<br />00 01 15 LIST OF DRAWINGS
<br />COMPLETE LIST OF DRAWINGS IN CONTRACT SET WITH DRAWING NO., SHEET DESCRIPTION AND DRAWING DATE.
<br />00 10 00 SOLICITATION FOR BIDS
<br />BID FORM / REQUEST FOR PROPOSAL (RFP) DOCUMENT BY OWNER OR OWNER'S REPRESENTATIVE; PROVIDED
<br />BY OWNER OR OWNER REP.
<br />00 52 00 AGREEMENT FORMS
<br />OWNER AGREEMENT TO BE BETWEEN OWNER AND CONTRACTOR. REFER TO RFP OR BID REQUEST.
<br />00 70 00 CONDITIONS OF THE CONTRACT
<br />PROVIDED BY OWNER OR OWNER REPRESENTATIVE.
<br />01 25 00 SUBSTITUTION PROCEDURES
<br />ALL PRODUCTS MUST MATCH CONTRACT DOCUMENTS OR SPECIFICATIONS. ANY SUBSTITUTIONS MUST BE
<br />SUBMITTED AND APPROVED BY ARCHITECT OR ENGINEER OF RECORD. SUBSTITUTIONS MUST PROVIDE MONETARY
<br />OR SCHEDULE VALUE TO THE PROJECT.
<br />01 29 00 PAYMENT PROCEDURES
<br />'APPLICATIONS FOR PAYMENT' SCHEDULE AND REQUIREMENTS MUST BE COORDINATED WITH OWNER OR OWNER
<br />REPRESENTATIVE. ARCHITECT IS REQUIRED TO REVIEW ALL APPLICATIONS FOR PAYMENT PRIOR TO SUBMISSION
<br />TO OWNER FOR FINAL PAYMENT APPROVAL. FULL SCHEDULE OF VALUES MUST BE INCLUDED, ALONG WITH
<br />PERCENTAGE COMPLETE / PAYMENT REQUESTED AMOUNTS. PROVIDE INDIVIDUAL TRADES PAY APPLICATIONS AS
<br />SUPPORT.
<br />01 32 00 CONSTRUCTION PROGRESS DOCUMENTA11ON
<br />CONTRACTOR MUST PROVIDE REGULAR RECORDED DOCUMENTATION OF CONSTRUCTION PROGRESS. FREQUENCY
<br />TO BE DETERMINED BY OWNER OR OWNER REPRESENTATIVE. PHOTOGRAPHIC DOCUMENTATION IS REQUIRED.
<br />IN —WALL PHOTOGRAPHS MUST BE TAKEN PRIOR TO CLOSING —UP OF ANY WALLS.
<br />PROJECT SCHEDULE, INCLUDING MILESTONE DATES AND PROGRESS COMPLETION, SHALL BE INCLUDED.
<br />01 50 00 TEMPORARY FACILITIES AND CONTROLS
<br />TEMPORARY UTILITIES AND UTILITY CONNECTIONS FOR CONSTRUCTION MUST BE COORDINATED WITH OWNER.
<br />01 56 10 TEMPORARY BARRIERS AND ENCLOSURES — INFECTION CONTROL
<br />REFER TO INFECTION CONTROL RISK ASSESSMENT FORM, BY OWNER. RISK ASSESSMENT DOCUMENTATION IS
<br />INCLUDED IN THIS DOCUMENT PACKAGE; ASSESSMENT MUST BE VERIFIED AND CONFIRMED BY OWNER'S
<br />INFECTION CONTROL DEPARTMENT.
<br />01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS DISCOVERY OF WATER DAMAGE AND ORGANIC CONTAMINANTS
<br />CONSULTANTS AND CONTRACTORS CONDUCTING WORK ARE REQUIRED TO NOTIFY OWNER OF ANY WATER
<br />DAMAGE OR CONCERNS OF ORGANIC CONTAMINANTS. ANY REQUIRED TESTING SHALL BE PERFORMED BY
<br />OWNER.
<br />01 58 13 TEMPORARY PROJECT SIGNAGE
<br />COORDINATE ALL SIGNAGE REQUIREMENTS AND LANGUAGE WITH OWNER. IMMEDIATE CONTACT INFORMATION
<br />MUST BE PROVIDED FOR EMERGENCY USE.
<br />01 70 00 EXECUTION AND CLOSEOUT DOCUMENTS
<br />PROVIDE FINAL AS —BUILT DOCUMENTATION FOR ALL DISCIPLINES TO THE ARCHITECT AND OWNER OR OWNER
<br />REPRESENTATIVE.
<br />PROVIDE OWNER MANUALS AND PRODUCT DATA FOR ALL MAJOR MECHANICAL, PLUMBING AND ELECTRICAL
<br />EQUIPMENT, AS DEFINED IN THE PROJECT DOCUMENTS.
<br />PROVIDE AND COORDINATE FINAL WARRANTY INFORMATION TO THE OWNER, AS DEFINED IN THE PROJECT
<br />DOCUMENTS.
<br />COORDINATE FINAL WALKTHROUGHS AND PUNCH LIST WITH ARCHITECT, ENGINEER AND OWNER OR OWNER
<br />REPRESENTATIVE. FINAL DOCUMENTATION OF ACCEPTANCE OF WORK BY ARCHITECT/ENGINEER MUST BE
<br />PROVIDED TO OWNER.
<br />02 41 19 SELECTIVE DEMOLITION
<br />COORDINATION DEMOLITION PRACTICES WITH OWNER OR OWNER REPRESENTATIVE. SCHEDULE DEMOLITION
<br />ACTIVITIES TO BE OF LEAST IMPACT TO REGULAR OPERATIONS BY OWNER. PROTECTIVE MEASURES SHALL BE
<br />PUT INTO PLACE, WITH CLEAR COMMUNICATION AND PROCESSES/PROCEDURES COORDINATED WITH OWNER OR
<br />OWNER REPRESENTATIVE.
<br />CONTRACTOR SHALL FOLLOW MATERIAL DISPOSAL WITH HOSPITAL STANDARD PROCEDURES. ALL ITEMS/
<br />MATERIAL TO BE REMOVED/DISPOSED MUST BE PROTECTED WHILE IN TRANSIT THROUGH THE HOSPITAL TO
<br />FINAL DISPOSAL AREA.
<br />02 26 23 ASBESTOS ASSESSMENT
<br />REQUIRED FOR ALL PROJECTS WITHIN THE HOSPITAL UNLESS RECENT SURVEY IS ON RECORD, BY OWNER.
<br />VERIFY TESTING COMPLETION BY OWNER.
<br />02 87 13 MOLD REMEDIATION
<br />COORDINATE ALL REQUIRED MOLD REMEDIATION WITH OWNER. REMEDIATION PROCESS MUST BE COORDINATED
<br />WITH OWNER, INFECTION CONTROL DEPARTMENT, USER GROUPS. REMEDIATION MUST BE COMPLETED BY A
<br />LICENSED PROFESSIONAL.
<br />03 30 00 CAST —IN —PLACE CONCRETE
<br />ALL CONCRETE POURS SHALL BE INSPECTED BY REGULATORY AUTHORITIES, OWNER REPRESENTATIVE,
<br />ARCHITECT AND STRUCTURAL ENGINEER, AS APPROPRIATE, BEFORE POURS. ALLOW A MINIMUM OF 72—HOUR
<br />NOTICE IF POURS ARE TO OCCUR WITHIN THE EXISTING HOSPITAL BUILDING TO ALLOW FOR SAFETY MEASURES
<br />AND COORDINATION WITH OPERATIONS.
<br />FOR ANY NEW CONCRETE HOUSEKEEPING PADS TO BE POURED AND ANCHORED TO AN EXISTING CONCRETE
<br />SLAB, ALL PAINT, SEALERS AND FINISHES MUST BE REMOVED BEFORE DOWELING AND POURING NEW SLAB,
<br />UNLESS OTHERWISE SPECIFIED.
<br />03 82 13 CONCRETE CORE DRILLING
<br />ALL CORE DRILL LOCATIONS MUST BE VERIFIED AND CONFIRMED WITH STRUCTURAL ENGINEER PRIOR TO WORK.
<br />ALL CORE DRILLING MUST BE COORDINATED WITH OWNER OR OWNER REPRESENTATIVE TO COMPLY WITH
<br />ICRA/SAFETY MEASURES AND TO MINIMIZE IMPACT ON EXISTING OPERATIONS.
<br />NOT USED
<br />05 10 00 STRUCTURAL METAL FRAMING
<br />REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL STEEL INFORMATION.
<br />PROVIDE 'UNISTRUT' SYSTEMS FOR STRUCTURAL RAIL SUPPORT SYSTEM, DELEGATED DESIGN. REFER TO AGFA
<br />DRAWINGS AND STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION. COORDINATE FINAL CEILING RAIL
<br />SUPPORT SYSTEM WITH AGFA EQUIPMENT, CONFIRM WITH AGFA REPRESENTATIVE FOR FINAL APPROVAL OF
<br />SYSTEM AND INSTALLATION LOCATION.
<br />06 10 53 MISCELLANEOUS ROUGH CARPENTRY
<br />ALL BLOCKING AND CONCEALED WOOD FRAMING TO BE FIRE —RETARDANT TREATED, COMPLYING WITH AWPA C20
<br />AND AWPA C27.
<br />06 40 23 INTERIOR ARCHITECTURAL WOODWORK
<br />MINIMUM AN PREMIUM GRADE MATERIALS AND WORKMANSHIP
<br />— ALL CABINETS TO BE MADE OF PLYWOOD, NO EXCEPTIONS
<br />— ALL BASE CABINETS TO BE INSTALLED OVER SHEET VINYL FLOORING, SHALL RUN CONTINUOUS UNDER BASE
<br />CABINET AND FLASH —COVED TO BACK WALL.
<br />— DRAWER CONSTRUCTION SHALL BE ALL PLYWOOD; NO PARTICLE BOARD AND NO METAL SIDES.
<br />— LEG SUPPORTS SHALL BE LAMINATED PLYWOOD
<br />— ALL BASE CABINET COUNTERTOP OUTSIDE CORNERS SHALL BE 2" RADIUS.
<br />— WALL CABINETS MUST HAVE LAMINATED FILLER PIECE TO CEILING, UNLESS OTHERWISE NOTED.
<br />— INSIDE OF CABINET WHITE LINER ONLY, NO MELAMINE
<br />— SOLID SURFACE COUNTERTOPS — CORIAN, WILSONART — SEE FINISH SCHEDULE FOR DETAILS
<br />PLASTIC LAMINATE — FORMICA, ARBORITE, WILSONART — SEE FINISH SCHEDULE FOR DETAILS
<br />— CABINET HARDWARE — TO MATCH EXISTING, OR
<br />HINGES — HINGES BLUM 120 DEG PRESS —IN, BLUM—BLlT5550
<br />BACK PLATE — BACK PLATE — OMM, BLUM BACK PLATE BL-175H7100
<br />DRAWER GLIDES — KNAPE/VOGT DRAWER GLIDES — FULL EXTENSION KV8400 SERIES
<br />PULLS — BRUSHED CHROME WIRE PULLS 96MM
<br />COUNTERTOP SUPPORT BRACKETS — RAKKS
<br />FOR COUNTERS 12" DEEP — STYLE EC-0808; FOR COUNTERS 18" DEEP — STYLE EC0812; FOR COUNTERS
<br />24" DEEP - EH-1818 WITH RADIUS; FOR COUNTERS 30" DEEP - EH-1824 WITH RADIUS
<br />ADDITIONAL SUPPORT ANGLE RAKKS EH —CS 2 X 2 X 1 /8" ALUMINUM ANGLE CLEAT STOCK.
<br />— GROMMETS — 3" DIAMETER, WITH RIM AND REMOVABLE PLASTIC COVER (BLACK)
<br />07 81 00 APPLIED FIREPROOFING
<br />FIREPROOFING EXISTING STRUCTURE AT CORE DRILL OR PENETRATION LOCATIONS MUST MATCH EXISTING
<br />FIREPROOFING METHOD.
<br />07 84 10 PENETRATION FIRESTOPPING
<br />ALL FIRESTOPPING MUST BE UL SYSTEM, AND MUST BE APPROVED BY ARCHITECT PRIOR TO INSTALLATION.
<br />- PENETRATIONS IN FIRE —RESISTANCE —RATED WALLS: PROVIDE PENETRATION FIRESTOPPING WITH RATINGS
<br />DETERMINED PER ASTM E 814 OR UL 1479.
<br />— PENETRATIONS IN HORIZONTAL ASSEMBLIES: PROVIDE PENETRATION FIRESTOPPING WITH RATINGS
<br />DETERMINED PER ASTM E 814 OR UL 1479. F—RATING SHALL BE AT LEAST 1—HOUR, BUT NOT LESS THAN
<br />THE FIRE —RESISTANCE RATING OF THE CONSTRUCTION PENETRATED. T—RATING SHALL BE AT LEAST
<br />1—HOUR, BUT NOT LESS THAN THE FIRE —RESISTANCE RATING OF CONSTRUCTION PENETRATED EXCEPT FOR
<br />FLOOR PENETRATIONS WITHIN THE CAVITY OF A WALL.
<br />— PENETRATIONS IN SMOKE BARRIERS: PROVIDE PENETRATION FIRESTOPPING WITH RATINGS DETERMINED PER
<br />UL 1479.
<br />APPROVED MANUFACTURERS — HILTI, STI, 3M
<br />BOD — 3M FIRE BARRIER CP 25WBt SEALANT
<br />UL—SYSTEM LABEL SHALL BE AFFIXED ADJACENT TO THE PENETRATION.
<br />07 84 40 FIRE —RESISTIVE JOINT SYSTEMS
<br />APPROVED MANUFACTURERS — HILTI, STI, 3M
<br />07 92 00 JOINT SEALANTS
<br />FOLLOW MANUFACTURERS INSTALLATION INSTRUCTIONS FOR ALL JOINT SEALANT INSTALLATION.
<br />PROVIDE SILICONE, URETHANE OR LATEX JOINT SEALANTS, AS APPROPRIATE, FOR SPECIFIC INSTALLATION TYPE.
<br />— SILICONE JOINT SEALANT : CONTROL AND EXPANSION JOINTS IN OVERHEAD SURFACES; OTHER JOINTS AS
<br />NOTED.
<br />APPROVED MANUFACTURERS: DOW CORNING CORP 790; GE ADVANCED MATERIALS SILPRUF LM SCS2700;
<br />TREMCO INC SPECTREM 1
<br />— URETHANE JOINT SEALANT. INTERIOR JOINTS IN HORIZONTAL TRAFFIC SURFACES — ISOLATION JOINTS IN
<br />CAST —IN —PLACE CONCRETE SLABS; CONTROL AND EXPANSION JOINTS IN TILE FLOORING; OTHER JOINTS AS
<br />NOTED.
<br />APPROVED MANUFACTURERS: BASF BUILDING SYSTEMS SONOLASTIC NP 2; PECORA CORP DYNATRED;
<br />TREMCO INC VULKEM 227
<br />— ACRYLIC —LATEX SEALANT. INTERIOR JOINTS IN VERTICAL SURFACES AND HORIZONTAL NONTRAFFIC
<br />SURFACES THAT WILL BE FIELD —PAINTED — PERIMETER JOINTS BETWEEN INTERIOR WALL SURFACES AND
<br />FRAMES OF INTERIOR DOORS, ACCESS DOORS AND WINDOWS; OTHER JOINTS AS NOTED.
<br />APPROVED MANUFACTURERS: BASF BUILDING SYSTEMS SONOLAC; BOSTIK INC CHEM—CALK 600; TREMCO
<br />INC TREMFLEX 834
<br />— MILDEW —RESISTANT SILICONE SEALANT: MILDEW —RESISTANT JOINTS IN VERTICAL SURFACES AND HORIZONTAL
<br />NON -TRAFFIC SURFACES — JOINTS BETWEEN PLUMBING FIXTURES AND ADJOINING WALLS, FLOORS AND
<br />COUNTERS; TILE CONTROL AND EXPANSION JOINTS; OTHER JOINTS AS NOTED.
<br />APPROVED MANUFACTURERS: BASF BUILDING SYSTEMS OMNIPLUUS; DOW CORNING CORP 786 MILDEW
<br />RESISTANT, TREMCO INC TREMSIL 200 SANITARY
<br />08 12 13 HOLLOW METAL FRAMES
<br />PROVIDE 1/16" LEAD —LINED EQUIVALENT GLAZING AND FRAME PER PHYSICIST REPORT.
<br />ENAMEL PAINTED FRAME
<br />APPROVED MANUFACTURER: RAY —BAR LEAD —LINED FRAME; RADIATION PROTECTION PRODUCTS (RPP)
<br />08 56 49 GLAZING
<br />PROVIDE 1/16" LEAD —LINED EQUIVALENT GLAZING AND FRAME PER PHYSICIST REPORT.
<br />APPROVED MANUFACTURER: RAY —BAR LEAD —LINED VIEW WINDOWS; RADIATION PROTECTION PRODUCTS (RPP)
<br />09 06 00 SCHEDULES FOR FINISHES
<br />REFER TO INTERIOR FINISH PLAN OR INTERIOR FINISH SCHEDULE IN THE DOCUMENTS FOR INTERIOR FINISH
<br />SCHEDULE.
<br />09 21 16 GYPSUM BOARD ASSEMBLIES
<br />MUST COMPLY WITH ASTM C 36/C 36M OR ASTM C 1396/C 1396M, AS APPLICABLE TO TYPE OF GYPSUM
<br />BOARD AND WHICHEVER IS MORE STRINGENT.
<br />5/8" TYPE X GYPSUM BOARD — TYPICAL
<br />MOISTURE AND MOLD RESISTANT TYPE — ASTM D 3273, SCORE OF 10 AS RATED ACCORDING TO ASTM D 3274..
<br />LONG EDGES TAPERED — WET WALLS (BOD "PURPLE BOARD" BY US GYPSUM)
<br />PROVIDE LEAD —LINED 1/16" GYPSUM WALL BOARD, AS REQ'D, REFER TO PHYSICIST REPORT.
<br />09 22 16 NON—STRUCTURAL METAL FRAMING
<br />20 GA STEEL STUDS FOR INTERIOR FRAMING AT 16" OC
<br />20 GA STEEL STUDS FOR HEADERS AND FOOTERS
<br />DOUBLE 20 GA STEEL STUDS FOR FRAMING OF DOORS AND WINDOWS
<br />FOLLOW MANUFACTURER'S RECOMMENDATIONS FOR FRAMING GAUGE OF LEAD —LINED DOORS OR DOORS GREATER
<br />THAN 3'-6".
<br />09 30 00 11LING
<br />REFER TO FINISH SCHEDULE
<br />USE MANUFACTURER'S RECOMMENDED ADHESIVE PROGRAM/SYSTEM.
<br />09 51 13 ACOUSTIC PANEL CEILINGS
<br />ACT1 — REFER TO FINISH SCHEDULE
<br />APPROVED MANUFACTURERS: ARMSTRONG, SQUARE LAY —IN
<br />METAL SUSPENSION SYSTEM:
<br />BOD: PRELUDE XL 15/16" EXPOSED TEE SYSTEMS, OR EQUAL
<br />APPROVED MANUFACTURERS: ARMSTRONG
<br />09 65 00 RESILIENT FLOORING
<br />SHEET VINYL B.O.D.: REFER TO FINISH SCHEDULE
<br />ADHESIVES: PER MANUFACTURER'S RECOMMENDATION
<br />RUBBER BASE B.O.D.: JOHNSONITE/TARKETT DURACOVE THERMOPLASTIC RUBBER 1/8"; 4" HT TYPICAL
<br />09 72 00 WALL COVERINGS
<br />WALL PROTECTION BY INPRO CORP.; 0.08" THICKNESS.
<br />REFER TO FINISH SCHEDULE FOR DETAILS AND LOCATIONS
<br />09 91 23 INTERIOR PAINTING
<br />REFER TO INTERIOR FINISHES DRAWINGS FOR PAINT COLORS/LOCATIONS
<br />LOW VOC PAINT REQUIRED
<br />SHERWIN WILLIAMS PROMAR 200, EGGSHELL (SEMIGLOSS AT DOOR/WINDOW FRAMES)
<br />NEW WALLS: 1 COAT PRIMER, 2 COATS FINISH (MINIMUM)
<br />EXISTING WALLS: 1 COAT KILZ OR PRIMER, 2 COATS FINISH
<br />FRAMES: SEMIGLOSS; 1 COAT PRIMER, 2 COATS FINISH
<br />REFER TO FINISH SCHEDULE FOR ADDITIONAL DETAILS
<br />10 14 00 SIGNAGE
<br />NOT USED (EXISTING TO REMAIN)
<br />10 26 23 PROTECTIVE WALL COVERING
<br />INPRO — 160 CG HIGH IMPACT CORNER GUARDS (2")
<br />10 28 13 TOILET ACCESSORIES
<br />GRAB BARS (GB) — EXISTING TO REMAIN
<br />MIRROR (MIR) — NEW — CFCI — BOBRICK B-293-1836
<br />SOAP DISPENSER (SD) — EXISTING TO REMAIN
<br />TOILET PAPER DISPENSER (TPD) — EXISTING TO REMAIN
<br />PAPER TOWEL DISPENSER (PTD) — EXISTING TO REMAIN
<br />SHELF — EXISTING TO REMAIN
<br />10 44 00 FIRE PROTECTION SPECIALTIES
<br />NOT USED (EXISTING TO REMAIN)
<br />11 77 00 REFER TO EQUIPMENT PACKAGE PROVIDED BY VENDOR 'AGFA' TITLED "DR 800 DIGITAL HIGH FREQUENCY
<br />UNIVERSAL R/F SYSTEM SUITE" DATED 05/03/2021.
<br />REVIEW ALL VENDOR —PROVIDED EQUIPMENT PLANS TO ENSURE COORDINA11ON WITH THIS CONTRACT DOCUMENT
<br />PACKAGE.
<br />12 35 70 HOSPITAL CASEWORK
<br />REFER TO DIVISION 06 AND DRAWINGS FOR INFORMATION.
<br />13 49 00 RADIATION PROTECTION
<br />OWNER TO PROVIDE LEAD SHIELDING REPORT BY PHYSICIST BOTH PRIOR TO AND POST -CONSTRUCTION.
<br />REFER TO SPECIFICATIONS DIVISIONS 08 AND 09, AND DRAWINGS, FOR ADDITIONAL INFORMATION ABOUT
<br />SHIELDING REQUIREMENTS.
<br />ALL LEAD SHIELDING SHALL BE CONTINUOUS UP TO 7'-0".
<br />NOT USED
<br />106 WEST NORTH BAY STREET I TAMPA, FL 33603
<br />http://cjaegroup.com
<br />STAMPS AND APPROVALS
<br />I HEREBY CERTIFY THAT THIS PLAN, SPECIFICATION OR REPORT WAS
<br />PREPARED BY ME OR UNDER MY DIRECT SUPERVISION, AND THAT i AM A
<br />DULY LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF FLORIDA.
<br />TO THE BEST OF MY KNOWLEDGE, THESE PLANS AND SPECIFICATIONS
<br />COMPLY WITH THE APPLICABLE BUILDING CODES.
<br />CARLA J. HARVEY, LICENSE NO: AR95088
<br />PROJECT NAME
<br />ADVENTHEALTH ZEPHYRHILLS
<br />ROOM 6 X-RAY REPLACEMENT
<br />PROJECT LOCATION
<br />7050 GALL BOULEVARD
<br />ZEPHYRHILLS, FL 33541
<br />PROJECT NUMBER
<br />2021-009
<br />PROJECT PHASE
<br />100% CONSTRUCTION DOCUMENTS
<br />ISSUE DATE
<br />AUGUST 18, 2021
<br />REVISIONS LIST
<br />(�NO. I DATE DESCRIPTION
<br />SHEET TITLE
<br />PROJECT SPECIFICATIONS
<br />SHEET NO.
<br />Amol
<br />
|