GENERAL ELECTRICAL NOTES <br />1. ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH THE APPLICABLE EDITION OF THE NATIONAL <br />ELECTRICAL CODE AND ALL LOCAL AND STATE CODES. <br />2. ALL MATERIAL SHALL BE NEW AND SHALL CONFORM TO THE STANDARDS OF THE UNDERWRITER'S <br />LABORATORIES, INC., AND THE NATIONAL MANUFACTURERS ASSOCIATION. <br />3. ALL ELECTRICAL PERMITS AND INSPECTION FEES SHALL BE OBTAINED AND PAID FOR BY THE ELECTRICAL <br />CONTRACTOR. <br />4. DRAWINGS ARE DIAGRAMMATIC ONLY AND INDICATE ONLY THE GENERAL ARRANGEMENT. SEE <br />ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONS. <br />5. ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIALS FOR ONE YEAR EFFECTIVE <br />THE DAY HE PROJECT IS ACCEPTED BY THE OWNER. <br />6. ELECTRICAL CONTRACTOR SHALL MAKE ALL ELECTRICAL POWER CONNECTIONS TO HVAC, PLUMBING, <br />AND OTHER EQUIPMENT AS REQUIRED. <br />7. A COMPLETE GROUNDING SYSTEM SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH ARTICLE <br />250 OF THE NEC, AND AS SHOWN ON THE DRAWINGS. <br />8. ALL CUTTING AND PATCHING OF WALLS AND FLOORS FOR ELECTRICAL EQUIPMENT SHALL BE THE <br />RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. <br />9. ALL WIRING SHALL BE INSTALLED IN GALVANIZED RIGID CONDUIT, INTERMEDIATE METAL CONDUIT, OR <br />EMT. EMT SHALL NOT BE USED IN OR UNDER CONCRETE SLABS, OR IN MASONRY WALLS. USE SCHEDULE <br />40 PVC OUTDOORS WHERE NOT SUBJECT TO PHYSICAL DAMAGE OR BELOW FLOOR SLAB. <br />CONCEALED BRANCH CIRCUITS RATED 30 AMPS OR LESS MAY UTILIZE TYPE MC FLEXIBLE METAL CABLE <br />WHERE CODE ALLOWS. SUPPORT WITHIN 12" OF ALL CONNECTIONS AND NOT MORE THAN 4'-6" ON <br />CENTER. <br />ALL RACEWAYS (EXCEPT THOSE BELOW SLAB OR GRADE) SHALL BE INSTALLED PARALLEL OR <br />PERPENDICULAR TO BUILDING LINES. <br />10. BRANCH CIRCUIT CONDUCTORS SHALL BE COPPER RATED AT NOT LESS THAN 600 VOLTS. MINIMUM SIZE <br />SHALL BE #12 AWG UNLESS OTHERWISE NOTED ON THE DRAWINGS. ALL WIRE #8 AWG AND LARGER <br />SHALL BE STRANDED. ALL CONDUCTORS #10 AND SMALLER SHALL BE SOLID, UNLESS OTHERWISE <br />NOTED. <br />FEEDERS RATED GREATER THAN 150 AMPERES MAY UTILIZE 750C COMPACT ALUMINUM CONDUCTORS OF <br />EQUIVALENT AMPACITY, TYPE XHHW OR XHHW-2 INSULATION, EQUIVALENT TO ALCAN SERIES 8000 <br />CONDUCTORS. CONTRACTOR TO VERIFY CONDUIT SIZES REQUIRED FOR ALUMINUM FEEDERS. <br />11. BRANCH CIRCUIT CONDUCTORS SHALL BE TYPE THHN OR THWN AS REQ'D. <br />12. PROVIDE A PULLWIRE IN ALL EMPTY CONDUITS. <br />13. PROVIDE A TYPED DIRECTORY IN ALL PANELBOARDS CLEARLY DESCRIBING THE LOCATION OF AND TYPE <br />OF LOAD BEING SERVED FOR ALL CIRCUITS. <br />14. PROVIDE ENGRAVED PHENOLIC NAMEPLATES FOR ALL PANELBOARDS AND DISCONNECT SWITCHES, <br />BLACK LETTERS ON WHITE BACKGROUND. <br />15. FUSES 0 - 600 AMPS SHALL BE UL CLASS "RK-1" LOW PEAK DUAL ELEMENT TIME DELAY WITH 2O0,000 <br />AMPERE INTERRUPTING RATING AS MANUFACTURED BY BUSS, UNLESS NOTED OTHERWISE. <br />16. VERIFY ALL REQUIREMENTS AND COORDINATE EXACT LOCATION OF INCOMING ELECTRICAL SERVICE <br />WITH LOCAL POWER COMPANY PRIOR TO PROJECT START-UP. NOTIFY ENGINEER OF ANY CHANGES AS <br />MAY BE REQUIRED. <br />AVAILABLE FAULT CURRENT AT SERVICE TRANSFORMER TO BE FIELD VERIFIED WITH SERVING UTILITY. <br />ACTUAL FAULT CURRENT VALUES TO BE FIELD MARKED ON ALL GEAR IN ACCORDANCE WITH NEC 110.24. <br />17. PROVIDE SCHEDULE 40 PVC CONDUIT UNDERGROUND FROM TELEPHONE EQUIPMENT ROOM TO <br />CONNECTION POINT AS DIRECTED BY LOCAL TELEPHONE COMPANY. <br />18. ALL TERMINALS, SPLICING CONNECTORS, LUGS, ETC. SHALL BE IDENTIFIED FOR USE WITH THE MATERIAL <br />(CU/AL) OF THE CONDUCTOR AND SHALL BE PROPERLY INSTALLED. <br />19. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL ELECTRICAL EQUIPMENT <br />FROM FOREIGN MATERIAL DURING CONSTRUCTION (PAINT, SPACKLE, ETC.). <br />20. PENETRATIONS OF REQUIRED SMOKE PARTITIONS SHALL BE SEALED USING METHODS APPROVED UNDER <br />THE STATE BUILDING CODE. COORDINATION WITH THE GENERAL CONTRACTOR SHALL BE MAINTAINED <br />TO INSURE THAT THIS SMOKE STOPPING IS ACCOMPLISHED. <br />21. WHERE PENETRATIONS ARE MADE THROUGH A REQUIRED FIRE -RESISTIVE WALL, FLOOR, OR PARTITION <br />FOR THE PURPOSE OF RUNNING RACEWAY CARRYING ELECTRICAL, TELEPHONE, TELEVISION, OR LOCAL <br />COMMUNICATION AND/OR SIGNALING CIRCUITS, THE OPENING AROUND THE RACEWAY SHALL BE FIRE <br />STOPPED PER THE STATE BUILDING CODE. COORDINATION WITH THE GENERAL CONTRACTOR SHALL BE <br />MAINTAINED TO INSURE THAT THIS FIRE STOPPING IS ACCOMPLISHED. USE APPROVED ASSEMBLIES <br />SUCH AS THE FOLLOWING: <br />UP TO 1" PENETRATIONS OF 1, 2,3 & 4 HOUR GYPSUM WALLS - U.L.#WL1001 <br />UP TO 4" PENETRATIONS OF 1 & 2 HOUR GYPSUM WALLS - U.L.#WL1001 <br />UP TO 4" PENETRATIONS OF 1 & 2 HOUR CONC. OR BLOCK WALLS & FLOORS - U.L.#CAJ1009 <br />UP TO 4" PENETRATIONS OF 3 & 4 HOUR CONC. OR BLOCK WALLS & FLOORS - U.L.#CBJ1020. <br />22. IN REQUIRED FIRE RATED WALLS AND PARTITIONS, OPENINGS FOR INSTALLATION OF BOXES THAT ARE <br />GREATER THAN 16 SQUARE INCHES SHALL BE PROTECTED AS REQ'D BY U.L. COORDINATE CLOSELY WITH <br />THE GENERAL CONTRACTOR TO INSURE THAT THE INTEGRITY OF THE U.L. RATING IS MAINTAINED. <br />23. WHERE A HOME RUN IS SHOWN, THE CIRCUIT SHALL BE INSTALLED IN A DEDICATED CONDUIT, DO NOT <br />COMBINE WITH OTHER CIRCUITS. WHERE A CIRCUIT HOMERUN IS NOT SHOWN, THE CONTRACTOR SHALL <br />COMBINE CIRCUITS AS FOLLOWS: <br />• A MAXIMUM OF THREE 20A BRANCH CIRCUITS MAY BE COMBINED IN A COMMON HOMERUN SHARING A <br />COMMON NEUTRAL OR WITH SEPARATE NEUTRALS FOR A MAXIMUM OF TOTAL OF SIX CURRENT <br />CARRYING CONDUCTORS. <br />• 20A BRANCH CIRCUITS SERVING NON -LINEAR LOADS (FLUOR. LIGHTING, EMPLOYEE WORKSTATIONS, <br />DATA SYSTEMS, ETC.) USING SHARED NEUTRALS SHALL UTILIZE #10 CU NEUTRAL, MINIMUM. <br />• ALL BRANCH CIRCUITS LARGER THAN 20A SHALL BE SEPARATELY HOMERUN TO THE PANEL. <br />24. ALL RACEWAYS SHALL BE CONCEALED UNLESS OTHERWISE NOTED. THE ELECTRICAL CONTRACTOR <br />SHALL BE RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH CONCEALING RACEWAYS AFTER INITIAL <br />CONSTRUCTION. <br />25, CLOSE OUT DOCUMENTS: <br />• AS-BUILTS: WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE <br />ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER, INCLUDING: <br />1) A SINGLE -LINE DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND <br />2) FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL DISTRIBUTION. <br />• OPERATION AND MAINTENANCE MANUALS: AN OPERATING MANUAL AND MAINTENANCE MANUAL <br />SHALL BE PROVIDED TO THE BUILDING OWNER. THE MANUALS SHALL INCLUDE, AT A MINIMUM, THE <br />FOLLOWING: <br />1) SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF <br />EQUIPMENT REQUIRING MAINTENANCE; <br />2) OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING <br />MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED; <br />3) NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY. <br />26. COMMISSIONING: <br />WHERE OCCUPANT SENSORS, TIME SWITCHES, PROGRAMMABLE SCHEDULE CONTROLS, <br />PHOTOSENSORS, OR DAYLIGHTING CONTROLS ARE INSTALLED, COMMISSIONING SHALL BE PROVIDED. <br />FOR ANY OCCUPANCY SENSORS, CONFIRM THAT THE PLACEMENT, SENSITIVITY, AND TIME-OUT <br />ADJUSTMENTS YIELD ACCEPTABLE PERFORMANCE; FOR ANY TIME SWITCHES AND PROGRAMMABLE <br />SCHEDULE CONTROLS, CONFIRM THAT PROGRAMMING TURNS LIGHTS OFF; FOR ANY PHOTOSENSOR <br />CONTROLS, CONFIRM THAT THE PLACEMENT AND SENSITIVITY ADJUSTMENTS REDUCE ELECTRIC LIGHTS <br />BASED ON THE AMOUNT OF USABLE DAYLIGHT IN SPACE AS SPECIFIED. COMMISSIONING SHALL BE <br />PERFORMED BY THE CONTRACTOR UNDER THE DIRECTION OF THE LIGHTING CONTROLS CERTIFIED <br />MANUFACTURER'S REPRESENTATIVE. CERTIFICATE DOCUMENTATION OF THE REPRESENTATIVE SHALL <br />BE INCLUDED IN SHOP DRAWING / PRODUCT DATA SUBMITTAL. <br />ELECTRICAL SYMBOL LEGEND <br />WIRING AND WIRING DEVICES <br />COMMUNICATIONS <br />WIRING SYSTEM CONCEALED IN WALL OR CEILING. DASHED LINES INDICATE WIRING RUN BELOW SLAB / GRADE. <br />OUTLETS SHALL BE MOUNTED AT SAME HEIGHT AS ADJACENT RECEPTACLE, w/ CONDUIT STUBBED OUT ABOVE ACCESSIBLE CEILING. <br />_ <br />'W' INDICATES 48" AFF MOUNTING. <br />/ <br />\ <br />LOW VOLTAGE CONTROL WIRING SYSTEM CONCEALED IN WALL OR CEILING. <br />• 'INT' INDICATES INTERCOM OUTLET. <br />WIRING SYSTEM TO BE RUN EXPOSED. DASHED LINES INDICATE WIRING RUN BELOW SLAB / GRADE. <br />VVTELEPHONE <br />OUTLET w/ 3/4"C, CEILING, FLOOR AND WALL MOUNTED. <br />® ® 0 <br />DATA OUTLET w/ 1"C, CEILING, FLOOR AND WALL MOUNTED. <br />BRANCH CIRCUIT HOMERUN TO PANEL. NUMBER OF ARROWHEADS INDICATE NUMBER OF CIRCUITS. THREE CIRCUITS OF ALTERNATING <br />FLOOR AND WALL MOUNTED. <br />PHASES MAY BE COMBINED IN ONE CONDUIT, HOWEVER THEY SHALL EITHER BE EQUIPPED w/ DEDICATED NEUTRALS, COMMON TRIP <br />® ® <br />COMBINATION TEL / DATA OUTLET w/ 1"C, CEILING, <br />CIRCUIT BREAKERS, OR HANDLE -TIES ON THEIR BREAKERS. <br />4 <br />WALL MOUNTED TV OUTLET w/ 1"C, UON, SEE ARCH PLANS FOR MOUNTING HEIGHT. <br />MOTOR PROVIDED AND INSTALLED BY MECH. CONTRACTOR, WIRED BY ELEC. CONTRACTOR, NUMERALS INDICATE HORSEPOWER. <br />O® <br />RECEPTACLE (SIMPLEX, DUPLEX, DOUBLE DUPLEX, 220V OR SPECIAL), COMBINATION TEUDATA OUTLET w/ 1"C, AND INTERCOM OUTLET IN <br />Q <br />JUNCTION BOX, CEILING AND WALL MOUNTED. <br />FLOOR / WALL BOX, WIREMOLD FB-SERIES OR APPROVED EQUAL, UON. <br />• 'P' INDICATES SYSTEMS FURNITURE POWER WHIP, SEE DETAILS. <br />FGAPI <br />GENERATOR ANNUNCIATOR PANEL. <br />• 'C' INDICATES SYSTEMS FURNITURE COMMUNICATIONS WHIP, SEE DETAILS. <br />sP sP <br />SPEAKER CEILING AND WALL MOUNTED. <br />KD <br />SINGLE SERVICE FLOORBOX / POKE -THROUGH, JUNCTION BOX. <br />Ds <br />DISCONNECT SWITCH FOR NOTIFICATION. <br />• ON -GRADE: HUBBELL B2536 SERIES BOX OR APPROVED EQUAL, UON. <br />• ABOVE GRADE: HUBBELL S1 PT4X4-J BOX SERIES OR APPROVED EQUAL, UON. <br />DB <br />DOOR BELL PUSH BUTTON. <br />• 'P' INDICATES SYSTEMS FURNITURE POWER WHIP, SEE DETAILS. <br />LOW VOLTAGE TRANSFORMER. <br />• 'C' INDICATES SYSTEMS FURNITURE COMMUNICATIONS WHIP, SEE DETAILS. <br />D�A <br />VISUAL / AUDIBLE DOOR NOTIFICATION. <br />FIRE ALARM DEVICES <br />SITE <br />rc <br />INTERCOMM. <br />• 'C' INDICATES CEILING MOUNTED. <br />BOLLARD LIGHT FIXTURE. <br />vc <br />VOLUME CONTROL. <br />® <br />CARBON MONOXIDE DETECTOR WALL OR CEILING MOUNTED. <br />u <br />GROUND BAR. <br />❑H <br />HEAT DETECTOR WALL OR CEILING MOUNTED. <br />GROUND MOUNTED FLOODLIGHT FIXTURE. <br />wAP <br />WAP. <br />❑s <br />SMOKE DETECTOR WALL OR CEILING MOUNTED. <br />DATA PATCH PANEL. <br />GROUND MOUNTED LINEAR SIGNLIGHT FIXTURE. <br />❑° <br />SMOKE DETECTOR DUCT MOUNTED. <br />FACP <br />FIRE ALARM CONTROL PANEL. <br />POST TOP LIGHT FIXTURE. <br />SWITCHING <br />FAAP <br />FIRE ALARM ANNUNCIATOR PANEL. <br />�❑ <br />POLE MOUNTED SITE LIGHT FIXTURE (1 HEAD). <br />20A, 120/277 VOLT, +48" AFF TO TOP, UON. <br />'Z <br />NAc <br />FIRE ALARM NOTIFICATION APPLIANCE CABINET. <br />INDICATES 2-POLE. <br />'3' INDICATES 3-WAY. <br />ERRCS <br />EMERGENCY RESPONDER RADIO COVERAGE SYSTEM. <br />�-♦� <br />POLE MOUNTED SITE LIGHT FIXTURE (2 HEAD). <br />W INDICATES 4-WAY. <br />DOOR HOLDER INTERFACE DEVICE. <br />'D' INDICATES 0-10V DIMMER SWITCH. COORDINATE EXACT TYPE AND RATING w/ LIGHTING CONTROLLED. <br />NURSE CALL <br />rM ❑ <br />INPUT MODULE INTERFACE DEVICE. <br />'T' INDICATES 0-60 MINUTE TIMER SWITCH. <br />'KG INDICATES KEY OPERATED SWITCH. <br />❑R <br />RELAY INTERFACE DEVICE. <br />NCAP <br />NURSE CALL ANNUNCIATOR PANEL (MASTER STATION). <br />'LV' INDICATES LOW VOLTAGE SWITCH. <br />Fs <br />FIRE ALARM FLOW SWITCH. <br />Ncec <br />NURSE CALL EQUIPMENT CABINET. <br />'LV2' INDICATES 2-RELAY LOW VOLTAGE SWITCH. <br />'[#]' INDICATES LIGHTING CONTROL ZONE. SEE LIGHTING CONTROL SCHEDULE FOR DETAILS. <br />Ps <br />FIRE ALARM PRESSURE SWITCH. <br />sD <br />STAFF DUTY STATION. <br />'OV' INDICATES LIGHTING CONTACTOR OVERRIDE SWITCH. <br />rs <br />FIRE ALARM TAMPER SWITCH. <br />lsA <br />STAFF ASSIST STATION. <br />0 <br />FIRE ALARM PULL STATION. <br />Ec <br />EMERGENCY CALL STATION (CODE BLUE). <br />$ <br />SINGLE POLE SWITCH. <br />LF <br />LOW FREQUENCY ALARM DEVICE. <br />DL <br />NURSE DOME LIGHT. <br />$ VS <br />LINE VOLTAGE, VACANCY SENSOR SWITCH, MANUAL -ON / AUTO -OFF, DUAL -TECHNOLOGY, PROVIDE COMPLETE ROOM COVERAGE. <br />8 <br />VISUAL ONLY ALARM DEVICE. <br />zL <br />NURSE ZONE LIGHT. <br />$ OC <br />LINE VOLTAGE, OCCUPANCY SENSOR SWITCH, AUTO -ON / AUTO -OFF, DUAL -TECHNOLOGY, PROVIDE COMPLETE ROOM COVERAGE. <br />Pc <br />PATIENT CALL STATION. <br />ff] <br />VISUAL / AUDIBLE ALARM DEVICE. <br />ss <br />❑ <br />PATIENT CALL BATH STATION. <br />s OC/D <br />LINE VOLTAGE, OCCUPANCY SENSOR SWITCH w/ DIMMING, AUTO -ON / AUTO -OFF, DUAL -TECHNOLOGY, PROVIDE COMPLETE ROOM <br />'T' <br />COVERAGE. <br />LBJ <br />BELL ALARM DEVICE. <br />INDICATES TOILET STATION, INSTALL WITHIN 12" OF <br />sP <br />SPEAKER ALARM DEVICE. <br />TOILET BOWL. <br />'S' INDICATES SHOWER STATION. <br />VS/D <br />LINE VOLTAGE, VACANCY SENSOR SWITCH w/ DIMMING, AUTO -ON / AUTO -OFF, DUAL -TECHNOLOGY, PROVIDE COMPLETE ROOM <br />COVERAGE. <br />PP PP2 <br />LOW -VOLTAGE CONCEALED POWER PACK FOR OCCUPANCY SENSOR. <br />ss <br />SPEAKER / STROBE ALARM DEVICE. <br />LIGHTNING PROTECTION <br />co <br />SINGLE STATION CARBON MONOXIDE ALARM. <br />PPA PPA2 <br />LOW -VOLTAGE CONCEALED POWER PACK FOR OCCUPANCY SENSOR, AUTO -ON / AUTO -OFF. <br />Q <br />SINGLE STATION HEAT ALARM. <br />LIGHTNING PROTECTION AIR TERMINAL. <br />PPM PPM <br />LOW -VOLTAGE CONCEALED POWER PACK FOR OCCUPANCY SENSOR, MANUAL -ON / AUTO -OFF. <br />s <br />O <br />SINGLE STATION SMOKE ALARM . <br />�` <br />LIGHTNING PROTECTION DOWN CONDUCTOR <br />PPD PPD2 <br />LOW -VOLTAGE CONCEALED POWER PACK FOR OCCUPANCY SENSOR, MANUAL -ON / AUTO -OFF, 0-10V DIMMING. <br />O <br />SINGLE STATION DUCT SMOKE ALARM. <br />AND GROUND ROD. <br />vs vs <br />LOW -VOLTAGE DUAL -TECHNOLOGY VACANCY SENSOR, CEILING AND WALL MOUNTED, MANUAL -ON / AUTO -OFF w/ EXTENDED RANGE (AT <br />. <br />LIGHTNING PROTECTION CONDUCTOR. <br />LEAST 56'-0"MINOR MOTION RANGE DIAMETER AT 9'-0" AFF MOUNTING HEIGHT ) <br />Q <br />SINGLE STATION DUCT SMOKE REMOTE ALARM. <br />oc oc <br />LOW -VOLTAGE DUAL -TECHNOLOGY OCCUPANCY SENSOR, CEILING AND WALL MOUNTED, AUTO -ON / AUTO -OFF w/ EXTENDED RANGE (AT <br />LEAST 56-0" MINOR MOTION RANGE DIAMETER AT 9'-0" AFF MOUNTING HEIGHT). <br />RECEPTACLES <br />ALL RECEPTACLES SHALL BE A MINIMUM RATING OF 120 VOLT, 20 AMP, UON, VERTICAL MOUNTED BOX HEIGHTS SHALL BE TO CENTER, <br />Pc <br />NORTH FACING ROOF MOUNTED PHOTOCELL. <br />HORIZONTAL MOUNTED BOX HEIGHTS SHALL BE TO TOP, UON. <br />EEI <br />TIMECLOCK, REFER TO LIGHTING CONTROL DIAGRAM. <br />• 'AFI' INDICATES ARC FAULT CIRCUIT INTERRUPTER. <br />iv <br />INVERTER, 50W, 277V, 90 MINUTE BATTERY. <br />• 'GFI' INDICATES GROUND FAULT CIRCUIT INTERRUPTER. <br />LIGHTING FIXTURES <br />• 'WP' INDICATES WEATHERPROOF IN USE, WEATHER -RESISTANT RECEPTACLE w/ IN -USE EXTRA DUTY COVER. RECEPTACLES LOCATED IN <br />WET OR DAMP LOCATIONS SHALL BE WP, WHETHER INDICATED OR NOT. <br />• 'EWC' INDICATES ELECTRIC WATER COOLER. <br />SEE FIXTURE SCHEDULE FOR DETAILS. <br />• 'EX' INDICATES EXISTING TO BE REUSED. <br />'N/L' INDICATES FIXTURE UNSWITCHED (NITE LIGHT). <br />• 'HD' INDICATES HAND DRYER CONNECTION. <br />LOWER CASE LETTERING DENOTES SWITCH /RELAY CONTROLLING THE FIXTURE. <br />• 'TR' INDICATES TAMPER RESISTANT (INTEGRAL TO RECEPTACLE). ALL DWELLING UNIT DUPLEX RECEPTACLES SHALL BE LISTED TAMPER <br />SHADING: <br />RESISTANT TYPE. ALL NON -LOCKING, 120V, 15A AND 20A RECEPTACLES SHALL BE TAMPER -RESISTANT, EXCEPT IN MECHANICAL ROOMS, <br />1/2 SHADING INDICATES FIXTURE TO BE PROVIDED w/ 90-MINUTE, MINIMUM BATTERY BACKUP. <br />ELECTRICAL ROOMS, AND JANITORS CLOSETS, WHETHER INDICATED OR NOT. <br />O> <br />DOWNLIGHT RECESSED FIXTURE, ARROW INDICATES WALL WASH TYPE AND DIRECTION TO AIM FIXTURE. <br />• 'CH' INDICATES HALF CONTROLLED. <br />DOWNLIGHT SURFACE MOUNTED FIXTURE. <br />• 'CF' INDICATES FULL CONTROLLED (BOTH PLUGS OF DUPLEX). <br />• 'SB' INDICATES RECEPTACLE FOR SMARTBOARD, SEE DETAIL. <br />EMERGENCY EGRESS LIGHT FIXTURE. <br />• 'DING INDICATES POWER/USB CHARGING. <br />> i> <br />EXIT SIGN FIXTURE, CEILING AND WALL MOUNTED. SHADING INDICATES ILLUMINATED FACE, ARROWS INDICATE CHEVRONS. <br />® <br />SHADING: <br />• CENTER SHADING INDICATES DEVICE MOUNTED ABOVE COUNTER TOP T-8" AFF, UON. <br />• 1/2 SHADING INDICATES DEVICE TO BE SWITCHED. <br />CEILING FAN. <br />0 <br />SIMPLEX RECEPTACLE, CEILING, FLOOR AND WALL MOUNTED. <br />0 <br />q <br />DUPLEX RECEPTACLE, CEILING, FLOOR AND WALL MOUNTED. FLOOR IS SINGLE SERVICE FLOORBOX / POKE -THROUGH, ONE DUPLEX <br />LINEAR PENDANT FIXTURE. <br />RECEPTACLE. <br />• ON -GRADE: HUBBELL B2536 SERIES BOX OR APPROVED EQUAL, UON. <br />2' x 4' LIGHTING FIXTURE. DIAGONAL INDICATES FIXTURE UNSWITCHED (NITE LIGHT). <br />• ABOVE GRADE: HUBBELL S1 PT4X4-J SERIES BOX OR APPROVED EQUAL, UON. <br />0 <br />® <br />9 <br />DOUBLE DUPLEX RECEPTACLE, CEILING, FLOOR AND WALL MOUNTED. <br />❑ <br />2' x 2' LIGHTING FIXTURE. <br />0 <br />0 <br />9 <br />220V RECEPTACLE, CEILING, FLOOR AND WALL MOUNTED. <br />'DRYER' INDICATES NEMA 14-30R. <br />-0 <br />ROUND BOWL / DRUM PENDANT FIXTURE. <br />SPECIAL RECEPTACLE (AS INDICATED), CEILING, FLOOR AND WALL MOUNTED. <br />t--t <br />4' STRIP FIXTURE. <br />® <br />MULTI -OUTLET ASSEMBLY. <br />0 <br />SURFACE FIXTURE. <br />WALL MOUNTED LIGHT FIXTURE. <br />MISCELLANEOUS DEVICES} <br />0 <br />TRACK LIGHT FIXTURE. <br />FSD <br />120V FIRE / SMOKE DAMPER (FURNISHED & INSTALLED BY DIV 23, CIRCUITED BY DIV 26). <br />�.z <br />STEP LIGHT FIXTURE. <br />SD <br />120V SMOKE DAMPER (FURNISHED & INSTALLED BY DIV 23, CIRCUITED BY DIV 26). <br />DISTRIBUTION DEVICES <br />n <br />120V MOTORIZED DAMPER (FURNISHED & INSTALLED BY DIV 23, CIRCUITED BY DIV 26). <br />DASHED LINES ADJACET TO EQUIPMENT INDICATES CLEARANCES. <br />T <br />Oj <br />HEAVY DUTY DISCONNECT SWITCH. PROVIDE NEMA 3R ENCLOSURES FOR EXTERIOR DISCONNECTS. <br />30/3120 <br />NUMBERS INDICATE AMP FRAME / # POLES / AMP FUSE. <br />ER <br />EMERGENCY RELAY. <br />'NF' INDICATES NON -FUSIBLE. <br />120 / 208V PANELBOARD, SURFACE OR RECESS MOUNTED. SEE SCHEDULE FOR DETAILS. <br />SECURITY INFRASTRUCTURE <br />1777 71 <br />277 / 480V PANELBOARD, SURFACE OR RECESS MOUNTED. SEE SCHEDULE FOR DETAILS. <br />ALL CONDUITS INDICATED BELOW SHALL BE ROUTED TO THE SECURITY PANEL IN THE COMM ROOM. COORDINATE w/ SECURITY INSTALLER <br />FOR LOCATION OF SECURITY PANEL. <br />TRANSFORMER. <br />cc <br />CCTV CAMERA. <br />SWITCHBOARD, SEE SCHEDULE FOR DETAILS. <br />ACP <br />ACCESS CONTROL PANEL. <br />cR <br />CARD READER, OUTLET BOX AT T-10" AFF. <br />sPD <br />SURGE PROTECTIVE DEVICE. <br />Dc <br />DOOR CONTACT. <br />Q <br />UTILITY METER <br />ML <br />MAGNETIC LOCK. <br />0 <br />ENCLOSED CIRCUIT BREAKER <br />PB <br />PUSH BUTTON, OUTLET BOX AT T-10" AFF. <br />FGC1 <br />GATE CONTACT. <br />REQUEST TO EXIT. <br />Es <br />ELECTRIC STRIKE. <br />Ms <br />MOTION SENSOR. <br />FGBI <br />GLASS BREAK SENSOR. <br />McVEIGH&MANGUM <br />ENGINEERING INC <br />Atlanta • Charlotte • Jacksonville Raleigh <br />www.MeVeighMangum.com <br />1955 Lake Park Drive SE, Suite 325 <br />Smyrna, Georgia 30080 <br />Ph: (678) 213-1616 <br />email: mail@McVeighMangum.com <br />PEF005182 <br />Eng. ofRecord:LADD D. MARKS, P.E. License No.:58264 <br />Mid"% <br />�R <br />A <br />N <br />D <br />A <br />L <br />L� <br />I <br />I <br />arcitectl <br />Roswell Mill <br />85-A Mill Street, Suite 200 <br />Roswell, Georgia 30075 <br />t 770.650.7558 f 770.650.7559 <br />e-mail architects cx randalipaulson.com <br />These plans and specifications are the property of Randall -Paulson Architects, <br />Incorporated. These documents may not he copied, reproduced, used or <br />implemented in any way, in part orio whale, without the written consent of <br />Randall -Paulson Architects, Incorporated. All common law rights of copyright are <br />horehy specifically reserved. <br />TENANT <br />BUILD -OUT <br />at <br />ZEPHYRHILLS <br />for <br />U.S. HIGHWAY 301 & PRETTY <br />POND ROAD, <br />ZEPHYRHILLS, FLORIDA 33541 <br />Print Record <br />Revisions <br />Date Project No. <br />14 JUNE 2021 2021217.00 <br />Sheet Title <br />LEGEND & GENERAL NOTES <br />Sheet No. <br />EmO01 <br />Released for Construction <br />❑ Not Released for Construction <br />L� :, h i _. u;•.mw., :.: r AM <br />ins �,,. «. : _s.z �� i e „ ., m i.,;:..e..a u'; arc m1. G3N d6 j w",; �t <br />