Laserfiche WebLink
U <br />DIVISION 16000 ELECTRICAL SPECIFICATIONS <br />SECTION 16010 <br />GENERAL PROVISIONS <br />PART1-GENERAL <br />1.01 WORK INCLUDED <br />A. Furnish all labor, materials, and equipment as required by the plans and specifications to provide a <br />complete and operable electrical system. This specification describes the types of materials, methods, and <br />management to be utilized. This includes the work listed in this division as well as equipment furnished <br />under other divisions not specifically mentioned herein. <br />B. Guarantee all materials and labor for a period of (1) year from date of substantial completion. Pass on any <br />additional manufacturer warranties to the owner. <br />C. Contractor shall coordinate with electric and telephone utilities prior to bid and furnish both with their <br />required sets of plans within 10 days of being awarded project. Obtain pdfs of plans from GC to plot and <br />send to the utility companies. <br />1.02 CODES AND STANDARDS <br />A. All equipment, materials, and methods of design and installation are to comply with the National Electrical <br />Code (NEC), the Occupational Safety and Health Act (OSHA), and the requirements of applicable local <br />codes. Codes and standards of the following organizations may be referred to in this section and shall be <br />considered as the minimum acceptable. A reference herein to any portion of the standard or code is not to <br />be considered as negating any other portion of the standard or code. <br />1. National Electrical Code (NEC), 2008 ed. <br />2. National Electric Manufacturers Association (NEMA) <br />3. Underwriters Laboratories, Inc. (UL) <br />4. Florida Building Code (FBC), 2010 ed. <br />5. Florida Fire Prevention Code (FFPC), 2010 ed. <br />1.03 EQUIPMENT, MATERIAL AND WORKMANSHIP <br />A. All equipment and material shall be new unless allowed below, free from defects, of current manufacture, <br />and listed by Underwriters Laboratories, Inc., (UL) where UL requirements apply. All materials are to be <br />products of reputable and experienced manufacturers. <br />B. Provide protection for materials and equipment against loss or damage throughout the contract. Provide <br />protection from the effect of weather prior to installation, store items to be installed in indoor weather <br />protected location. <br />C. Following installation, protect materials and equipment from corrosion, physical damage and effects of <br />moisture on insulation. <br />D. Do not cut or notch any structural member or building surface without specific approval of the Structural <br />Engineer. <br />E. All work will be performed by accomplished, qualified and experienced personnel working under <br />continuous competent supervision. <br />F. Contractor shall restore fire ratings of all rated assemblies penetrated with the appropriate assembly: <br />W-L-1049, W-L-3214, W-L-4008, C-AJ-1353, C-AJ-1354, C-AJ-1080, or equivalent suitable with penetrant and <br />wall/floor assembly. <br />1.04 PERMITS <br />A. Obtain and pay for all permits and inspections pertinent to the electrical installation. <br />1.05 SITE INSPECTION <br />A. Prior to submitting a bid, visit the project site and ascertain conditions affecting the proposed work and all <br />existing electrical facilities. <br />B. Furnish all labor associated with accompanying Engineer during observations of construction. <br />1.06 TEMPORARY INSTALLATION <br />A. Provide all temporary lighting and 120V/20A power reachable with a 100ft extension cord for use by trades. <br />B. Temporary installation shall conform to the requirements of the NEC, OSHA, and the State and local <br />governing bodies. <br />C. Pay all cost for temporary power services and power usage charges until project final acceptance by owner. <br />1.07 SHOP DRAWINGS <br />A. Submit 6 copies of all project submittal data and shop drawings. <br />B. Submit complete shop drawings for review prior to purchase of the following: <br />1. Light fixtures. <br />2. Wiring devices. <br />3. Panelboards, switchboards, transformers, safety switches, and fuses. <br />4. Fire alarm system. <br />C. Contractor shall review shop drawings and submittals of every trade where an electrical connection is <br />required and report any variances from electrical characteristics noted on the electrical drawings to the <br />Engineer before proceeding with rough -in work. <br />1.08 RECORD DRAWINGS <br />A. Maintain a neatly marked set of record drawings showing installation location, and/or routing of conduits, <br />depth of buried cables, pull boxes, junction boxes, outlets, and a single -line diagram of the building <br />electrical distribution system and floor plans indicating location and area served for all distribution. After <br />final inspection, within 30 days after the date of system acceptance, transfer all record information to the <br />Owner as required in the contract. <br />B. If the contractor elects not to utilize circuitry as designated on plans and in schedules, contractor shall <br />provide as -built markups of plans and schedules to engineer. <br />C. An operating manual and maintenance manual shall be provided to the building owner. The manuals shall <br />include, at a minimum, the following: <br />1. Submittal data stating equipment rating and selected options for each piece of equipment requiring <br />maintenance. <br />2. Operation manuals and maintenance manuals for each piece of equipment requiring maintenance. <br />Required routine maintenance actions shall be clearly identified. <br />3. Names and addresses of at least one qualified service agency. <br />PART 2 - EXECUTION <br />2.01 INSTALLATION <br />A. The electrical plans show general arrangements and locations for equipment conduit, outlets, etc. Unless <br />detailed or dimensioned, exact locations of conduit, routing of cables and placement of equipment will be <br />governed by structural conditions, physical interference, owner equipment, and locations of electrical <br />termination on equipment. Examine architectural, structural, and mechanical plans and shop drawings for <br />the various equipment in order to determine exact routing and placement of all raceways, cables, and <br />equipment, to assure a workable installation in accordance with NEC. Such coordination shall be <br />anticipated during bid. <br />B. Where plans and specifications or schedules are in conflict, contractor shall assume the most stringent <br />requirements apply and submit an RFI prior to submitting bid. <br />C. Any product substitutions from specified make & model numbers shall be qualified in bid in writing with <br />explanation of reason for substitution and cost savings associated with substitution. <br />D. Contractor shall obtain Fire Protection drawings where ESFR fire protection is installed and maintain 12" <br />clearance (24" if FM Global has jurisdiction) from all ESFR sprinkler heads with light fixtures, raceways, and <br />any other electrical component. <br />***END OF SECTION*** <br />SECTION 16070 <br />ELECTRICAL CONNECTIONS FOR EQUIPMENT <br />PART1-GENERAL <br />1.01 WORK INCLUDED <br />A. Provide all labor, materials and equipment as required furnishing connections to all electrical equipment, <br />lights, etc. <br />PART 2 - PRODUCTS <br />2.01 GENERAL <br />A. See Section 16111, Conduit Raceways; Section 16140 Wiring Devices; and Section 16120 Wire and Cables for <br />additional requirements. Provide final connections for equipment consistent with the following: <br />1. Permanently installed fixed equipment - flexible seal-tite conduit from branch circuit terminal <br />equipment, or raceway; to equipment, control cabinet, terminal junction box, or wiring terminals. <br />Totally enclose all wiring in raceway. <br />2. Movable and/or portable equipment - wiring device, cord cap, and multi -conductor cord suitable for <br />the equipment and in accordance with NEC requirements (Article 400). <br />3. Other methods as required by the National Electrical Code and/or as required by special equipment <br />or field conditions. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION OF ELECTRICAL CONNECTIONS <br />A. Make electrical connections in accordance with connector manufacturer's written instructions and with <br />recognized industry practices, and complying with requirements of NEC and NECA's "Standard of <br />Installation" to ensure that products fulfill requirements. <br />B. Connect electrical power supply conductors to equipment conductors in accordance with equipment <br />manufacturer's written instructions and wiring diagrams. <br />C. Verify all electrical loads (voltage, phase, full load amperes, number and point of connections, minimum <br />circuit ampacity, etc.) for equipment furnished under other Sections of this specification, by reviewing <br />respective shop drawings furnished under each section. Report any variances from electrical characteristics <br />noted on the electrical drawings to the Engineer before proceeding with rough -in work. <br />D. Obtain and review the equipment shop drawings to determine particular final connection requirements <br />before rough in begins for each equipment item. <br />E. Contractor shall pay particular attention to lug arrangements in project submittal data, as well as in the field <br />when equipment arrives, with respect to specified conductors for every piece of equipment and report any <br />variances from electrical characteristics noted on the electrical drawings to the Engineer before proceeding <br />with rough -in work. <br />***END OF SECTION*** <br />SECTION 16111 <br />CONDUIT RACEWAYS <br />PART 1- GENERAL <br />1.01 WORK INCLUDED <br />A. Furnish all labor, materials and equipment as required to install all flexible or rigid conduit, couplings, <br />supports and nonmetallic ducts, as shown on the Plans. <br />PART 2 - PRODUCTS <br />2.01 MATERIALS <br />A. GENERAL: Provide conduit, and fittings of types, grades, sizes, and weights (wall thicknesses) as indicated; <br />with minimum trade size of 1/2" above grade and 3/4" below grade. <br />B. Electrical Metallic Tubing (EMT) with die cast or steel set -screw fitting for dry and damp locations, <br />compression for wet locations. <br />C. RIGID METAL CONDUIT (RMC) with threaded fittings and UL 6 listing. <br />D. RIGID NON-METALLIC CONDUIT (RNC): Schedule 40, with matching glue -on socket fittings. <br />E. FLEXIBLE METALLIC CONDUIT (FMC): Galvanized interlocked steel strip with positive locking cadmium <br />plated steel or malleable iron fittings. <br />F. LIQUID -TIGHT FLEXIBLE METAL CONDUIT (LT): Provide liquid -tight, flexible metal conduit; <br />constructed of single strip, flexible continuous, interlocked, and double -wrapped steel; galvanized inside <br />and outside; coated with liquid -tight jacket of flexible polyvinyl chloride (PVC) with positive locking <br />cadmium plated steel or malleable iron fittings and compression type steel ferrule and neoprene gasket <br />sealing rings. <br />G. EXPANSION FITTINGS: OZ Type AX, or equivalent to suit application. <br />2.02 SCHEDULE OF LOCATIONS <br />A. RMC or Schedule 80 PVC in all areas subject to physical damage to an elevation of 48" AFF/AFG. <br />B. EMT for all above grade areas in the building unless noted otherwise. <br />C. RNC for all areas below grade. <br />D. LT for all exposed locations within coolers and freezers. <br />E. Make connections to motors and equipment with FMC and LT as environmental conditions dictate. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION <br />A. Install conduit concealed in all areas where possible. <br />B. Coordinate installation of conduit in masonry work. <br />C. Plug ends of conduits to prevent entry of dirt or moisture. Provide non -shrinking electrical putty to seal <br />conduits which emerge from grade after conductors are installed. <br />D. Route all exposed conduits parallel or perpendicular to building lines. <br />E. Do not exceed number of bends in conduit beyond that allowed by the NEC. <br />F. PVC conduit runs less than 50 ft shall incorporate Schedule 80 elbows, over 50 ft use RMC coated with <br />bitumastic. Prior to backfill, take digital photographs. <br />G. Keep conduits at least 12" away from gas lines and hot water pipes, and in no case permit conductors to <br />reach higher than rated temperatures. <br />H. Fasten raceways securely in place. Firmly fasten conduit within three feet of each outlet, junction box, <br />cabinet, or fitting. Support metallic conduit in accordance with the NEC. Use "bolt -on" raceway fasteners <br />designed for the purpose in exposed and wet areas, "snap -on" black metal "Caddy" clips in metal stud <br />walls and above ceilings. All fasteners, straps, clips, etc. shall be UL listed for their use. Where conduit is <br />surface mounted in kitchen, secure with stand-off style straps which allow all sides of the conduit to be <br />cleaned. <br />I. Weatherproof any penetration through exterior of building including slab on grade. <br />J. Provide pull boxes as dictated by wire pulling requirements. Unless shown otherwise, face into secondary <br />or unfinished rooms. <br />K. All raceways shall be kept at least 1-1/2" away from metal roof decking. <br />L. All empty raceways used for structured cabling shall be terminated with connectors and bushings. <br />M. Make watertight roof penetrations at equipment served. Conduits shall not be run horizontally exposed on <br />top of roofs. <br />N. Provide suitable protection of conduits during construction to prevent debris from entering while conduits <br />are not terminated. <br />O. Do not install raceways within 12" horizontally of ESFR sprinkler heads (24" if FM Global has jurisdiction). <br />***END OF SECTION*** <br />SECTION 16120 <br />BUILDING WIRE AND CABLE <br />PART 1- GENERAL <br />1.01 WORK INCLUDED <br />A. Furnish all labor, materials, and equipment as required to install all wires and cables as shown on the Plans, <br />and as required to connect all electrical services and equipment. <br />PART 2 - PRODUCTS <br />2.01 MATERIALS <br />A. All wiring shall be copper unless specifically noted otherwise on plans. Where type XHHW-2 aluminum <br />conductors are permitted per the plans, conductor terminations shall be made with compression pigtail <br />adapters (ILSCO Type ACM or ACO) with anti -oxidant applied to exposed conductor. Owner is advised to <br />refer to NFPA 70B for periodic inspection recommendations. <br />B. Minimum size conductors and insulation types: <br />1. Branch circuits and feeders, # 12 AWG THHN/THWN. <br />2. Service entrance, XHI-IW or THWN. <br />3. Control circuits, # 14 AWG THHN/THWN. <br />C. MC Cable may be used in lieu of conduit and wire where installed in accordance with all of the following <br />conditions. <br />1. Concealed and only where approved by owner. <br />2. Per requirements of the NEC and local codes. <br />3. Branch circuits 30 amps and below. <br />4. Where installed after the first junction box from a panel, i.e. do not connect MC cable to panelboards. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION <br />A. Color coding shall be as follows: <br />Voltage Phase A Phase B Phase C Neutral <br />120/240 Black Orange Blue White <br />B. Provide a green grounding conductor in all raceways except service entrance. Provide a green with yellow <br />stripe conductor in raceways with isolated ground conductors specified on plans. <br />C. Provide conductors with identification tags as manufactured by Brady or approved equal. <br />D. Install wires and cables continuous without splices from source of supply to distribution equipment and <br />from source of supply to motors, lighting, or power outlets. Do not use pull boxes for making splices. Do <br />not install splices in conduits or trench. <br />E. Support vertically installed conductors at intervals not to exceed those allowed by the NEC. Do not splice <br />vertically installed conductors. <br />F. Remove any existing wiring (line voltage and low voltage) which is abandoned in place or will become <br />obsolete due to construction. <br />G. Any feeder lengths described in Voltage Drop or Fault Current Study tables are not to be relied upon for <br />bidding or construction. Contractor is advised to review specification 16010, 2.01, A for coordination with <br />other trades which may affect feeder installation routing and lengths. <br />H. Prior to energizing, check service lateral and feeders for electrical continuity and clear of short-circuits. <br />Check with "Megger" tester for phase -to -phase, phase -to -neutral, and phase -to -ground insulation resistance <br />levels to insure system insulation levels are in accordance with manufacturer's recommendations. Use 500 <br />volt tester for 208 volt and 240 volt applications;1000 volt tester for 480 volt applications. If resistance levels <br />are low, take corrective measures as necessary including but not limited to replacement of all materials as <br />required. <br />***END OF SECTION*** <br />SECTION 16130 <br />PULL AND JUNCTION BOXES <br />PART 1- GENERAL <br />1.01 DESCRIPTION <br />A. Construct junction or pull boxes less than 100 cubic inches as "standard outlet boxes". <br />B. Construct junction or pull boxes greater than 100 cubic inches as "cabinets". <br />C. Provide all covers of same gauge metal and include screws. <br />PART 2 - PRODUCTS <br />2.01 STANDARD OUTLET BOXES <br />A. Make of material resistant to corrosion or suitably protected, both internally and externally by galvanizing. <br />B. Boxes installed in damp or wet locations shall be U.L. approved for the purpose. <br />C. Metal boxes to meet NEC construction specifications. <br />D. Boxes exposed or surface mounted shall be die-cast or permanent- mold cast aluminum body with threaded <br />external hub and cast cover. <br />E. Provide in -ground junction box, Quazite #PG1118BA12 /PG1118HH00 or equivalent for in ground <br />applications. Top flush with finished grade. <br />2.02 CABINETS <br />A. 14 gauge sheet steel with corrosion resistant finish. <br />B. Ample space for wires, connections and equipment. <br />C. Cabinet fronts: Sheet steel panels with hinged door and locking provisions. <br />D. Flush cabinets: Cover shall be approximately 3/4" larger than cabinet on all sides, set with front firmly <br />against the finished wall surface. <br />E. Telephone cabinets: Size and depths as noted on Drawings, with fire -retardant wood backboards. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION <br />A. Install junction boxes so that covers are readily accessible after the completion of the installation. <br />B. <br />Mount rigidly in place with front of box level and plumb. <br />C. <br />Secure flush covers with corrosion resistant screws or bolts. <br />D. <br />Provide each pull box with sufficient clamps to which cables shall be secured in neat and orderly fashion <br />I <br />? T <br />` 1 d K- <br />permitting ready identification. <br />E. <br />Mount pull boxes connected to concealed conduits with covers flush with the finished wall. <br />fi <br />Architecture, <br />1 I1C. <br />F. <br />Neatly write each "panel - circuit" contained in each junction box on the cover with a permanent marker. <br />***END OF SECTION*** <br />WIEDRICK ARCHITECTURE INC. <br />SECTION 16140 <br />` " <br />AA26001799 <br />WIRING DEVICES <br />2020 HEIDELBERG AVE. <br />PART 1-GENERAL <br />= <br />DUNEDIN, FLORIDA, 34698 <br />1.01 WORK INCLUDED <br />727.736.8627 <br />A. <br />The work under this section includes wall switches, receptacles, occupancy sensors, wall dimmers, device <br />plates and box covers, poke -through service fittings, access floor boxes, photocells and time clocks. <br />y <br />STATE OF FLORIDA <br />PART 2-PRODUCTS <br />PROFESSIONAL ENGINEER: <br />MATTHEW OTTO <br />2.01 DESCRIPTION <br />PE 58722 <br />A. <br />WALL SWITCHES: 20-amp,120/277V commercial grade. Single pole (White): Leviton CS120-2W. 3-way <br />(White): Leviton CS320-2W. 4-way (White): Leviton CS420-2W. 2-pole (White): Leviton CS220-2W. <br />B. <br />RECEPTACLES (multiple on a branch circuit): 15-amp, 120V commercial grade. Duplex (White): Leviton <br />w <br />Z <br />CR15-W. Duplex Tamper Resistant (White): Leviton CR15S-GW. <br />�j <br />Z <br />C. <br />RECEPTACLES (single duplex or simplex on a branch circuit): 20-amp,120V commercial grade. Duplex�-•� <br />O <br />(White): Leviton CR20-W. Simplex (White): Leviton 5801-W.�-{ <br />H <br />D. <br />GFCI RECEPTACLES: 20-amp,120V commercial grade. Duplex (White): Leviton 7899-W. Receptacles <br />w a U') ,n . <br />serving vending machines and drinking fountains shall be GFCI type. <br />H <br />x <br />E. <br />GFCI RECEPTACLES: 20-amp,120V commercial grade, weather resistant. Duplex (White): Leviton <br />o <br />H o rn 00 <br />W7899-W for all outdoor, cooler, freezer, and any other damp or wet locations. <br />O <br />F. <br />OCCUPANCY SENSORS (wall mounted): Dual technology, maximum load of 80OW at 120V or 120OW at <br />p <br />277V, Watt Stopper DW-100-W. Adjust for 15 minute time delay and appropriate sensitivity.CZ <br />G. <br />OCCUPANCY SENSORS (ceiling mounted 10' AFF or less): Maximum load of 80OW at 120V or 120OW at <br />O w H v w E <br />U <br />277V, Watt Stopper DT-355-W (DT-300-W with BZ150 power pack for low voltage applications). Adjust for <br />U <br />w <br />15 minute time delay and appropriate sensitivity. <br />I w <br />H. <br />TIMER SWITCH: Digital adjustable with a range of 5 minutes to 12 hours. Maximum load of 80OW at 120V <br />r <br />U <br />or 1200W at 277V, Watt Stopper TS-400. <br />I. <br />PHOTOCELL: Weatherproof, adjustable. Intermatic K4100 series. <br />o <br />Z <br />Q <br />J. <br />TIME CLOCK: Single or multi -circuit as indicated on the plans. Intermatic ET90000 series. <br />c <br />IIPtPIp <br />� <br />w <br />`ttttfh <br />PART 3 <br />- EXECUTION <br />* P ........••.. ° <br />®= <br />3.01 GENERAL <br />No. 58722 <br />A. <br />All devices are to be installed in 4" square boxes, except when installed in masonry. <br />• ,bi <br />'• STATE OF <br />:• <br />B. <br />Cover plates in commercial kitchens shall be type 302 stainless steel. All other cover plates shall be smooth®'•.•.• <br />F P <br />C <br />4U� -Z'o <br />ae <br />white nylon unless otherwise specified herein. <br />�f°c`�s ., 0RkO...��N, <br />C. <br />Cover plates for receptacles installed in damp or wet locations shall be weatherproof while -in -use. <br />O <br />'��SRO N AL <br />D. <br />Cover plates for light switches in exterior, cooler, and freezer applications shall be equivalent to Carlon <br />E98TSCN-CAR weatherproof cover. <br />E. <br />Note mounting heights indicated by the symbology and notes on the plans. <br />F. <br />All devices shall have a bonding pigtail conductor from grounding terminal to the metal box system (except <br />IG). Self -grounding receptacles using mounting screws as bonding means are not approved. <br />G. <br />Except as otherwise indicated on the Drawings, mount devices flush, with long dimension vertical, and <br />grounding pin on receptacles on bottom. Group adjacent switches and receptacles under a single, <br />multi -gang wall plate. Where communications outlets are shown adjacent to power receptacles, both shall <br />be installed at same elevation. <br />O <br />N <br />It <br />***END OF SECTION*** <br />CLO <br />SECTION 16170 <br />Q J <br />LL <br />GROUNDING AND BONDING <br />= <br />Lo J <br />PART1-GENERAL <br />J <br />1.01 WORK INCLUDED <br />� _ <br />A. <br />Grounding electrodes and conductors, equipment grounding conductors and bonding. <br />i - <br />UJI <br />PART 2 <br />- PRODUCTS <br />o <br />a <br />N <br />2.01 ROD ELECTRODE <br />Q <br />0 <br />A. <br />Material: Copper -clad steel. <br />° <br />B. <br />Diameter: 3/4" minimum, <br />w <br />C. <br />Length: l0' minimum. Rod shall be driven at least 9'-6" deep. <br />J <br />UJ <br />PROJECT ADDRESS: <br />D. <br />Provide the number of rods required to obtain proper ground resistance. <br />038444 <br />5TH AVE. <br />ZEPHYRHILLS, FL 33542 <br />2.02 MECHANICAL CONNECTORS <br />UJ <br />UJ <br />A. <br />The mechanical connector bodies shall be manufactured from high strength, high conductivity cast copper <br />alloy material. Bolts, nuts, washers and lock washers shall be made of Silicon Bronze and supplied as a part <br />of the connector body and shall be of the two bolt type. <br />B. <br />Split bolt connector types are NOT allowed. <br />CLIENT: <br />C. <br />The connectors shall meet or exceed UL 467 and be clearly marked with the catalog number, conductor size <br />0 <br />FLORIDA PHARMACY <br />and manufacturer. <br />LU <br />SOLUTIONS, INC. <br />0 <br />13933 17TH ST. SUITE 300 <br />2.03 COMPRESSION CONNECTORS <br />Z <br />DADE CITY, FL 33525 <br />A. <br />The compression connectors shall be manufactured from pure wrought copper. The conductivity of this <br />Z <br />0 <br />UJ <br />material shall be no less than 99% by IACS standards. <br />; <br />DATE <br />DESCRIPTION <br />B. <br />The installation of the connectors shall be made with a compression, tool and die system, as recommended <br />° <br />by the manufacturer of the connectors. <br />0 <br />C. <br />The connectors shall be clearly marked with the manufacturer, catalog number, conductor size and the <br />LD <br />required compression tool settings.LU <br />o <br />D. Each connector shall be factory filled with an oxide -inhibiting compound. <br />0 <br />2.04 EXOTHERMIC CONNECTIONS <br />Z <br />A. <br />WIRE <br />z <br />LU <br />1. Material: Stranded copper (aluminum not permitted). <br />2. Grounding Electrode Conductor: Size as shown on drawings, specifications or as required by NFPA <br />o <br />SPECIFICATIONS <br />70, whichever is larger. <br />UJ <br />o <br />MDO <br />PROJECT #: 14-87 <br />Z <br />Z <br />E001 <br />10/15/14 <br />