PANEL "A"
<br />SQUARE D : QO
<br />120/240V. 1 PH, 3W
<br />VOLTAGE/PHASE
<br />200A MCB
<br />200A BUS
<br />NEMA-1
<br />SURFACE
<br />22,000 AIC
<br />FEED-THRU LUGS
<br />OPTIONS:
<br />CKT
<br />AMPS
<br />POLE
<br />DESCRIPTION
<br />NOTES
<br />LOAD
<br />CKT
<br />AMPS
<br />POLE
<br />DESCRIPTION
<br />NOTES
<br />LOAD
<br />VA
<br />1
<br />20
<br />1
<br />RECEPT - TEUDATA
<br />1
<br />360
<br />2
<br />20
<br />1
<br />FUTURE LANSCAPE LTG
<br />900
<br />3
<br />20
<br />1
<br />RECEPT - SEC/ACCESS
<br />1
<br />360
<br />4
<br />20
<br />1
<br />FUTURE LANSCAPE LTG
<br />900
<br />5
<br />20
<br />1
<br />RECEPT- GENERAL
<br />1
<br />540
<br />6
<br />20
<br />1
<br />LOW VOLTAGE LIGHTING
<br />5
<br />539
<br />7
<br />20
<br />1
<br />RECEPT- COUNTER
<br />1
<br />360
<br />8
<br />20
<br />1
<br />LOW VOLTAGE LIGHTING
<br />5
<br />539
<br />9
<br />20
<br />1
<br />RECEPT- COUNTER
<br />1
<br />360
<br />10
<br />20
<br />1
<br />LOW VOLTAGE LIGHTING
<br />5
<br />539
<br />11
<br />20
<br />1
<br />RECEPT- GENERAL
<br />1
<br />900
<br />12
<br />20
<br />1
<br />LIGHTING CONTROLS
<br />5
<br />500
<br />13
<br />20
<br />1
<br />RECEPT - EWC
<br />1
<br />400
<br />14
<br />20
<br />1
<br />EMERGENCY/EXIT
<br />4
<br />200
<br />15
<br />20
<br />1
<br />RECEPT - WOMENS GFI
<br />1
<br />180
<br />16
<br />20
<br />1
<br />FANS - RGT WING
<br />1
<br />300
<br />17
<br />20
<br />1
<br />RECEPT - MENS GFI
<br />1
<br />180
<br />18
<br />20
<br />1
<br />FANS - RGT WING
<br />1
<br />300
<br />19
<br />20
<br />1
<br />RECEPT- VENDING
<br />1
<br />800
<br />20
<br />20
<br />1
<br />FANS - SITTING
<br />1
<br />400
<br />21
<br />20
<br />1
<br />RECEPT- VENDING
<br />1
<br />800
<br />22
<br />20
<br />1
<br />FANS - LEFT WING
<br />1
<br />300
<br />23
<br />20
<br />1
<br />RECEPT- GENERAL
<br />1
<br />720
<br />24
<br />20
<br />1
<br />FANS - LEFT WING
<br />1
<br />300
<br />25
<br />20
<br />1
<br />RECEPT - GENERAL
<br />1
<br />720
<br />26
<br />20
<br />1
<br />EF-1
<br />1
<br />100
<br />27
<br />1 20
<br />1
<br />RECEPT - COUNTER
<br />1
<br />360
<br />28
<br />30
<br />2
<br />WATER HEATER
<br />2250
<br />29
<br />20
<br />1
<br />RECEPT - COUNTER
<br />1
<br />360
<br />30
<br />2250
<br />31
<br />20
<br />1
<br />RECEPT - SEASONAL
<br />1
<br />1000
<br />32
<br />20
<br />2
<br />INSTA HOT
<br />1500
<br />33
<br />20
<br />1
<br />RECEPT-SEASONAL
<br />1
<br />1000
<br />34
<br />1500
<br />35
<br />1 20
<br />1
<br />RECEPT- SEASONAL
<br />1
<br />1000
<br />36
<br />20
<br />2
<br />PANEL 'B'(FEED-THRU)
<br />3
<br />9456
<br />37
<br />20
<br />1
<br />EF-4
<br />1
<br />100
<br />38
<br />9456
<br />39
<br />20
<br />1
<br />EF-3
<br />1
<br />100
<br />40
<br />30
<br />2
<br />SPD
<br />2
<br />1
<br />0
<br />41
<br />20
<br />1
<br />EF-2
<br />1
<br />100
<br />42
<br />1 0
<br />NOTES:
<br />LOAD CONNECTED DEMAND DEMAND
<br />DESCRIPTION LOAD (VA) FACTOR LOAD (VA)
<br />1.
<br />2 #12 CU #12 CU GIRD - 1/2"C
<br />LIGHTING 11717 1.25 14646.25
<br />HVAC - COOL 0 0.00 0
<br />HVAC - HEAT 0 0.00 0
<br />RECEPTACLE 8400 1.00 8400
<br />MISC 22012 1.00 22012
<br />2.
<br />INSTALL PER MANUFACTURER REQUIREMENTS
<br />3.
<br />SEE RISER DIAGRAM FOR WIRE SIZES
<br />4.
<br />BREAKER SHALL BE LOCKED IN THE "ON" POSITION
<br />5.
<br />REFER TO LUMASTREAM DOCUMENTS
<br />6.
<br />TOTAL 42129 45058.25
<br />7.
<br />TOTAL DEMAND CURRENT 120/240V 1 PH 187.7 AMPS
<br />PANEL T"
<br />SQUARE D : QO
<br />1201240V, 1 PH, 3W
<br />VOLTAGE/PHASE
<br />200A ML4
<br />200A BUS
<br />NEMA-11
<br />SURFACE
<br />22,000 AIC
<br />OPTIONS:
<br />CKT
<br />AMPS
<br />POLE
<br />DESCRIPTION
<br />NOTES
<br />LOAD
<br />VA
<br />CKT
<br />AMPS
<br />POLE
<br />DESCRIPTION
<br />NOTES
<br />LOAD
<br />VA
<br />1
<br />100
<br />2
<br />POOL PANEL `P'
<br />1,2
<br />'"''6
<br />2
<br />20
<br />1
<br />FUTURE EXT LI GHTI NG
<br />500
<br />3
<br />W6
<br />4
<br />20
<br />1
<br />FUTURE EXT UC44T1 NG
<br />500
<br />5 1
<br />20
<br />1
<br />SPARE
<br />0
<br />6
<br />20
<br />1
<br />FUTURE EXT U C3 ITI NG
<br />500
<br />7
<br />20
<br />1
<br />SPARE
<br />0
<br />8
<br />20
<br />1
<br />FUTURE EXT LIGHTING
<br />500
<br />9
<br />20.
<br />1
<br />SPARE
<br />0
<br />10
<br />20
<br />1
<br />FUTURE EXT U GHTI NG
<br />500
<br />11
<br />20
<br />1
<br />SPARE
<br />0
<br />12
<br />20
<br />1
<br />FUTURE EXT U GHTI NG
<br />500
<br />13
<br />1
<br />SPACE ONLY
<br />0
<br />14
<br />20
<br />1
<br />FUTURE EXT U GHTING
<br />500
<br />15
<br />1
<br />SPACE ONLY
<br />0
<br />16
<br />20
<br />1
<br />FUTURE EXT LIGHTING
<br />500
<br />17
<br />1
<br />SPACE ONLY
<br />0
<br />18
<br />20
<br />1
<br />F UTUF E EXT U GFITI NG
<br />500
<br />19
<br />1
<br />SPACE ONLY
<br />0
<br />20
<br />20
<br />1
<br />FUTURE EXT LIGHTING
<br />500.
<br />21
<br />1
<br />SPACE ONLY
<br />0
<br />22
<br />20
<br />1
<br />FUTURE EXT LI GHTI ING
<br />500
<br />23
<br />1
<br />SPACE ONLY
<br />0
<br />24
<br />20
<br />1
<br />FUTURE EXT LIGHTING
<br />500
<br />25
<br />1
<br />SPACE ONLY
<br />0'
<br />261
<br />1
<br />SPACE ONLY
<br />0
<br />27
<br />1
<br />SPACE ONLY
<br />0
<br />28
<br />1
<br />SPACE ONLY
<br />0
<br />29
<br />1
<br />SPACE ONLY
<br />0
<br />30
<br />1
<br />SPACE ONLY
<br />0.
<br />31
<br />1
<br />SPACE ONLY
<br />0
<br />1 32
<br />1
<br />SPACE ONLY
<br />0
<br />33
<br />1
<br />SPACE ONLY
<br />0
<br />341
<br />1
<br />SPACE ONLY
<br />0
<br />35
<br />1
<br />SPACE ONLY
<br />0
<br />36
<br />1
<br />SPACE ONLY
<br />0'
<br />37
<br />1
<br />SPACE ONLY
<br />0
<br />38
<br />1
<br />SPACE ONLY
<br />0
<br />39
<br />1
<br />SPACE ONLY
<br />0
<br />40
<br />1
<br />SPACE ONLY
<br />0
<br />41
<br />1
<br />SPACE ONLY
<br />0'
<br />42
<br />1
<br />SPACE OI.
<br />0
<br />NOTES:
<br />LOAD CONNECTED DEMAND DEMAND
<br />DESCRIPTION LOAD (VA) FACTOR LOAD (VA)
<br />1.
<br />SEE RISER DIAGRAM FOR WIRE SIZES
<br />LIGHTING 6000 1.25 7500.
<br />HVAC - .COOL 0 0_Q0 0
<br />HVAC.- HEAT 0 0.00 0:
<br />RECEPTACLE 0 0.00 0
<br />Me 12012 1.00 12912
<br />2.
<br />POOL EQUIPMENT PANEL BY OTHERS
<br />3
<br />4.
<br />5_
<br />6,
<br />TOTAL 18912 20412
<br />7.
<br />TOTAL DEMAND CURRENT @ 120/240VJ 1PH 85.1 AMPS
<br />LIGHTING POWER DENSITY
<br />CALCULATION
<br />SPACE TYPE
<br />TOTAL SQ FT
<br />ALLOWED
<br />LPD
<br />ALLOWABLE
<br />WATTAGE
<br />LOUNGE/BREAKROOM
<br />2713
<br />0.73
<br />1980.49
<br />RESTROOMS
<br />471
<br />0.98
<br />461.58
<br />CORR[DOR/TRANSITION
<br />147
<br />0.66
<br />97.02
<br />ACTIVE STORAGE
<br />1308
<br />10.63
<br />1194.04
<br />ELECTRICAL/MECHANICAL
<br />180
<br />10.95
<br />176
<br />TOTAL ALLOWABLE WATTS
<br />2809.13
<br />TOTAL ACTUAL WATTS
<br />1619
<br />PASSES 2017 FBC ENERGY CONSERVATION ARTICLE 405.4.2
<br />YES
<br />ELECTRICAL SYMBOL LEGEND
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />SURFACE MOUNT SCONCE FIXTURE ON FLUSH 4" SQUARE J-BOX, WITH MOUNTING
<br />SEE FIXTURE SCHEDULE
<br />A
<br />HARDWARE. LETTER INDICATES TYPE.
<br />®q
<br />1' X 4' FLUORESCENT FIXTURE, LETTER INDICATES TYPE
<br />SEE FIXTURE SCHEDULE
<br />® A
<br />2' X 4' FLUORESCENT TROFFER, LETTER INDICATES TYPE
<br />SEE FIXTURE SCHEDULE
<br />RECESSED DOWNUGHT WITH TRIM AND REQUIRED CEILING ADAPTERS. LETTER
<br />SEE FIXTURE SCHEDULE
<br />A
<br />INDICATES TYPE.
<br />X
<br />®
<br />EXIT LIGHT, SHADING INDICATES NUMBER OF FACES, ARROWS INDICATE DIRECTIONAL
<br />SEE FIXTURE SCHEDULE
<br />INDICATORS REQUIRED. LETTER INDICATES TYPE.
<br />EM
<br />BATTERY POWERED EMERGENCY EGRESS LIGHT WITH WALL BRACKET, (2) HEAD
<br />SEE FIXTURE SCHEDULE
<br />UNLESS OTHERWISE NOTED. LETTER INDICATES TYPE.
<br />SWITCH, SINGLE POLE, 20 A. 120/277 VAC. REFER TO SPECIFICATIONS FOR DEVICE
<br />48" AFF TO TOP
<br />COLOR, WALL PLATE COLOR AND MATERIAL, AND DEVICE MODEL NUMBER.
<br />UNLESS NOTED OTHERWISE
<br />SWITCH, THREE-WAY, 20 A. 120/277 VAC. REFER TO SPECIFICATIONS FOR DEVICE
<br />48" AFF TO TOP
<br />COLOR, .WALL PLATE COLOR AND MATERIAL, AND DEVICE MODEL NUMBER.
<br />UNLESS NOTED OTHERWISE
<br />DUPLEQ RECEPTACLE, IREFER I DEVICE
<br />NOTEDUNLESS
<br />COLOR, WALLPLATE REQUREMENTS, AND EVI E MODEL NUMBER.CATIONS
<br />THE SYMBOLS BELOW
<br />THE
<br />DEFINE MOUNTING HEIGHTS:
<br />Q
<br />TWO (2) DUPLEX RECEPTACLES IN COMMON BOX, 20 A. 120 VAC. REFER TO
<br />>
<br />SPECIFICATIONS FOR DEVICE COLOR, WALL PLATE REQUIREMENTS, AND DEVICE
<br />18" AFF TO CENTERLINE
<br />MODEL NUMBER.
<br />(p 4
<br />ABOVE COUNTER
<br />SIMPLEX RECEPTACLE, 20 A, 120 VAC. REFER TO SPECIFICATIONS FOR DEVICE
<br />Q 36
<br />COLOR, WALL PLATE REQUIREMENTS, AND DEVICE MODEL NUMBER.
<br />BELOW COUNTER
<br />L�,,--,,--,,
<br />NON -FUSED DISCONNECT SWITCH,
<br />60" AFF TO TOP
<br />60/W/3/N3R
<br />CURRENT RATING/FUSING/NUMBER OF POLES/ENCLOSURE
<br />UNLESS NOTED OTHERWISE
<br />i
<br />BRANCH CIRCUIT PANELBOARD, 120/208 V OR 120/240 V. SURFACE MOUNT
<br />78" AFF TO TOP
<br />UNLESS NOTED OTHERWISE
<br />ELECTRIC METER
<br />60" AFF TO TOP
<br />UNLESS NOTED OTHERWISE
<br />HOME RUN TO PANEL. LABEL INDICATES PANEL NAME AND CIRCUIT NUMBER(S).
<br />SEE SPECIFICATIONS
<br />CIRCUITS WITHOUT FURTHER DESIGNATION INDICATES A 2 WIRE CIRCUIT WITH A
<br />L1A-1,3
<br />PARITY SIZED EQUIPMENT GROUND. CIRCUIT WITH MORE THAN 2 WIRES IS SHOWN
<br />AS FOLLOWS:
<br />= 3 PHASE WIRES AND AN EQUIPMENT GROUND
<br />= 3 PHASE WIRES, 1 NEUTRAL AND AN EQUIPMENT GROUND
<br />= 3 PHASE WIRES, 1 NEUTRAL, AN ISOLATED GROUND AND AN EQUIPMENT GROUND
<br />ALL CONDUCTORS ARE #12 AWG Cu UNLESS NOTED OTHERWISE.
<br />RACEWAY CONCEALED IN WALL OR ABOVE CEILINGS
<br />SEE SPECIFICATIONS
<br />RACEWAY CONCEALED UNDER FLOOR OR BELOW GRADE
<br />SEE SPECIFICATIONS
<br />"GFI" NOTATION MEANS ASSOCIATED DEVICE SHALL BE GROUND FAULT CIRCUIT
<br />AS DEFINED BY SYMBOL
<br />GFI
<br />INTERRUPTER TYPE. REFER TO SPECIFICATIONS FOR DEVICE COLOR, WALL PLATE
<br />REQUIREMENTS, AND MODEL NUMBER.
<br />WP
<br />"WP" NOTATION MEANS ASSOCIATED DEVICE SHALL BE MOUNTED IN WEATHERPROOF
<br />AS DEFINED BY SYMBOL
<br />ENCLOSURE.
<br />AFC 15,6251
<br />AFC 11.5791
<br />1 1 AFC 11,402-1
<br />i
<br />9
<br />1 AFC 10.2051
<br />B
<br />UTILITY PAD
<br />MTD TRANSFORMER
<br />120/24OV.10
<br />A
<br />°
<br />i PANEL "A"
<br />PANEL "B"
<br />O
<br />200A MCB
<br />120/240V.10
<br />200A MLO
<br />120/240V.10
<br />NEMA-1
<br />NEMA-1
<br />METER
<br />i o
<br />j 22K AIC N
<br />22K AIC
<br />RISER DIAGRAM
<br />120/24OV. 10
<br />LC-1
<br />0
<br />NEMA 3R
<br />C
<br />i 6,634 AFC
<br />° 10,000 AIC
<br />i NEMA-3R
<br />i PANEL
<br />P
<br />i 1BY
<br />20/240V.1,
<br />i
<br />i
<br />i
<br />i
<br />i
<br />RISER DIAGRAM -
<br />WIRE TAG LEGEND
<br />�A
<br />1 SET: (2)
<br />#3/0 CU, #3/0 CU
<br />N, 2" C.
<br />❑B
<br />1 SET: (2)
<br />#3/0 CU, #3/0 CU
<br />N. (1) #6
<br />CU EG, 2" C.
<br />c�
<br />1 SET. (2)
<br />#3 CU, #3 CU N, (1)
<br />#8 E.G.
<br />- 1 1 /4" C.
<br />G1
<br />#2 CU GIRD
<br />AND 5/8" DRIVEN
<br />RODS PER
<br />NEC AND LOCAL CODE.
<br />BOND TO BUILDING STEEL AND/OR COLD
<br />WATER WHERE APPLICABLE.
<br />O KEYED DRAWING NOTES O
<br />1. PROVIDE SURGE PROTECTION DEVICE AT PANEL INDICATED. LEA
<br />MODEL # SP200-120/240-SP OR APPROVED EQUAL.
<br />2. LIGHTING CONTROL PANEL BY OTHERS.
<br />EMERALD
<br />ENGINEERING INC"
<br />9942 CURRIE DAVIS DR. STE H., TAMPA, FL 33619
<br />TEL (813) 995-0300 FLORIDA EB# 0027845
<br />WWW.EMERALDMEP.COM EEI PROJECT# 180822
<br />ELECTRICAL SPECIFICATIONS
<br />1. THE ELECTRICAL CONTRACTOR REFERRED TO HEREAFTER, AS THE "CONTRACTOR" SHALL PROVIDE A
<br />COMPLETE ELECTRICAL SYSTEM AS INDICATED ON THE DRAWINGS AND SPECIFIED HEREIN.
<br />2. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, FEES, AND INSPECTIONS REQUIRED TO
<br />COMMENCE AND COMPLETE ELECTRICAL WORK.
<br />3. CONTRACTOR SHALL REFER TO INTERIOR ARCHITECTURAL CASE WORK ELEVATIONS FOR EXACT
<br />MOUNTING HEIGHTS AND/OR LOCATIONS OF SWITCHES, OUTLETS, AND WIRING DEVICES.
<br />4. ALL WORK SHALL BE PERFORMED DURING PERIODS ACCEPTABLE TO THE OWNER. SCHEDULE ALL
<br />WORK WITH THE OWNER'S REPRESENTATIVE BEFORE PROCEEDING.
<br />5. AT PROJECT COMPLETION, THE CONTRACTOR SHALL INSURE THAT ALL ELECTRICAL SYSTEMS
<br />OPERATE PROPERLY. CONTRACTOR SHALL DEMONSTRATE OPERATION OF EACH SYSTEM WITH THE
<br />OWNER'S REPRESENTATIVE.
<br />6. ELECTRICAL WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION
<br />(AHJ) AND WITH THE FOLLOWING CODES:
<br />- NFPA 70 (NATIONAL ELECTRICAL CODE), 2014 EDITION
<br />- FLORIDA BUILDING CODE, 6TH EDITION (2017)
<br />7. WORKMANSHIP SHALL BE HIGH QUALITY AND FOLLOW INDUSTRY STANDARDS. SUBSTANDARD WORK
<br />WILL BE REJECTED. THE CONTRACTOR IS RESPONSIBLE FOR REPAIR AND REWORK TO RECTIFY
<br />SUBSTANDARD WORK. QUALITY OF WORK SHALL BE DETERMINED BY THE OWNER'S REPRESENTATIVE
<br />AND/OR ENGINEER OF RECORD.
<br />8. PLANS ARE GENERALLY DIAGRAMMATIC. THE CONTRACTOR SHALL COORDINATE WITH THE OTHER
<br />TRADES SO THAT INTERFERENCES BETWEEN CONDUITS, PIPING, EQUIPMENT, DUCTS, AND STRUCTURAL
<br />WORK WILL BE AVOIDED. IN SUCH CASE, THE CONTRACTOR FAILS TO COORDINATE WITH OTHER
<br />TRADES AND INTERFERENCES ARE ALLOWED DEVELOP, THE OWNER'S AUTHORIZED REPRESENTATIVE
<br />WILL DECIDE WHICH EQUIPMENT, DUCT, CONDUIT, ETC., MUST BE RELOCATED, REGARDLESS OF WHICH
<br />WAS INSTALLED FIRST. ELECTRICAL REWORK REQUIRED TO CORRECT INTERFERENCES WILL BE AT THE
<br />CONTRACTORS EXPENSE.
<br />9. ALL ELECTRICAL EQUIPMENT AND MATERIALS SHALL BE APPROVED BY UNDERWRITERS LABORATORY
<br />FOR THE APPLICATION AND SHALL BEAR A UL LABEL.
<br />10. CONTRACTOR SHALL GUARANTEE ALL WORK FOR A PERIOD OF ONE YEAR FROM DATE OF OWNER'S
<br />ACCEPTANCE. THE CONTRACTOR SHALL RECTIFY ANY DEFECTS DUE TO FAULTY MATERIALS OR
<br />WORKMANSHIP AND PAY FOR DAMAGE CAUSED BY FAILURE AND REWORK. THE OWNER WILL GIVE
<br />NOTICE OF DEFECTS WITH REASONABLE PROMPTNESS AFTER DISCOVERY. THE CONTRACTOR SHALL
<br />START REWORK WITHIN TEN (10) WORKING DAYS OF NOTIFICATION AND COMPLETE REPAIRS IN A
<br />TIMELY MANNER.
<br />11. AT PROJECT COMPLETION THE CONTRACTOR SHALL COMPILE TWO (2) COMPLETE SETS OF RECORD
<br />DRAWINGS INDICATING ALL DEVIATIONS FROM CONSTRUCTION DOCUMENTS. ONE SET SHALL BE
<br />ISSUED TO THE ARCHITECT AND ONE SET SHALL BE ISSUED TO OWNER'S REPRESENTATIVE.
<br />12. LABEL ALL ELECTRICAL EQUIPMENT WITH ENGRAVED LAMINATED PLASTIC NAMEPLATE THAT CLEARLY
<br />DESCRIBES THE EQUIPMENT NAME, VOLTAGE, AMPERAGE RATING, AND FUNCTION. NAMEPLATES SHALL
<br />BE RED BACKGROUND WITH WHITE STENCILED UPPER CASE LETTERING A MINIMUM OF 3/16" IN
<br />HEIGHT.
<br />13. PROVIDE TYPEWRITTEN PANELBOARD DIRECTORIES WITH ACCURATE AS -BUILT INFORMATION.
<br />DIRECTORIES SHALL REFLECT TYPE OF LOAD AND AREA SERVED FOR EACH BREAKER.
<br />14. CONDUCTORS SHALL BE COPPER UNLESS OTHERWISE NOTED. INSULATION SHALL BE DUAL TYPE
<br />THHN/THWN 75'C. CONDUCTORS SHALL BE COLOR CODED IN ACCORDANCE WITH NFPA 70. COLOR
<br />CODING SHALL BE BY MEANS OF COLORED INSULATING MATERIAL, COLORED BRAID OR JACKET OVER
<br />THE INSULATION OR BY MEANS OF SUITABLE COLORED, PERMANENT, NON -AGING, INSULATING TAPE
<br />APPUED TO CONDUCTORS AT EACH CABINET OR JUNCTION POINT. THE FOLLOWING SYSTEM OF
<br />COLOR CODING SHALL BE ADHERED TO:
<br />- GROUND LEADS: GREEN
<br />- 120/240 NEUTRAL CONDUCTOR: WHITE
<br />- 120/240 VOLT, PHASE CONDUCTORS: BLACK, RED
<br />15. CONDUIT SHALL BE PROPERLY ALIGNED, GROUPED AND SUPPORTED. EXPOSED CONDUIT SHALL BE
<br />INSTALLED AT RIGHT ANGLES TO OR PARALLEL TO THE PRINCIPAL STRUCTURAL MEMBERS. CONDUIT
<br />SHALL BE SUPPORTED AT INTERVALS NOT EXCEEDING 8 FEET. CONDUIT SHALL BE SUPPORTED FROM
<br />STRUCTURE AND NOT FROM CEILING SUPPORT SYSTEM. CONDUIT SHALL BE CONCEALED EXCEPT IN
<br />MECHANICAL ROOMS, ELECTRICAL ROOMS, OPEN STRUCTURE CANOPIES, AND EXTERIOR SERVICE
<br />ENTRANCES. ACCEPTABLE CONDUIT TYPES; EMT, GRS, FMC, MC CABLE IN DRY CONCEALED
<br />LOCATIONS, PVC IN BELOW GRADE OR IN CONCRETE.
<br />16. ALL INTERIOR ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS
<br />REQUIRED BY NFPA 70 AND AS SPECIFIED HEREIN.. METALLIC RACEWAYS SHALL BE MECHANICALLY
<br />AND ELECTRICALLY SECURE AT ALL JOINTS AND AT ALL BOXES, CABINETS, FITTINGS, AND
<br />EQUIPMENT. METALLIC RACEWAYS SHALL BE CONNECTED TO A DIRECT GROUND AT POINT OF
<br />ELECTRICAL SERVICE ENTRANCE AND SHALL BE ELECTRICALLY CONTINUOUS THROUGHOUT THE ENTIRE
<br />SYSTEM.
<br />GENERAL DRAWING NOTES
<br />1. ALL FEEDERS AND BRANCH CONDUCTORS INDICATED HEREIN
<br />COMPLY WITH 2O17 FLORIDA BUILDING CODE.
<br />2. THE LIGHTING DESIGNS CONTAINED HEREIN COMPLY WITH 2O17
<br />FLORIDA BUILDING CODE - ENERGY CONSERVATION.
<br />00
<br />r
<br />N
<br />1
<br />r
<br />1
<br />s
<br />i
<br />EN
<br />4 P ,
<br />TATEOF
<br />ADAM T. WELL, PE
<br />FL. REG. NO. PE73853
<br />U7
<br />z
<br />0
<br />cn
<br />w
<br />cc
<br />C
<br />O
<br />co
<br />a
<br />N
<br />N
<br />CU
<br />J
<br />a
<br />m
<br />N
<br />U)
<br />cz
<br />O
<br />.W
<br />70
<br />=3
<br />rn
<br />J
<br />N
<br />Q
<br />Q
<br />N
<br />N
<br />N
<br />0
<br />BSB
<br />DESIGN
<br />www.bsbdesign.com
<br />100 Main.St. Suite 209
<br />Safety Harbor, Florida 34695
<br />813 265 4808
<br />JOB NO: AM180320.00 PROJ MGR: AP
<br />DRAWN: DS CHECKED: AP
<br />SPECIFICATIONS, SCHEDULES
<br />LEGEND AND RISER DIAGRAM
<br />EO. 1