5PEG I E I GAT I ON5
<br />I.
<br />ALL WORK SHALL BE IN STRICT AGGORDANGE WITH THE LATEST EDITION OF N.E.G.
<br />AND ALL LOCAL CODES AND ORDINANCES.
<br />L
<br />2.
<br />ALL MATERIALS SHALL BE NEW AND OF DOMESTIC ORIGIN AND SHALL BEAR
<br />UNDERWRITERS' LABEL WHERE APPLICABLE.
<br />E
<br />3.
<br />ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN
<br />G
<br />A FIRST -GLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM 15 TO BE FULLY
<br />OPERABLE AND ACCEPTANCE OF THIS SYSTEM BY THE EN&INEER/ARCHITECT
<br />'T'
<br />MUST BE A CONDITION OF THE SUB CONTRACT.
<br />7
<br />4.
<br />ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE
<br />WITH THE PROGRESS OF CONSTRUCTION.
<br />5.
<br />CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM
<br />G
<br />DEFECTS FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF
<br />ACCEPTANCE.
<br />A
<br />6.
<br />CORRECTION OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL CHARGE
<br />L
<br />AND TO INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE
<br />INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY.
<br />1. ALL REQUIRED INSURANCE TO BE PROVIDED FOR PROTECTION AGAIN5T PUBLIC
<br />LIABILITY OF PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
<br />5. CONTRACTOR TO PAY FOR ALL PERMITS, FEES, INSPECTIONS AND TESTING.
<br />q. ELECTRICAL INSTALLATION TO MEET ALL STANDARD REQUIREMENTS OF LOCAL
<br />POWER AND TELEPHONE COMPANIES.
<br />10. MINIMUM WIRE SIZE SHALL BE #12 AWG, EXCLUDING CONTROL WIRING. UNLE55
<br />OTHERWISE NOTED, ALL CONDUCTORS SHALL BE COPPER WITH THWN/THHN
<br />INSULATION. CONDUCTORS #12 AND SMALLER MAY BE SOLID; ALL THOSE #10
<br />AND LARGER TO BE STRANDED.
<br />II. ALL UNDERGROUND RACEWAYS SHALL BE GALVANIZED RIGID STEEL CONDUIT
<br />OR SCHEDULE 40 PVC. ALL OTHER RACEWAYS TO COMPLY WITH 6OVERNING
<br />CODES. MINIMUM CONDUIT UNDERGROUND SHALL BE 3/4" CONDUIT U.O.N.
<br />12. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH
<br />THREADED HUBS IN WET OR DAMP LOCATIONS, AND BE OF SPECIAL
<br />CONSTRUCTION FOR OTHER CLASSIFIED AREAS. ALL BOXES SHALL BE RECESSED
<br />(FLUSH) IN 14A1_1_5 OR CEILINGS WHENEVER POSSIBLE.
<br />13. DISCONNECT SWITCHES SHALL BE H.P. RATED, GENERAL DUTY, QUICK -MAKE,
<br />QUICK -BREAK TYPE. ENCLOSURES SHALL BE AS REQUIRED BY N.E.G. AND
<br />LOCATION (WEATHERPROOF, EXPLOSION PROOF, ETC).
<br />14. ALL GENERAL PURPOSE SWITCHES AND RECEPTACLES SHALL BE THE PRODUCT OF
<br />A SINGLE MANUFACTURER. COLOR OF DEVICES AND PLATES SHALL BE DICTATED
<br />BY ARCHITECT/OWNER TO MATCH BUILDING STANDARD.
<br />A. SWITCHES: BUILDING STANDARD
<br />B. RECEPTACLES: BUILDING STANDARD
<br />G. COVER PLATES: BUILDING STANDARD
<br />NOTE: ALL OTHER REQUIRED DEVICES SHALL MATCH IN COLOR AND STYLE.
<br />15. ALL RACEWAY5 AND PIPES SPACED IN OR THROUGH ANY CONCRETE SLAB SHALL
<br />BE SPACED A MINIMUM OF THREE TIMES THE DIAMETER OF THE LARGEST
<br />RACEWAY.
<br />16. IT 15 NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF
<br />CON5TRUGTJON. THE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL
<br />ITEMS FORA COMPLETE ELECTRICAL SYSTEM, AND PROVIDE ALL NECESSARY
<br />DEVICES AND COMPONENTS FOR EQUIPMENT TO BE PLACED IN PROPER WORKING
<br />ORDER.
<br />11. ALL ELECTRICAL RACEWAYS (METALLIC, AND NON-METALLIC) SHALL HAVE AN
<br />EQUIPMENT GROUND CONDUCTOR 51ZED IN ACCORDANCE WITH THE LATEST
<br />EDITION OF THE N.E.G.
<br />15. LOAD DATA 15 BASED ON INFORMATION GIVEN ENGINEER AT THE TIME OF
<br />DESIGN. VERIFY ALL EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING.
<br />Iq. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES.
<br />THE CONTRACTOR 15 TO PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT
<br />JOB CONDITIONS.
<br />20. CONDUIT SYSTEM REQUIREMENTS:
<br />ABOVE FIN15H FLOOR, CEILIN65 ETC... (INDOOR) - EMT WITH DIEGA5T SET 50REW
<br />FITTINGS.
<br />GALVANIZED RIGID CONDUITS - ABOVE GRADE AND WHERE SUSCEPTIBLE TO
<br />PHYSICAL DAMAGE.
<br />FLEXIBLE CONDUITS - INDOOR, ONLY SHORT RUNS NOT TO EXCEED 6'-O".
<br />SEAL TITE - OUTDOOR, ONLY SHORT RUNS NOT TO EXCEED 6-O".
<br />21. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY
<br />22• CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL CONDUIT PENETRATIONS
<br />MADE THROUGH FIRE RATED WALLS, CEILINGS, SLABS, ETC. PENETRATION SEALS
<br />SHALL BE PER U.L. A55EM13LY STANDARDS.
<br />23. CONTRACTOR SHALL PROVIDE SHOP DRAWING SUBMITTALS FOR (IF APPLICABLE)
<br />WIRING DEVICES, AND ALL SYSTEMS.
<br />24. TYPE 'MC' GABLE SHALL ONLY BE ALLOWED WHERE APPROVED BY OWNER'S
<br />REPRESENTATIVE AND ACCEPTED BY LOCAL AUTHORITY HAVING JURISDICTION.
<br />HOWEVER, HOMERUNS SHALL REMAIN IN CONDUITS. 'MG' GABLE USED SHALL BE
<br />TYPE 'HCF', APPROVED FOR HEALTHCARE FACILITIES FOR COMPLIANCE WITH
<br />N.E.G. 51-7-13(a) I (b) - REDUNDANT GROUNDS.
<br />L"EC END
<br />E
<br />MOUNTING HEIGHTS SHOWN ARE MAXAM/MINIMUM
<br />NOT ALL DEVICES SHOWN IN LEGEND ARE REQUIRED.
<br />HANDICAPPED ACCESSIBILITY 5TANDARM - THEY SHALL
<br />REVIEW POWER AND LIGHTING PLANS AND DETAILS
<br />L
<br />NOY
<br />BE ALTERED WITHOUT WRITTEN AUfiHORIZATION.
<br />FOR ITEMS WHICH APPLY TO TH15 PROJECT.
<br />1--� FLUORESCENT LIGHT FIXTURE, LETTER INDICATES TYPE
<br />®
<br />MAIN DISTRIBUTION PANEL
<br />G
<br />QB
<br />RECESSED LIGHT FIXTURE, LETTER INDICATES TYPE
<br />O
<br />SPECIAL NOTES, SEE PLANS
<br />T
<br />I o
<br />WALL BRACKET L16HT FIXTURE, LETTER INDICATES TYPE
<br />CONDUIT CONGEALED IN WALL OR ABOVE CEILIN6 WITH CO VXTOR5
<br />0 LIGHT FIXTURE UNSWITGHED FOR NIGHT LIGHT MLJ
<br />/ \
<br />AS SHOWN ON PANEL SCHEDULE. U.OK
<br />CONDUIT CONGEAL® BELOW FLOOR SLAB OR FINISHED GRADE WITH
<br />EXIT L16W (ARROW INDICATES DIRECTION)
<br />CONDUCTORS AS SHOWN ON PANEL SCHEDULE U.ON.
<br />BATTERY POWERED EMERGENCY LIGHT
<br />CONDUIT EXPOSED ON WALL OR CEILING WITH CONDUCTORS AS SHOWN
<br />ON PANEL SCHEDULE. U.OX
<br />5
<br />SINGLE POLE SWITCH
<br />�
<br />FLEXIBLE CONDUIT NOT TO EXCEED 6 FEET IN LENGTH
<br />A
<br />52
<br />DOUBLE POLE SWITCH, MOUNT 46" A.F.F. UDN.
<br />5s
<br />THREI=-WAY SWITCH, MOUNT 46" A.FF. U.a.N.
<br />O
<br />WIREMOLD (SIZE AND LENGTH AS NOTED)
<br />TELEVISION OUTLET, PROVIDE SINGLE 6AN6 BOX WITH 3/4" CONDUIT
<br />S°
<br />DIMMER SWITCH, WATTS AS NOTED, MOUNT 46" AF.F. U.ON
<br />Fig
<br />WITH RILL WIRE AND INSULATINS BUSHING 5TUBBED INTO CEILING
<br />SPACE. MOUNT BOX 161 A.F.F. U.ON.
<br />S"
<br />MOTOR RATED SWITCH
<br />4=1
<br />DISCONNECT SWITCH
<br />DUPLEX RECEPTACLE, MOUNT 18" A.F.F. U.O.N.
<br />DUPLEX REGEPTAGLE, MOUNT ABOVE COUNTER HEIGHT U.ON
<br />100/3/80
<br />DISCONNECT DES16HATM (SIZE/POLES/FUSE) "NF" INDICATES
<br />NON -FUSED; DE INDICATES DUAL ELEMENT FUSES.
<br />QUADRAPLEX RECEPTACLE, MOUNT 160 A.F.F. U.ON.
<br />❑T
<br />DRY TYPE TRANSFORMER
<br />F�
<br />SPECIAL RECEPTACLE AS NOTED
<br />p
<br />CONTACTOR 06 NOTED)
<br />�eFl
<br />GROUND FAULT INTERRUPTER RECEPTACLE, LEMTON t► Mb-I, MOUNT
<br />roc
<br />TIME CLOCK
<br />ABOVE COUNTER HE16HT U.O.N.
<br />PK.
<br />PHOTOCELL
<br />1a
<br />DUPLEX RECEPTACLE, ISOLATED 6ROUW TYPE, LEVITON e5%2-I61
<br />MOUNT AT IS" A.FF. U.O.N.
<br />MOTOR PERMANENTLY C44244MTED WITH FLEXIBLE CONDUIT
<br />L1644TIN6 OR POWER PANELBOARD
<br />[�
<br />PUSHBUTTON, MOUNT 46" A.F.F. U.ON.
<br />TELEPHONE OR DATA WALL OUTLET, PROVIDE SINGLE 6AN6 BOX
<br />WITH 3/4" CONDUIT WITH PULL WIRE AND INSULATINS BUSHING
<br />JQ
<br />UNCTION BOX (FLUSH MOUNT IN FINISHED AREAS U.ONJ
<br />STUBBED INTO CEILING SPACE. MOUNT BOX 16" AFF. U.O.N.
<br />COMBINATION TELE/DATA OUTLET, PROVIDE DOUBLE GANG BOX WITH
<br />W
<br />TELEPHONE WALL OUTLET, PROVIDE SINGLE GANG BOX WITH 3/4'
<br />Q
<br />SINGLE GANG MUD RING AND (2) 9/4" CONDUITS WITH PULL WIRE AND
<br />CONDUIT WITH PULL WIRE AND INSULATINS BUSHINS STUBBED INTO
<br />INSULATIN & BUSHING STUBBED INTO CEILING SPADE. MOUNT BOX
<br />GEILINS SPACE. MOUNT BOX 46" A.F.F. U.ON. ("W' INDICATES
<br />AT 16" A.F.F. U.O.N.
<br />WALL PHONE)
<br />E.6.
<br />ABBREVIATIONS
<br />EQUIPMENT GROUND EWG ELECTRIC, WATER COOLER
<br />N.L.
<br />N1644T LIGHT UDN. UNLESS OTHERWISE NOTED
<br />Le.
<br />ISOLATED GROUND E/F-EF EXHAUST FAN
<br />EX.
<br />EXISTINS DEVICE N.T.S. NOT TO SCALE
<br />WP
<br />WEATHERPROOF AM-AHU AIR HANDLING UNIT
<br />A.FF.
<br />ABOVE FINISH FLOOR N.I.G. NOT IN CONTRACT
<br />RTU
<br />ROOF TOP UNIT ACG-GU CONDENSINS UNIT
<br />NOTE: MOUNTING HEIGHTS NOTED ARE TO CENTERLINE OF DEVICE SHOWN. U.O.N.
<br />NORTH
<br />KEY PLAN
<br />SCALE: I"=10'-O"
<br />CHEHAYEB & ASSOCIATES, INC.
<br />CONSULTING PROFESSIONAL ENGINEERS
<br />CTS
<br />3702 AZEELE ST. (813) 876-f4f5
<br />TAMPA, FL 33609 (fax) 876-0913
<br />LIC. #49521 SOUHEIL CHEHAYEB CERT. #7340
<br />08-127
<br />NOTE5
<br />G
<br />O
<br />IT 15 THE CONTRACTOR'S RESPONSIBILITY TO REVIEW ALL DRAWINGS AND
<br />SPECIFICATIONS, INCLUDING BUT NOT LIMITED TO ARCHITECTURAL, CIVIL,
<br />N
<br />STRUCTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL PRIOR TO SUBMITTING
<br />A BID. REPORT ANY D15CREPANCIE5 TO ARCHITECT OR ENGINEER
<br />T
<br />PRIOR TO BID.
<br />BIDDERS ARE TO V151T THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING
<br />CONDITIONS AND SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF
<br />/�
<br />A
<br />THE WORK. THE SUBMISSION OF A BID WILL BE EVIDENCE THAT SUCH AN
<br />EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT, OR
<br />r
<br />MATERIALS REQUIRED, OR FOR ANY DIFFICULTIES ENCOUNTERED WHICH COULD
<br />`i
<br />HAVE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE, WILL NOT BE
<br />T
<br />ALLOWED.
<br />IT 15 THE RESPONSIBILITY OF THE CONTRACTOR TO NOTIFY THE ARCHITECT
<br />O
<br />OF ANY DISCREPANCIES ENCOUNTERED ON THE PLANS OR IN EXISTING
<br />R
<br />51TE CONDITIONS PRIOR TO SUBMISSION OF BID.
<br />ALL EXISTING CIRCUITS TO REMAIN SHALL BE RECONNECTED WHETHER
<br />INDICATED OR NOT ON PROJECT DOCUMENTS.
<br />NEW AND EXISTING CIRCUIT DESIGNATIONS MAY NOT REPRESENT ACTUAL
<br />FIELD CONDITIONS. THEY ARE INTENDED FOR REFERENCE ONLY.
<br />CONTRACTOR SHALL COORDINATE WITH OTHER TRADES IN REGARDS TO
<br />THEIR SCOPE OF WORK WHICH WILL REQUIRE ELECTRICAL WORK SUCH AS
<br />015CONNECTION AND/OR RECONNECTION OF EQUIPMENT, AND WHICH MAY
<br />NOT BE SHOWN OR INDICATED ON THE DRAWINGS.
<br />THESE NOTES APPLY TO ALL SHEETS.
<br />No. I Date
<br />- EXISTING SERVICE WIREWAY
<br />AND DISCONNECTS
<br />- EXISTING
<br />METER
<br />AREA OF RENOVATION
<br />(THIS PROJECT)
<br />REVISIONS
<br />N3A
<br />100F_
<br />r..
<br />6
<br />zLO
<br />n
<br />N
<br />Q w o
<br />U¢o�
<br />_D
<br />CIS V)
<br />.. � mo
<br />LiJ � T
<br />WU)z�
<br />:n E
<br />�LLJz=°'8
<br />r Q 7 9 c) c :k
<br />Q r-
<br />o~E
<br />Q LL v:
<br />= 0 CO
<br /><V1
<br />r/ n� ,
<br />~_ C!) bCc—
<br />_D<QHW i
<br />Issued for:
<br />Date:
<br />❑ PRELIMINARY
<br />❑ PRICING
<br />❑ BIDDING
<br />■ PERMIT
<br />is-olLos
<br />❑ CONSTRUCTION
<br />2
<br />en
<br />z°
<br />�
<br />Q
<br />h '
<br />a
<br />LLI
<br />F
<br />h
<br />tJ5
<br />O
<br />z
<br />CT3
<br />r L.
<br />ui
<br />U
<br />--�ILL
<br />_Q
<br />Z
<br />W
<br />o
<br />U
<br />A
<br />f]
<br />00
<br />M
<br />R•
<br />SOUR
<br />L c-i;AI't g, P.E.
<br />ft
<br />C. Ni 49521
<br />t Drawn by: P.M. Checked by: S.C. J