I <br />I <br />2 <br />I 3 <br />I 4 <br />0 <br />C <br />0 <br />I <br />SUITE SCHEDULE - FIRST FLOOR <br />SUITE <br />NUMBER <br />TOTAL SQ. <br />FOOTAGE <br />AREA DESCRIPTION <br /># OF REMOTE <br />EXIT ACCESS <br />DOORS <br />SUITE TYPE <br />SUITE 1-A <br />2,021 SF <br />PRE ADMIT TESTING <br />1 <br />NON -SLEEPING <br />SUITE 1-B <br />5,336 SF <br />RADIOLOGY <br />2 <br />NON -SLEEPING <br />SUITE 1-C <br />930 SF <br />ULTRASOUND <br />1 <br />NON -SLEEPING <br />SUITE 1-D <br />1,178 SF <br />MRI <br />1 <br />NON -SLEEPING <br />SUITE 1-E <br />1,495 SF <br />ANGIOGRAPHY <br />2 <br />NON -SLEEPING <br />SUITE 1-F <br />2,117 SF <br />NUCLEAR MED <br />2 <br />NON -SLEEPING <br />SUITE 1-G <br />770 SF <br />OFFICE <br />1 <br />NON -SLEEPING <br />SUITE 1-H <br />7,270 SF <br />KITCHEN <br />4 <br />NON -SLEEPING <br />SUITE 1-1 <br />5,360 SF <br />ADMINISTRATION <br />4 <br />NON -SLEEPING <br />SUITE 1-J <br />1,610 SF <br />CHAPEL/ PASSAGE <br />4 <br />NON -SLEEPING <br />SUITE 1-K <br />1,745 SF <br />SPEECH THERAPY <br />2 <br />NON -SLEEPING <br />SUITE 1-L <br />1,506 SF <br />PHYSICAL THERAPY <br />1 <br />NON -SLEEPING <br />SUITE 1-M <br />5,630 SF <br />PHYSICAL THERAPY <br />3 <br />NON -SLEEPING <br />SUITE 1-N <br />3,110 SF <br />STAFF WORK <br />3 <br />NON -SLEEPING <br />SUITE 1-0 <br />1,140 SF <br />DRY STORAGE <br />2 <br />NON -SLEEPING <br />SUITE 1-P <br />2,430 SF <br />HUMAN RESOURCES <br />1 <br />NON -SLEEPING <br />SUITE 1-Q <br />3,550 SF <br />RECEIVING <br />3 <br />NON -SLEEPING <br />SUITE 1-R <br />4,950 SF <br />STERILE PROCESSING <br />2 <br />NON -SLEEPING <br />1 LIFE SAFETY PLAN - LEVEL 1 N� <br />SCALE: 1/32" = 1'-0" <br />EXIT TABULATION - FIRST FLOOR <br />SMOKE <br />COMPARTMENT <br />OCCUPANY TYPE <br />OCCUPANTS <br />EXIT WIDTH <br />ZONE <br />AREA <br />SQ. FT. <br />NUMBER <br />INCHES <br />REQ. <br />PROV. <br />1A <br />12,370 <br />TREATMENT <br />12,370 <br />240 <br />52 <br />0.2 <br />10.4 <br />17711 <br />1 B <br />19,950 <br />OUTPATIENT <br />4,290 <br />100 <br />43 <br />0.2 <br />8.6" <br />101" <br />TREATMENT <br />15,660 <br />240 <br />66 <br />13.2" <br />1C <br />16,584 <br />OUTPATIENT <br />6,386 <br />100 <br />64 <br />0.2 <br />1311 <br />16611 <br />TREATMENT <br />4,015 <br />240 <br />17 <br />3.4 <br />MECHANICAL <br />1,955 <br />300 <br />7 <br />1.4 <br />ASSEMBLY <br />4,228 <br />15 <br />282 <br />56.4 <br />1 D <br />13,992 <br />OUTPATIENT <br />6,837 <br />100 <br />69 <br />0.2 <br />13.8" <br />152" <br />MECHANICAL <br />1,135 <br />300 <br />4 <br />.8 <br />ASSEMBLY <br />6,020 <br />15 <br />402 <br />80.4 <br />1E <br />13,884 <br />TREATMENT <br />11,249 <br />240 <br />47 <br />0.2 <br />9.4 <br />31" <br />MECHANICAL <br />1,347 <br />300 <br />5 <br />1 <br />ASSEMBLY <br />1,248 <br />15 <br />84 <br />16.8 <br />1F <br />12,597 <br />TREATMENT <br />11,858 <br />240 <br />50 <br />0.2 <br />10 <br />134" <br />MECHANICAL <br />739 <br />300 <br />3 <br />.6 <br />1G <br />4,890 <br />ANCILLARY <br />4,150 <br />240 <br />18 <br />0.2 <br />3.6 <br />124" <br />MECHANICAL <br />740 <br />300 <br />3 <br />.6 <br />1 H <br />6,290 <br />OUTPATIENT <br />3,360 <br />100 <br />34 <br />0.2 <br />6.8 <br />6611 <br />TREATMENT <br />2,930 <br />240 <br />13 <br />2.6 <br />11 <br />13,393 <br />TREATMENT <br />13,393 <br />240 <br />56 <br />0.2 <br />11.2 <br />22011 <br />11 <br />13,022 <br />TREATMENT <br />13,022 <br />240 <br />55 <br />0.2 <br />11 <br />132" <br />TOTAL <br />126,972 <br />1,374 <br />275 <br />1, 303" <br />LIFE SAFETY LEGEND <br />FE <br />FIRE EXTINGUISHER <br />FEC <br />FIRE EXTINGUISHER CABINET <br />FHC <br />FIRE HOSE CABINET & EXTINGUISHER CABINET <br />z <br />HAZARDOUS AREAS <br />FB <br />FIRE BLANKET <br />Q <br />SMOKE DETECTOR <br />Q <br />HEAT DETECTOR <br />EXIT LIGHT <br />1 <br />EXIT LIGHT W/ DIRECTIONAL ARROW <br />4 <br />FIRE ALARM HORN! STROBE <br />E] <br />FIRE ALARM MANUAL PULL STATION <br />© <br />FIRE ALARM STROBE <br />osP <br />STAND PIPE <br />® <br />CARD READER <br />2A <br />SMOKE ZONE <br />SUITE: 1-A <br />SUITE NAME <br />44 <br />EXIT ARROW / CLEAR WIDTH <br />ETD <br />EXIT TRAVEL DISTANCE <br />CPT <br />COMMON PATH OF TRAVEL <br />THE FOLLOWING REQUIREMENTS & REFERENCES NOTED ARE BASED UPON <br />a. <br />FULLY SPRINKLED BUILDING, AND <br />b. <br />EXISTING HEALTHCARE OCCUPANCY - 2009 NFPA 101, FLORIDA <br />SPECIFIC EDITION <br />c. <br />2007 NFPA 80 <br />r <br />LIMITS OF NON SLEEPING SUITES t 1. LIMITS <br />(NFPA 101 PAR 19-2.5.7) ' (NFPA <br />OF SLEEPING SUITES <br />101 PAR 19-2.5.7) <br />��+" <br />ALL CORRIDOR WALLS ARE TO BE SMOKE TIGHT. <br />GASKETING OF DOORS SHOULD NOT BE NECESSARY <br />(NFPA 101 PAR A.8.4.3.4) (NFPA 101 PAR 19.3.6.3.1) <br />SMOKE RESISTANT CORRIDORS WITH PARTITIONS EXTENDED TO DECK ABOVE <br />(NFPA 101 Par 19.3.6.3.1) <br />■ <br />■ <br />a. 20 MINUTE RATED 1314" SOLID CORE WOOD DOOR, FRAME AND WINDOWS <br />(19.3.6.3.1) <br />■ <br />b. POSITIVE LATCHING REQUIRED <br />(A19.3.6.3.5(1)) <br />■ <br />c. NON RATED PROTECTIVE PLATE ON DOORS, UNLIMITED IN HEIGHT, ARE PERMITTED <br />(19.3.6.3.12) <br />■ <br />■ <br />d. DOOR CLOSER NOT REQUIRED <br />(19-3.6.3.11) <br />■ <br />e. MAX 118" GAP AT HINGE, LATCH & TOP ON PULL SIDE OF SINGLE DOORS AND AT <br />■ <br />MEETING EDGES OF PAIR OF DOORS <br />(NFPA 80 6.3.1.7 <br />■ <br />f. MAX. 1" UNDERCUT FROM BTM OF DOOR TO FINISH FLOOR <br />(19.3.6.3.4) <br />■ <br />g. PERIMETER WALLS OF AREAS OPEN TO CORRIDOR CONSTRUCTED TO MATCH <br />■ <br />■ <br />CORRIDOR PARTITIONS AND CEILING <br />(8.4.2) <br />h. FIRE OR SMOKE DAMPERS NOT REQUIRED <br />(19.3.7.4) <br />ONE HOUR FIRE WALL ASSEMBLY (NFPA 101 Par 8.3.4.2) <br />a. 314 HOUR RATED DOOR & FRAME <br />(TABLE 8.3.4.2) <br />■ <br />b. SELF CLOSING OR AUTOMATIC CLOSING REQUIRED <br />(8.3.3.3) <br />e <br />G. POSITIVE LATCHING REQUIRED <br />(19.3.6.3.5) <br />d. NON RATED PROTECTIVE PLATE UP TO 48" <br />(19.3.2.1.4) <br />■ <br />e. MAX 118" GAP AT HINGE, LATCH & TOP ON PULL SIDE <br />(8.5.4.1 & NFPA 80 6.3.1.7) <br />■ <br />f. MAX 314" DOOR UNDERCUT <br />(NFPA 80 4.8.4.1) <br />g. FIRE GLAZING SIZE LIMITED TO AREA TESTED <br />(NFPA 80 4.4.5) <br />h. FIRE DAMPERS REQUIRED <br />(8.3.5.6.1) <br />i. NO LOUVERS IN DOORS <br />(8.4.3.3) <br />i <br />TWO HOUR FIRE WALL ASSEMBLY (NFPA 101 Par 8.3.4.2) <br />a. 1 112 HOUR RATED DOOR & FRAME <br />(TABLE 8.3.4.2) <br />■ <br />b. SELF CLOSING OR AUTOMATIC CLOSING REQUIRED <br />(8.3.3.3) <br />c. POSITIVE LATCHING REQUIRED <br />(19.3.6.3.5) <br />- <br />d. RATED PROTECTIVE PLATE REQUIRED IF TOP OF PLATE IS GREATER <br />i <br />THAN 48" ABOVE BOTTOM OF DOOR <br />(19.3.2.1.4) <br />LE <br />e. MAX 1/8" GAP AT HINGE, LATCH & TOP ON PULL SIDE <br />(8.5.4.1 & NFPA 80 6.3.1.7) <br />f. MAX 314" DOOR UNDERCUT <br />(NFPA 80 4.8.4.1) <br />-_ <br />g. FIRE GLAZING SIZE LIMITED TO AREA TESTED <br />(NFPA 80 4.4.5) <br />■ <br />h. 1112 HOUR FIRE DAMPER REQUIRED <br />(8.3.5.6.1) <br />i. NO LOUVERS IN DOORS <br />(8.4.3.3) <br />ONE HOUR FIRE/SMOKE BARRIER WALL ASSEMBLY (NFPA 101, <br />Par 19-3.7) <br />a. 20 MIN. RATED SOLID CORE WOOD DOOR OR STEEL DOOR & FRAME <br />(TABLE 8.3.4.2) <br />b. SELF CLOSING OR AUTOMATIC CLOSING REQUIRED <br />(19.3.7.8 & 8.5.4.4) <br />■ <br />c. POSITIVE LATCHING NOT REQUIRED AT CROSS CORRIDOR DOORS <br />(19.3.7.8) <br />d. NON RATED PROTECTIVE PLATE UNLIMITED IN HEIGHT IS PERMITTED <br />(19.3.7.6.1) <br />■ <br />e. MAX 118" GAP AT HINGE, LATCH & TOP ON PULL SIDE OF SINGLE DOORS <br />AND AT MEETING EDGES OF PAIR OF DOORS <br />(8.5.4.1 & NFPA 80 6.3.1.7) <br />■_ <br />f. EXISTING ASTRAGALS SHALL REMAIN <br />■ <br />g. MAX 314" DOOR UNDERCUT <br />(NFPA 80 4.8.4.1) <br />h. FIRE GLAZING SIZE LIMITED TO AREA TESTED <br />(NFPA 80 4.4.5) <br />■ <br />i. FIRE/SMOKE DAMPER(S) REQUIRED <br />(8.5.5.2) <br />j. NO LOUVERS IN DOORS <br />(8.4.3.3) <br />TWO HOUR FIRE/SMOKE BARRIER WALL ASSEMBLY (NFPA 101, <br />Par 19.3.7) <br />_ <br />a. 1 112 HOUR RATED DOOR & FRAME <br />(TABLE 8.3.4.2) <br />■ <br />b. SELF CLOSING OR AUTOMATIC CLOSING REQUIRED <br />(19.3.7.8 & 8.5.4.4) <br />c. POSITIVE LATCHING REQUIRED <br />(19.3.7.8) <br />d. RATED PROTECTIVE PLATE REQUIRED IF TOP OF PLATE IS GREATER <br />_■ <br />THAN 16" ABOVE BOTTOM OF DOOR <br />(NFPA 80 6.4.5) <br />e. MAX 118" GAP AT HINGE, LATCH & TOP ON PULL SIDE OF SINGLE DOORS <br />■ <br />AND AT MEETING EDGES OF PAIR OF DOORS <br />(8.5.4.1 & NFPA 80 6.3.1.7) <br />f. EXISTING ASTRAGALS SHALL REMAIN <br />g. MAX 314" DOOR UNDERCUT <br />(NFPA 80 4.8.4.1) <br />h. FIRE GLAZING SIZE LIMITED TO AREA TESTED <br />(NFPA 80 4.4.5) <br />■ <br />i. FIRE/SMOKE DAMPER(S) REQUIRED <br />(8.5.5.2) <br />j. NO LOUVERS IN DOORS <br />(8.4.3.3) <br />106 WEST NORTH BAY STREET / TAMPA, FL 33603 <br />http://cjaegroup.com <br />ENGINEERING <br />STAMPS AND APPROVALS <br />PAO, <br />i <br />I HEREBY CERTIFY THAT THIS PLAN, SPECIFICATION OR REPORT WAS <br />PREPARED BY ME OR UNDER MY DIRECT SUPERVISION, AND THAT I AM A <br />DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF FLORIDA. <br />TO THE BEST OF MY KNOWLEDGE, THESE PLANS AND SPECIFICATIONS <br />COMPLY WITH THE APPLICABLE BUILDING CODES. <br />CARLA J. HARVEY; LICENSE NO: AR95088 <br />14 <br />Adivnent <br />Zephyrhilis <br />PROJECT NAME <br />ADVENTHEALTH ZEPHYRHILLS <br />ROOM 6 X-RAY REPLACEMENT <br />PROJECT LOCATION <br />7050 GALL BOULEVARD <br />ZEPHYRHILLS, FL 33541 <br />PROJECT NUMBER <br />2021-009 <br />PROJECT PHASE <br />100% CONSTRUCTION DOCUMENTS <br />ISSUE DATE <br />AUGUST 18, 2021 <br />REVISIONS LIST <br />NO. I DATE DESCRIPTION <br />SHEET TITLE <br />OVERALL FIRST FLOOR LIFE SAFETY <br />PLAN AND CODE ANALYSIS <br />SHEET NO. <br />Lsmoi <br />KEY PLAN N0 <br />