I
<br />I
<br />2
<br />I 3
<br />I 4
<br />0
<br />C
<br />0
<br />I
<br />SUITE SCHEDULE - FIRST FLOOR
<br />SUITE
<br />NUMBER
<br />TOTAL SQ.
<br />FOOTAGE
<br />AREA DESCRIPTION
<br /># OF REMOTE
<br />EXIT ACCESS
<br />DOORS
<br />SUITE TYPE
<br />SUITE 1-A
<br />2,021 SF
<br />PRE ADMIT TESTING
<br />1
<br />NON -SLEEPING
<br />SUITE 1-B
<br />5,336 SF
<br />RADIOLOGY
<br />2
<br />NON -SLEEPING
<br />SUITE 1-C
<br />930 SF
<br />ULTRASOUND
<br />1
<br />NON -SLEEPING
<br />SUITE 1-D
<br />1,178 SF
<br />MRI
<br />1
<br />NON -SLEEPING
<br />SUITE 1-E
<br />1,495 SF
<br />ANGIOGRAPHY
<br />2
<br />NON -SLEEPING
<br />SUITE 1-F
<br />2,117 SF
<br />NUCLEAR MED
<br />2
<br />NON -SLEEPING
<br />SUITE 1-G
<br />770 SF
<br />OFFICE
<br />1
<br />NON -SLEEPING
<br />SUITE 1-H
<br />7,270 SF
<br />KITCHEN
<br />4
<br />NON -SLEEPING
<br />SUITE 1-1
<br />5,360 SF
<br />ADMINISTRATION
<br />4
<br />NON -SLEEPING
<br />SUITE 1-J
<br />1,610 SF
<br />CHAPEL/ PASSAGE
<br />4
<br />NON -SLEEPING
<br />SUITE 1-K
<br />1,745 SF
<br />SPEECH THERAPY
<br />2
<br />NON -SLEEPING
<br />SUITE 1-L
<br />1,506 SF
<br />PHYSICAL THERAPY
<br />1
<br />NON -SLEEPING
<br />SUITE 1-M
<br />5,630 SF
<br />PHYSICAL THERAPY
<br />3
<br />NON -SLEEPING
<br />SUITE 1-N
<br />3,110 SF
<br />STAFF WORK
<br />3
<br />NON -SLEEPING
<br />SUITE 1-0
<br />1,140 SF
<br />DRY STORAGE
<br />2
<br />NON -SLEEPING
<br />SUITE 1-P
<br />2,430 SF
<br />HUMAN RESOURCES
<br />1
<br />NON -SLEEPING
<br />SUITE 1-Q
<br />3,550 SF
<br />RECEIVING
<br />3
<br />NON -SLEEPING
<br />SUITE 1-R
<br />4,950 SF
<br />STERILE PROCESSING
<br />2
<br />NON -SLEEPING
<br />1 LIFE SAFETY PLAN - LEVEL 1 N�
<br />SCALE: 1/32" = 1'-0"
<br />EXIT TABULATION - FIRST FLOOR
<br />SMOKE
<br />COMPARTMENT
<br />OCCUPANY TYPE
<br />OCCUPANTS
<br />EXIT WIDTH
<br />ZONE
<br />AREA
<br />SQ. FT.
<br />NUMBER
<br />INCHES
<br />REQ.
<br />PROV.
<br />1A
<br />12,370
<br />TREATMENT
<br />12,370
<br />240
<br />52
<br />0.2
<br />10.4
<br />17711
<br />1 B
<br />19,950
<br />OUTPATIENT
<br />4,290
<br />100
<br />43
<br />0.2
<br />8.6"
<br />101"
<br />TREATMENT
<br />15,660
<br />240
<br />66
<br />13.2"
<br />1C
<br />16,584
<br />OUTPATIENT
<br />6,386
<br />100
<br />64
<br />0.2
<br />1311
<br />16611
<br />TREATMENT
<br />4,015
<br />240
<br />17
<br />3.4
<br />MECHANICAL
<br />1,955
<br />300
<br />7
<br />1.4
<br />ASSEMBLY
<br />4,228
<br />15
<br />282
<br />56.4
<br />1 D
<br />13,992
<br />OUTPATIENT
<br />6,837
<br />100
<br />69
<br />0.2
<br />13.8"
<br />152"
<br />MECHANICAL
<br />1,135
<br />300
<br />4
<br />.8
<br />ASSEMBLY
<br />6,020
<br />15
<br />402
<br />80.4
<br />1E
<br />13,884
<br />TREATMENT
<br />11,249
<br />240
<br />47
<br />0.2
<br />9.4
<br />31"
<br />MECHANICAL
<br />1,347
<br />300
<br />5
<br />1
<br />ASSEMBLY
<br />1,248
<br />15
<br />84
<br />16.8
<br />1F
<br />12,597
<br />TREATMENT
<br />11,858
<br />240
<br />50
<br />0.2
<br />10
<br />134"
<br />MECHANICAL
<br />739
<br />300
<br />3
<br />.6
<br />1G
<br />4,890
<br />ANCILLARY
<br />4,150
<br />240
<br />18
<br />0.2
<br />3.6
<br />124"
<br />MECHANICAL
<br />740
<br />300
<br />3
<br />.6
<br />1 H
<br />6,290
<br />OUTPATIENT
<br />3,360
<br />100
<br />34
<br />0.2
<br />6.8
<br />6611
<br />TREATMENT
<br />2,930
<br />240
<br />13
<br />2.6
<br />11
<br />13,393
<br />TREATMENT
<br />13,393
<br />240
<br />56
<br />0.2
<br />11.2
<br />22011
<br />11
<br />13,022
<br />TREATMENT
<br />13,022
<br />240
<br />55
<br />0.2
<br />11
<br />132"
<br />TOTAL
<br />126,972
<br />1,374
<br />275
<br />1, 303"
<br />LIFE SAFETY LEGEND
<br />FE
<br />FIRE EXTINGUISHER
<br />FEC
<br />FIRE EXTINGUISHER CABINET
<br />FHC
<br />FIRE HOSE CABINET & EXTINGUISHER CABINET
<br />z
<br />HAZARDOUS AREAS
<br />FB
<br />FIRE BLANKET
<br />Q
<br />SMOKE DETECTOR
<br />Q
<br />HEAT DETECTOR
<br />EXIT LIGHT
<br />1
<br />EXIT LIGHT W/ DIRECTIONAL ARROW
<br />4
<br />FIRE ALARM HORN! STROBE
<br />E]
<br />FIRE ALARM MANUAL PULL STATION
<br />©
<br />FIRE ALARM STROBE
<br />osP
<br />STAND PIPE
<br />®
<br />CARD READER
<br />2A
<br />SMOKE ZONE
<br />SUITE: 1-A
<br />SUITE NAME
<br />44
<br />EXIT ARROW / CLEAR WIDTH
<br />ETD
<br />EXIT TRAVEL DISTANCE
<br />CPT
<br />COMMON PATH OF TRAVEL
<br />THE FOLLOWING REQUIREMENTS & REFERENCES NOTED ARE BASED UPON
<br />a.
<br />FULLY SPRINKLED BUILDING, AND
<br />b.
<br />EXISTING HEALTHCARE OCCUPANCY - 2009 NFPA 101, FLORIDA
<br />SPECIFIC EDITION
<br />c.
<br />2007 NFPA 80
<br />r
<br />LIMITS OF NON SLEEPING SUITES t 1. LIMITS
<br />(NFPA 101 PAR 19-2.5.7) ' (NFPA
<br />OF SLEEPING SUITES
<br />101 PAR 19-2.5.7)
<br />��+"
<br />ALL CORRIDOR WALLS ARE TO BE SMOKE TIGHT.
<br />GASKETING OF DOORS SHOULD NOT BE NECESSARY
<br />(NFPA 101 PAR A.8.4.3.4) (NFPA 101 PAR 19.3.6.3.1)
<br />SMOKE RESISTANT CORRIDORS WITH PARTITIONS EXTENDED TO DECK ABOVE
<br />(NFPA 101 Par 19.3.6.3.1)
<br />■
<br />■
<br />a. 20 MINUTE RATED 1314" SOLID CORE WOOD DOOR, FRAME AND WINDOWS
<br />(19.3.6.3.1)
<br />■
<br />b. POSITIVE LATCHING REQUIRED
<br />(A19.3.6.3.5(1))
<br />■
<br />c. NON RATED PROTECTIVE PLATE ON DOORS, UNLIMITED IN HEIGHT, ARE PERMITTED
<br />(19.3.6.3.12)
<br />■
<br />■
<br />d. DOOR CLOSER NOT REQUIRED
<br />(19-3.6.3.11)
<br />■
<br />e. MAX 118" GAP AT HINGE, LATCH & TOP ON PULL SIDE OF SINGLE DOORS AND AT
<br />■
<br />MEETING EDGES OF PAIR OF DOORS
<br />(NFPA 80 6.3.1.7
<br />■
<br />f. MAX. 1" UNDERCUT FROM BTM OF DOOR TO FINISH FLOOR
<br />(19.3.6.3.4)
<br />■
<br />g. PERIMETER WALLS OF AREAS OPEN TO CORRIDOR CONSTRUCTED TO MATCH
<br />■
<br />■
<br />CORRIDOR PARTITIONS AND CEILING
<br />(8.4.2)
<br />h. FIRE OR SMOKE DAMPERS NOT REQUIRED
<br />(19.3.7.4)
<br />ONE HOUR FIRE WALL ASSEMBLY (NFPA 101 Par 8.3.4.2)
<br />a. 314 HOUR RATED DOOR & FRAME
<br />(TABLE 8.3.4.2)
<br />■
<br />b. SELF CLOSING OR AUTOMATIC CLOSING REQUIRED
<br />(8.3.3.3)
<br />e
<br />G. POSITIVE LATCHING REQUIRED
<br />(19.3.6.3.5)
<br />d. NON RATED PROTECTIVE PLATE UP TO 48"
<br />(19.3.2.1.4)
<br />■
<br />e. MAX 118" GAP AT HINGE, LATCH & TOP ON PULL SIDE
<br />(8.5.4.1 & NFPA 80 6.3.1.7)
<br />■
<br />f. MAX 314" DOOR UNDERCUT
<br />(NFPA 80 4.8.4.1)
<br />g. FIRE GLAZING SIZE LIMITED TO AREA TESTED
<br />(NFPA 80 4.4.5)
<br />h. FIRE DAMPERS REQUIRED
<br />(8.3.5.6.1)
<br />i. NO LOUVERS IN DOORS
<br />(8.4.3.3)
<br />i
<br />TWO HOUR FIRE WALL ASSEMBLY (NFPA 101 Par 8.3.4.2)
<br />a. 1 112 HOUR RATED DOOR & FRAME
<br />(TABLE 8.3.4.2)
<br />■
<br />b. SELF CLOSING OR AUTOMATIC CLOSING REQUIRED
<br />(8.3.3.3)
<br />c. POSITIVE LATCHING REQUIRED
<br />(19.3.6.3.5)
<br />-
<br />d. RATED PROTECTIVE PLATE REQUIRED IF TOP OF PLATE IS GREATER
<br />i
<br />THAN 48" ABOVE BOTTOM OF DOOR
<br />(19.3.2.1.4)
<br />LE
<br />e. MAX 1/8" GAP AT HINGE, LATCH & TOP ON PULL SIDE
<br />(8.5.4.1 & NFPA 80 6.3.1.7)
<br />f. MAX 314" DOOR UNDERCUT
<br />(NFPA 80 4.8.4.1)
<br />-_
<br />g. FIRE GLAZING SIZE LIMITED TO AREA TESTED
<br />(NFPA 80 4.4.5)
<br />■
<br />h. 1112 HOUR FIRE DAMPER REQUIRED
<br />(8.3.5.6.1)
<br />i. NO LOUVERS IN DOORS
<br />(8.4.3.3)
<br />ONE HOUR FIRE/SMOKE BARRIER WALL ASSEMBLY (NFPA 101,
<br />Par 19-3.7)
<br />a. 20 MIN. RATED SOLID CORE WOOD DOOR OR STEEL DOOR & FRAME
<br />(TABLE 8.3.4.2)
<br />b. SELF CLOSING OR AUTOMATIC CLOSING REQUIRED
<br />(19.3.7.8 & 8.5.4.4)
<br />■
<br />c. POSITIVE LATCHING NOT REQUIRED AT CROSS CORRIDOR DOORS
<br />(19.3.7.8)
<br />d. NON RATED PROTECTIVE PLATE UNLIMITED IN HEIGHT IS PERMITTED
<br />(19.3.7.6.1)
<br />■
<br />e. MAX 118" GAP AT HINGE, LATCH & TOP ON PULL SIDE OF SINGLE DOORS
<br />AND AT MEETING EDGES OF PAIR OF DOORS
<br />(8.5.4.1 & NFPA 80 6.3.1.7)
<br />■_
<br />f. EXISTING ASTRAGALS SHALL REMAIN
<br />■
<br />g. MAX 314" DOOR UNDERCUT
<br />(NFPA 80 4.8.4.1)
<br />h. FIRE GLAZING SIZE LIMITED TO AREA TESTED
<br />(NFPA 80 4.4.5)
<br />■
<br />i. FIRE/SMOKE DAMPER(S) REQUIRED
<br />(8.5.5.2)
<br />j. NO LOUVERS IN DOORS
<br />(8.4.3.3)
<br />TWO HOUR FIRE/SMOKE BARRIER WALL ASSEMBLY (NFPA 101,
<br />Par 19.3.7)
<br />_
<br />a. 1 112 HOUR RATED DOOR & FRAME
<br />(TABLE 8.3.4.2)
<br />■
<br />b. SELF CLOSING OR AUTOMATIC CLOSING REQUIRED
<br />(19.3.7.8 & 8.5.4.4)
<br />c. POSITIVE LATCHING REQUIRED
<br />(19.3.7.8)
<br />d. RATED PROTECTIVE PLATE REQUIRED IF TOP OF PLATE IS GREATER
<br />_■
<br />THAN 16" ABOVE BOTTOM OF DOOR
<br />(NFPA 80 6.4.5)
<br />e. MAX 118" GAP AT HINGE, LATCH & TOP ON PULL SIDE OF SINGLE DOORS
<br />■
<br />AND AT MEETING EDGES OF PAIR OF DOORS
<br />(8.5.4.1 & NFPA 80 6.3.1.7)
<br />f. EXISTING ASTRAGALS SHALL REMAIN
<br />g. MAX 314" DOOR UNDERCUT
<br />(NFPA 80 4.8.4.1)
<br />h. FIRE GLAZING SIZE LIMITED TO AREA TESTED
<br />(NFPA 80 4.4.5)
<br />■
<br />i. FIRE/SMOKE DAMPER(S) REQUIRED
<br />(8.5.5.2)
<br />j. NO LOUVERS IN DOORS
<br />(8.4.3.3)
<br />106 WEST NORTH BAY STREET / TAMPA, FL 33603
<br />http://cjaegroup.com
<br />ENGINEERING
<br />STAMPS AND APPROVALS
<br />PAO,
<br />i
<br />I HEREBY CERTIFY THAT THIS PLAN, SPECIFICATION OR REPORT WAS
<br />PREPARED BY ME OR UNDER MY DIRECT SUPERVISION, AND THAT I AM A
<br />DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF FLORIDA.
<br />TO THE BEST OF MY KNOWLEDGE, THESE PLANS AND SPECIFICATIONS
<br />COMPLY WITH THE APPLICABLE BUILDING CODES.
<br />CARLA J. HARVEY; LICENSE NO: AR95088
<br />14
<br />Adivnent
<br />Zephyrhilis
<br />PROJECT NAME
<br />ADVENTHEALTH ZEPHYRHILLS
<br />ROOM 6 X-RAY REPLACEMENT
<br />PROJECT LOCATION
<br />7050 GALL BOULEVARD
<br />ZEPHYRHILLS, FL 33541
<br />PROJECT NUMBER
<br />2021-009
<br />PROJECT PHASE
<br />100% CONSTRUCTION DOCUMENTS
<br />ISSUE DATE
<br />AUGUST 18, 2021
<br />REVISIONS LIST
<br />NO. I DATE DESCRIPTION
<br />SHEET TITLE
<br />OVERALL FIRST FLOOR LIFE SAFETY
<br />PLAN AND CODE ANALYSIS
<br />SHEET NO.
<br />Lsmoi
<br />KEY PLAN N0