U <br />PART 3 EXECUTION <br />3.01 GENERAL <br />A. Install Products in accordance with manufacturer's instructions. <br />B. Mechanical connections shall be accessible for inspection and checking. No insulation shall be installed over <br />mechanical ground connections. <br />C. Attach grounds permanently before permanent building service is energized. <br />D. Install rod electrodes at "non -trip -hazard" locations indicated or as required by Code, whichever requires <br />the most rods. Install additional rod electrodes as required to achieve specified resistance to ground. <br />E. Provide bonding to meet NEC Requirements, including but not limited to bonding between telephone, <br />television, and security systems. <br />F. Coordinate with general contractor to insure at least (2) column anchor bolts are tied to footing steel rebar at <br />column nearest electrical service using the usual steel tie wires. <br />3.02 FIELD QUALITY CONTROL <br />A. Inspect grounding and bonding system conductors and connections for tightness and proper installation. <br />B. Measure ground resistance from system grounding electrode connection at service entrance (neutral -ground <br />bond removed) to earth ground reference point using suitable ground testing equipment. Resistance shall <br />not exceed 25 ohms. <br />***END OF SECTION*** <br />SECTION 16426 <br />DISTRIBUTION EQUIPMENT <br />PART 1 - GENERAL <br />1.01 WORK INCLUDED <br />A. Standard and custom products equivalent to Square D, NQOD, NF, I -Line panelboards, and QMB <br />switchboards, as well as safety switches, contactors, and starters. Cutler Hammer, Siemens, and GE are <br />acceptable manufacturers. <br />PART 2 - PRODUCTS <br />2.01 MATERIALS <br />A. All distribution gear shall be fully bussed and fingered for all pole positions numbered on schedules. <br />B. All distribution gear shall have a ground bus. <br />C. For 4-wire systems, the neutral bus shall be the equivalent ampacity as the phase bus bars. <br />D. Provide mechanically fastened permanent plastic nametag with 1/4"H letters indicating name of each <br />switchboard, panelboard, and transformer as well as a permanent plastic nametag indicating each load fed <br />for each switchboard. <br />E. All panelboards and switchboards shall use bolt -on circuit breaker overcurrent devices. <br />F. Provide circuit breakers UL listed as Type HACR for air conditioning equipment branch circuits. <br />G. Do not use tandem circuit breakers. <br />H. Safety switches used for service disconnecting means shall be Heavy Duty,100,000 AIC minimum. All <br />others may be General Duty. <br />I. Provide Class L fuses for individual motors, 50 hp and larger; Class J for service mains including tenant <br />meter disconnects downstream of mains; Class RK5 fuses for all other applications. <br />J. Refer to panel schedules for ampacities, voltage, phase, NEMA rating, mounting configuration, AIC rating, <br />and accessories. <br />K. Lighting contactors shall have 30 amp rated contacts, minimum. <br />L. Provide a typewritten panel directory for each panelboard or loadcenter with sufficient detail to distinguish <br />each circuit from all others within the panelboard or loadcenter. <br />M. Sharing a neutral is permitted for up to three circuits, one per phase, of the same amp rating for 208Y/120V <br />branch circuits on non -dimmed circuits. Where a shared neutral conductor is used for multiple branch <br />circuits, contractor shall either group circuits together in panel and provide a manufacturer furnished and <br />listed handle -tie to simultaneously trip all of the circuits sharing the neutral or provide multi -pole circuit <br />breakers. Plans may not depict shared neutrals, but they are allowed in accordance with the above <br />specification. <br />N. All circuit breakers used for service disconnecting means,1,200 amps and larger, shall have electronic trip <br />units equivalent to Square D MicroLogic 5.OH (6.OH where GFI is specified). Such breakers shall be <br />accompanied with a factory installed phase failure relay, Taylor PND-###-T3 or equivalent. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION <br />A. Install panelboards plumb with wall finishes with height 6-6" AFF to top. <br />B. Provide filler plates for unused spaces in panelboards. <br />C. Inspect for physical damage, proper alignment, anchorage, and grounding. Check proper installation and <br />tightness of connections. <br />D. Rigidly mount disconnects and starters adjacent to load served, maintaining working clearance required by <br />NEC. <br />E. Electrical equipment, such as switchboards, panelboards, industrial control panels, meter socket enclosures, <br />and motor control centers, that are in other than dwelling occupancies, and are likely to require <br />examination, adjustment, servicing, or maintenance while energized shall be field marked to warn qualified <br />persons of potential electric arc flash hazards. Provide factory labels to comply. <br />F. Where the area above the dedicated electrical space above electrical equipment contains systems which <br />could leak or condensate, provide suitable protection to avoid damage to the electrical equipment. <br />G. All floor mounted electrical gear is to be installed on 4" tall concrete housekeeping pads. <br />***END OF SECTION*** <br />SECTION 16500 <br />INTERIOR LIGHTING <br />PART 1 - GENERAL <br />1.01 QUALITY ASSURANCE <br />A. Comply with NEC requirements as applicable to wiring types and lengths for fixture whips. Provide <br />lighting components and fittings that are UL-listed and labeled. <br />PART 2 - PRODUCTS <br />2.01 MATERIALS <br />A. Lighting fixtures shall be the type indicated on Drawings and as specified. Fixtures of same type shall be of <br />identical make, design, and appearance. Size of lighting fixtures shall be as specified for the lamp or fixture <br />wattage indicated on Drawings. Specific manufacturer and model number references are indicated as a <br />standard of quality and other manufacturers may be supplied provided the product meets or exceeds the <br />specifications. <br />B. Ballasts shall comply with applicable state, federal and industry performance safety standards including <br />FCC requirements governing electromagnetic and radio frequency interference, IEEE standards for line <br />voltage transient protection and harmonic distortion. <br />C. When occupancy sensors are controlling fluorescent fixtures, ballasts shall be programmed rapid start. <br />Instant start is acceptable otherwise. <br />D. Ballasts shall comply with 2008 NEC 410.130 (G) requirement for integral disconnecting means. <br />E. Provide lamps with lighting fixtures. Lamps shall be as manufactured by General Electric, Philips, Venture, <br />or Sylvania. <br />F. Fluorescent lamps shall be 3,000 lumen minimum, 841, 850 for fluorescent high -bays. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION <br />A. Clean surfaces of dirt, cement, plaster and debris. Furnish cleansers compatible with material surfaces <br />being cleaned. <br />B. Replace defective lamps and ballasts. <br />C. Support recessed fixtures in ceilings as follows: Fixtures shall be independently supported from structure <br />above using (2) #12 ceiling tie -wires per fixture at diagonal corners. <br />D. Recessed fixtures shall fit snugly against ceilings to prevent light leakage. <br />E. Light fixtures and associated wiring shall be installed in accordance with NEC Article 410. <br />F. Where supported via threaded means, all nuts shall be double nutted with lock -washers. <br />***END OF SECTION*** <br />SECTION 16741 <br />TELEPHONE AND DATA SYSTEM <br />PART 1- GENERAL <br />1.01 QUALITY ASSURANCE <br />A. Comply with applicable requirements of NEMA and UL standards. Provide products and components that <br />have been UL listed and labeled. <br />PART 2 - PRODUCTS <br />2.01 MATERIALS <br />A. Outlet boxes shall consist of 4" square deep boxes. Provide minimum 2-1/4" deep boxes unless required <br />otherwise by field conditions. <br />B. Provide backboard in telephone equipment rooms consisting of 3/4" deep X 4' wide X 8' high AC plywood <br />unless noted otherwise on plans. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION <br />A. Provide minimum 1" conduits from outlet boxes to accessible space above ceiling, terminated with bushing. <br />Where hard ceilings are installed, route conduit to nearest accessible location. <br />B. Paint both sides of telephone backboards with 2 coats of fire retardant paint prior to installation. <br />C. Use long sweep rigid 90-degree elbows on telephone service entrance conduits. <br />D. Provide a ground bar at each telephone backboard location. Provide a #4 Green copper ground from each <br />ground bar to main telephone systems ground or to building grounding electrode system. <br />E. Provide a pull string in all conduits. <br />***END OF SECTION*** <br />ELECTRICAL LEGEND <br />SYMBOL <br />DESCRIPTION <br />MOUNTING <br />SYMBOL <br />DESCRIPTION <br />MOUNTING <br />O <br />CEILING LIGHT FIXTURE. <br />SEE FIXTURE SCHEDULE. <br />DUPLEX RECEPTACLE. SEE SPECIFICATIONS. <br />18" AFF TO CENTERLINE UON. <br />® <br />CEILING LIGHT FIXTURE WITH EMERGENCY POWER BACKUP. <br />SEE FIXTURE SCHEDULE. <br />DUPLEX RECEPTACLE, ABOVE COUNTER. SEE SPECIFICATIONS. <br />44" AFF TO CENTERLINE UON. <br />O— <br />WALL WASH LIGHT FIXTURE. ARROW INDICATES WASH DIRECTION. <br />SEE FIXTURE SCHEDULE. <br />DUPLEX RECEPTACLE, ONE-HALF SWITCHED. SEE SPECIFICATIONS. <br />18" AFF TO CENTERLINE UON. <br />4 <br />WALL BRACKET LIGHT FIXTURE. <br />SEE FIXTURE SCHEDULE. <br />® <br />DUPLEX RECEPTACLE, FLOOR OR POKE-THRU. SEE SPECIFICATIONS. <br />FLUSH IN FLOOR UON. <br />WALL BRACKET LIGHT FIXTURE WITH EMERGENCY POWER BACKUP. <br />SEE FIXTURE SCHEDULE. <br />DOUBLE DUPLEX RECEPTACLE. SEE SPECIFICATIONS. <br />18" AFF TO CENTERLINE UON. <br />Q <br />WALL BRACKET LIGHT FIXTURE. <br />SEE FIXTURE SCHEDULE. <br />DOUBLE DUPLEX RECEPTACLE, ABOVE COUNTER. SEE SPECIFICATIONS. <br />44" AFF TO CENTERLINE UON. <br />WALL BRACKET LIGHT FIXTURE WITH EMERGENCY POWER BACKUP. <br />SEE FIXTURE SCHEDULE. <br />T <br />SIMPLEX RECEPTACLE. SEE SPECIFICATIONS. <br />18" AFF TO CENTERLINE UON. <br />o <br />WALL MOUNTED SCONCE LIGHT FIXTURE <br />SEE FIXTURE SCHEDULE. <br />CLOCK OUTLET <br />84" AFF TO CENTERLINE UON. <br />® <br />WALL MOUNTED SCONCE LIGHT FIXTURE WITH EMERGENCY POWER <br />BACKUP. <br />SEE FIXTURE SCHEDULE. <br />V <br />SPECIAL RECEPTACLE. NEMA CONFIGURATION AS NOTED. <br />18" AFF TO CENTERLINE UON. <br />❑O <br />1' X 1' LIGHT FIXTURE. <br />SEE FIXTURE SCHEDULE. <br />DUPLEX RECEPTACLE MOUNTED FLUSH IN CEILING. <br />AS NOTED <br />® <br />1' X 1' LIGHT FIXTURE WITH EMERGENCY POWER BACKUP. <br />SEE FIXTURE SCHEDULE. <br />MULTI -OUTLET SURFACE RACEWAY WITH NEMA 5-15R SIMPLEX <br />RECEPTACLES AT 12" CENTERS UON. <br />44" AFF TO CENTERLINE UON. <br />® <br />2' X 2' LIGHT FIXTURE. <br />SEE FIXTURE SCHEDULE. <br />Iffm— <br />208Y/120V OR 240/120V PANELBOARD. <br />78" AFF TO TOP. <br />® <br />2' X 2' LIGHT FIXTURE WITH EMERGENCY POWER BACKUP. <br />SEE FIXTURE SCHEDULE. <br />1295- <br />277Y/480V PANELBOARD. <br />78" AFF TO TOP. <br />2' X 4' LIGHT FIXTURE. <br />SEE FIXTURE SCHEDULE. <br />,0 <br />DISCONNECT SWITCH. <br />NEMA/AMPS/POLE/FUSE/VOLTAGE. PROVIDE NEMA 1, 600V UON. <br />AS NOTED. <br />2' X 4' LIGHT FIXTURE WITH EMERGENCY POWER BACKUP. <br />SEE FIXTURE SCHEDULE. <br />m <br />MOTOR STARTER. <br />AS NOTED. <br />0 <br />SURFACE MOUNTED LIGHT FIXTURE. <br />SEE FIXTURE SCHEDULE. <br />COMBINATION MOTOR STARTER/DISCONNECT SWITCH. <br />NEMA/AMPS/POLE/FUSE/VOLTAGE. PROVIDE NEMA 1, 600V UON. <br />AS NOTED. <br />SURFACE MOUNTED LIGHT FIXTURE WITH EMERGENCY POWER <br />BACKUP. <br />SEE FIXTURE SCHEDULE. <br />=DJ <br />ELECTRIC DUCT HEATER. <br />BY OTHERS. <br />WALL MOUNTED LIGHT FIXTURE. <br />SEE FIXTURE SCHEDULE. <br />N <br />MOTOR CONNECTION OR EXHAUST FAN. <br />BY OTHERS. <br />4 <br />WALL MOUNTED LIGHT FIXTURE WITH EMERGENCY POWER BACKUP. <br />SEE FIXTURE SCHEDULE. <br />© <br />POWER POLE WITH POWER AND COMMUNICATIONS RACEWAY <br />PROVISIONS AS NOTED. <br />AS NOTED. <br />i--D—� <br />FLUORESCENT STRIP LIGHT FIXTURE. <br />SEE FIXTURE SCHEDULE. <br />v <br />COMMUNICATIONS/DATA OUTLET. <br />18" AFF TO CENTERLINE UON. <br />FLUORESCENT STRIP LIGHT FIXTURE WITH EMERGENCY POWER <br />BACKUP. <br />SEE FIXTURE SCHEDULE. <br />® <br />COMMUNICATIONS/DATA OUTLET, FLOOR OR POKE-THRU. <br />FLUSH IN FLOOR UON. <br />00— <br />FLOOD LIGHT FIXTURE. <br />SEE FIXTURE SCHEDULE. <br />® <br />COMBINATION COMMUNICATIONS/DATA AND DUPLEX RECEPTACLE <br />OUTLET, FLOOR BOX. <br />FLUSH IN FLOOR UON. <br />TRACK LIGHT FIXTURE (STRAIGHT). <br />SEE FIXTURE SCHEDULE. <br />® <br />COMBINATION COMMUNICATIONS/DATA AND QUAD RECEPTACLE <br />OUTLET, FIRE RATED POKE-THRU. <br />FLUSH IN FLOOR UON. <br />�- <br />TRACK LIGHT FIXTURE (CURVED). <br />SEE FIXTURE SCHEDULE. <br />P p <br />FURNITURE SYSTEM BASE FEED (POWER AND DATA), REFER TO NOTES <br />AND SPECIFICATIONS. <br />AS NOTED. <br />PENDANT MOUNTED LIGHT FIXTURE. <br />SEE FIXTURE SCHEDULE. <br />4 <br />CABLE TV OUTLET. <br />18" AFF TO CENTERLINE UON. <br />ACCENT LIGHT FIXTURE. <br />SEE FIXTURE SCHEDULE. <br />SECURITY SYSTEM CARD READER OUTLET. <br />48" AFF TO CENTERLINE UON. <br />CEILING FAN. <br />SEE FIXTURE SCHEDULE. <br />OQ <br />SECURITY SYSTEM CLOSED CIRCUIT TV CAMERA. <br />AS NOTED. <br />® <br />SINGLE -FACE CEILING MOUNTED EXIT SIGN WITH AIMING ARROWS AS <br />INDICATED. FILL REPRESENTS READABLE FACE DIRECTION. <br />SEE FIXTURE SCHEDULE. <br />® <br />FAZE ALARM SYSTEM CONTROL PANEL. <br />78" AFF TO TOP. <br />TWO -FACE CEILING MOUNTED EXIT SIGN WITH AIMING ARROWS AS <br />INDICATED. FILL REPRESENTS READABLE FACE DIRECTION. <br />SEE FIXTURE SCHEDULE. <br />® <br />FIRE ALARM SYSTEM REMOTE ANNUNCIATOR PANEL. <br />66" AFF TO TOP. <br />WALL MOUNTED EXIT SIGN WITH AIMING ARROWS AS INDICATED. FILL REPRESENTS READABLE FACE DIRECTION. <br />SEE FIXTURE SCHEDULE. <br />Q <br />FIRE ALARM SYSTEM SMOKE DETECTOR. <br />CEILING UON. <br />WALL MOUNTED EMERGENCY BATTERY PACK LIGHT FIXTURE. <br />SEE FIXTURE SCHEDULE. <br />� <br />s <br />FIRE ALARM SYSTEM DUCT TYPE SMOKE DETECTOR. <br />IN SUPPLY DUCT > 2,000 CFM <br />IN RETURN DUCT > 15,000 CFM <br />COMBINATION EMERGENCY BATTERY LIGHT AND EXIT SIGN WITH <br />AIMING ARROWS AS INDICATED. FILL REPRESENTS READABLE FACE. <br />SEE FIXTURE SCHEDULE. <br />DUCT SMOKE DETECTOR REMOTE TEST STATION. <br />66" AFF TO CENTERLINE UON. <br />OQ-- <br />POLE MOUNTED LIGHT FIXTURE, ARROW INDICATES OPTICS AIMING. <br />SEE FIXTURE SCHEDULE. <br />© <br />FIRE ALARM SYSTEM HEAT DETECTOR. <br />CEILING UON. <br />SINGLE -POLE TOGGLE OR AUTOMATIC SWITCH. <br />48" AFF TO CENTERLINE UON. <br />FIRE ALARM SYSTEM PULL STATION. <br />48" AFF TO CENTERLINE UON. <br />TWO -POLE TOGGLE SWITCH. <br />48" AFF TO CENTERLINE UON. <br />Ts <br />FIRE ALARM SYSTEM TAMPER SWITCH. <br />FIELD COORDINATE. <br />3 <br />THREE-WAY TOGGLE OR AUTOMATIC SWITCH. <br />48" AFF TO CENTERLINE UON. <br />Fs <br />FIRE ALARM SYSTEM FLOW SWITCH. <br />FIELD COORDINATE. <br />FOUR-WAY TOGGLE OR AUTOMATIC SWITCH. <br />48" AFF TO CENTERLINE UON. <br />® <br />FIRE ALARM SYSTEM RELAY CONTROL MODULE. <br />FIELD COORDINATE. <br />i° <br />OCCUPANCY SENSOR SWITCH. <br />48" AFF TO CENTERLINE UON. <br />❑M <br />FIRE ALARM SYSTEM MONITORING MODULE. <br />FIELD COORDINATE. <br />MOMENTARY CONTACT TOGGLE SWITCH. <br />48" AFF TO CENTERLINE UON. <br />❑D <br />FIRE ALARM SYSTEM MAGNETIC DOOR HOLDER. <br />ON WALL 6" BELOW TOP OF <br />DOOR. <br />TIMER SWITCH. <br />48" AFF TO CENTERLINE UON. <br />FIRE ALARM SYSTEM HORN. <br />80" AFF TO BOTTOM. <br />0eo0 <br />DIMMER SWITCH. PROVIDE WATTAGE RATING INDICATED. <br />F DENOTES FLUORESCENT DIMMER. <br />48" AFF TO CENTERLINE UON. <br />Q <br />FIRE ALARM SYSTEM STROBE, 75 CANDELA UON. <br />80" AFF TO BOTTOM. <br />Q <br />CEILING MOUNTED OCCUPANCY SENSOR SWITCH. <br />CEILING UON. <br />FIRE ALARM SYSTEM HORN/STROBE, 75 CANDELA UON. <br />80" AFF TO BOTTOM. <br />JQ E] <br />JUNCTION BOX OR OUTLET BOX. <br />AS NOTED. <br />FIRE ALARM SYSTEM CEILING MOUNTED HORN/STROBE, CANDELA <br />UON. 30' MAX MOUNTING HEIGHT. <br />SURFACE ON CEILING. <br />F-�U <br />GROUND ROD. <br />AS NOTED. <br />MM <br />FIRE ALARM SYSTEM MINI -HORN. <br />80" AFF TO BOTTOM. <br />CONDUIT CONCEALED IN WALL OR ABOVE CEILING. <br />SEE SPECIFICATIONS. <br />R <br />FIRE ALARM SYSTEM BELL. <br />96" AFF TO TOP UON. <br />_ <br />� <br />CONDUIT CONCEALED IN SLAB OR UNDERGROUND. <br />SEE SPECIFICATIONS. <br />C <br />UP DN <br />CONDUIT RUN UP OR DOWN AS NOTED. <br />------- <br />CONDUIT EXPOSED ON WALL OR CEILING. <br />SEE SPECIFICATIONS. <br />PHASE, NEUTRAL, EQUIPMENT GROUND, AND ISOLATED GROUND. <br />ALL HOMERUNS SHALL BE MINIMUM 1/2" CONDUIT WITH 3 #12, UON. <br />LINE SHADING FOR EXISTING ELECTRICAL <br />/C PC <br />TIME CLOCK / PHOTOCELL <br />LINE SHADING FOR NEW ELECTRICAL <br />00 <br />REFER TO KEYED NOTES. <br />ABBREVIATIONS <br />ABBREVIATIONS <br />AFF <br />ABOVE FINISHED FLOOR. <br />HID <br />HIGH INTENSITY DISCHARGE. <br />AFG <br />ABOVE FINISHED GRADE. <br />HP <br />HORSEPOWER. <br />ATS <br />AUTOMATIC TRANSFER SWITCH. <br />IG <br />ISOLATED GROUND. <br />BIG <br />BELOW FINISH GRADE. <br />LCP <br />LIGHTING CONTROL PANEL <br />C <br />CONDUIT. <br />LSIG <br />LONG, SHORT, INSTANTANEOUS & GROUND FAULT TRIP SETTINGS (ALL ADJUSTABLE). <br />CLG <br />CEILING MOUNTED. <br />N <br />NEW. <br />D <br />DEMOLITION <br />NEUT <br />NEUTRAL. <br />DN <br />CONDUIT DOWN. <br />NF <br />NON -FUSED. <br />E <br />EXISTING. <br />NL <br />NIGHT LIGHT. <br />EC <br />ELECTRICAL CONTRACTOR. <br />NP <br />NAMEPLATE. <br />EG <br />EQUIPMENT GROUND. <br />OFCI <br />OWNER FURNISHED, CONTRACTOR INSTALLED. <br />EXP <br />EXPLOSION PROOF. <br />PNL <br />PANEL. <br />EWC <br />ELECTRIC WATER COOLER. <br />RE <br />RELOCATED. <br />EWH <br />ELECTRIC WATER HEATER. <br />UON <br />UNLESS OTHERWISE NOTED. <br />GEC <br />GROUNDING ELECTRODE CONDUCTOR. <br />UPS <br />UNINTERRUPTIBLE POWER SUPPLY. <br />GFI <br />GROUND FAULT INTERRUPTER (BREAKER) / GROUND FAULT CIRCUIT INTERRRUPTER (RECEPTACLE). <br />WP <br />WEATHERPROOF. <br />FTL <br />FEED THRU LUGS (FEED DOWNSTREAM SECTION WITH IDENTICAL FEEDER AS PREVIOUS SECTION) <br />XFMR <br />TRANSFORMER <br />THE DESIGN FLOOD ELEVATION IS 12" AFF, UON. <br />0 <br />w <br />a <br />0 <br />a <br />0 <br />U <br />UJ <br />UJ <br />LU <br />Of <br />Z <br />0 <br />0 <br />z <br />LU <br />m <br />J <br />J <br />Q <br />U <br />O <br />a <br />X <br />UJ <br />0 <br />Z <br />Q <br />Z <br />0 <br />0 <br />w <br />Z <br />w <br />0 <br />0 <br />0 <br />z <br />Cdr1C <br />Architecture, I nc. <br />WIEDRICK ARCHITECTURE INC. <br />AA26001799 <br />2020 HEIDELBERG AVE. <br />DUNEDIN, FLORIDA, 34698 <br />727.736.8627 <br />STATE OF FLORIDA <br />PROFESSIONAL ENGINEER: <br />MATTHEW OTTO <br />PE 58722 <br />m <br />`.J <br />a <br />w <br />U <br />0 <br />E <br />N <br />H <br />E~ ° <br />wV <br />`n U <br />WE`r'Lr <br />F" <br />CO o <br />O <br />r�, <br />v <br />om-4 <br />N <br />�J) v o <br />0 <br />w <br />w <br />1� <br />�� <br />w <br />4 <br />0 <br />z <br />�n <br />m <br />rn <br />No. 58722 <br />®'a •''0 STATE OF <br />`°•• •' �O <br />N LID <br />ch <br />J <br />Q _J <br />LL <br />-�--� <br />U) <br />J <br />t <br />UJ <br />IY <br />I <br />J N <br />Q <br />PROJECT ADDRESS: <br />38444 5TH AVE. <br />ZEPHYRHILLS, FL 33542 <br />rl I�nl-r� <br />FLORIDA PHARMACY <br />SOLUTIONS, INC. <br />13933 17TH ST. SUITE 300 <br />DADE CITY, FL 33525 <br />DATE I DESCRIPTION <br />LEC;END, 5PEC'5 CONTINUED <br />MDO <br />PROJECT #: 14-87 <br />E002 <br />10/15/14 <br />