<br />PART 3 EXECUTION
<br />3.01 GENERAL
<br />A. Install Products in accordance with manufacturer's instructions.
<br />B. Mechanical connections shall be accessible for inspection and checking. No insulation shall be installed over
<br />mechanical ground connections.
<br />C. Attach grounds permanently before permanent building service is energized.
<br />D. Install rod electrodes at "non -trip -hazard" locations indicated or as required by Code, whichever requires
<br />the most rods. Install additional rod electrodes as required to achieve specified resistance to ground.
<br />E. Provide bonding to meet NEC Requirements, including but not limited to bonding between telephone,
<br />television, and security systems.
<br />F. Coordinate with general contractor to insure at least (2) column anchor bolts are tied to footing steel rebar at
<br />column nearest electrical service using the usual steel tie wires.
<br />3.02 FIELD QUALITY CONTROL
<br />A. Inspect grounding and bonding system conductors and connections for tightness and proper installation.
<br />B. Measure ground resistance from system grounding electrode connection at service entrance (neutral -ground
<br />bond removed) to earth ground reference point using suitable ground testing equipment. Resistance shall
<br />not exceed 25 ohms.
<br />***END OF SECTION***
<br />SECTION 16426
<br />DISTRIBUTION EQUIPMENT
<br />PART 1 - GENERAL
<br />1.01 WORK INCLUDED
<br />A. Standard and custom products equivalent to Square D, NQOD, NF, I -Line panelboards, and QMB
<br />switchboards, as well as safety switches, contactors, and starters. Cutler Hammer, Siemens, and GE are
<br />acceptable manufacturers.
<br />PART 2 - PRODUCTS
<br />2.01 MATERIALS
<br />A. All distribution gear shall be fully bussed and fingered for all pole positions numbered on schedules.
<br />B. All distribution gear shall have a ground bus.
<br />C. For 4-wire systems, the neutral bus shall be the equivalent ampacity as the phase bus bars.
<br />D. Provide mechanically fastened permanent plastic nametag with 1/4"H letters indicating name of each
<br />switchboard, panelboard, and transformer as well as a permanent plastic nametag indicating each load fed
<br />for each switchboard.
<br />E. All panelboards and switchboards shall use bolt -on circuit breaker overcurrent devices.
<br />F. Provide circuit breakers UL listed as Type HACR for air conditioning equipment branch circuits.
<br />G. Do not use tandem circuit breakers.
<br />H. Safety switches used for service disconnecting means shall be Heavy Duty,100,000 AIC minimum. All
<br />others may be General Duty.
<br />I. Provide Class L fuses for individual motors, 50 hp and larger; Class J for service mains including tenant
<br />meter disconnects downstream of mains; Class RK5 fuses for all other applications.
<br />J. Refer to panel schedules for ampacities, voltage, phase, NEMA rating, mounting configuration, AIC rating,
<br />and accessories.
<br />K. Lighting contactors shall have 30 amp rated contacts, minimum.
<br />L. Provide a typewritten panel directory for each panelboard or loadcenter with sufficient detail to distinguish
<br />each circuit from all others within the panelboard or loadcenter.
<br />M. Sharing a neutral is permitted for up to three circuits, one per phase, of the same amp rating for 208Y/120V
<br />branch circuits on non -dimmed circuits. Where a shared neutral conductor is used for multiple branch
<br />circuits, contractor shall either group circuits together in panel and provide a manufacturer furnished and
<br />listed handle -tie to simultaneously trip all of the circuits sharing the neutral or provide multi -pole circuit
<br />breakers. Plans may not depict shared neutrals, but they are allowed in accordance with the above
<br />specification.
<br />N. All circuit breakers used for service disconnecting means,1,200 amps and larger, shall have electronic trip
<br />units equivalent to Square D MicroLogic 5.OH (6.OH where GFI is specified). Such breakers shall be
<br />accompanied with a factory installed phase failure relay, Taylor PND-###-T3 or equivalent.
<br />PART 3 - EXECUTION
<br />3.01 INSTALLATION
<br />A. Install panelboards plumb with wall finishes with height 6-6" AFF to top.
<br />B. Provide filler plates for unused spaces in panelboards.
<br />C. Inspect for physical damage, proper alignment, anchorage, and grounding. Check proper installation and
<br />tightness of connections.
<br />D. Rigidly mount disconnects and starters adjacent to load served, maintaining working clearance required by
<br />NEC.
<br />E. Electrical equipment, such as switchboards, panelboards, industrial control panels, meter socket enclosures,
<br />and motor control centers, that are in other than dwelling occupancies, and are likely to require
<br />examination, adjustment, servicing, or maintenance while energized shall be field marked to warn qualified
<br />persons of potential electric arc flash hazards. Provide factory labels to comply.
<br />F. Where the area above the dedicated electrical space above electrical equipment contains systems which
<br />could leak or condensate, provide suitable protection to avoid damage to the electrical equipment.
<br />G. All floor mounted electrical gear is to be installed on 4" tall concrete housekeeping pads.
<br />***END OF SECTION***
<br />SECTION 16500
<br />INTERIOR LIGHTING
<br />PART 1 - GENERAL
<br />1.01 QUALITY ASSURANCE
<br />A. Comply with NEC requirements as applicable to wiring types and lengths for fixture whips. Provide
<br />lighting components and fittings that are UL-listed and labeled.
<br />PART 2 - PRODUCTS
<br />2.01 MATERIALS
<br />A. Lighting fixtures shall be the type indicated on Drawings and as specified. Fixtures of same type shall be of
<br />identical make, design, and appearance. Size of lighting fixtures shall be as specified for the lamp or fixture
<br />wattage indicated on Drawings. Specific manufacturer and model number references are indicated as a
<br />standard of quality and other manufacturers may be supplied provided the product meets or exceeds the
<br />specifications.
<br />B. Ballasts shall comply with applicable state, federal and industry performance safety standards including
<br />FCC requirements governing electromagnetic and radio frequency interference, IEEE standards for line
<br />voltage transient protection and harmonic distortion.
<br />C. When occupancy sensors are controlling fluorescent fixtures, ballasts shall be programmed rapid start.
<br />Instant start is acceptable otherwise.
<br />D. Ballasts shall comply with 2008 NEC 410.130 (G) requirement for integral disconnecting means.
<br />E. Provide lamps with lighting fixtures. Lamps shall be as manufactured by General Electric, Philips, Venture,
<br />or Sylvania.
<br />F. Fluorescent lamps shall be 3,000 lumen minimum, 841, 850 for fluorescent high -bays.
<br />PART 3 - EXECUTION
<br />3.01 INSTALLATION
<br />A. Clean surfaces of dirt, cement, plaster and debris. Furnish cleansers compatible with material surfaces
<br />being cleaned.
<br />B. Replace defective lamps and ballasts.
<br />C. Support recessed fixtures in ceilings as follows: Fixtures shall be independently supported from structure
<br />above using (2) #12 ceiling tie -wires per fixture at diagonal corners.
<br />D. Recessed fixtures shall fit snugly against ceilings to prevent light leakage.
<br />E. Light fixtures and associated wiring shall be installed in accordance with NEC Article 410.
<br />F. Where supported via threaded means, all nuts shall be double nutted with lock -washers.
<br />***END OF SECTION***
<br />SECTION 16741
<br />TELEPHONE AND DATA SYSTEM
<br />PART 1- GENERAL
<br />1.01 QUALITY ASSURANCE
<br />A. Comply with applicable requirements of NEMA and UL standards. Provide products and components that
<br />have been UL listed and labeled.
<br />PART 2 - PRODUCTS
<br />2.01 MATERIALS
<br />A. Outlet boxes shall consist of 4" square deep boxes. Provide minimum 2-1/4" deep boxes unless required
<br />otherwise by field conditions.
<br />B. Provide backboard in telephone equipment rooms consisting of 3/4" deep X 4' wide X 8' high AC plywood
<br />unless noted otherwise on plans.
<br />PART 3 - EXECUTION
<br />3.01 INSTALLATION
<br />A. Provide minimum 1" conduits from outlet boxes to accessible space above ceiling, terminated with bushing.
<br />Where hard ceilings are installed, route conduit to nearest accessible location.
<br />B. Paint both sides of telephone backboards with 2 coats of fire retardant paint prior to installation.
<br />C. Use long sweep rigid 90-degree elbows on telephone service entrance conduits.
<br />D. Provide a ground bar at each telephone backboard location. Provide a #4 Green copper ground from each
<br />ground bar to main telephone systems ground or to building grounding electrode system.
<br />E. Provide a pull string in all conduits.
<br />***END OF SECTION***
<br />ELECTRICAL LEGEND
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />O
<br />CEILING LIGHT FIXTURE.
<br />SEE FIXTURE SCHEDULE.
<br />DUPLEX RECEPTACLE. SEE SPECIFICATIONS.
<br />18" AFF TO CENTERLINE UON.
<br />®
<br />CEILING LIGHT FIXTURE WITH EMERGENCY POWER BACKUP.
<br />SEE FIXTURE SCHEDULE.
<br />DUPLEX RECEPTACLE, ABOVE COUNTER. SEE SPECIFICATIONS.
<br />44" AFF TO CENTERLINE UON.
<br />O—
<br />WALL WASH LIGHT FIXTURE. ARROW INDICATES WASH DIRECTION.
<br />SEE FIXTURE SCHEDULE.
<br />DUPLEX RECEPTACLE, ONE-HALF SWITCHED. SEE SPECIFICATIONS.
<br />18" AFF TO CENTERLINE UON.
<br />4
<br />WALL BRACKET LIGHT FIXTURE.
<br />SEE FIXTURE SCHEDULE.
<br />®
<br />DUPLEX RECEPTACLE, FLOOR OR POKE-THRU. SEE SPECIFICATIONS.
<br />FLUSH IN FLOOR UON.
<br />WALL BRACKET LIGHT FIXTURE WITH EMERGENCY POWER BACKUP.
<br />SEE FIXTURE SCHEDULE.
<br />DOUBLE DUPLEX RECEPTACLE. SEE SPECIFICATIONS.
<br />18" AFF TO CENTERLINE UON.
<br />Q
<br />WALL BRACKET LIGHT FIXTURE.
<br />SEE FIXTURE SCHEDULE.
<br />DOUBLE DUPLEX RECEPTACLE, ABOVE COUNTER. SEE SPECIFICATIONS.
<br />44" AFF TO CENTERLINE UON.
<br />WALL BRACKET LIGHT FIXTURE WITH EMERGENCY POWER BACKUP.
<br />SEE FIXTURE SCHEDULE.
<br />T
<br />SIMPLEX RECEPTACLE. SEE SPECIFICATIONS.
<br />18" AFF TO CENTERLINE UON.
<br />o
<br />WALL MOUNTED SCONCE LIGHT FIXTURE
<br />SEE FIXTURE SCHEDULE.
<br />CLOCK OUTLET
<br />84" AFF TO CENTERLINE UON.
<br />®
<br />WALL MOUNTED SCONCE LIGHT FIXTURE WITH EMERGENCY POWER
<br />BACKUP.
<br />SEE FIXTURE SCHEDULE.
<br />V
<br />SPECIAL RECEPTACLE. NEMA CONFIGURATION AS NOTED.
<br />18" AFF TO CENTERLINE UON.
<br />❑O
<br />1' X 1' LIGHT FIXTURE.
<br />SEE FIXTURE SCHEDULE.
<br />DUPLEX RECEPTACLE MOUNTED FLUSH IN CEILING.
<br />AS NOTED
<br />®
<br />1' X 1' LIGHT FIXTURE WITH EMERGENCY POWER BACKUP.
<br />SEE FIXTURE SCHEDULE.
<br />MULTI -OUTLET SURFACE RACEWAY WITH NEMA 5-15R SIMPLEX
<br />RECEPTACLES AT 12" CENTERS UON.
<br />44" AFF TO CENTERLINE UON.
<br />®
<br />2' X 2' LIGHT FIXTURE.
<br />SEE FIXTURE SCHEDULE.
<br />Iffm—
<br />208Y/120V OR 240/120V PANELBOARD.
<br />78" AFF TO TOP.
<br />®
<br />2' X 2' LIGHT FIXTURE WITH EMERGENCY POWER BACKUP.
<br />SEE FIXTURE SCHEDULE.
<br />1295-
<br />277Y/480V PANELBOARD.
<br />78" AFF TO TOP.
<br />2' X 4' LIGHT FIXTURE.
<br />SEE FIXTURE SCHEDULE.
<br />,0
<br />DISCONNECT SWITCH.
<br />NEMA/AMPS/POLE/FUSE/VOLTAGE. PROVIDE NEMA 1, 600V UON.
<br />AS NOTED.
<br />2' X 4' LIGHT FIXTURE WITH EMERGENCY POWER BACKUP.
<br />SEE FIXTURE SCHEDULE.
<br />m
<br />MOTOR STARTER.
<br />AS NOTED.
<br />0
<br />SURFACE MOUNTED LIGHT FIXTURE.
<br />SEE FIXTURE SCHEDULE.
<br />COMBINATION MOTOR STARTER/DISCONNECT SWITCH.
<br />NEMA/AMPS/POLE/FUSE/VOLTAGE. PROVIDE NEMA 1, 600V UON.
<br />AS NOTED.
<br />SURFACE MOUNTED LIGHT FIXTURE WITH EMERGENCY POWER
<br />BACKUP.
<br />SEE FIXTURE SCHEDULE.
<br />=DJ
<br />ELECTRIC DUCT HEATER.
<br />BY OTHERS.
<br />WALL MOUNTED LIGHT FIXTURE.
<br />SEE FIXTURE SCHEDULE.
<br />N
<br />MOTOR CONNECTION OR EXHAUST FAN.
<br />BY OTHERS.
<br />4
<br />WALL MOUNTED LIGHT FIXTURE WITH EMERGENCY POWER BACKUP.
<br />SEE FIXTURE SCHEDULE.
<br />©
<br />POWER POLE WITH POWER AND COMMUNICATIONS RACEWAY
<br />PROVISIONS AS NOTED.
<br />AS NOTED.
<br />i--D—�
<br />FLUORESCENT STRIP LIGHT FIXTURE.
<br />SEE FIXTURE SCHEDULE.
<br />v
<br />COMMUNICATIONS/DATA OUTLET.
<br />18" AFF TO CENTERLINE UON.
<br />FLUORESCENT STRIP LIGHT FIXTURE WITH EMERGENCY POWER
<br />BACKUP.
<br />SEE FIXTURE SCHEDULE.
<br />®
<br />COMMUNICATIONS/DATA OUTLET, FLOOR OR POKE-THRU.
<br />FLUSH IN FLOOR UON.
<br />00—
<br />FLOOD LIGHT FIXTURE.
<br />SEE FIXTURE SCHEDULE.
<br />®
<br />COMBINATION COMMUNICATIONS/DATA AND DUPLEX RECEPTACLE
<br />OUTLET, FLOOR BOX.
<br />FLUSH IN FLOOR UON.
<br />TRACK LIGHT FIXTURE (STRAIGHT).
<br />SEE FIXTURE SCHEDULE.
<br />®
<br />COMBINATION COMMUNICATIONS/DATA AND QUAD RECEPTACLE
<br />OUTLET, FIRE RATED POKE-THRU.
<br />FLUSH IN FLOOR UON.
<br />�-
<br />TRACK LIGHT FIXTURE (CURVED).
<br />SEE FIXTURE SCHEDULE.
<br />P p
<br />FURNITURE SYSTEM BASE FEED (POWER AND DATA), REFER TO NOTES
<br />AND SPECIFICATIONS.
<br />AS NOTED.
<br />PENDANT MOUNTED LIGHT FIXTURE.
<br />SEE FIXTURE SCHEDULE.
<br />4
<br />CABLE TV OUTLET.
<br />18" AFF TO CENTERLINE UON.
<br />ACCENT LIGHT FIXTURE.
<br />SEE FIXTURE SCHEDULE.
<br />SECURITY SYSTEM CARD READER OUTLET.
<br />48" AFF TO CENTERLINE UON.
<br />CEILING FAN.
<br />SEE FIXTURE SCHEDULE.
<br />OQ
<br />SECURITY SYSTEM CLOSED CIRCUIT TV CAMERA.
<br />AS NOTED.
<br />®
<br />SINGLE -FACE CEILING MOUNTED EXIT SIGN WITH AIMING ARROWS AS
<br />INDICATED. FILL REPRESENTS READABLE FACE DIRECTION.
<br />SEE FIXTURE SCHEDULE.
<br />®
<br />FAZE ALARM SYSTEM CONTROL PANEL.
<br />78" AFF TO TOP.
<br />TWO -FACE CEILING MOUNTED EXIT SIGN WITH AIMING ARROWS AS
<br />INDICATED. FILL REPRESENTS READABLE FACE DIRECTION.
<br />SEE FIXTURE SCHEDULE.
<br />®
<br />FIRE ALARM SYSTEM REMOTE ANNUNCIATOR PANEL.
<br />66" AFF TO TOP.
<br />WALL MOUNTED EXIT SIGN WITH AIMING ARROWS AS INDICATED. FILL REPRESENTS READABLE FACE DIRECTION.
<br />SEE FIXTURE SCHEDULE.
<br />Q
<br />FIRE ALARM SYSTEM SMOKE DETECTOR.
<br />CEILING UON.
<br />WALL MOUNTED EMERGENCY BATTERY PACK LIGHT FIXTURE.
<br />SEE FIXTURE SCHEDULE.
<br />�
<br />s
<br />FIRE ALARM SYSTEM DUCT TYPE SMOKE DETECTOR.
<br />IN SUPPLY DUCT > 2,000 CFM
<br />IN RETURN DUCT > 15,000 CFM
<br />COMBINATION EMERGENCY BATTERY LIGHT AND EXIT SIGN WITH
<br />AIMING ARROWS AS INDICATED. FILL REPRESENTS READABLE FACE.
<br />SEE FIXTURE SCHEDULE.
<br />DUCT SMOKE DETECTOR REMOTE TEST STATION.
<br />66" AFF TO CENTERLINE UON.
<br />OQ--
<br />POLE MOUNTED LIGHT FIXTURE, ARROW INDICATES OPTICS AIMING.
<br />SEE FIXTURE SCHEDULE.
<br />©
<br />FIRE ALARM SYSTEM HEAT DETECTOR.
<br />CEILING UON.
<br />SINGLE -POLE TOGGLE OR AUTOMATIC SWITCH.
<br />48" AFF TO CENTERLINE UON.
<br />FIRE ALARM SYSTEM PULL STATION.
<br />48" AFF TO CENTERLINE UON.
<br />TWO -POLE TOGGLE SWITCH.
<br />48" AFF TO CENTERLINE UON.
<br />Ts
<br />FIRE ALARM SYSTEM TAMPER SWITCH.
<br />FIELD COORDINATE.
<br />3
<br />THREE-WAY TOGGLE OR AUTOMATIC SWITCH.
<br />48" AFF TO CENTERLINE UON.
<br />Fs
<br />FIRE ALARM SYSTEM FLOW SWITCH.
<br />FIELD COORDINATE.
<br />FOUR-WAY TOGGLE OR AUTOMATIC SWITCH.
<br />48" AFF TO CENTERLINE UON.
<br />®
<br />FIRE ALARM SYSTEM RELAY CONTROL MODULE.
<br />FIELD COORDINATE.
<br />i°
<br />OCCUPANCY SENSOR SWITCH.
<br />48" AFF TO CENTERLINE UON.
<br />❑M
<br />FIRE ALARM SYSTEM MONITORING MODULE.
<br />FIELD COORDINATE.
<br />MOMENTARY CONTACT TOGGLE SWITCH.
<br />48" AFF TO CENTERLINE UON.
<br />❑D
<br />FIRE ALARM SYSTEM MAGNETIC DOOR HOLDER.
<br />ON WALL 6" BELOW TOP OF
<br />DOOR.
<br />TIMER SWITCH.
<br />48" AFF TO CENTERLINE UON.
<br />FIRE ALARM SYSTEM HORN.
<br />80" AFF TO BOTTOM.
<br />0eo0
<br />DIMMER SWITCH. PROVIDE WATTAGE RATING INDICATED.
<br />F DENOTES FLUORESCENT DIMMER.
<br />48" AFF TO CENTERLINE UON.
<br />Q
<br />FIRE ALARM SYSTEM STROBE, 75 CANDELA UON.
<br />80" AFF TO BOTTOM.
<br />Q
<br />CEILING MOUNTED OCCUPANCY SENSOR SWITCH.
<br />CEILING UON.
<br />FIRE ALARM SYSTEM HORN/STROBE, 75 CANDELA UON.
<br />80" AFF TO BOTTOM.
<br />JQ E]
<br />JUNCTION BOX OR OUTLET BOX.
<br />AS NOTED.
<br />FIRE ALARM SYSTEM CEILING MOUNTED HORN/STROBE, CANDELA
<br />UON. 30' MAX MOUNTING HEIGHT.
<br />SURFACE ON CEILING.
<br />F-�U
<br />GROUND ROD.
<br />AS NOTED.
<br />MM
<br />FIRE ALARM SYSTEM MINI -HORN.
<br />80" AFF TO BOTTOM.
<br />CONDUIT CONCEALED IN WALL OR ABOVE CEILING.
<br />SEE SPECIFICATIONS.
<br />R
<br />FIRE ALARM SYSTEM BELL.
<br />96" AFF TO TOP UON.
<br />_
<br />�
<br />CONDUIT CONCEALED IN SLAB OR UNDERGROUND.
<br />SEE SPECIFICATIONS.
<br />C
<br />UP DN
<br />CONDUIT RUN UP OR DOWN AS NOTED.
<br />-------
<br />CONDUIT EXPOSED ON WALL OR CEILING.
<br />SEE SPECIFICATIONS.
<br />PHASE, NEUTRAL, EQUIPMENT GROUND, AND ISOLATED GROUND.
<br />ALL HOMERUNS SHALL BE MINIMUM 1/2" CONDUIT WITH 3 #12, UON.
<br />LINE SHADING FOR EXISTING ELECTRICAL
<br />/C PC
<br />TIME CLOCK / PHOTOCELL
<br />LINE SHADING FOR NEW ELECTRICAL
<br />00
<br />REFER TO KEYED NOTES.
<br />ABBREVIATIONS
<br />ABBREVIATIONS
<br />AFF
<br />ABOVE FINISHED FLOOR.
<br />HID
<br />HIGH INTENSITY DISCHARGE.
<br />AFG
<br />ABOVE FINISHED GRADE.
<br />HP
<br />HORSEPOWER.
<br />ATS
<br />AUTOMATIC TRANSFER SWITCH.
<br />IG
<br />ISOLATED GROUND.
<br />BIG
<br />BELOW FINISH GRADE.
<br />LCP
<br />LIGHTING CONTROL PANEL
<br />C
<br />CONDUIT.
<br />LSIG
<br />LONG, SHORT, INSTANTANEOUS & GROUND FAULT TRIP SETTINGS (ALL ADJUSTABLE).
<br />CLG
<br />CEILING MOUNTED.
<br />N
<br />NEW.
<br />D
<br />DEMOLITION
<br />NEUT
<br />NEUTRAL.
<br />DN
<br />CONDUIT DOWN.
<br />NF
<br />NON -FUSED.
<br />E
<br />EXISTING.
<br />NL
<br />NIGHT LIGHT.
<br />EC
<br />ELECTRICAL CONTRACTOR.
<br />NP
<br />NAMEPLATE.
<br />EG
<br />EQUIPMENT GROUND.
<br />OFCI
<br />OWNER FURNISHED, CONTRACTOR INSTALLED.
<br />EXP
<br />EXPLOSION PROOF.
<br />PNL
<br />PANEL.
<br />EWC
<br />ELECTRIC WATER COOLER.
<br />RE
<br />RELOCATED.
<br />EWH
<br />ELECTRIC WATER HEATER.
<br />UON
<br />UNLESS OTHERWISE NOTED.
<br />GEC
<br />GROUNDING ELECTRODE CONDUCTOR.
<br />UPS
<br />UNINTERRUPTIBLE POWER SUPPLY.
<br />GFI
<br />GROUND FAULT INTERRUPTER (BREAKER) / GROUND FAULT CIRCUIT INTERRRUPTER (RECEPTACLE).
<br />WP
<br />WEATHERPROOF.
<br />FTL
<br />FEED THRU LUGS (FEED DOWNSTREAM SECTION WITH IDENTICAL FEEDER AS PREVIOUS SECTION)
<br />XFMR
<br />TRANSFORMER
<br />THE DESIGN FLOOD ELEVATION IS 12" AFF, UON.
<br />0
<br />w
<br />a
<br />0
<br />a
<br />0
<br />U
<br />UJ
<br />UJ
<br />LU
<br />Of
<br />Z
<br />0
<br />0
<br />z
<br />LU
<br />m
<br />J
<br />J
<br />Q
<br />U
<br />O
<br />a
<br />X
<br />UJ
<br />0
<br />Z
<br />Q
<br />Z
<br />0
<br />0
<br />w
<br />Z
<br />w
<br />0
<br />0
<br />0
<br />z
<br />Cdr1C
<br />Architecture, I nc.
<br />WIEDRICK ARCHITECTURE INC.
<br />AA26001799
<br />2020 HEIDELBERG AVE.
<br />DUNEDIN, FLORIDA, 34698
<br />727.736.8627
<br />STATE OF FLORIDA
<br />PROFESSIONAL ENGINEER:
<br />MATTHEW OTTO
<br />PE 58722
<br />m
<br />`.J
<br />a
<br />w
<br />U
<br />0
<br />E
<br />N
<br />H
<br />E~ °
<br />wV
<br />`n U
<br />WE`r'Lr
<br />F"
<br />CO o
<br />O
<br />r�,
<br />v
<br />om-4
<br />N
<br />�J) v o
<br />0
<br />w
<br />w
<br />1�
<br />��
<br />w
<br />4
<br />0
<br />z
<br />�n
<br />m
<br />rn
<br />No. 58722
<br />®'a •''0 STATE OF
<br />`°•• •' �O
<br />N LID
<br />ch
<br />J
<br />Q _J
<br />LL
<br />-�--�
<br />U)
<br />J
<br />t
<br />UJ
<br />IY
<br />I
<br />J N
<br />Q
<br />PROJECT ADDRESS:
<br />38444 5TH AVE.
<br />ZEPHYRHILLS, FL 33542
<br />rl I�nl-r�
<br />FLORIDA PHARMACY
<br />SOLUTIONS, INC.
<br />13933 17TH ST. SUITE 300
<br />DADE CITY, FL 33525
<br />DATE I DESCRIPTION
<br />LEC;END, 5PEC'5 CONTINUED
<br />MDO
<br />PROJECT #: 14-87
<br />E002