lum�. •4u.uu�es. .•. � _ _ ...W:YI:. iLW .L._..l �.:�1. _ I:. 1. I ..�LI.. I. .', t. ..._.. i_ ..J...IL. � l �..l '.:�I W W.l IL1.l _ d:'141. 119..-4![B�LLY!' W®1191111LLll1:'IAI.LI".Lk ,:imL"Yi .. l i i 11 S .-1 _ _ __ _ _ _.dYla.'w - _ l . I i..l• - _ L . 26 l
<br />__ -. .. . _. _ _ ___. _:_`. ... _.. _ :-._.- __. �._ -..� _ -._.. .. :yam__.. ..-i. y..-- I 1.. I-l-NI..-I e.JW�..:uii�LL:s.41� _lil _ -��.l w. _1.-.:L11L LW1�l..�:�..Wi �S�.L C W. �' �IYI'Y--1lMl•11
<br />I
<br />3
<br />I
<br />C
<br />F
<br />I
<br />c
<br />I
<br />n
<br />IAIQI 11 ATInAI IAnVf-T
<br />NOTES:
<br />1. PULL FLEXIBLE DUCT INNER LINER OVER
<br />RIGID DUCT WITH MINIMUM 4" OVERLAP.
<br />SEAL FLEXIBLE DUCT INNER LINING TO
<br />RIGID DUCT WITH MASTIC ON THE INSIDE
<br />OF THE LINER.
<br />2. SECURE LINER WITH STAINLESS STEEL
<br />DRAW BAND.
<br />3. SECURE FLEXIBLE DUCT INSULATION
<br />AND OUTER JACKET WITH STAINLESS
<br />STEEL DRAW BAND.
<br />4. PULL RIGID DUCT INSULATION AND BUTT
<br />JOINT TO TERMINATION OF FLEXIBLE
<br />DUCT. APPLY 3" WIDE TAPE SIMILAR TO
<br />FSK TAPE TO CREATE VAPOR BARRIER
<br />SEAM. TAPE SHALL BE COMPATIBLE
<br />WITH FLEXIBLE DUCT INSULATION
<br />JACKET AND RIGID DUCT INSULATION
<br />JACKET, APPLY MASTIC OVER TAPE FOR
<br />DURABILITY.
<br />3 FLEXIBLE DUCT CONNECTOR TO INSULATED RIGID DUCT
<br />SCALE: 12" = V-0"
<br />NOTES:
<br />MIN. 1" WIDE BAND
<br />CLAMP AT ELBOW
<br />FLEXIBLE DUCT
<br />pRAWBAND (1)
<br />(3) DRAWBAND (2)
<br />DIFFUSER WITH
<br />ROUND INLET CONNECTION
<br />CEILING FIRE DAMPER. INSTALLED PER
<br />MANUFACTURER RECOMMENDATIONS (UL
<br />555)
<br />CEILING
<br />1. PULL FLEXIBLE DUCT'S INNER LINER OVER DIFFUSER COLLAR AND SECURE WITH DRAW
<br />BAND.
<br />2. SECURE FLEXIBLE DUCT INSULATION AND OUTER JACKET WITH DRAW BAND.
<br />3. MAINTAIN MIN. 1.5 RADIUS ELBOW
<br />4 DIFFUSER/GRILLE CONNECTOR
<br />SCALE: 12" = V-0"
<br />IMAGING EQUIPMENT NOTES
<br />THESE DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE IMAGING EQUIPMENT VENDOR
<br />PLANS AND/OR DETAILS, AND THEY ARE INTENDED TO GIVE THE CONTRACTOR A GENERAL
<br />KNOWLEDGE OF THE WORK ASSOCIATED WITH THE INSTALLATION OF THE IMAGING
<br />EQUIPMENT. IT IS NOT INTENDED TO INDICATE ALL WIRING, CONNECTIONS, J-BOXES,
<br />SWITCHES, ETC, OR ANCILLARY COMPONENTS REQUIRED FOR INSTALLATION. ALL
<br />EQUIPMENT SHALL BE INSTALLED PER THE OWNER APPROVED MANUFACTURER'S
<br />INSTALLATION DRAWINGS. INSTALLATION SHALL BE COORDINATED IN FIELD WITH IMAGING
<br />EQUIPMENT MANUFACTURER.
<br />IT IS THE INTENTION OF THESE DRAWINGS THAT ALL WORK (LABOR, MATERIALS, ETC.)
<br />REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM SHALL BE PROVIDED.
<br />EQUIPMENT MANUFACTURER SHALL SUPPLY FIXED LENGTH CABLES, WHEREBY ALL
<br />MEASUREMENTS SHALL BE DETERMINED FROM ELECTRICAL TROUGH RUNS INDICATED ON
<br />THE DRAWINGS. ANY CHANGES TO EQUIPMENT PLACEMENT OR TROUGH ROUTINGS AT JOB
<br />SITE WILL CAUSE THE DELIVERY OF INACCURATE AND ERRONEOUS CABLE LENGTHS. THIS
<br />MAY RESULT IN ADDITIONAL COST FOR REPLACEMENT CABLES AND DELAY EQUIPMENT
<br />INSTALLATION. COORDINATE PLACEMENT OF ALL EQUIPMENT WITH EQUIPMENT INSTALLER
<br />PRIOR TO ROUGH -IN.
<br />ALL RADIOLOGY EQUIPMENT SHALL BE TESTED AND RECORDED FOR CHASSIS LEAKAGE IN
<br />ACCORDANCE WITH NFPA 99, SECTION 8-4.1.3.4. PROVIDE A WRITTEN REPORT, SIGNED,
<br />SEALED AND DATED BY THE PERSON SUPERVISING THE TEST FOR EACH PIECE OF
<br />EQUIPMENT TABULATION PERMITTED AND RECOMMENDED.
<br />r MECHANICAL FLOOR PLAN - NEW
<br />SCALE: 1/4" = V-0"
<br />AIR DISTRIBUTION DEVICE SCHEDULE
<br />SYMBOL
<br />TYPE
<br />AIRFLOW
<br />SIZE
<br />DUCT
<br />COLOR
<br />REMARKS
<br />(CFM)
<br />(1N x IN)
<br />CONNECTION SIZE
<br />0 - 50
<br />12 x 12
<br />SUPPLY DIFFUSERS SHALL BE EQUAL TO PRICE AMD
<br />SUPPLY
<br />WITH18x18 DIMENSION "A" SIZE FOR UNIFORM APPEARANCE
<br />51 - 240
<br />24 x 24
<br />MAX.NECK VELOCITY 700 FPM
<br />SUPPLY CEILING
<br />SEE PLAN
<br />WHITE
<br />MAX. NC = 30
<br />241 - 325
<br />24 x 24
<br />CD
<br />GRILLE 24x24
<br />MODULAR
<br />FOR DUCT
<br />CONNECTION
<br />MAX. PRESSURE DROP 0.10"
<br />CEILING LAY -IN OR SURFACE MOUNT
<br />CFM
<br />SIZE
<br />USED FOR GENERAL PURPOSE
<br />330 - 480
<br />24 x 24
<br />485 - 740
<br />24 x 24
<br />0 - 50
<br />12 x 12
<br />RETURN/EXHAUST GRILLES SHALL BE EQUAL TO PRICE 630 L-STYLE WITH 10x10
<br />RETURN/EXHAUST AIR
<br />DUCT CONNECTION SIZE
<br />51 - 240
<br />24 x 24
<br />MAX. NECK VELOCITY 450 FPM
<br />RG
<br />SEE PLAN
<br />MAX. NC = 20
<br />MAX. PRESSURE DROP 0.10"WHITE
<br />CFM
<br />RETURN
<br />241 - 325
<br />24 x 24
<br />FOR DUCT
<br />CEILING LAY -IN OR SURFACE MOUNT
<br />GRILLE
<br />CONNECTION
<br />USED FOR GENERAL PURPOSE
<br />EA
<br />330 - 480
<br />24 x 24
<br />PROVIDE 22x22 GRILLE PLENUM BOXES FOR ALL 24x24 RETURN/EXHAUST
<br />CFM
<br />GRILLES WITH AIRFLOW GREATER THAN 400 CFM.
<br />485 - 98fl
<br />24 x 24
<br />LOW EXHAUST
<br />30 x 10
<br />EXHAUST GRILLES SHALL BE EQUAL TO PRICE 630 L-STYLE WITH 450 DEFLECTION
<br />OR
<br />SEE PLAN
<br />3/4" BLADE SPACING
<br />24 x 12
<br />RETURN AIR
<br />LOW RETURN
<br />360-720
<br />FOR DUCT'
<br />WHITE
<br />MAX. NECK VELOCITY 400 FPM
<br />MAX. NC = 20
<br />GRILLE
<br />CONNECTION
<br />MAX. PRESSURE DROP 0.10"
<br />EA
<br />20 x 14
<br />CEILING LAY -IN OR SURFACE MOUNT
<br />CFM
<br />USED FOR GENERAL PURPOSE
<br />18 x 16
<br />GRILLES WITH AIRFLOW GREATER THAN 360 CFM.
<br />NOTES:
<br />1. TRANSITION DUCTWORK AS REQUIRED TO GRILLE CONNECTION SIZE INDICATED.
<br />2. DIFFUSERS/GRILLES/REGISTERS SHALL BE ALUMINUM.
<br />3. PROVIDE INTEGRAL VOLUME DAMPER.
<br />4. PROVIDE FLEXIBLE DUCT CONNECTIONS TO ALL AIR DISTRIBUTION DEVICES IN LAY -IN CEILINGS. EXPOSED AIR DISTRIBUTION DEVICES SHALL HAVE HARD DUCT CONNECTIONS.
<br />GENERAL NOTES
<br />1. EXISTING SYSTEMS SHOWN HEREIN WERE TAKEN
<br />FROM DOCUMENTS FURNISHED BY OTHERS AND
<br />MAY NOT REFLECT EXACT FIELD CONDITIONS.
<br />THEREFORE, THE ENGINEER CAN NOT
<br />GUARANTEE THE ACCURACY OF SAME, NOR THAT
<br />ALL SYSTEMS AND/OR SYSTEMS COMPONENTS
<br />ARE SHOWN. THE CONTRACTOR SHALL VERIFY
<br />FIELD CONDITIONS PRIOR TO BID AND INFORM
<br />THE ENGINEER OF ANY MAJOR DISCREPANCY
<br />THAT IT WILL REQUIRE RELOCATING EXISTING
<br />PIPING, CONDUIT, EQUIPMENT, ETC. TO ALLOW
<br />INSTALLATION OF NEW WORK AND COULD
<br />POTENTIALLY AFFECT THE COST.
<br />2. REFER TO INFECTION CONTROL RISK
<br />ASSESSMENT IN PROJECT MANUAL FOR
<br />REQUIRED PREVENTIVE MEASURES TO BE TAKEN
<br />FOR EACH AREA,
<br />3. DUE TO THE CEILING SPACE LIMITATIONS, IT IS
<br />IMPERATIVE THAT ALL DUCTWORK, PIPING,
<br />LIGHTING AND EQUIPMENT INSTALLATION TO BE
<br />COORDINATED AMONG ALL TRADES PRIOR TO THE
<br />INSTALLATION OF ANY UTILITIES. PIPING RISERS
<br />AND DROPS ARE SHOWN. CONTRACTOR TO
<br />PROVIDE AT NO ADDITIONAL COST TO THE OWNER
<br />ALL DUCT OFFSETS, BENDS AND TRANSITIONS
<br />REQUIRED FOR A COMPLETE FUNCTIONAL
<br />SYSTEM.
<br />4. ROUTE ALL DUCTWORK IN ABOVE CEILING. HOLD
<br />DUCTWORK TIGHT TO STRUCTURE. FOR CLARITY,
<br />NOT ALL THE DUCTWORK RISERS AND DROPS ARE
<br />SHOWN.
<br />5. FOR CLARITY, NOT ALL THE DUCTWORK AND
<br />6. CONTRACTOR TO COORDINATE WITH ALL TRADES
<br />TO ENSURE A MINIMUM CLEARANCE OF 36" IS
<br />PROVIDED FOR ALL AIR TERMINAL DEVICES.
<br />SPACE SHALL BE MAINTAINED FROM THE TOP OF
<br />AIR TERMINAL DEVICE TO THE TOP OF THE
<br />CEILING,
<br />7. INSTALL DUCTWORK RUN -OUT TO ALL SUPPLY,
<br />RETURN AND EXHAUST DIFFUSERS/GRILLES WITH
<br />A MINIMUM OF 2 ELBOWS 6 FT OF FLEXIBLE DUCTA
<br />8. AFTER DEMOLITION, CAP REMAINING OPEN ENDED
<br />DUCTS/PIPING AS REQUIRED.
<br />9. SOME WORK MAY BE REQUIRED TO BE
<br />PERFORMED AFTER HOURS OR ON WEEKENDS.
<br />COORDINATE ALL SYSTEM SHUTDOWNS WITH
<br />OWNER IN WRITING,
<br />10. CONTRACTOR TO CAP OR SHUT DOWN ALL
<br />SUPPLY, RETURN AND EXHAUST AIR DUCTWORK
<br />AND DIFFUSERS SERVING AREAS UNDER
<br />CONSTRUCTION TO HELP MAINTAIN NEGATIVE
<br />PRESSURE.
<br />11. PROVIDE VISUAL AIRFLOW INDICATORS AT EACH
<br />CONSTRUCTION ENTRANCE TO THE WORK ZONE.
<br />SCRUBBER SHALL BE 99.97% HEPA AND ALL
<br />REQUIREMENTS SHALL BE COORDINATED WITH
<br />INFECTION CONTROL RISK ASSESSMENT
<br />MEASURES IN PROJECT MANUAL. CONNECT A
<br />TEMPORARY RETURN DUCT AS SHOWN AND
<br />BALANCE AS NECESSARY TO MAINTAIN A MINIMUM
<br />NEGATIVE 0.01" IN THE CONSTRUCTION AREA AT
<br />ALL TIMES. REMAINING AIRFLOW SHALL BE
<br />RECIRCULATED TO THE CONSTRUCTION ZONE.
<br />AIR SCRUBBER SHALL OPERATE CONTINUOUSLY
<br />DURING CONSTRUCTION,
<br />12. ALL NEW DUCTWORK SHALL MATCH EXISTING.
<br />VERIFY EXISTING DUCTWORK CONSTRUCTION
<br />AND THICKNESS, DUCTWORK SHALL BE
<br />CONSTRUCTED TO WITHSTAND PRESSURES IN
<br />THE SYSTEM BUT NOT LESS THAN 2"WG FOR
<br />SUPPLY DOWNSTREAM OF AIR TERMINALS, 3"WG
<br />UPSTREAM OF THE AIR TERMINAL DEVICES
<br />AND -3"WG FOR RETURN SYSTEMS. FIELD VERIFY
<br />EXISTING DUCTWORK SIZES. NEW DUCTWORK
<br />AND FLEX DUCT TO MATCH EXISTING.
<br />13, HATCHED AREAS ARE NOT UNDER THE SCOPE OF
<br />THIS PROJECT. ALL EXISTING AIR HANDLING
<br />UNITS, DUCTWORK, DIFFUSERS, GRILLES, PIPING,
<br />ETC., IN THE HATCHED AREAS ARE EXISTING TO
<br />REMAIN.
<br />14. AT CONCLUSION OF PROJECT, SUBMIT A
<br />COMPLETE T & B REPORT.
<br />KEYED NOTES
<br />1 RELOCATE LOW RETURN GRILLE TO PLAN EAST
<br />SIDE OF THE CHASE TO ALLOW IMAGING
<br />EQUIPMENT INSTALLATION.
<br />2 REBALANCE TO AIRFLOW IN DARK OR PREVIOUS
<br />RECORDED VALUES.
<br />MARK LOCATION SERVICE -AIRFLOW DATA FILTERS COOLING COIL WATER SIDE REMARKS
<br />SUPPLY AIR OUTDOOR AIR PRE -FILTER FINAL CAPACITY AIR SIDE 1
<br />RTU __..... .__^-___. ___._..-.__.. ._.____._._.__ _^_� - WATER MAX EWT LWT BASIS OF DESIGN:
<br />TYPE TYPE TOTAL SENSIBLE EAT j' LAT - FLOW PD. (°F) (°F) TRANE
<br />(CFM) (CFM) ( } _._-1-- T_--a-- (GPM) (FT WC)
<br />(MBH) (MBH) DB °F �WB (OF)' DB ff) WB (OF)
<br />AHU RADIOLOGY / V-BANK FLAT __....� �
<br />2 PENTHOUSE CATH LABS 2 & 3 27,346 13;085 211 THROWAWAY CARTRIDGE 1,575,130 77.1 68.7 50. 49.8 236.9 - 40.3 53.6 MCCA066EAB050A00
<br />REHEAT I I
<br />I
<br />MARK
<br />TYPE
<br />MAX -
<br />MIN
<br />MAX.
<br />MAX.
<br />MIN. COIL
<br />HEATING COIL
<br />NOTES
<br />RH
<br />RH-1
<br />X-RAY 6
<br />AIRFLOW
<br />(CFM)
<br />525 _
<br />AIRFLOW
<br />(CFM)
<br />N/A
<br />AIR
<br />PD
<br />("WG)
<br />0.5._ ._.
<br />WATER
<br />PD
<br />(" H20)
<br />5.0__.,.
<br />SIZE
<br />(IN.)
<br />_12x10._.__
<br />_____ -
<br />REHEAT CAP. EAT EWT LWT
<br />AIRFLOW
<br />T650 14.8 155.0 180.0 160.01
<br />BASIS OF DESIGN:
<br />EXHAUST FAN (EXISTINPI_
<br />MARK
<br />#
<br />-EF-20
<br />SERVES -
<br />RADIOLOGY
<br />CFM
<br />�1,950
<br />ESP
<br />W.G.)
<br />0.75
<br />QTY.
<br />1
<br />TYPE
<br />_DOWNBLASTJ
<br />DRIVE
<br />BELT
<br />CONTROL
<br />CONST.
<br />MOUNTING
<br />ROOF
<br />ELECTRICAL
<br />HP VOLT PH
<br />tO 120 1
<br />NOTES
<br />BASIS OF DESIGN:
<br />GREENHECK
<br />GB-180-5-X
<br />106 WEST NORTH BAY STREET I TAMPA, FL 33603
<br />www.cjaegroup.com
<br />MECHANICAL -ELECTRICAL -PLUMBING
<br />800 HIGHLAND AVE. STE 102
<br />ORLANDO, FL 32803
<br />CA LIC. NO.: 31963
<br />PHONE: (407) 250-6485
<br />WWW.DCL-ENG.COM
<br />STAMPS AND APPROVALS
<br />I HEREBY CERTIFY THAT THIS PLAN, SPECIFICATION OR REPORT WAS
<br />PREPARED BY ME OR UNDER MY DIRECT SUPERVISION, AND THAT I AM A
<br />DULY LICENSED ENGINEER UNDER THE LAWS OF THE STATE OF FLORIDA.
<br />TO THE BEST OF MY KNOWLEDGE THESE PLANS AND SPECIFICATIONS
<br />COMPLY WITH THE APPLICABLE BUILDING CODES.
<br />DANIEL CESAR, PE; LICENSE NO: 68670
<br />PROJECT NAME
<br />ADVENT HEALTH ZEPHYRHILLS ROOM 6
<br />X-RAY REPLACEMNET
<br />PROJECT LOCATION
<br />7050 GALL BOULEVARD
<br />ZEPHYRHILLS, FL 33541
<br />PROJECT NUMBER
<br />2021-009
<br />PROJECT PHASE
<br />100% CONSTRUCTION DOCUMENTS
<br />ISSUE DATE
<br />AUGUST 18, 2021
<br />REVISIONS LIST
<br />NO• I DATE I DESCRIPTION
<br />SHEET TITLE
<br />MECHANICAL
<br />FLOOR PLAN -
<br />NEW
<br />SHEET NO.
<br />M301