ELECTRICAL LEGEND
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />BRANCH CIRCUIT CONDUIT AND WIRE CONCEALED ABOVE CEILING OR
<br />AS REQUIRED PER NEC.
<br />BEHIND FINISHED WALL. PROVIDE NUMBER OF CONDUCTORS AS
<br />REQUIRED, MIN. #12 AWG WITH EQUIPMENT GROUND WIRE (EG).
<br />BRANCH CIRCUIT CONDUIT AND WIRE CONCEALED BELOW FINISHED
<br />AS REQUIRED PER NEC.
<br />FLOOR OR UNDERGROUND. PROVIDE NUMBER OF CONDUCTORS AS
<br />REQUIRED, MIN. #12 AWG WITH EQUIPMENT GROUND WIRE (EG).
<br />— — — — — — —
<br />RACEWAY EXPOSED N WALL OR CEILING. PROVIDE NUMBER OF
<br />AS REQUIRED PER NEC.
<br />CONDUCTORS REQUIRED, MIN. #12 AWG WITH EQUIP GROUND (EG).
<br />X-1,3,5
<br />HOMERUN TO PANELBOARD — LETTER INDICATES PANEL DESIGNATION,
<br />AS REQUIRED PER NEC.
<br />NUMBER INDICATES CIRCUIT(S), MINIMUM 3/4" CONDUIT. PROVIDE
<br />HOT
<br />MIN. #12 AWG CONDUCTORSS AND GROUND WIRE. FOR HOMERUNS
<br />EXCEEDING 90', PROVIDE #10 AWG CONDUCTORS AND GROUND WIRE.
<br />NEUT
<br />HOMERUN WITHOUT DESIGNATION SHALL BE A MIN. 2—#12, 1-1 2 EG
<br />DEDICATED
<br />CIRCUIT (0DR) SEPARATE NEUTRAL. COMPUTER
<br />1. G.
<br />(REQUIRES
<br />SEPARATE NEUTRALC, 10
<br />REQUFIORSMORE
<br />HREACURREJ10
<br />DERATEACONDUCTORS PER) NEC THAN THREE URREMIN.J
<br />EG NOT SHOWN
<br />CARRYING CONDUCTORS PER HOMERUN.
<br />A
<br />INCANDESCENT, FLUORESCENT OR HIGH INTENSITY DISCHARGE
<br />CEILING — SEE
<br />O
<br />LUMINAIRE (LIGHTING FIXTURE), LETTER INDICATES TYPE
<br />FIXTURE SCHEDULE
<br />® A
<br />LUMINAIRE (LIGHTING FIXTURE) WITH EMERGENCY BATTERY BACK—UP,
<br />CEILING — SEE
<br />LETTER INDICATES TYPE.
<br />FIXTURE SCHEDULE
<br />A
<br />0°
<br />1
<br />®
<br />FLUORESCENT LUMINAIRE FIXTURE, LETTER INDICATES TYPE, NUMBER
<br />CEILING — SEE
<br />CID
<br />1 = CIRCUIT NUMBER, LOWER CASE LETTER a = SWITCH DESIGNATION
<br />FIXTURE SCHEDULE
<br />MAU
<br />FLUORESCENT LUMINAIRE FIXTURE WITH EMERGENCY BATTERY PACK,
<br />CEILING — SEE
<br />LETTER INDICATES TYPE.
<br />FIXTURE SCHEDULE
<br />A 1
<br />®a
<br />FLUORESCENT LUMINAIRE FIXTURE, LETTER INDICATES TYPE, NUMBER
<br />CEILING — SEE
<br />1 = CIRCUIT NUMBER, LOWER CASE LETTER a = SWITCH DESIGNATION
<br />FIXTURE SCHEDULE
<br />A 1
<br />FLUORESCENT LUMINAIRE FIXTURE, LETTER INDICATES TYPE, NUMBER
<br />WALL — SEE
<br />9=90
<br />1 = CIRCUIT NUMBER, LOWER CASE LETTER a = SWITCH DESIGNATION
<br />FIXTURE SCHEDULE
<br />A 1
<br />FLUORESCENT STRIP LIGHT FIXTURE, LETTER INDICATES TYPE, NUMBER
<br />CEILING — SEE
<br />��a
<br />1 = CIRCUIT NUMBER, LOWER CASE LETTER a = SWITCH DESIGNATION
<br />FIXTURE SCHEDULE
<br />[� A
<br />INCANDESCENT, FLUORESCENT OR HIGH INTENSITY DISCHARGE
<br />WALL — SEE
<br />Q
<br />LUMINAIRE (LIGHTING FIXTURE), LETTER INDICATES TYPE
<br />FIXTURE SCHEDULE
<br />EMERGENCY LIGHTING LUMAIRE FIXTURE WITH EMERGENCY BATTERY
<br />'EM'
<br />MOUNT 6" BELOW CEILING,
<br />BACK—UP, TYPE U.O.N.
<br />10'-0" AFF, OR AS NOTED
<br />®i X
<br />EXIT LIGHT, LETTER INDICATES TYPE. PROVIDE SINGLE OR DOUBLE
<br />UNIVERSAL MOUNTING, SEE
<br />FACE AND DIRECTIONAL ARROWS AS INDICATED ON DRAWINGS
<br />SCHEDULE AND BEHIIULTINS
<br />Tcg v
<br />ELECTRIFIED TRACK WITH TRACK HEADS, LENGTH AND NUMBER OF
<br />CEILING — SEE
<br />22
<br />TRACK HEADS AS INDICATED N DRAWINGS, LETTER INDICATES TYPE.
<br />FIXTURE SCHEDULE
<br />Sa
<br />SINGLE POLE SWITCH, 20A, 277V U.O.N.
<br />M . H . 48" AFF
<br />K=KEY TYPE, LOWER CASE LETTER a = SWITCH DESIGNATION
<br />TO TOP
<br />a
<br />THREE WAY SWITCH, 20A, 277V U . 0. N .
<br />M . H . 48" AFF
<br />S 3
<br />LOWER CASE LETTER a = SWITCH DESIGNATION
<br />TO TOP
<br />a
<br />FOUR WAY SWITCH, 20A, 277V U.O.N.
<br />M.H. 48" AFF
<br />S4
<br />LOWER CASE LETTER a = SWITCH DESIGNA11ON
<br />TO TOP
<br />S M
<br />MOTOR/HP RATED TOGGLE SWITCH SIZED PER MOTOR
<br />SURFACE, ADJACENT TO
<br />MANUFACTURER'S RECOMMENDATION, MINIMUM 20 AMP.
<br />OR ON MOTOR
<br />1000 WATT INCANDESCENT DIMMER SWITCH WITH WALLPLATE.
<br />M.H. 48" AFF
<br />S D
<br />LUTRON MAESTRO MA-1000. FLUORESCENT AND LOW VOLTAGE
<br />TO TOP
<br />DIMMERS SHALL BE COMPATIBLE WITH BALLAST AND LAMP.
<br />TIME SWITCH, (TIME CLOCK), WITH 7 DAY, 24 HOUR SETTINGS,
<br />M.H. 60" AFF TO TOP
<br />RESERVE SPRING AND ENCLOSURE
<br />OF ENCLOSURE
<br />OS
<br />1500 WATT WALL MOUNTED OCCUPANCEY SENSOR SWITCH WITH
<br />M.H. 48" AFF
<br />WALLPLATE.
<br />TO TOP
<br />®
<br />1500 WATT CEILING MOUNTED OCCUPANCEY SENSOR SWITCH WITH
<br />FLUSH IN CEILING
<br />COVER PLATE.
<br />m
<br />SINGLE RECEPTACLE — 20 AMP, 120VAC U.O.N.
<br />MOUNTED 18" AFF
<br />`Y
<br />TO CENTERLINE
<br />DUPLEX RECEPTACLE — 20 AMP, 120VAC U.O.N.
<br />MOUNTED 18" AFF
<br />TO CENTERLINE
<br />DUPLEX RECEPTACLE — 20 AMP, 120VAC U.O.N.
<br />MOUNTED 44" AFF TO
<br />CENTERLINE OR AS NOTED
<br />DOUBLE DUPLEX RECEPTACLE — 20 AMP, 120VAC U.O.N.
<br />MOUNTED 18" AFF
<br />TO CENTERLINE
<br />DOUBLE DUPLEX RECEPTACLE — 20 AMP, 120VAC U.O.N.
<br />MOUNTED 44" AFF TO
<br />CENTERLINE OR AS NOTED
<br />GH
<br />DUPLEX RECEPTACLE — 120VAC, WP DENOTES WEATHERPROOF
<br />MOUNTED 18" AFF
<br />WPq?
<br />GFI DENOTES GROUND FAULT PROTECTION.
<br />TO CENTERLINE
<br />®
<br />SPECIAL RECEPTACLE, AMPERAGE, NEMA TYPE AS
<br />MOUNTED 18" AFF
<br />INDICATED.
<br />TO CENTERLINE U.O.N.
<br />DUPLEX RECEPTACLE — 20 AMP, 120VAC U.O.N. COMPUTER
<br />MOUNTED 18" AFF
<br />PC
<br />RECEPTACLE WITH SEPARATE NEUTRAL MIN. #10 AWG.
<br />TO CENTERLINE
<br />®
<br />FLUSH FLOOR DUPLEX RECEPTACLE WITH ROUND FULLY ADJUSTABLE,
<br />DEEP, SINGLE GANG BOX WITH BRASS FLANGE COVER PLATE AND
<br />FLUSH IN
<br />FLOOR
<br />4 1" CONDUIT HUBS.
<br />®
<br />FLUSH FLOOR DOUBLE DUPLEX RECEPTACLE WITH ROUND FULLY
<br />ADJUSTABLE, DEEP, SINGLE GANG BOX WITH BRASS FLANGE COVER
<br />FLUSH IN
<br />FLOOR
<br />PLATE AND 4-1" CONDUIT HUBS.
<br />COMBINATION COMMUNICATION/POWER FLOOR BOX WITH DUPLEX
<br />FLUSH IN
<br />RECEPTACLE, ROUND FULLY ADJUSTABLE DEEP TWO —GANG WITH
<br />FLOOR
<br />BRASS FLANGE COVER AND 6-1" CONDUIT HUBS.
<br />COMBINATION COMMUNICATION/POWER FLOOR BOX WITH DOUBLE
<br />FLUSH IN
<br />0
<br />®
<br />DUPLEX RECEPTACLE, ROUND FULLY ADJUSTABLE DEEP TWO —GANG
<br />FLOOR
<br />WITH BRASS FLANGE COVER AND 6-1" CONDUIT HUBS.
<br />4"x4%2-1/2" DEEP BOX WITH 1" EMPTY CONDUIT WITH PULL
<br />MOUNTED 18" AFF
<br />0
<br />STRING AND CONDUIT STUBBED INTO ACCESSIBLE CEILING SPACE,
<br />TO CENTERLINE U.O.N.
<br />PROVIDE CONDUIT BUSHING. DATA/VOICE OUTLET.
<br />4"x4"x2-1/2" DEEP BOX WITH 1" EMPTY CONDUIT WITH PULL
<br />MOUNTED 18" AFF
<br />STRING AND CONDUIT STUBBED INTO ACCESSIBLE CEILING SPACE,
<br />TO CENTERLINE U.O.N.
<br />PROVIDE CONDUIT BUSHING. VOICE OUTLET.
<br />4%4%2-1 /2" DEEP BOX WITH 1" EMPTY CONDUIT WITH PULL
<br />M . H . 44" AFF
<br />0
<br />STRING AND CONDUIT STUBBED INTO ACCESSIBLE CEILING SPACE,
<br />TO CENTER OR
<br />PROVIDE CONDUIT BUSHING. DATA/VOICE OR (V) VOICE OUTLET.
<br />AS NOTED
<br />1V
<br />TV CABLE OUTLET WITH JUNCTION BOX, -4 IA* CONDUIT WITH BUSHING
<br />MOUNTED 18" AFF
<br />Q
<br />STUBBED INTO ACCESSIBLE CEILING SPACE.
<br />TO CENTERLINE U.O.N.
<br />FLOOR MOUNTED COMMUNICATION LEGEND, WITH MINIMUM 1" C
<br />FLUSH IN
<br />UNDER GROUND WITH PULL STRING
<br />FLOOR
<br />POWER/DATA COMMUNICATION POLE WITH 2 QUAD RECEPTACLES
<br />SECURE TO STRUCTURE
<br />AND DATA CONDUIT STUBBED INTO ACCESSIBLE CEILING SPACE.
<br />PER MANUFACTURER
<br />COMMUNICATION RACK FOR DATA/COMMUNCITION EQUUIPMENT
<br />FLOOR MOUNTED U.O.N.
<br />®
<br />AND CABLING, SEE SPECIFICATIONS AND DETAILS
<br />120/208 VOLT OR 120/240 VOLT PANELBOARD, SEE
<br />M.H. 6'-0" TO TOP
<br />PANEL SCHEDULE
<br />OR AS NOTED
<br />DISTRIBUTION PANELBOARD, VOLTAGE AS INDICATED
<br />M.H. 6'-0" TO TOP
<br />SEE PANEL SCHEDULE
<br />OR AS NOTED
<br />�,
<br />HEAVY DUTY NON —FUSIBLE SAFETY SWITCH, (30/3/NF), U.O.N.,
<br />M.H. 5'-6" TO TOP, ON
<br />(AMPERAGE/NUMBER OF POLES/NON—FUSED)
<br />EQUIP., OR AS NOTED
<br />�,
<br />HEAVY DUTY FUSIBLE SAFETY SWITCH WITH FUSES, (AMP/POLE/FUSE)
<br />M . H. 5-6" TO TOP, ON
<br />(AMPERAGE/NUMBER OF POLES/FUSE SIZE)
<br />EQUIP., OR AS NOTED
<br />Ep
<br />COMBINATION MOTOR STARTER/DISCONNECT WITH FUSES. FUSE IN
<br />M.H. 5'-6" TO TOP, ON
<br />ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.
<br />EQUIP., OR AS NOTED
<br />8
<br />MAGNETIC MOTOR STARTER WITH FUSES. FUSE IN ACCORDANCE
<br />M.H. 5'-6" TO TOP, ON
<br />WITH MANUFACTURERS RECOMMENDATIONS.
<br />EQUIP., OR AS NOTED
<br />m
<br />VARIABLE FREQUENCY DRIVE AS INDICATED. COORDINATE WITH
<br />M.H. 5'-6" TO TOP, ON
<br />MECHANICAL CONTRACTOR.
<br />EQUIP., OR AS NOTED
<br />�,
<br />ENCLOSED CIRCUIT BREAKER AS INDICATED.
<br />M.H. 5-6" TO TOP, ON
<br />EQUIP., OR AS NOTED
<br />ELECTRICAL LEGEND
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />MOTOR CONNECTION. PROVIDE FLEXIBLE CONNECTION AND
<br />AS NOTED
<br />DISCONNECT
<br />°
<br />JUNCTION BOX OR OUTLET BOX, 4" SQUARE BOX UNLESS
<br />CEILING, WALL OR AS
<br />OTHERWISE NOTED, OR SIZED PER NEC.
<br />NOTED
<br />®
<br />SECURITY SYSTEM KEY PAD BY OTHERS. PROVIDE 4"x4"x2-1/2"
<br />M.H. 54" AFF
<br />J—BOXWITH 1" EMPTY CONDUIT, BUSHING AND PULL STRING
<br />TO BOTTOM OR
<br />STUBBED INTO ACCESSIBLE CEILING SPACE.
<br />AS NOTED
<br />GENERAL LEGEND NOTES:
<br />1. SYMBOLS SHOWN ON LEGEND MAY NOT APPEAR ON PLANS OR DETAILS. WHERE
<br />SYMBOL
<br />APPEARS ON PLANS OR DETAILS FURNISH AND INSTALL AS SPECIFIED.
<br />2. NUMBERS SHOWN ON PLANS ADJACENT TO WIRING DEVICES INDICATE BRANCH CIRCUIT NUMBER(S).
<br />ABBREVIATIONS:
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />MAX.
<br />MAXIMUM
<br />PC, C
<br />COMPUTER
<br />MIN.
<br />MINIMUM
<br />D
<br />DEDICATED CIRCUIT
<br />MCB
<br />MAIN CIRCUIT BREAKER
<br />E. EX, ETR
<br />EXISTING TO REMAIN
<br />MLO
<br />MAIN LUG ONLY
<br />EWC
<br />ELECTRIC WATER COOLER
<br />N/A
<br />NOT APPLICABLE
<br />EWH
<br />ELECTRIC WATER HEATER
<br />NEUT
<br />NEUTRAL
<br />EG
<br />EQUIPMENT GROUND
<br />NF
<br />NON —FUSED
<br />ESB
<br />ENERGY SAVING BALLAST
<br />PC
<br />PERSONAL COMPUTER CIRCUIT
<br />GA
<br />GROUND FAULT PROTECTION
<br />TIE
<br />TIE INTO CIRCUIT
<br />G, GND
<br />GROUND
<br />TVSS
<br />TRANSIENT VOLTAGE SURGE SUPPRESSION
<br />GWB
<br />GYPSUM WALL BOARD
<br />TYP
<br />TYPICAL FOR ALL
<br />HP
<br />HORSE POWER
<br />U.O.N.
<br />UNLESS OTHERWISE NOTED
<br />IG
<br />ISOLATED GROUND
<br />RL
<br />RE —LOCATED
<br />M.H.
<br />MOUNTING HEIGHT
<br />WP
<br />WEATHER PROOF
<br />X—FMR
<br />TRANSFORMER
<br />LIGHTING FIXTURE SCHEDULE
<br />TYPE
<br />DESCRIPTION
<br />VOLTS
<br />LAMPS
<br />MOUNTING
<br />A
<br />2'X4' PARABOLIC FLUORESCENT LUMINAIRE WITH
<br />120
<br />3-48" 32 WATT
<br />RECESSED
<br />LOW IRIDESCENT SEMI—SPECULAR 18—CELL
<br />T-8, 3500K,
<br />LAY —IN CEILING
<br />LOUVER, T-8 LAMPS, AND BALLAST. METALUX
<br />85CRI &
<br />#2EPGX-332S361—GL—EB81, OR EQUIVALENT.
<br />ELECTRONIC
<br />BALLAST
<br />AE
<br />2'X4' PARABOLIC FLUORESCENT LUMINAIRE WITH
<br />120
<br />3-48" 32 WATT
<br />RECESSED
<br />LOW IRIDESCENT SEMI—SPECULAR 18—CELL
<br />T-8, 3500K,
<br />LAY —IN CEILING
<br />LOUVER, T-8 LAMPS, AND 2—LAMP 1,100 LUMEN
<br />85CRI &
<br />EMERGENCY BALLAST. METALUX #2EPGX—
<br />ELECTRONIC
<br />332S361—GL—EB8I—EL 2L, OR EQUIVALENT.
<br />BALLAST
<br />B
<br />2'X4' RECESSED FLUORESCENT LUMINAIRE WITH
<br />120
<br />3-48" 32 WATT
<br />RECESSED
<br />0.125 ACRYLIC LENS, T-8 LAMPS AND BALLAST.
<br />T-8, 3500K,
<br />LAY —IN CEILING
<br />METALUX #2GR8-332A—EB81, OR EQUIVALENT.
<br />85CRI &
<br />ELECTRONIC
<br />BALLAST
<br />C
<br />4 FOOT FLUORESCENT LUMINAIRE WITH LENSED
<br />120
<br />2-48" F32T8
<br />SURFACE OR
<br />ACRYLIC COVER. METALUX #CR-232A—EB8I —GL,
<br />3500K, 85CRI
<br />CHAIN HUNG 9'
<br />OR EQUIVALENT BY COLUMBIA, LITHONIA, OR
<br />& ELECTRONIC
<br />AFF
<br />DAY —BRIGHT.
<br />BALLAST
<br />D
<br />7" ROUND INCANDESCENT OPEN DOWNLIGHT WITH
<br />120
<br />1—PAR30 100
<br />RECESSED
<br />LOW IRIDESCENT REFLECTOR AND PAR LAMP,
<br />WATT HALOGEN
<br />LAY —IN CEILING
<br />HALO #HD6-6600—LI
<br />EM
<br />2—HEAD EMERGENCY BATTERY PACK WITH 90
<br />120
<br />5.4W INC
<br />WALL MOUNTED
<br />MINUTE BATTERY BACK—UP. SURE—LITES
<br />8'-6" A.F.F.
<br />#CU-1—NC—SD, OR EQUIVALENT.
<br />F
<br />7" ROUND FLOURESCENT DOWNLIGHT WITH
<br />120
<br />2-26W OTT,
<br />RECESSED N
<br />REFLECTOR AND COMPACT FLUORESCENT LAMP,
<br />3500K &
<br />CEILING
<br />PORTFOLIO #C7226E-7251 LI
<br />ELECTRONIC
<br />BALLAST
<br />G
<br />7" ROUND HID WIDE BEAM OPEN DOWNLIGHT WITH
<br />120
<br />1-70 WATT
<br />RECESSED IN
<br />LOW IRIDESCENT REFLECTOR AND HID LAMP,
<br />OPEN RATED
<br />CEILING
<br />PORTFOLIO #MD7-730-70-1E-7750—LI
<br />METAL HALIDE
<br />W
<br />WALL MOUNTED INCANDESCENT LUMINAIRE WITH
<br />120
<br />3-60 WATT
<br />SURFACE ON
<br />DIE CAST ALUMINUM BOADY AND LISTED FOR WET
<br />CANDELABRA
<br />WALL, VERIFY
<br />LOCATIONS. PROVIDE BLACK FINISH. THOMAS
<br />MOUNTING
<br />LIGHTING, COVINGTON SERIS #SL9142-7, OR
<br />HEIGHT WITH
<br />EQUIVALENT.
<br />ARCHITECT
<br />X
<br />LED EXIT SIGN WITH BRUSHED FACE ALUMINUM
<br />120
<br />LED
<br />SURFACE, OR
<br />HOUSING AND RED LETTERS. PROVIDE WITH
<br />SEMI —RECESSED
<br />EMERGENCY BATTERY BACK—UP, AND UNIVERSAL
<br />ON CEILING OR
<br />MOUNTING. SURE—LITES #TPX7-07OR—SD, OR
<br />WALL
<br />EQUIVALENT.
<br />ELECTRICAL SPECIFICATIONS
<br />P�1. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH:
<br />D NFPA 70, (NEC),;QG51=DITION -
<br />NFPA 72, .9W EDITION.
<br />NFPA 101, LIFE SAFETY CODE 2003 EDITION.
<br />FLORIDA BUILDING CODE 2004 EDITION, WITH 05 & 06 SUPPLEMENTS.
<br />FLORIDA FIRE PREVENTION CODE 2004.
<br />ALL APPLICABLE RULES AND REGULATIONS OF LOCAL CODES.
<br />2. ALL WIRING SHALL BE COPPER TYPE THHN/THWN. SOLID FOR #10 AND
<br />SMALLER, STRANDED FOR ALL CONDUCTORS #8 AND LARGER.
<br />3. UNLESS OTHERWISE NOTED ALL CABLES AND CONDUCTORS SHALL BE INSTALLED
<br />IN AN APPROVED RACEWAY AS FOLLOWS:
<br />INTERIOR:
<br />a) EMT, SET SCREW TYPE FITTINGS OR COMPRESSION TYPE FITTINGS IN DAMP
<br />LOCATIONS.
<br />b) FLEXIBLE CONNECTION WHIPS (MAXIMUM 6'-0" LENGTH).
<br />FLEXIBLE CONDUIT SHALL BE USED FOR ALL FINAL CONNECTIONS TO MOTORS,
<br />LIGHTING FIXTURES AND OTHER VIBRATING EQUIPMENT.
<br />ALL INTERIOR CONDUITS SHALL BE CONCEALED EXCEPT IN ELECTRICAL AND
<br />MECHANICAL ROOMS.
<br />EXTERIOR (EXPOSED):
<br />a) RIGID GALVANIZED CONDUIT OR INTERMEDIATE METAL CONDUIT, (THREADED
<br />FITTINGS AS MANUFACTURED BY CONDUIT MANUFACTURER).
<br />b) FLEXIBLE LIQUIDTIGHT CONNECTION WHIPS (MAXIMUM 6'-0' LENGTH).
<br />FLEXIBLE LIQUIDTIGHT CONDUIT SHALL BE USED FOR ALL FINAL CONNECTIONS
<br />TO MOTORS AND OTHER VIBRATING EQUIPMENT.
<br />ALL RACEWAYS SHALL BE INSTALLED PERPENDICULAR AND PARALLEL
<br />TO MAJOR STRUCTURAL ELEMENTS AND IN A NEAT AND WORKMAN LIKE
<br />MANNER.
<br />EXTERIOR (UNDERGROUND):
<br />a) SCHEDULE 40 PVC.
<br />4. DISCONNECTING MEANS SHALL BE OF THE HEAVY—DUTY TYPE. UNLESS OTHERWISE
<br />INDICATED PROVIDE NEMA 1 ENCLOSURE INTERIOR, NEMA-3R EXTERIOR.
<br />5. CONTRACTOR SHALL CLEAN EACH AREA WHERE WORK IS PERFORMED ON A
<br />DAILY BASIS.
<br />6. ALL CUTTING AND PATCHING SHALL BE RESTORED TO MATCH EXISTING
<br />SURFACE AND FINISH. WHERE NECESSARY TO DRILL THROUGH EXISTING FIRE
<br />RATED PARTITIONS OR FLOORS CONTRACTOR SHALL PATCH USING MATERIALS
<br />OF N EQUIVALENT FIRE RATING.
<br />5. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO
<br />NEW WALLS, FLOOR, FURNITURE ETC. AND SHALL REPLACE ANY DAMAGED
<br />ITEMS WITHOUT ADDITIONAL COST TO OWNER. USE TEMPORARY COVERS TO
<br />AVOID SPREAD OF DUST AND CONSTRUCTION DEBRIS AS REQUIRED.
<br />6. UPON COMPLETION OF THE WORK THE ELECTRICAL CONTRACTOR SHALL
<br />TEST ALL NEW EQUIPMENT, DEVICES, ETC. FOR PROPER OPERATION.
<br />REPLACE MALFUNCTIONING UNITS AND RE —TEST TO FULFILL REQUIREMENTS.
<br />7. PNELBOARDS SHALL BE ACCURATELY LABELED TO IDENTIFY FINAL CIRCUIT
<br />NUMBERS UTILIZED, THEIR LOAD AND LOCATION.
<br />8. ELECTRICAL INSTALLATION SHALL BE CLOSELY COORDINATED WITH ALL OTHER
<br />WORK. CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH
<br />ILL—TIMED INSTALLATION INCLUDING ANY ASSOCIATED REPAIRS OR
<br />REPLACEMENTS.
<br />9. "PROVIDE" SHALL MEAN "FURNISH AND INSTALL".
<br />10. LIGHTING TOGGLE SWITCHES AND COVERPLATES SHALL BE 20 AMP, COMMERCIAL
<br />GRADE TOGGLE TYPE SWITCHES, LEVITON SC120-2, OR EQUIVALENT. ALL SWITCHES
<br />AND COVERPLATES SHALL BE WHITE. ALL SWITCHES SHALL BE GANGED IN ONE
<br />COMMON COVERPLATE. LOCATIONS AND HEIGHTS SHALL BE COORDINATED WITH
<br />DOOR SWINGS AND COUNTER HEIGHTS.
<br />COVERPLATES SHALL BE PLASTIC, LEVITON UREA OR EQUIVALENT.
<br />11. DUPLEX AND DOUBLE DUPLEX RECEPTACLES SHALL BE 15 AMP, 125 VOLT RATED,
<br />COMMERCIAL GRADE, LEVITON CR15 OR EQUIVALENT. RECEPTACLES SHALL HAVE
<br />A GREEN GROUNDING SCREW TERMINAL AND A SELF GROUNDING CLIP. ALL
<br />RECEPTACLES SHALL BE WHITE. DEDICATED RECEPTACLES SHALL BE 20 AMP
<br />RATED. EXACT LOCATIONS AND MOUNTING HEIGHTS SHALL BE COORDINATED
<br />WITH THE COUNTER HEIGHTS AND ALL LOCATIONS SHALL BE VERIFIED WITH
<br />THE OWNER PRIOR TO ROUGH —IN.
<br />GFCI TYPE RECEPTACLES SHALL BE 20 AMP 120V, NON FEED—THRU TYPE.
<br />COVERPLATES SHALL MATCH LIGHTING SWITCHES.
<br />12. PANELBOARDS SHALL BE EQUIPPED WITH COPPER BUS, 98% CONDUCTIVITY.
<br />CIRCUIT BREAKERS SHALL BE OF THE BOLT —ON TYPE, AIC RATINGS
<br />AS INDICATED. ACCEPTABLE MANUFACTURERS: GE, SQUARE D, SIEMENS,
<br />AND CUTLER —HAMMER.
<br />13. SUPPORTING DEVICES
<br />DAMP LOCATIONS AND OUTDOORS: HOT DIP GALVANIZED MATERIALS, U CHANNEL
<br />SYSTEM COMPONENTS.
<br />DRY LOCATION: STEEL MATERIALS.
<br />STRENGTH OF SUPPORTS: ADEQUATE TO CARRY THE LOAD TIMES A SAFETY
<br />FACTOR OF FOUR; MINIMUM 200—LB DESIGN LOAD.
<br />14. ELECTRICAL IDENTIFICATION
<br />ENGRAVED PLASTIC LAMINATE. INSTALL ON EACH UNIT OF EQUIPMENT. THIS
<br />INCLUDES POWER, LIGHTING AND ALL SYSTEMS.
<br />USE THE FOLLOWING COLORS FOR SERVICE, FEEDERS AND BRANCH CIRCUITS:
<br />1. 120/208V. PHASE A. BLACK. PHASE B: RED. PHASE C: BLUE.
<br />15. TVSS UNITS SHALL BE OF THE MODULAR DESIGN TYPE WITH FUSES RATED AT
<br />80 KAIC, RED AND GREEN LED'S FOR POWER AND PROTECTION STATUS.
<br />UL1449 CLAMPING VOLTAGE FOR WYE CIRCUITS AS FOLLOWS:
<br />LINE TO NEUTRAL: 40OV.
<br />LINE TO GROUND: 40OV.
<br />NEUTRAL TO GROUND: 40OV.
<br />16. TEMPORARY ELECTRICAL SERVICE:
<br />COST OR USE CHARGES FOR TEMPORARY FACILITIES ARE NOT CHARGEABLE TO
<br />THE OWNER, ARCHITECT OR ENGINEER.
<br />PROVIDE RECEPTACLE OUTLETS ADEQUATE FOR CONNECTION OF POWER TOOLS
<br />AND EQUIPMENT.
<br />PROVIDE TEMPORARY LIGHTING WITH LOCAL SWITCHING THAT PROVIDES ADEQUATE
<br />ILLUMINATION FOR CONSTRUCTION OPERATION AND TRAFFIC CONDITIONS.
<br />GENERAL PROJECT NOTES
<br />REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL PROJECT REQUIREMENTS.
<br />6014HammockHaAve
<br />Lthia'a 33547
<br />FWW Soma of PlOaftial En*mm - Umm / UM
<br />Qaooe �a Ewo cciallo. MIC. Au MWI MUM
<br />O#Ice:813.394.1638
<br />Fa:c813-651.9721
<br />All Alm m mYFD
<br />REVISIONS
<br />Q8-13-08
<br />•00
<br />�00
<br />6
<br />5�
<br />a�
<br />0
<br />O
<br />C) W
<br />F�
<br />1--1 1.4
<br />E
<br />A
<br />11-1
<br />W
<br />E-4 A
<br />H
<br />W
<br />w
<br />o
<br />N
<br />r�
<br />�o
<br />.. I
<br />00
<br />~I co
<br />M
<br />0&
<br />N�
<br />1�+-"I co
<br />0o
<br />to
<br />M
<br />wM
<br />E-� U-
<br />J
<br />W
<br />�z
<br />�w
<br />z
<br />LLJ
<br />� a
<br />A N
<br />DAI`
<br />11 /7/07
<br />scmL.
<br />AS NOTED
<br />im No- 27013
<br />SHM
<br />Eml
<br />ov
<br />
|