2020 FLORIDA MECHANICAL CODE - VENTILATION CALCULATION
<br />212028 SAGE DENTAL - ZEPHYRHILLS
<br />Vbz
<br />BREATHING ZONE
<br />Ez
<br />Voz
<br />DEFAULT
<br />CALCULATED
<br />PEOPLE
<br />PEOPLE
<br />Rp
<br />Vbzp
<br />Ra
<br />Vbza
<br />OUTDOOR
<br />ZONE AIR
<br />ZONE OUTDOOR
<br />EXHAUST
<br />AREA
<br />OCCUPANCY
<br />OCCUPANCY
<br />OCCUPANCY
<br />COUNT
<br />COUNT
<br />VENT. RATE
<br />VENT. RATE
<br />AIRFLOW
<br />A J IqN
<br />���
<br />DISTRIBUTION
<br />AIRFLOW
<br />RATE
<br />ROOM NAME
<br />SF
<br />CLASSIFICATION
<br />QTY/1000 SF
<br />PEOPLE
<br />LOAD
<br />VENT.
<br />CFM / P
<br />CFM
<br />CFM / SF
<br />CFM
<br />CFM
<br />'
<br />EFFECTIVENESS
<br />CFM
<br />CFM
<br />OPEN BAYS 1,2,7,8
<br />587
<br />Office spaces
<br />5
<br />3
<br />8
<br />5
<br />15
<br />0.06
<br />35.2
<br />50.2
<br />return
<br />0.8
<br />63
<br />Ceiling supply of
<br />warm air and ceiling
<br />OPEN BAY 3,4,5,E
<br />596
<br />Office spaces
<br />5
<br />3
<br />8
<br />5
<br />15
<br />0.06
<br />35.8
<br />50.8
<br />return
<br />0.8
<br />63
<br />Ceiling supply of
<br />warm a ceiling
<br />air and
<br />TREATMENT 1
<br />120
<br />Office spaces
<br />5
<br />1
<br />2
<br />5
<br />5
<br />0.06
<br />7.2
<br />12.2
<br />m
<br />0.8
<br />15
<br />Ceiling supply of
<br />warm air and
<br />TREATMENT 2
<br />120
<br />Office spaces
<br />5
<br />1
<br />2
<br />5
<br />5
<br />0.06
<br />7.2
<br />12.2
<br />return
<br />etum
<br />0.8
<br />15
<br />Ceiling supply of
<br />warm air and ceiling
<br />OFFICE 102
<br />76
<br />Office spaces
<br />5
<br />1
<br />2
<br />5
<br />5
<br />0.06
<br />4.6
<br />9.6
<br />return
<br />0.8
<br />12
<br />Ceiling supply of
<br />warm air and ceiling
<br />BUSINESS OFFICE 101
<br />219
<br />Offices aces
<br />P
<br />5
<br />2
<br />4
<br />5
<br />10
<br />0.06
<br />13.1
<br />23.1
<br />return
<br />0.8
<br />29
<br />Ceiling supply of
<br />warm aceiling
<br />BREAK ROOM 104
<br />211
<br />Office spaces
<br />5
<br />2
<br />8
<br />5
<br />10
<br />0.06
<br />12.7
<br />22.7
<br />return
<br />0.8
<br />28
<br />Ceiling supply of
<br />warm air and ceiling
<br />CONSULTANT 108
<br />87
<br />Offices aces
<br />P
<br />5
<br />1
<br />2
<br />5
<br />5
<br />0.06
<br />5.2
<br />10.2
<br />return
<br />0.8
<br />13
<br />Ceiling supply of
<br />warm air and ceiling
<br />WAITING 100
<br />270
<br />Booking/waiting
<br />50
<br />14
<br />10
<br />7.5
<br />105
<br />0.06
<br />16.2
<br />121.2
<br />return
<br />0.8
<br />152
<br />Ceiling supply of
<br />warm air and ceiling
<br />LAB
<br />93
<br />Offices aces
<br />P
<br />5
<br />1
<br />1
<br />5
<br />5
<br />0.06
<br />5.6
<br />10.6
<br />return
<br />0.8
<br />13
<br />Ceiling supply of
<br />warm air and ceiling
<br />BIO
<br />12
<br />Office spaces
<br />5
<br />1
<br />1
<br />5
<br />5
<br />0.06
<br />0.7
<br />5.7
<br />return
<br />0.8
<br />7
<br />Ceiling supply of
<br />warm air and ceiling
<br />STERILIZATION
<br />121
<br />Office spaces
<br />5
<br />1
<br />2
<br />5
<br />5
<br />0.06
<br />7.3
<br />1 12.3
<br />return
<br />0.8
<br />15
<br />Ceiling supply of
<br />warm air and ceiling
<br />TOILET 109
<br />55
<br />Toilet rooms and bathrooms
<br />1
<br />return
<br />0.8
<br />70
<br />Ceiling supply of
<br />warm air and ceiling
<br />TOILET 110
<br />55
<br />Toilet rooms and bathrooms
<br />1
<br />return
<br />0.8
<br />70
<br />Ceiling supply of
<br />warm air and ceiling
<br />CORRIDOR LOWER
<br />437
<br />Corridors
<br />0.06
<br />26.2
<br />26.2
<br />return
<br />0.8
<br />33
<br />Ceiling supply of
<br />warm air and ceiling
<br />CORRIDOR UPPER
<br />264
<br />Corridors
<br />0.06
<br />15.8
<br />15.8
<br />return
<br />0.8
<br />20
<br />TOTAL
<br />3,633
<br />52
<br />190
<br />230.0
<br />420.0
<br />511
<br />140
<br />SYSTEM OUTDOOR AIRFLOW = 510
<br />TOTAL EXH. RATE PLUS 10% FOR PRESSURIZATION = 154
<br />FINAL VENT. AIR REQUIREMENT Greater of Above = 510
<br />NOTES:
<br />1. COMPARISON OF THE TOTAL EXHAUST TO THE TOTAL VENTILATION IS TO ENSURE THAT THE VENTILATION AIR IS A MINIMUM OF 10% GREATER THAN THE EXHAUST AIR.
<br />2. ASSUME 75 CFM EXFILTRATION PER T-0" DOOR. EXHAUST SUPPLEMENT IS TO ELIMINATE USAGE OF BAROMETRIC LOUVER FOR OVER -PRESSURIZATION.
<br />EXHAUST FAN SCHEDULE
<br />EQUIP. NO.
<br />AREA SERVED
<br />MANUFACTURER
<br />MODEL
<br />TYPE
<br />FAN AIR FLOW
<br />(CFM)
<br />EXT. STATIC
<br />(in. w.g.)
<br />MAX SONES
<br />DRIVE TYPE
<br />POWER SUPPLY
<br />(V-(P-HZ)
<br />Control
<br />Notes
<br />TYPE MARK
<br />MARK
<br />EF
<br />1
<br />TOILET
<br />GREENHECK
<br />SP-A90
<br />CEILING
<br />70
<br />0.25
<br />0.4
<br />DIRECT
<br />115-1-60
<br />LIGHT SWITCH
<br />1,2,3
<br />EF
<br />2
<br />TOILET
<br />GREENHECK
<br />SP-A90
<br />CEILING
<br />70
<br />0.25
<br />0.4
<br />DIRECT
<br />115-1-60
<br />LIGHT SWITCH
<br />1,2,3
<br />EF
<br />3
<br />MECHANICAL
<br />GREENHECK
<br />SP-A110
<br />CEILING
<br />100
<br />1 0.25
<br />1 0.5
<br />1 DIRECT
<br />115-1-60
<br />CONTINUOUS
<br />1,2,3
<br />EF
<br />4
<br />MED GAS
<br />GREENHECK
<br />SP-A90
<br />CEILING
<br />70
<br />1 0.25
<br />1 0.4
<br />1 DIRECT
<br />115-1-60
<br />CONTINUOUS
<br />1,2,3
<br />NOTES:
<br />1. FANS SHALL HAVE AMCA CERTIFIED PERFORMANCE RATINGS AND SHALL BEAR AMCA RATINGS SEAL.
<br />2. PROVIDE SPRING/NEOPRENE VIBRATION ISOLATION DAMPERS
<br />3. PROVIDE WITH VARIGREEN MOTOR. ADJUST FOR AIR BALANCE.
<br />PACKAGED ROOFTOP UNIT SCHEDULE (ELEC)
<br />UNIT ELECTRICAL
<br />ENERGY
<br />ELECTRIC
<br />EQUIP. NO.
<br />SUPPLY FAN
<br />COMPRESSOR
<br />CONDENSER
<br />PROPERTIES
<br />DIRECT EXPANSION COOLING
<br />ANALYSIS
<br />HEATING
<br />SUPPLY
<br />OUTSIDE
<br />EXT.
<br />D_
<br />=
<br />UNIT
<br />MODEL
<br />NOMINALMANUFACTURER
<br />AIR FLOW
<br />AIR FLOW
<br />STATIC
<br />m
<br />$
<br />TOTAL
<br />SENSIBLE
<br />ENTERING
<br />LEAVING
<br />WEIGHT
<br />NOTES
<br />TYPE MARK
<br />MARK
<br />TONS
<br />(CFM)
<br />(CFM)
<br />(in. w.g.)
<br />rY
<br />g
<br />�
<br />COOLING
<br />COOLING
<br />AIR TEMP.
<br />AIR TEMP.
<br />ARI EER/IEER
<br />kW
<br />(LBS)
<br />a
<br />O
<br />d
<br />Of
<br />0
<br />U-
<br />w
<br />CAPACITY
<br />CAPACITY
<br />(DBMB)
<br />(DB/WB)
<br />O
<br />(MBH)
<br />(MBH)
<br />a
<br />RTU
<br />1
<br />CARRIER
<br />50HCD08
<br />1 7.5
<br />1 2625
<br />1 255
<br />1 0.64
<br />1 1
<br />1 1.00
<br />1 2
<br />1 13.E
<br />1 2
<br />1
<br />208-3-60
<br />1 94.8
<br />1 76.8
<br />1 80/67
<br />1 55/54
<br />1 12.20/13.2
<br />1 16
<br />1 1729
<br />1 1,2,3,4,5,E
<br />RTU
<br />2
<br />CARRIER
<br />50HCD08
<br />1 7.5
<br />1 2625
<br />1 255
<br />1 0.64
<br />1 1
<br />1 1.00
<br />1 2
<br />1 13.E
<br />1 2
<br />1
<br />208-3-60
<br />1 94.8
<br />1 76.8
<br />1 80/67
<br />1 55/54
<br />1 12.20/13.2
<br />1 16
<br />1 1729
<br />1 1,2,3,4,5,E
<br />NOTES:
<br />1. PROVIDE FAN CONTROLLER WITH NON -FUSED DISCONNECT AND THRU-THE-BASE CONNECTIONS.
<br />2. PROVIDE HINGED PANELS AND UNPOWERED (SEPARATE CIRCUIT) CONVENIENCE OUTLET,
<br />3. PROVIDE LOUVERED HAIL GUARD.
<br />4. PROVIDE 14" FACTORY ROOF CURB ACCESSORY.
<br />5. PROVIDE 7-DAY PROGRAMMABLE THERMOSAT WITH AUTOCHANGEOVER, NIGHT SETBACK,
<br />OCCUPANCY OVER -RIDE, LCD DISPLAY, AND HUMIDITY SENSOR.
<br />6. PROVIDE WITH HUMIDI-MIZER OPTION.
<br />MECHANICAL GENERAL NOTES
<br />1. IN PREPARATION OF THESE PLANS, THE ENGINEER HAS USED CERTAIN
<br />ABBREVIATIONS, CONVENTIONS, AND SYMBOLS, THE MEANING OF
<br />WHICH ARE ILLUSTRATED AND EXPLAINED WITHIN THE LEGEND.
<br />2. PLANS ARE DIAGRAMMATIC ONLY. THEY ARE INTENDED TO INDICATE
<br />CAPACITY, SIZE, LOCATION, DIRECTION, AND GENERAL ARRANGEMENT,
<br />BUT NOT EXACT DETAILS OF CONSTRUCTION. THE FACT THAT ONLY
<br />CERTAIN FEATURES OF THE INSTALLATION ARE INDICATED MUST NOT
<br />BE TAKEN TO MEAN THAT OTHER FEATURES WILL NOT BE REQUIRED.
<br />3. COORDINATE WITH THE OTHER TRADES TO ENSURE THAT EACH TRADE
<br />SHALL HAVE SUFFICIENT SPACE TO INSTALL THEIR EQUIPMENT
<br />(DUCTWORK, PIPING, ELECTRICAL WORK, ETC.).
<br />4. IN GENERAL, ALL PIPING AND DUCTWORK SHALL BE RUN IN THE CEILING
<br />SPACE UNLESS NOTED OR INDICATED OTHERWISE.
<br />5. VERIFY ALL DIMENSIONS FROM ARCHITECTURAL PLANS AND FIELD
<br />DIMENSIONS.
<br />6. DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE
<br />DIMENSIONS.
<br />7. ALL RISES AND DROPS IN PIPING AND DUCTWORK MAY NOT
<br />NECESSARILY HAVE BEEN SHOWN. CONTRACTOR TO VERIFY.
<br />8. PROVIDE ALL STRUCTURAL MEMBERS, SUPPORT BRACKETS, FLASHING,
<br />HARDWARE, ETC. REQUIRED TO INSTALL A COMPLETE SYSTEM.
<br />9. DIFFUSERS AND REGISTER LOCATIONS SHALL BE COORDINATED WITH
<br />LIGHT FIXTURE AND OTHER CEILING DEVICE LOCATIONS, FIELD VERIFY.
<br />10. MOUNT ALL THERMOSTATS AND/OR SENSORS 4 FEET ABOVE FINISHED
<br />FLOOR, UNLESS OTHERWISE NOTED.
<br />AIR DISTRIBUTION DEVICE SCHEDULE
<br />A - TITUS MODEL TMS-AA LOUVER -FACED CEILING DIFFUSER
<br />B - TITUS MODEL 50F RETURN/EXHAUST EGGCRATE GRILLE
<br />C - TITUS MODEL 30OFS SIDEWALL SUPPLY REGISTER (W/ O.B.D.)
<br />D - TITUS MODEL 350 FS SIDEWALL RETURN GRILLE
<br />NOTES:
<br />1. COLOR TO BE SPECIFIED BY ARCHITECT.
<br />2. NECK SIZES TO MATCH SIZE OF DUCTWORK TO EACH AIR DEVICE.
<br />EACH AIR DEVICE SHALL HAVE A VOLUME DAMPER IN THE DUCT
<br />CONNECTED TO THE DEVICE UNLESS NOTED OTHERWISE. IF AIR DEVICE
<br />IS LOCATED IN AN INACCESSIBLE CEILING, VOLUME DAMPER SHALL BE
<br />INTEGRAL WITH THE AIR DEVICE.
<br />EACH AIR DEVICE SHALL HAVE A VOLUME DAMPER IN THE DUCT
<br />CONNECTED TO THE DEVICE UNLESS NOTED OTHERWISE. IF AIR DEVICE
<br />IS LOCATED IN AN INACCESSIBLE CEILING, PROVIDE INTEGRAL AIR DEVICE
<br />ACCESS PANEL EQUAL TO TITUS MODEL TRM, "RAPID MOUNT FRAME"
<br />AND LOCATE VOLUME DAMPER WITHIN 2'-0" OF CENTER OF DEVICE.
<br />I
<br />©©� El-
<br />4-WAY 3-WAY 2-WAY 2-WAY 1-WAY
<br />THROW THROW OPPOSITE CORNER THROW
<br />THROW THROW
<br />ABBREVIATIONS
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />AHU
<br />AIR HANDLING UNIT
<br />A
<br />AMPERE
<br />BHP
<br />BRAKE HORSEPOWER
<br />BTUH
<br />BRITISH THERMAL UNIT PER HOUR
<br />CLG
<br />CEILING
<br />CD
<br />CONDENSATE DRAIN
<br />CU
<br />CONDENSING UNIT
<br />CFM
<br />CUBIC FEET PER MINUTE
<br />0
<br />DIAMETER
<br />DX
<br />DIRECT EXPANSION
<br />DN
<br />DOWN
<br />DB
<br />DRY BULB
<br />EL
<br />ELEVATION
<br />EAT
<br />ENTERING AIR TEMPERATURE
<br />EQUIP
<br />EQUIPMENT
<br />EXH
<br />EXHAUST
<br />EA
<br />EXHAUST AIR
<br />EF
<br />EXHAUST FAN
<br />ESP
<br />EXTERNAL STATIC PRESSURE
<br />FPM
<br />FEET PER MINUTE
<br />FB
<br />FILTER BOX
<br />FD
<br />FIRE DAMPER
<br />FPI
<br />FINS PER INCH
<br />FLEX
<br />FLEXIBLE
<br />FLR or FL
<br />FLOOR
<br />GALV
<br />GALVANIZED
<br />HP
<br />HORSEPOWER
<br />KW
<br />KILOWATT
<br />MANUF
<br />MANUFACTURER
<br />VD
<br />MANUAL VOLUME DAMPER
<br />MAX
<br />MAXIMUM
<br />MIN
<br />MINIMUM
<br />OA
<br />OUTSIDE AIR
<br />LBS
<br />POUNDS
<br />RA
<br />RETURN AIR AND/OR ROOM AIR
<br />RTU
<br />ROOFTOP UNIT
<br />OBD
<br />OPPOSED BLADE DAMPER
<br />OVAL
<br />SQFT
<br />SQUARE FEET
<br />SQIN
<br />SQUARE INCHES
<br />SA
<br />SUPPLY AIR
<br />TEMP
<br />TEMPERATURE
<br />MBH
<br />THOUSAND BTU/H
<br />TAD
<br />TRANSFER AIR DUCT
<br />TYP
<br />TYPICAL
<br />UC
<br />UNDERCUT
<br />V
<br />VOLTS
<br />WB
<br />WET BULB
<br />GENERAL SYMBOLS
<br />PLAN OR DETAIL NO.
<br />SHEET NUMBER
<br />OKEYED
<br />NOTE TO PLAN
<br />QREVISION
<br />NUMBER
<br />N
<br />NORTH ARROW
<br />MECHANICAL SYMBOL LEGEND
<br />xCEILING
<br />SUPPLY DIFFUSER
<br />zCEILING
<br />RETURN GRILLE
<br />zCEILING
<br />EXHAUST GRILLE
<br />0
<br />CEILING EXHAUST FAN
<br />IN -LINE EXHAUST FAN
<br />WALL
<br />DYNAMIC FIRE DAMPER, STYLE'B' FIRE
<br />DUCT
<br />DAMPER, STYLE'CR' FIRE DAMPER FOR
<br />FD
<br />ROUND DUCTS
<br />WALL
<br />DUCT :::::4
<br />SD
<br />DYNAMIC SMOKE DAMPER
<br />WALL
<br />DUCT
<br />COMBINATION DYNAMIC FIRE / SMOKE DAMPER
<br />FSD
<br />sD
<br />DUCT SMOKE DETECTOR
<br />RETURN / EXHAUST DUCT TURNING DN
<br />RETURN / EXHAUST DUCT TURNING UP
<br />SUPPLY / OUTSIDE DUCT TURNING DN
<br />SUPPLY / OUTSIDE DUCT TURNING UP
<br />EXISTING DUCT
<br />TRANSFER OPENING IN WALL ABOVE CEILING
<br />UC
<br />3/4" UNDERCUT BELOW DOOR
<br />RD
<br />RADIANT DAMPER (RD)
<br />CONNECT TO EXISTING
<br />O
<br />DISCONNECT FROM EXISTING
<br />SIDE WALL SUPPLY GRILLE
<br />�-r-
<br />SIDE WALL RETURN GRILLE
<br />A-12x12
<br />200 CFM
<br />AIR DEVICE TYPE AND SIZE AIR FLOW CFM
<br />THERMOSTAT, HUMIDISTAT, CO2 SENSOR
<br />-R�
<br />REFRIGERANT PIPING (LINE SET)
<br />C----
<br />CONDENSATE DRAIN PIPING
<br />?---+C)
<br />PIPE TURNING UP
<br />PIPE TURNING DOWN
<br />2 POSITION MOTORIZED DAMPER
<br />MANUAL VOLUME DAMPER
<br />CHWS
<br />CHILLED WATER SUPPLY PIPING
<br />CHWR
<br />CHILLED WATER RETURN PIPING
<br />CWS
<br />CONDENSING WATER SUPPLY PIPING
<br />CWR
<br />CONDENSING WATER RETURN PIPING
<br />N
<br />GATE VALVE
<br />BALL VALVE
<br />CHECK VALVE
<br />STRAINER
<br />STRAINER WITH BLOW DOWN VALVE
<br />I
<br />I
<br />UNION
<br />NEEDLE VALVE WITH PRESSURE GAUGE
<br />4
<br />THERMOMETER
<br />I�I
<br />BUTTERFLY VALVE
<br />BALANCING VALVE
<br />FLEX CONNECTION
<br />MOTORIZED CONTROL VALVE
<br />TRIPLE DUTY VALVE
<br />��❑
<br />VERTICAL INLINE PUMP (PLAN VIEW)
<br />PUMP
<br />AUTOMATIC AIR VENT
<br />\\\0\ 11 I G l 111 /jai
<br />i
<br />0 1
<br />r
<br />�0 SATE_ F ,44i
<br />Z
<br />°4 GRID P.-' ����
<br />JA*4
<br />MCVE I G H GUM
<br />ENGINEERING INC
<br />Atlanta • Charlotte • Jacksonville Raleigh
<br />www.MeVeigbManguTn.com
<br />1955 Lake Park Drive SE, Suite 325
<br />Smyrna, Georgia 30080
<br />Ph: (678) 213-1616
<br />email: mail@McVeighMangum.com
<br />PEF005182
<br />Eng. of Record: KENNETH GONZALEZ License No.:61015
<br />R A D A L L
<br />P A U L S 0 N
<br />r c h t e c t S
<br />Roswell Mill
<br />85-A Mill Street, Suite 200
<br />Roswell, Georgia 30015
<br />t 170.650.1550 f 770.650.7550
<br />e-mail architects@randallpaulson.com
<br />arch itecture/interiors
<br />These plans and specifications are the property of llandall-Paulson Architects,
<br />Incorporated. These documents may not he copied, reproduced used or
<br />implemented in any way, in part or in whole, without the written consent of
<br />Randall -Paulson Architects, Incorporated. All common law rights of copyright are
<br />hereby specifically reserved.
<br />TENANT
<br />BUILD -OUT
<br />at
<br />ZEPHYRHILLS
<br />for
<br />z
<br />,�w�IMfr iIIMM�M.
<br />U.S. HIGHWAY 301 & PRETTY
<br />POND ROAD,
<br />ZEPHYRHILLS, FLORIDA 33541
<br />Print Record
<br />14 JUNE 2021 ISSUE FOR PERMIT
<br />Revisions
<br />Date Project No.
<br />14 JUNE 2021 2021217.00
<br />Sheet Title
<br />NOTES, LEGENDS, & SYMBOLS
<br />Sheet No.
<br />MM001
<br />Released for Construction
<br />❑ Not Released for Construction
<br />
|