GENERAL ELECTRICAL NOTES
<br />1. ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH THE APPLICABLE EDITION OF THE NATIONAL
<br />ELECTRICAL CODE AND ALL LOCAL AND STATE CODES.
<br />2. ALL MATERIAL SHALL BE NEW AND SHALL CONFORM TO THE STANDARDS OF THE UNDERWRITER'S
<br />LABORATORIES, INC., AND THE NATIONAL MANUFACTURERS ASSOCIATION.
<br />3. ALL ELECTRICAL PERMITS AND INSPECTION FEES SHALL BE OBTAINED AND PAID FOR BY THE ELECTRICAL
<br />CONTRACTOR.
<br />4. DRAWINGS ARE DIAGRAMMATIC ONLY AND INDICATE ONLY THE GENERAL ARRANGEMENT. SEE
<br />ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONS.
<br />5. ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIALS FOR ONE YEAR EFFECTIVE
<br />THE DAY HE PROJECT IS ACCEPTED BY THE OWNER.
<br />6. ELECTRICAL CONTRACTOR SHALL MAKE ALL ELECTRICAL POWER CONNECTIONS TO HVAC, PLUMBING,
<br />AND OTHER EQUIPMENT AS REQUIRED.
<br />7. A COMPLETE GROUNDING SYSTEM SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH ARTICLE
<br />250 OF THE NEC, AND AS SHOWN ON THE DRAWINGS.
<br />8. ALL CUTTING AND PATCHING OF WALLS AND FLOORS FOR ELECTRICAL EQUIPMENT SHALL BE THE
<br />RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
<br />9. ALL WIRING SHALL BE INSTALLED IN GALVANIZED RIGID CONDUIT, INTERMEDIATE METAL CONDUIT, OR
<br />EMT. EMT SHALL NOT BE USED IN OR UNDER CONCRETE SLABS, OR IN MASONRY WALLS. USE SCHEDULE
<br />40 PVC OUTDOORS WHERE NOT SUBJECT TO PHYSICAL DAMAGE OR BELOW FLOOR SLAB.
<br />CONCEALED BRANCH CIRCUITS RATED 30 AMPS OR LESS MAY UTILIZE TYPE MC FLEXIBLE METAL CABLE
<br />WHERE CODE ALLOWS. SUPPORT WITHIN 12" OF ALL CONNECTIONS AND NOT MORE THAN 4'-6" ON
<br />CENTER.
<br />ALL RACEWAYS (EXCEPT THOSE BELOW SLAB OR GRADE) SHALL BE INSTALLED PARALLEL OR
<br />PERPENDICULAR TO BUILDING LINES.
<br />10. BRANCH CIRCUIT CONDUCTORS SHALL BE COPPER RATED AT NOT LESS THAN 600 VOLTS. MINIMUM SIZE
<br />SHALL BE #12 AWG UNLESS OTHERWISE NOTED ON THE DRAWINGS. ALL WIRE #8 AWG AND LARGER
<br />SHALL BE STRANDED. ALL CONDUCTORS #10 AND SMALLER SHALL BE SOLID, UNLESS OTHERWISE
<br />NOTED.
<br />FEEDERS RATED GREATER THAN 150 AMPERES MAY UTILIZE 750C COMPACT ALUMINUM CONDUCTORS OF
<br />EQUIVALENT AMPACITY, TYPE XHHW OR XHHW-2 INSULATION, EQUIVALENT TO ALCAN SERIES 8000
<br />CONDUCTORS. CONTRACTOR TO VERIFY CONDUIT SIZES REQUIRED FOR ALUMINUM FEEDERS.
<br />11. BRANCH CIRCUIT CONDUCTORS SHALL BE TYPE THHN OR THWN AS REQ'D.
<br />12. PROVIDE A PULLWIRE IN ALL EMPTY CONDUITS.
<br />13. PROVIDE A TYPED DIRECTORY IN ALL PANELBOARDS CLEARLY DESCRIBING THE LOCATION OF AND TYPE
<br />OF LOAD BEING SERVED FOR ALL CIRCUITS.
<br />14. PROVIDE ENGRAVED PHENOLIC NAMEPLATES FOR ALL PANELBOARDS AND DISCONNECT SWITCHES,
<br />BLACK LETTERS ON WHITE BACKGROUND.
<br />15. FUSES 0 - 600 AMPS SHALL BE UL CLASS "RK-1" LOW PEAK DUAL ELEMENT TIME DELAY WITH 2O0,000
<br />AMPERE INTERRUPTING RATING AS MANUFACTURED BY BUSS, UNLESS NOTED OTHERWISE.
<br />16. VERIFY ALL REQUIREMENTS AND COORDINATE EXACT LOCATION OF INCOMING ELECTRICAL SERVICE
<br />WITH LOCAL POWER COMPANY PRIOR TO PROJECT START-UP. NOTIFY ENGINEER OF ANY CHANGES AS
<br />MAY BE REQUIRED.
<br />AVAILABLE FAULT CURRENT AT SERVICE TRANSFORMER TO BE FIELD VERIFIED WITH SERVING UTILITY.
<br />ACTUAL FAULT CURRENT VALUES TO BE FIELD MARKED ON ALL GEAR IN ACCORDANCE WITH NEC 110.24.
<br />17. PROVIDE SCHEDULE 40 PVC CONDUIT UNDERGROUND FROM TELEPHONE EQUIPMENT ROOM TO
<br />CONNECTION POINT AS DIRECTED BY LOCAL TELEPHONE COMPANY.
<br />18. ALL TERMINALS, SPLICING CONNECTORS, LUGS, ETC. SHALL BE IDENTIFIED FOR USE WITH THE MATERIAL
<br />(CU/AL) OF THE CONDUCTOR AND SHALL BE PROPERLY INSTALLED.
<br />19. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL ELECTRICAL EQUIPMENT
<br />FROM FOREIGN MATERIAL DURING CONSTRUCTION (PAINT, SPACKLE, ETC.).
<br />20. PENETRATIONS OF REQUIRED SMOKE PARTITIONS SHALL BE SEALED USING METHODS APPROVED UNDER
<br />THE STATE BUILDING CODE. COORDINATION WITH THE GENERAL CONTRACTOR SHALL BE MAINTAINED
<br />TO INSURE THAT THIS SMOKE STOPPING IS ACCOMPLISHED.
<br />21. WHERE PENETRATIONS ARE MADE THROUGH A REQUIRED FIRE -RESISTIVE WALL, FLOOR, OR PARTITION
<br />FOR THE PURPOSE OF RUNNING RACEWAY CARRYING ELECTRICAL, TELEPHONE, TELEVISION, OR LOCAL
<br />COMMUNICATION AND/OR SIGNALING CIRCUITS, THE OPENING AROUND THE RACEWAY SHALL BE FIRE
<br />STOPPED PER THE STATE BUILDING CODE. COORDINATION WITH THE GENERAL CONTRACTOR SHALL BE
<br />MAINTAINED TO INSURE THAT THIS FIRE STOPPING IS ACCOMPLISHED. USE APPROVED ASSEMBLIES
<br />SUCH AS THE FOLLOWING:
<br />UP TO 1" PENETRATIONS OF 1, 2,3 & 4 HOUR GYPSUM WALLS - U.L.#WL1001
<br />UP TO 4" PENETRATIONS OF 1 & 2 HOUR GYPSUM WALLS - U.L.#WL1001
<br />UP TO 4" PENETRATIONS OF 1 & 2 HOUR CONC. OR BLOCK WALLS & FLOORS - U.L.#CAJ1009
<br />UP TO 4" PENETRATIONS OF 3 & 4 HOUR CONC. OR BLOCK WALLS & FLOORS - U.L.#CBJ1020.
<br />22. IN REQUIRED FIRE RATED WALLS AND PARTITIONS, OPENINGS FOR INSTALLATION OF BOXES THAT ARE
<br />GREATER THAN 16 SQUARE INCHES SHALL BE PROTECTED AS REQ'D BY U.L. COORDINATE CLOSELY WITH
<br />THE GENERAL CONTRACTOR TO INSURE THAT THE INTEGRITY OF THE U.L. RATING IS MAINTAINED.
<br />23. WHERE A HOME RUN IS SHOWN, THE CIRCUIT SHALL BE INSTALLED IN A DEDICATED CONDUIT, DO NOT
<br />COMBINE WITH OTHER CIRCUITS. WHERE A CIRCUIT HOMERUN IS NOT SHOWN, THE CONTRACTOR SHALL
<br />COMBINE CIRCUITS AS FOLLOWS:
<br />• A MAXIMUM OF THREE 20A BRANCH CIRCUITS MAY BE COMBINED IN A COMMON HOMERUN SHARING A
<br />COMMON NEUTRAL OR WITH SEPARATE NEUTRALS FOR A MAXIMUM OF TOTAL OF SIX CURRENT
<br />CARRYING CONDUCTORS.
<br />• 20A BRANCH CIRCUITS SERVING NON -LINEAR LOADS (FLUOR. LIGHTING, EMPLOYEE WORKSTATIONS,
<br />DATA SYSTEMS, ETC.) USING SHARED NEUTRALS SHALL UTILIZE #10 CU NEUTRAL, MINIMUM.
<br />• ALL BRANCH CIRCUITS LARGER THAN 20A SHALL BE SEPARATELY HOMERUN TO THE PANEL.
<br />24. ALL RACEWAYS SHALL BE CONCEALED UNLESS OTHERWISE NOTED. THE ELECTRICAL CONTRACTOR
<br />SHALL BE RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH CONCEALING RACEWAYS AFTER INITIAL
<br />CONSTRUCTION.
<br />25, CLOSE OUT DOCUMENTS:
<br />• AS-BUILTS: WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE
<br />ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER, INCLUDING:
<br />1) A SINGLE -LINE DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND
<br />2) FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL DISTRIBUTION.
<br />• OPERATION AND MAINTENANCE MANUALS: AN OPERATING MANUAL AND MAINTENANCE MANUAL
<br />SHALL BE PROVIDED TO THE BUILDING OWNER. THE MANUALS SHALL INCLUDE, AT A MINIMUM, THE
<br />FOLLOWING:
<br />1) SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF
<br />EQUIPMENT REQUIRING MAINTENANCE;
<br />2) OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING
<br />MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED;
<br />3) NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY.
<br />26. COMMISSIONING:
<br />WHERE OCCUPANT SENSORS, TIME SWITCHES, PROGRAMMABLE SCHEDULE CONTROLS,
<br />PHOTOSENSORS, OR DAYLIGHTING CONTROLS ARE INSTALLED, COMMISSIONING SHALL BE PROVIDED.
<br />FOR ANY OCCUPANCY SENSORS, CONFIRM THAT THE PLACEMENT, SENSITIVITY, AND TIME-OUT
<br />ADJUSTMENTS YIELD ACCEPTABLE PERFORMANCE; FOR ANY TIME SWITCHES AND PROGRAMMABLE
<br />SCHEDULE CONTROLS, CONFIRM THAT PROGRAMMING TURNS LIGHTS OFF; FOR ANY PHOTOSENSOR
<br />CONTROLS, CONFIRM THAT THE PLACEMENT AND SENSITIVITY ADJUSTMENTS REDUCE ELECTRIC LIGHTS
<br />BASED ON THE AMOUNT OF USABLE DAYLIGHT IN SPACE AS SPECIFIED. COMMISSIONING SHALL BE
<br />PERFORMED BY THE CONTRACTOR UNDER THE DIRECTION OF THE LIGHTING CONTROLS CERTIFIED
<br />MANUFACTURER'S REPRESENTATIVE. CERTIFICATE DOCUMENTATION OF THE REPRESENTATIVE SHALL
<br />BE INCLUDED IN SHOP DRAWING / PRODUCT DATA SUBMITTAL.
<br />ELECTRICAL SYMBOL LEGEND
<br />WIRING AND WIRING DEVICES
<br />COMMUNICATIONS
<br />WIRING SYSTEM CONCEALED IN WALL OR CEILING. DASHED LINES INDICATE WIRING RUN BELOW SLAB / GRADE.
<br />OUTLETS SHALL BE MOUNTED AT SAME HEIGHT AS ADJACENT RECEPTACLE, w/ CONDUIT STUBBED OUT ABOVE ACCESSIBLE CEILING.
<br />_
<br />'W' INDICATES 48" AFF MOUNTING.
<br />/
<br />\
<br />LOW VOLTAGE CONTROL WIRING SYSTEM CONCEALED IN WALL OR CEILING.
<br />• 'INT' INDICATES INTERCOM OUTLET.
<br />WIRING SYSTEM TO BE RUN EXPOSED. DASHED LINES INDICATE WIRING RUN BELOW SLAB / GRADE.
<br />VVTELEPHONE
<br />OUTLET w/ 3/4"C, CEILING, FLOOR AND WALL MOUNTED.
<br />® ® 0
<br />DATA OUTLET w/ 1"C, CEILING, FLOOR AND WALL MOUNTED.
<br />BRANCH CIRCUIT HOMERUN TO PANEL. NUMBER OF ARROWHEADS INDICATE NUMBER OF CIRCUITS. THREE CIRCUITS OF ALTERNATING
<br />FLOOR AND WALL MOUNTED.
<br />PHASES MAY BE COMBINED IN ONE CONDUIT, HOWEVER THEY SHALL EITHER BE EQUIPPED w/ DEDICATED NEUTRALS, COMMON TRIP
<br />® ®
<br />COMBINATION TEL / DATA OUTLET w/ 1"C, CEILING,
<br />CIRCUIT BREAKERS, OR HANDLE -TIES ON THEIR BREAKERS.
<br />4
<br />WALL MOUNTED TV OUTLET w/ 1"C, UON, SEE ARCH PLANS FOR MOUNTING HEIGHT.
<br />MOTOR PROVIDED AND INSTALLED BY MECH. CONTRACTOR, WIRED BY ELEC. CONTRACTOR, NUMERALS INDICATE HORSEPOWER.
<br />O®
<br />RECEPTACLE (SIMPLEX, DUPLEX, DOUBLE DUPLEX, 220V OR SPECIAL), COMBINATION TEUDATA OUTLET w/ 1"C, AND INTERCOM OUTLET IN
<br />Q
<br />JUNCTION BOX, CEILING AND WALL MOUNTED.
<br />FLOOR / WALL BOX, WIREMOLD FB-SERIES OR APPROVED EQUAL, UON.
<br />• 'P' INDICATES SYSTEMS FURNITURE POWER WHIP, SEE DETAILS.
<br />FGAPI
<br />GENERATOR ANNUNCIATOR PANEL.
<br />• 'C' INDICATES SYSTEMS FURNITURE COMMUNICATIONS WHIP, SEE DETAILS.
<br />sP sP
<br />SPEAKER CEILING AND WALL MOUNTED.
<br />KD
<br />SINGLE SERVICE FLOORBOX / POKE -THROUGH, JUNCTION BOX.
<br />Ds
<br />DISCONNECT SWITCH FOR NOTIFICATION.
<br />• ON -GRADE: HUBBELL B2536 SERIES BOX OR APPROVED EQUAL, UON.
<br />• ABOVE GRADE: HUBBELL S1 PT4X4-J BOX SERIES OR APPROVED EQUAL, UON.
<br />DB
<br />DOOR BELL PUSH BUTTON.
<br />• 'P' INDICATES SYSTEMS FURNITURE POWER WHIP, SEE DETAILS.
<br />LOW VOLTAGE TRANSFORMER.
<br />• 'C' INDICATES SYSTEMS FURNITURE COMMUNICATIONS WHIP, SEE DETAILS.
<br />D�A
<br />VISUAL / AUDIBLE DOOR NOTIFICATION.
<br />FIRE ALARM DEVICES
<br />SITE
<br />rc
<br />INTERCOMM.
<br />• 'C' INDICATES CEILING MOUNTED.
<br />BOLLARD LIGHT FIXTURE.
<br />vc
<br />VOLUME CONTROL.
<br />®
<br />CARBON MONOXIDE DETECTOR WALL OR CEILING MOUNTED.
<br />u
<br />GROUND BAR.
<br />❑H
<br />HEAT DETECTOR WALL OR CEILING MOUNTED.
<br />GROUND MOUNTED FLOODLIGHT FIXTURE.
<br />wAP
<br />WAP.
<br />❑s
<br />SMOKE DETECTOR WALL OR CEILING MOUNTED.
<br />DATA PATCH PANEL.
<br />GROUND MOUNTED LINEAR SIGNLIGHT FIXTURE.
<br />❑°
<br />SMOKE DETECTOR DUCT MOUNTED.
<br />FACP
<br />FIRE ALARM CONTROL PANEL.
<br />POST TOP LIGHT FIXTURE.
<br />SWITCHING
<br />FAAP
<br />FIRE ALARM ANNUNCIATOR PANEL.
<br />�❑
<br />POLE MOUNTED SITE LIGHT FIXTURE (1 HEAD).
<br />20A, 120/277 VOLT, +48" AFF TO TOP, UON.
<br />'Z
<br />NAc
<br />FIRE ALARM NOTIFICATION APPLIANCE CABINET.
<br />INDICATES 2-POLE.
<br />'3' INDICATES 3-WAY.
<br />ERRCS
<br />EMERGENCY RESPONDER RADIO COVERAGE SYSTEM.
<br />�-♦�
<br />POLE MOUNTED SITE LIGHT FIXTURE (2 HEAD).
<br />W INDICATES 4-WAY.
<br />DOOR HOLDER INTERFACE DEVICE.
<br />'D' INDICATES 0-10V DIMMER SWITCH. COORDINATE EXACT TYPE AND RATING w/ LIGHTING CONTROLLED.
<br />NURSE CALL
<br />rM ❑
<br />INPUT MODULE INTERFACE DEVICE.
<br />'T' INDICATES 0-60 MINUTE TIMER SWITCH.
<br />'KG INDICATES KEY OPERATED SWITCH.
<br />❑R
<br />RELAY INTERFACE DEVICE.
<br />NCAP
<br />NURSE CALL ANNUNCIATOR PANEL (MASTER STATION).
<br />'LV' INDICATES LOW VOLTAGE SWITCH.
<br />Fs
<br />FIRE ALARM FLOW SWITCH.
<br />Ncec
<br />NURSE CALL EQUIPMENT CABINET.
<br />'LV2' INDICATES 2-RELAY LOW VOLTAGE SWITCH.
<br />'[#]' INDICATES LIGHTING CONTROL ZONE. SEE LIGHTING CONTROL SCHEDULE FOR DETAILS.
<br />Ps
<br />FIRE ALARM PRESSURE SWITCH.
<br />sD
<br />STAFF DUTY STATION.
<br />'OV' INDICATES LIGHTING CONTACTOR OVERRIDE SWITCH.
<br />rs
<br />FIRE ALARM TAMPER SWITCH.
<br />lsA
<br />STAFF ASSIST STATION.
<br />0
<br />FIRE ALARM PULL STATION.
<br />Ec
<br />EMERGENCY CALL STATION (CODE BLUE).
<br />$
<br />SINGLE POLE SWITCH.
<br />LF
<br />LOW FREQUENCY ALARM DEVICE.
<br />DL
<br />NURSE DOME LIGHT.
<br />$ VS
<br />LINE VOLTAGE, VACANCY SENSOR SWITCH, MANUAL -ON / AUTO -OFF, DUAL -TECHNOLOGY, PROVIDE COMPLETE ROOM COVERAGE.
<br />8
<br />VISUAL ONLY ALARM DEVICE.
<br />zL
<br />NURSE ZONE LIGHT.
<br />$ OC
<br />LINE VOLTAGE, OCCUPANCY SENSOR SWITCH, AUTO -ON / AUTO -OFF, DUAL -TECHNOLOGY, PROVIDE COMPLETE ROOM COVERAGE.
<br />Pc
<br />PATIENT CALL STATION.
<br />ff]
<br />VISUAL / AUDIBLE ALARM DEVICE.
<br />ss
<br />❑
<br />PATIENT CALL BATH STATION.
<br />s OC/D
<br />LINE VOLTAGE, OCCUPANCY SENSOR SWITCH w/ DIMMING, AUTO -ON / AUTO -OFF, DUAL -TECHNOLOGY, PROVIDE COMPLETE ROOM
<br />'T'
<br />COVERAGE.
<br />LBJ
<br />BELL ALARM DEVICE.
<br />INDICATES TOILET STATION, INSTALL WITHIN 12" OF
<br />sP
<br />SPEAKER ALARM DEVICE.
<br />TOILET BOWL.
<br />'S' INDICATES SHOWER STATION.
<br />VS/D
<br />LINE VOLTAGE, VACANCY SENSOR SWITCH w/ DIMMING, AUTO -ON / AUTO -OFF, DUAL -TECHNOLOGY, PROVIDE COMPLETE ROOM
<br />COVERAGE.
<br />PP PP2
<br />LOW -VOLTAGE CONCEALED POWER PACK FOR OCCUPANCY SENSOR.
<br />ss
<br />SPEAKER / STROBE ALARM DEVICE.
<br />LIGHTNING PROTECTION
<br />co
<br />SINGLE STATION CARBON MONOXIDE ALARM.
<br />PPA PPA2
<br />LOW -VOLTAGE CONCEALED POWER PACK FOR OCCUPANCY SENSOR, AUTO -ON / AUTO -OFF.
<br />Q
<br />SINGLE STATION HEAT ALARM.
<br />LIGHTNING PROTECTION AIR TERMINAL.
<br />PPM PPM
<br />LOW -VOLTAGE CONCEALED POWER PACK FOR OCCUPANCY SENSOR, MANUAL -ON / AUTO -OFF.
<br />s
<br />O
<br />SINGLE STATION SMOKE ALARM .
<br />�`
<br />LIGHTNING PROTECTION DOWN CONDUCTOR
<br />PPD PPD2
<br />LOW -VOLTAGE CONCEALED POWER PACK FOR OCCUPANCY SENSOR, MANUAL -ON / AUTO -OFF, 0-10V DIMMING.
<br />O
<br />SINGLE STATION DUCT SMOKE ALARM.
<br />AND GROUND ROD.
<br />vs vs
<br />LOW -VOLTAGE DUAL -TECHNOLOGY VACANCY SENSOR, CEILING AND WALL MOUNTED, MANUAL -ON / AUTO -OFF w/ EXTENDED RANGE (AT
<br />.
<br />LIGHTNING PROTECTION CONDUCTOR.
<br />LEAST 56'-0"MINOR MOTION RANGE DIAMETER AT 9'-0" AFF MOUNTING HEIGHT )
<br />Q
<br />SINGLE STATION DUCT SMOKE REMOTE ALARM.
<br />oc oc
<br />LOW -VOLTAGE DUAL -TECHNOLOGY OCCUPANCY SENSOR, CEILING AND WALL MOUNTED, AUTO -ON / AUTO -OFF w/ EXTENDED RANGE (AT
<br />LEAST 56-0" MINOR MOTION RANGE DIAMETER AT 9'-0" AFF MOUNTING HEIGHT).
<br />RECEPTACLES
<br />ALL RECEPTACLES SHALL BE A MINIMUM RATING OF 120 VOLT, 20 AMP, UON, VERTICAL MOUNTED BOX HEIGHTS SHALL BE TO CENTER,
<br />Pc
<br />NORTH FACING ROOF MOUNTED PHOTOCELL.
<br />HORIZONTAL MOUNTED BOX HEIGHTS SHALL BE TO TOP, UON.
<br />EEI
<br />TIMECLOCK, REFER TO LIGHTING CONTROL DIAGRAM.
<br />• 'AFI' INDICATES ARC FAULT CIRCUIT INTERRUPTER.
<br />iv
<br />INVERTER, 50W, 277V, 90 MINUTE BATTERY.
<br />• 'GFI' INDICATES GROUND FAULT CIRCUIT INTERRUPTER.
<br />LIGHTING FIXTURES
<br />• 'WP' INDICATES WEATHERPROOF IN USE, WEATHER -RESISTANT RECEPTACLE w/ IN -USE EXTRA DUTY COVER. RECEPTACLES LOCATED IN
<br />WET OR DAMP LOCATIONS SHALL BE WP, WHETHER INDICATED OR NOT.
<br />• 'EWC' INDICATES ELECTRIC WATER COOLER.
<br />SEE FIXTURE SCHEDULE FOR DETAILS.
<br />• 'EX' INDICATES EXISTING TO BE REUSED.
<br />'N/L' INDICATES FIXTURE UNSWITCHED (NITE LIGHT).
<br />• 'HD' INDICATES HAND DRYER CONNECTION.
<br />LOWER CASE LETTERING DENOTES SWITCH /RELAY CONTROLLING THE FIXTURE.
<br />• 'TR' INDICATES TAMPER RESISTANT (INTEGRAL TO RECEPTACLE). ALL DWELLING UNIT DUPLEX RECEPTACLES SHALL BE LISTED TAMPER
<br />SHADING:
<br />RESISTANT TYPE. ALL NON -LOCKING, 120V, 15A AND 20A RECEPTACLES SHALL BE TAMPER -RESISTANT, EXCEPT IN MECHANICAL ROOMS,
<br />1/2 SHADING INDICATES FIXTURE TO BE PROVIDED w/ 90-MINUTE, MINIMUM BATTERY BACKUP.
<br />ELECTRICAL ROOMS, AND JANITORS CLOSETS, WHETHER INDICATED OR NOT.
<br />O>
<br />DOWNLIGHT RECESSED FIXTURE, ARROW INDICATES WALL WASH TYPE AND DIRECTION TO AIM FIXTURE.
<br />• 'CH' INDICATES HALF CONTROLLED.
<br />DOWNLIGHT SURFACE MOUNTED FIXTURE.
<br />• 'CF' INDICATES FULL CONTROLLED (BOTH PLUGS OF DUPLEX).
<br />• 'SB' INDICATES RECEPTACLE FOR SMARTBOARD, SEE DETAIL.
<br />EMERGENCY EGRESS LIGHT FIXTURE.
<br />• 'DING INDICATES POWER/USB CHARGING.
<br />> i>
<br />EXIT SIGN FIXTURE, CEILING AND WALL MOUNTED. SHADING INDICATES ILLUMINATED FACE, ARROWS INDICATE CHEVRONS.
<br />®
<br />SHADING:
<br />• CENTER SHADING INDICATES DEVICE MOUNTED ABOVE COUNTER TOP T-8" AFF, UON.
<br />• 1/2 SHADING INDICATES DEVICE TO BE SWITCHED.
<br />CEILING FAN.
<br />0
<br />SIMPLEX RECEPTACLE, CEILING, FLOOR AND WALL MOUNTED.
<br />0
<br />q
<br />DUPLEX RECEPTACLE, CEILING, FLOOR AND WALL MOUNTED. FLOOR IS SINGLE SERVICE FLOORBOX / POKE -THROUGH, ONE DUPLEX
<br />LINEAR PENDANT FIXTURE.
<br />RECEPTACLE.
<br />• ON -GRADE: HUBBELL B2536 SERIES BOX OR APPROVED EQUAL, UON.
<br />2' x 4' LIGHTING FIXTURE. DIAGONAL INDICATES FIXTURE UNSWITCHED (NITE LIGHT).
<br />• ABOVE GRADE: HUBBELL S1 PT4X4-J SERIES BOX OR APPROVED EQUAL, UON.
<br />0
<br />®
<br />9
<br />DOUBLE DUPLEX RECEPTACLE, CEILING, FLOOR AND WALL MOUNTED.
<br />❑
<br />2' x 2' LIGHTING FIXTURE.
<br />0
<br />0
<br />9
<br />220V RECEPTACLE, CEILING, FLOOR AND WALL MOUNTED.
<br />'DRYER' INDICATES NEMA 14-30R.
<br />-0
<br />ROUND BOWL / DRUM PENDANT FIXTURE.
<br />SPECIAL RECEPTACLE (AS INDICATED), CEILING, FLOOR AND WALL MOUNTED.
<br />t--t
<br />4' STRIP FIXTURE.
<br />®
<br />MULTI -OUTLET ASSEMBLY.
<br />0
<br />SURFACE FIXTURE.
<br />WALL MOUNTED LIGHT FIXTURE.
<br />MISCELLANEOUS DEVICES}
<br />0
<br />TRACK LIGHT FIXTURE.
<br />FSD
<br />120V FIRE / SMOKE DAMPER (FURNISHED & INSTALLED BY DIV 23, CIRCUITED BY DIV 26).
<br />�.z
<br />STEP LIGHT FIXTURE.
<br />SD
<br />120V SMOKE DAMPER (FURNISHED & INSTALLED BY DIV 23, CIRCUITED BY DIV 26).
<br />DISTRIBUTION DEVICES
<br />n
<br />120V MOTORIZED DAMPER (FURNISHED & INSTALLED BY DIV 23, CIRCUITED BY DIV 26).
<br />DASHED LINES ADJACET TO EQUIPMENT INDICATES CLEARANCES.
<br />T
<br />Oj
<br />HEAVY DUTY DISCONNECT SWITCH. PROVIDE NEMA 3R ENCLOSURES FOR EXTERIOR DISCONNECTS.
<br />30/3120
<br />NUMBERS INDICATE AMP FRAME / # POLES / AMP FUSE.
<br />ER
<br />EMERGENCY RELAY.
<br />'NF' INDICATES NON -FUSIBLE.
<br />120 / 208V PANELBOARD, SURFACE OR RECESS MOUNTED. SEE SCHEDULE FOR DETAILS.
<br />SECURITY INFRASTRUCTURE
<br />1777 71
<br />277 / 480V PANELBOARD, SURFACE OR RECESS MOUNTED. SEE SCHEDULE FOR DETAILS.
<br />ALL CONDUITS INDICATED BELOW SHALL BE ROUTED TO THE SECURITY PANEL IN THE COMM ROOM. COORDINATE w/ SECURITY INSTALLER
<br />FOR LOCATION OF SECURITY PANEL.
<br />TRANSFORMER.
<br />cc
<br />CCTV CAMERA.
<br />SWITCHBOARD, SEE SCHEDULE FOR DETAILS.
<br />ACP
<br />ACCESS CONTROL PANEL.
<br />cR
<br />CARD READER, OUTLET BOX AT T-10" AFF.
<br />sPD
<br />SURGE PROTECTIVE DEVICE.
<br />Dc
<br />DOOR CONTACT.
<br />Q
<br />UTILITY METER
<br />ML
<br />MAGNETIC LOCK.
<br />0
<br />ENCLOSED CIRCUIT BREAKER
<br />PB
<br />PUSH BUTTON, OUTLET BOX AT T-10" AFF.
<br />FGC1
<br />GATE CONTACT.
<br />REQUEST TO EXIT.
<br />Es
<br />ELECTRIC STRIKE.
<br />Ms
<br />MOTION SENSOR.
<br />FGBI
<br />GLASS BREAK SENSOR.
<br />McVEIGH&MANGUM
<br />ENGINEERING INC
<br />Atlanta • Charlotte • Jacksonville Raleigh
<br />www.MeVeighMangum.com
<br />1955 Lake Park Drive SE, Suite 325
<br />Smyrna, Georgia 30080
<br />Ph: (678) 213-1616
<br />email: mail@McVeighMangum.com
<br />PEF005182
<br />Eng. ofRecord:LADD D. MARKS, P.E. License No.:58264
<br />Mid"%
<br />�R
<br />A
<br />N
<br />D
<br />A
<br />L
<br />L�
<br />I
<br />I
<br />arcitectl
<br />Roswell Mill
<br />85-A Mill Street, Suite 200
<br />Roswell, Georgia 30075
<br />t 770.650.7558 f 770.650.7559
<br />e-mail architects cx randalipaulson.com
<br />These plans and specifications are the property of Randall -Paulson Architects,
<br />Incorporated. These documents may not he copied, reproduced, used or
<br />implemented in any way, in part orio whale, without the written consent of
<br />Randall -Paulson Architects, Incorporated. All common law rights of copyright are
<br />horehy specifically reserved.
<br />TENANT
<br />BUILD -OUT
<br />at
<br />ZEPHYRHILLS
<br />for
<br />U.S. HIGHWAY 301 & PRETTY
<br />POND ROAD,
<br />ZEPHYRHILLS, FLORIDA 33541
<br />Print Record
<br />Revisions
<br />Date Project No.
<br />14 JUNE 2021 2021217.00
<br />Sheet Title
<br />LEGEND & GENERAL NOTES
<br />Sheet No.
<br />EmO01
<br />Released for Construction
<br />❑ Not Released for Construction