Laserfiche WebLink
NOTE5 <br />P 1. ALL WORK SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL <br />CODE AND SHALL AL50 COMPLY WITH ALL APPLICABLE RULES AND <br />R REGULATIONS OF LOCAL AND STATE LAWS AND ORDINANCES. <br />0 2. ALL CONDUGTOR5 SHALL BE STRANDED COPPER, CONDUCTOR <br />J INSULATION SHALL BE TYPE THHN THERMOPLASTIC <br />600 VOLT OR EQUAL U.O.N. <br />E 3. THE INTERIOR ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND <br />EFFECTIVELY GROUNDED AS REQUIRED BY THE NEC. ALL METALLIC, <br />G RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY SECURE AT <br />ALL JOINTS AND AT ALL BOXES, CABINETS, FITTINGS AND EQUIPMENT. <br />T METALLIC, RACEWAY5 SHALL BE CONNECTED TO A DIRECT GROUND <br />AT THE POINT OF ELECTRICAL SERVICE ENTRANCE. <br />4. UPON COMPLETION OF WORK CORRECT ALL PANELBOARO CIRCUIT <br />DIRECTORY CARDS TO REFLECT A5-BUILT CONDITIONS. A SET OF <br />A5-BUILT DRAWIN655 SHALL AL50 BE PREPARED AND TURNED OVER <br />TO THE ARCHITECT. <br />5. ALL RACEWAYS SHALL BE PROVIDED WITH EQUIPMENT GROUND <br />CONDUCTOR. <br />6. CONTRACTOR SHALL FIELD VERIFY RECEPTACLE CONFIGURATION, <br />VOLTAGE, PHASE AND AMPERAGE FOR ALL REQUIRED OUTLETS. <br />PROVIDE DEDICATED CIRCUITS AS REQUIRED. ADV15E ENGINEER <br />IF NECESSARY. <br />-1. CONTRACTOR SHALL SUPPLY AND INSTALL ALL JUNCTION BOXES, <br />TROU6HS, WIRE, CIRCUIT BREAKERS, WIRE, ETC., UNLESS OTHERWISE <br />SPECIFIED. <br />8. CONDUIT RUNS ARE SHOWN SCHEMATICALLY. BUILDING CONDITIONS TO <br />DETERMINE THE ACTUAL RUNS. <br />4. CONDUIT ELBOWS TO BE LARGE SWEEPS PER NEC, 346-10. <br />10. CONTRACTOR SHALL PROVIDE AND COIL A MINIMUM 10'-0 INCH OF <br />SLACK CONDUCTOR FOR CONNECTION TO EQUIPMENT BY OTHERS. <br />IDENTIFY BOTH ENDS OF WIRE. <br />11. CONTRACTOR SHALL OBTAIN A COPY OF THE BrainLAB INSTALLATION <br />AND 51TINO DRAWING5 PRIOR TO START OF CONSTRUCTION AND <br />COMPLY ACCORDINGLY. <br />12. ALL TELEPHONE/DATA JACKS AND COMMUNICATION CABLING TO BE <br />PROVIDED AND INSTALLED BY OTHERS. ELECTRICAL CONTRACTOR TO <br />PROVIDE AND INSTALL ALL ASSOCIATED OUTLET BOXES AND CONDUITS. <br />13. CONDUITS AND DUCT, ABOVE CEILING OR BELOW FINISHED FLOOR, MUST <br />BE INSTALLED PER BrainLAB DRAWINGS TO REDUCE RUN LENGTH. <br />14. THESE DRAWINGS ARE DIAGRAMMATIC AND INTENDED ONLY TO SHOW <br />THE SCOPE OF WORK TO BE DONE. THE ELECTRICAL CONTRACTOR <br />SHALL BE RESPONSIBLE TO FIELD VERIFY THE SUITABILITY OF LOCATING <br />ALL NEW CONDUIT SHOWN ON THE PLANS OR IDENTIFIED IN THE NOTES. <br />CONTRACTOR NOTICE <br />I. THESE ELECTRICAL DRAWINGS HAVE BEEN DESIGNED WITH AND SHALL <br />BE BID IN CONJUNCTION WITH THE BratnLAB INSTALLATION AND SITING <br />DRAWING SET. SUBMISSION OF AN ELECTRICAL BID WILL BE CONSIDERED <br />AS EVIDENCE THAT THE BrainLAB DRAWINGS WERE REVIEWED AND THAT <br />ALL INFORMATION SHOWN HAS BEEN INCLUDED IN THE BID. LATER CLAIMS <br />FOR ADDITIONAL COMPENSATION FOR WORK DESCRIBED ON EITHER <br />SET OF DRAWING-5 SHALL NOT BE ACCEPTED. CONTRACTOR SHALL <br />REVIEW G.E. DRAWINGS FOR REQUIRED USE OF ALUMINUM CONDUIT <br />IN SPECIFIC LOCATIONS. <br />2. ELECTRICAL DRA"IN65 INDICATE THE INSTALLATION CONCEPT FOR THE <br />BratnLAB EQUIPMENT. HOWEVER, CONTRACTOR SHALL OBTAIN AND BID <br />EQUIPMENT INSTALLATION WITH BrainLAB INSTALLATION AND 51TIN6 <br />DRAWIN65 WHICH INDICATE ADDITIONAL REQUIREMENT5 NECESSARY <br />FOR PROPER INSTALLATION. ALL DEVICES, EQUIPMENT, APPARATUS, ETC'. <br />USED WITHIN THE ROOM MUST BE APPROVED BY THE BrainLAB PROJECT <br />MANAGER PRIOR TO INSTALLATION. <br />3. CONTRACTOR SHALL REFER TO INTERIOR ARCHITECTURAL DRAWINGS FOR <br />EXACT MOUNTING HEIGHTS AND/OR LOCATIONS OF ALL OUTLETS AND <br />WIRING DEVICES. <br />NOTE5 <br />K <br />O CONTROL ROOM POWER BOX, FURNISHED WITH BraInLAB EQUIPMENT, <br />INSTALLED BELOW COUNTER BY ELECTRICAL CONTRACTOR. <br />Y X-RAY TUBE FLOOR BOX, FURNISHED WITH BrafnLAB EQUIPMENT, <br />INSTALLED BY GENERAL CONTRACTOR. <br />�3 PROVIDE 2+00MPARTMENt 10 x3-1/2 HORIZONTAL SURFACE WALL <br />DUCT AT 12" A.F.F. TO TOP. VERIFY REQUIRED LENGTH, PROVIDE <br />ALL NECESSARY FITTIN65 AND SUPPORTS. PROVIDE 6ROMMETED <br />OPENINC75 AS DIRECTED BY EQUIPMENT SUPPLIER/INSTALLER. <br />�4 IN -ROOM POWER BOX, FURNISHED WITH BratnLAB EQUIPMENT, <br />INSTALLED ABOVE CEILING BY ELECTRICAL CONTRACTOR. <br />PROVIDE ALL NECESSARY SUPPORTS. <br />(1) 4" CONDUIT FROM XRAY TUBE FLOOR BOX, RUN BELOW SLAB, <br />AND TURNED UP BELOW HORIZONTAL WALL DUCT. <br />U6 VERIFY FOR REQUIRED TRANSITION FROM CONDUIT TO WALL DUCT <br />AND PROVIDE ACCORDINGLY. <br />O PROVIDE I" CONDUIT ("IRE) FROM EXISTING WARNING LIGHT BACK <br />TO COMPUTER CABINET. MAKE ALL REQUIRED TERMINATIONS. <br />® PROVIDE A 100 AMP, 3-POLE, NON -FUSED DISCONNECT SWITCH <br />FOR CONNECTION TO X-RAY GENERATOR. MAKE ALL REQUIRED <br />TERMINATIONS. <br />® (1) 3" CONDUIT (EMPTY W/PULLWIRE) FROM GENERATOR CABINET <br />TO CONTROL ROOM. VERIFY TERMINATIONS AT EACH END PRIOR <br />TO ROUGH -IN AND PROVIDE ACCORDINGLY. <br />10 (1) 2" CONDUIT (EMPTY W/PULLWIRE) FROM COMPUTER CABINET TO <br />CONTROL ROOM POWER BOX. <br />II GANTRY COUGH MOUNTED INTERFACE ELECTRONIC, (BY OTHERS). <br />12 (1) 2" CONDUIT (EMPTY W/PULLWIRE) FROM IN -ROOM POWER <br />BOX TO CEILING WORKSPACE. VERIFY TERMINATIONS. <br />13 (1) 1" CONDUIT (EMPTY W/PULLWIRE) FROM IN -ROOM POWER BOX TO <br />FLAT PANEL DETECTORS. VERIFY TERMINATIONS. <br />14 (1) 1" CONDUIT (EMPTY W/PULLWIRE) FROM IN -ROOM POWER BOX TO <br />CAMERA SYSTEM. VERIFY TERMINATIONS. <br />15 (1) 3 CONDUIT (EMPTY W/PULLWIRE) FROM COMPUTER CABINET TO <br />IN -ROOM POWER BOX. <br />I6 PROVIDE A 30 AMP, I -POLE, NON -FUSED D15CONNEGT SWITCH FOR <br />CONNECTION TO COMPUTER CABINET. MAKE ALL REQUIRED <br />TERMINATIONS. <br />17 (1) 2 CONDUIT (EMPTY W/PULLWIRE) FROM COMPUTER CABINET TO <br />GANTRY INTERFACE. <br />18 (1) 2" CONDUIT (EMPTY W/PULLWIRE) FROM COMPUTER CABINET TO <br />CAMERA SYSTEM ABOVE CEILING. <br />Iq (1) 3" CONDUIT (EMPTY W/PULLWIRE) FROM COMPUTER CABINET TO <br />FLAT PANEL DETECTORS ABOVE CEILING. <br />COORDINATE WITH EQUIPMENT SUPPLIEPANSTALLER FOR CONDUIT <br />TERMINATION REQUIREMENTS AT THE COMPUTER CABINET AND <br />COMPLY ACCORDINGLY. <br />21 EXISTING EMERGENCY -OFF PUSHBUTTON FOR ACCELERATOR. <br />CONTRACTOR SHALL USE SAME DEVICE TO ACTIVATE THE SHUNT - <br />TRIP FOR BrainLAB MAIN BREAKER IN PANEL 'A', FOR SIMULTANE <br />SHUT DOWN OF EQUIPMENT. <br />5Y5-rr=M &ROUND I NC NOTE5 <br />THE PROPOSED BrainLAB SYSTEM REQUIRES CONNECTION TO GROUND AT <br />A SINGLE POINT. TH15 POINT WILL BE ON THE WALL A5 A MAIN GROUND BUS BAR <br />AND 15 THE POTENTIAL EQUALIZATION POINT. COORDINATE LOCATION OF POTENTIAL <br />EQUALIZATION MAIN BUS BAR WITH EQUIPMENT SUPPLIER / INSTALLER. <br />I. ALL METAL DEVICES, INCLUDING METAL SURFACES OF FIXED MEDICAL EQUIPMENT, <br />WITHIN THE TREATMENT ROOM SHALL BE BONDED TO THE POTENTIAL EQUALIZATION <br />GROUND BUS BAR AS INDICATED BELOW. ITEMS SHALL INCLUDE, BUT NOT LIMITED TO: <br />a. X-RAY GENERATOR TO MAIN PEG BU5 BAR. <br />b. BOTH FLOOR BOXES TO X-RAY GENERATOR PEG BUS BAR. <br />c. BOTH FLAT PANEL -CEILING MOUNTS TO IN -ROOM DISTRIBUTION BOX PEG BUS BAR. <br />d. CAMERA CEILING MOUNT TO IN -ROOM DISTRIBUTION BOX PEG BUS BAR. <br />a. TOUGH 5GREEN CEILING FRAME TO IN -ROOM DISTRIBUTION BOX PEG BU5 BAR. <br />F. IN -ROOM DISTRIBUTION BOX PEG BUS BAR TO MAIN PEG BU5 BAR. <br />g. IN -ROOM DISTRIBUTION BOX PEG BUS BAR TO COMPUTER CABINET PEG BU5 BAR. <br />h. COMPUTER CABINET PEG BUS BAR TO MAIN PEG BUS BAR. <br />i. CONTROL ROOM DISTRIBUTION BOX TO COMPUTER CABINET PEG BUS BAR. <br />BOTH FLOOR BOXES TO MAIN PEQ BU5 BAR. <br />MAIN PEQ BUS BAR TO PATIENT COUGH, TABLE, LINAG FRAME. <br />2. VERIFY WITH EQUIPMENT SUPPLIER/I145TALLER FOR ALL REQUIRED GROUNDING <br />LOCATIONS AND PROVIDE ACCORDINGLY. <br />3. DEDICATED EARTH CONDUCTOR (GROUND) SHALL BE SAME 51ZE AS POWER WIRE5 <br />AT ALL TIMES FOR ALL ROUTINGS FROM GROUNDED NEUTRAL SOURCE TO BrainLAB <br />EQUIPMENT. <br />4. CONTRACTOR SHALL REFER TO 'ELECTRICAL SAFETY / EQUIPOTENTIAL GROUNDING' <br />SECTION 3.4 OF THE 51TE PREPARATION MANUAL FOR ALL REQUIRED TERMINATIONS <br />AND PROVIDE ACCORDINGLY. <br />PEQ = POTENTIAL EQUALIZATION BUS BAR. <br />GENERAL NOTE: <br />EQUIPMENT LAYOUT AND NOTES ARE BASED UPON GENERAL INFORMATION <br />GIVEN TO THE ENGINEER AT TIME OF DESIGN. THE GENERAL CONTRACTOR <br />SHALL COORDINATE ALL CONDUIT REQUIREMENTS, ALL CABLING LENGTHS <br />AND EQUIPMENT LAYOUT OF ACTUAL EQUIPMENT FURNISHED WITH BrainLAB <br />AUTHORIZED REPRESENTATIVE PRIOR TO CONSTRUCTION. <br />ELECTRICAL CONTRACTOR SHALL COORDINATE CLOSELY WITH <br />BrainLAB REPRESENTATIVE FOR CLARIFICATION OF GABLES AND <br />EQUIPMENT TO BE: <br />a) SUPPLIED/INSTALLED BY BrainLAB <br />b) SUPPLIED/INSTALLED BY CONTRACTOR <br />c) SUPPLIED BY BrainLAB / INSTALLED BY CONTRACTOR <br />d) AVAILABLE THROUGH BrainLAB / INSTALLED BY CONTRACTOR <br />CRITICAL NOTE <br />CONTRACTOR MUST COORDINATE THESE ELECTRICAL <br />DRAWINGS WITH BrainLAB INSTALLATION DRAWING-5 FOR <br />REFERENCE TO ADDITIONAL ELECTRICAL DETAILS AND <br />NOTES AND PROVIDE ACCORDINGLY. <br />CHEHAYEB & ASSOCIATES, INC. <br />CONSULTING PROFESSIONAL ENGINEERS <br />cTs <br />3702 AZEELE ST. (813) 876-1415 <br />` TAMPA, FL 33609 (fax) 876-0913 <br />LIC. #49521 SOUHEIL CHEHAYEB CERT. #7340 <br />08-127 <br />BrainLAB <br />COMPUTER <br />CABINET <br />A -I <br />��POWER AND <br />CONDUIT PLAN, <br />SCALE: 1/4" = 1'-0" <br />CONDUIT AND WIRE SYSTEMS WITHIN TH15 ROOM <br />SHALL COMPLY WITH REQUIREMENTS FOR <br />REDUNDANT GROUNDING PER N.E.G. ARTICLE <br />4i <br />I REVISIONS I <br />No. I Date Description <br />MIN <br />u <br />N <br />cq <br />W N <br />o o' <br />00 <br />U <br />0O <br />C*l zN <br />z Q <br />N <br />M <br />d00 <br />H 00 <br />Oro O • . <br />u in p <br />W a <br />a <br />Issued for: <br />Dater <br />❑ PRELIMINARY <br />❑ PRICING <br />❑ BIDDING <br />■ PERMIT <br />i0-oi-oa <br />❑ CONSTRUCTION <br />R <br />EIL PHAYEB, P.E. <br />LIC NIP. 49521 <br />55 <br />i <br />-- <br />I Drawn by: P.M. Checked by: S.C. J <br />