REFRIGERANT PIPING:
<br />NEOPRENE HANGER
<br />ISOLATORS
<br />II
<br />I I 1 II
<br />I I I II
<br />I I 1 II
<br />RETURN I I II
<br />A I R DUCT I I �� 1L_
<br />Li I
<br />FLOAT SWITCH: LOCATED AT LOW SPOT
<br />IN DRAIN PAN, TO SHUT DOWN UNIT
<br />IF WATER GETS INTO THE DRAIN PAN.
<br />CONDENSATE DRAIN AND P-TRAP:
<br />1" COPPER, 1/2" ARMAFLEX INSULATION
<br />DISCONNECT OR CIRCUIT
<br />BREAKER LOCATION: BY
<br />ELECTRICAL CONTRACTOR.
<br />SINGLE POINT SERVICE.
<br />I I-
<br />z LIJ I
<br />UNIT SHALL BE EQUIPPED WITH:
<br />ANTI -SHORT CYCLE TIMER
<br />CRANKCASE HEATER
<br />10 YEAR COMPRESSOR/COIL WARRANTY
<br />HIGH PRESSURE SWITCH
<br />LOW PRESSURE SWITCH
<br />LIQUID LINE FILTER/DRIER
<br />SUPPLY
<br />AIR
<br />DUCT
<br />SECURE TO PAD WITH \
<br />16 GAGE STRAP AND
<br />SCREWS. (2) PER SIDE
<br />AUXILLARY DRAIN PAN:
<br />22 GAUGE SHEET METAL
<br />SOLDERED WATER -TIGHT.
<br />2" DEEP & 3" LARGER
<br />THAN UNIT. SUPPORT
<br />FROM DUCTWORK ONLY.
<br />AIR HANDLER
<br />MARK
<br />---
<br />AHU-1
<br />AHU-2,3
<br />AHU-4
<br />MANUFACTURER
<br />---
<br />TRANE
<br />TRANE
<br />TRANE
<br />MODEL
<br />---
<br />GAM5BOA60
<br />GAM5BOA36
<br />GAM513OA48
<br />CAPACITY
<br />TONS
<br />5.0
<br />3.0
<br />4.0
<br />TOTAL COOLING
<br />MBH
<br />60
<br />36
<br />48
<br />SENSIBLE COOLING
<br />MBH
<br />45
<br />27
<br />36
<br />SUPPLY AIR
<br />CFM
<br />1800
<br />1200
<br />1600
<br />OUTSIDE AIR
<br />CFM
<br />200
<br />140
<br />225
<br />EXTERNAL STATIC PRESSURE
<br />IN H2O
<br />0.6
<br />0.6
<br />0.6
<br />FAN MOTOR
<br />HP/FLA
<br />1 /7.6
<br />1 /2/4. 1
<br />3/4/6
<br />ELECTRIC HEAT
<br />KW/VOLTS
<br />7.68
<br />7.68
<br />7.68
<br />FILTER TYPE
<br />---
<br />-
<br />-
<br />-
<br />ELECTRICAL DATA
<br />V/PH/HZ
<br />240/1
<br />240/1
<br />240/1
<br />MCA
<br />AMPS
<br />50
<br />45
<br />48
<br />MOCP
<br />AMPS
<br />50
<br />45
<br />50
<br />LOCATION
<br />---
<br />SEE PLAN
<br />SEE PLAN
<br />SEE PLAN
<br />WEIGHT
<br />LBS
<br />170
<br />142
<br />166
<br />HANGER SUPPORTS: ROUND 'SNAPLOCK" SHEET
<br />8' O.C. = 0-35" DUCTS METAL FOR RUN -OUTS
<br />6' O.C. = 36-59" DUCTS GREATER THAN 25', WITH
<br />( 1", 22 GAUGE - TYPICAL) 2" WRAP INSULATION. AN
<br />APPROVED EQUAL IS
<br />"SPIRO-PIPE"
<br />SPIN -IN FITTING:
<br />WITH SCOOP AND
<br />DAMPER, EXCEPT IN
<br />GYP. BOARD CEILINGS,
<br />DAMPER IN NECK
<br />-----------
<br />S S S N�
<br />AR EEC 1 TAPE AND MASTIC
<br />I I OUTER JACKET
<br />R �� \ I J (TYPICAL)
<br />- -
<br />I
<br />MINIMUM RADIUS EQUAL TO
<br />SADDLE: 22 GAUGE THE FLEX DUCT DIAMETER
<br />FLEXIBLE DUCT:
<br />MAXIMUM 25 FEET,
<br />DO NOT SAG OR
<br />KINK
<br />FIBERGLASS TAPE
<br />SUPPORTS TO
<br />PREVENT SAGS AND
<br />KINKS IN FLEX
<br />BAND CLAMP AND
<br />THREE SHEET METAL
<br />SCREWS THROUGH
<br />HELIX OF FLEXIBLE
<br />DUCT LINER
<br />(TYPICAL)
<br />24" MAXIMUM
<br />VERTICAL DUCT RUN
<br />REINFORCEMENT: WRAP INSULATION ABOVE CEILING DIFFUSER: SET
<br />0-24" = NOT REQUIRED THE CEILING DIFFUSERS THROW AS SHOWN ON PLANS
<br />25"+ = REQUIRED AT
<br />24" O.C.
<br />FIBERGLASS DUCT DETAIL
<br />1. FIBERGLASS DUCTS SHALL BE FABRICATED & INSTALLED PER THE LATEST
<br />EDITION OF SMACNA AND THE 2010 FLORIDA ENERGY CODE WITH LOCAL AMENDMENTS.
<br />MATERIAL SHALL BE 1-1/2" 800 El BOARD, WITH A MINIMUM 6.0 "R" VALUE
<br />AND BE NFPA 90A APPROVED.
<br />2. FABRICATION SHALL BE MACHINE CUT V-GROOVE OR SHIPLAP: BUTT JOINTS
<br />ARE NOT ACCEPTABLE. DUCT CLOSURE METHOD SHALL BE WITH GLASS FABRIC
<br />AND MASTIC USING "EPOLUX CADOPRENE 725", PRESSURE SENSITIVE TAPE, OR
<br />HEAT SEALABLE TAPE. ALL CLOSURE METHODS SHALL BE PER MANUFACTURERS
<br />INSTALLATION INSTRUCTIONS AND SHALL MEET THE REQUIREMENTS OF UL 181
<br />FOR A CLASS 1 AIR DUCT SYSTEM.
<br />3. SHEET METAL SLEEVES SHALL BE PROVIDED FOR; VOLUME DAMPERS, BRANCH
<br />TAKE -OFFS, REGISTER & GRILLE CONNECTIONS, RECTANGULAR DUCT
<br />CONNECTIONS, FIRE DAMPERS & DUCT HEATERS.
<br />4. REINFORCEMENT CHANNELS, OR TEES, SHALL BE PROVIDED AS NOTED ABOVE
<br />& AT ALL ELBOWS OR AT ALL BRANCH CONNECTIONS, PER FIGURE 4.1.
<br />5. HANGER SUPPORTS SHALL BE AS NOTED ABOVE (PER FIGURE 5-1D) FOR DUCTS
<br />UP TO 24", AND WITH TRAPEZE HANGERS (PER FIGURE 5-1B OR 5-1C) FOR
<br />DUCTS 25" AND ABOVE.
<br />6. ELBOWS SHALL BE SQUARE NECK (SAME IN OUT DIMENSION) WITH 2" DOUBLE
<br />THICKNESS TURNING VANES.
<br />7. OFFSETS SHALL NOT EXCEED 30' ANGLE, AND SHALL NOT REDUCE THE FREE
<br />AREA OF THE DUCT.
<br />8. TRANSITIONS SHALL NOT EXCEED 1:3 RATIO (4" TRANSITION PER FOOT
<br />SINGLE SIDED TRANSITION, AND 8" PER FOOT DOUBLE SIDED TRANSITION).
<br />9. RECTANGULAR BRANCH CONNECTIONS SHALL BE 45' ENTRY TYPE, WITH METAL
<br />SLEEVE & CLINCH LOCK CONNECTION. ENTRY LENGTH SHALL BE 25% OF BRANCH
<br />DUCT WIDTH.
<br />10. ROUND DUCT CONNECTIONS SHALL BE WITH "METAL MANUFACTURING COMPANY"
<br />TL-FD-6 SPIN -IN FITTINGS, WITH SCOOP, DAMPER AND HANDLE.
<br />11. FLEXIBLE ROUND DUCT SHALL INCLUDE: AN INNER POLYTHYLENE LINER, A
<br />SPRING HELIX, A 1-1/2" BLANKET INSULATION WITH MINIMUM 6.0 "R" VALUE
<br />AND AN ALUMINUM FOIL OUTER VAPOR BARRIER, AND BE UL-181 APPROVED.
<br />EQUIPMENT PAD B'.
<br />GENERAL CONTRACTOR
<br />DISCONNECT OR CIRCUIT
<br />BREAKER LOCATION: BY
<br />I ELECTRICAL CONTRACTOR.
<br />4
<br />rah' DO NOT MOUNT ON UNIT.
<br />ONTROL WIRING: APPROVED
<br />HIRE -TIES"
<br />EFRIGERANT PIPING:
<br />ERVICE VALVES: EXTERNAL
<br />D UNIT
<br />RATION ISOLATION PADS:
<br />3/8" THICK, RIBBED, NEOPRENE
<br />CONDENSER UNIT
<br />MARK
<br />---
<br />CU-1
<br />CU-2,3
<br />CU-4
<br />MANUFACTURER
<br />---
<br />TRANE
<br />TRANE
<br />TRANE
<br />MODEL
<br />---
<br />4TT8306OD1
<br />4TTB3036E1
<br />4TTB3048D1
<br />CAPACITY
<br />TONS
<br />5.0
<br />3.0
<br />4.0
<br />CIRCUITS
<br />NO.
<br />1
<br />1
<br />1
<br />EFFICIENCY
<br />SEER/EER
<br />13
<br />13
<br />13
<br />COMPRESSOR
<br />NO/RLA
<br />1/26.8
<br />1/15.3
<br />1/21.8
<br />CONDENSING FAN
<br />NO/FLA
<br />1 /0.93
<br />1 /0.74
<br />1 /1 .2
<br />ELECTRICAL DATA
<br />V/PH/HZ
<br />240/1
<br />240/1
<br />240/1
<br />MCA
<br />AMPS
<br />35
<br />20
<br />28
<br />MOCP
<br />AMPS
<br />60
<br />35
<br />50
<br />LOCATION
<br />---
<br />SEE PLAN
<br />SEE PLAN
<br />SEE PLAN
<br />WEIGHT
<br />LBS
<br />226
<br />159
<br />203
<br />NOTES
<br />---
<br />-
<br />-
<br />-
<br />HANGER SUPPORTS: 1/4"
<br />THREADED ROD & NEOPRENE
<br />ISOLATORS, DO NOT
<br />SUPPORT FROM CEILING
<br />DISCONNECT SWITCH:
<br />FURNISHED BY THE {
<br />MECHANICAL
<br />SUBCONTRACTOR
<br />i
<br />i
<br />VARIABLE SPEED i
<br />CONTROLLER L a 1
<br />CEILING
<br />11
<br />Z�
<br />SEAL ALL SHEET METAL
<br />DUCT WITH MASTIC
<br />ONLY (NO TAPE)
<br />- BACKDRAFT DAMPER:
<br />CLEAR OF SCREWS
<br />EXHAUST GRILLE: BY
<br />FAN MANUFACTURER
<br />CEILING FAN DETAIL
<br />MARK
<br />-
<br />TEF-1,2
<br />MANUFACTURER
<br />-
<br />GREENHECK
<br />MODEL
<br />-
<br />SP-B70
<br />SERVICE
<br />-
<br />SEE PLAN
<br />AIR QUANTITY
<br />CFM
<br />50
<br />EXTERNAL STATIC PRESSURE
<br />IN H2O
<br />0.3
<br />FAN TYPE
<br />-
<br />CENTRIFUGAL
<br />MAXIMUM FAN SPEED
<br />RPM
<br />643
<br />DRIVE
<br />-
<br />DIRECT
<br />MOTOR
<br />HP(W)
<br />45 W
<br />ELECTRICAL
<br />V/PH/HZ
<br />115/1
<br />CONTROLS
<br />-
<br />WITH LIGHTS
<br />SONES
<br />-
<br />2.0
<br />WEIGHT
<br />LBS.
<br />9
<br />NOTES
<br />-
<br />-
<br />MOUNTING ANGLES:
<br />1-1/2" x 1-1/2"
<br />WRAP INSULATION Al
<br />x 16 GA, FASTENED
<br />TO SLEEVE (ONLY)
<br />•
<br />WITH #10 SHEET
<br />BREAKAWAY CONNECTION: °
<br />METAL SCREWS ON
<br />PER FIGURE, SMACNA r
<br />8" CENTERS.
<br />"FIRE DAMPER & HEAT
<br />DO NOT FASTEN
<br />STOP GUIDE" 1981 TO
<br />AT CORNERS.
<br />EITHER SLEEVE (TYPE
<br />A) OR TO DAMPER I
<br />MAX 1/2"
<br />(FOR TYPE B) I
<br />CLEARANCE
<br />FIRE DAMPER.
<br />CLOSURE
<br />SIZE EQUAL TO I
<br />SPRING
<br />1/4" LESS THAN
<br />DUCT SIZE &
<br />FASTENED TO I I
<br />SLEEVE WITH
<br />DUCT: SIZE
<br />#8 SHEET METAL
<br />PER PLAN
<br />SCREWS ON 8"
<br />CENTERS .•.
<br />SLEEVE: SIZE & ;.
<br />FIRE -RATED LID:
<br />GAUGE TO MATCH
<br />OPENING BY GENERAL
<br />DUCT.
<br />CONTRACTOR. OPENING SIZE
<br />0-12" DUCT = 26 GA
<br />EQUAL TO DUCT SIZE PLUS
<br />13-30" DUCT = 24 GA MAX 6" �
<br />1/4" PER FOOT OF DUCT
<br />31-54" DUCT = 22 GA SLEEVE
<br />SIZE, TO ALLOW CLEARANCE
<br />55-84" DUCT = 20 GA EXTENSION
<br />OF OF 1/8" PER FOOT OF DUCT
<br />SIZE.
<br />HORIZONTAL FIRE DAMPER DETAIL
<br />1. ALL FIRE DAMPERS SHALL BE UL 555 APPROVED.
<br />2. FIRE DAMPERS WITH INTEGRAL SLEEVE AND FACTORY MOUNTING ANGLES ARE
<br />ACCEPTABLE (RUSKIN OR EQUAL).
<br />3. INSTALLATION SHALL COMPLY WITH UL APPROVED INSTALLATION INSTRUCTIONS.
<br />4. HORIZONTAL DAMPERS SHALL HAVE A STAINLESS STEEL CLOSURE SPRING
<br />FOR OPERATION OF THE DAMPER.
<br />5. PROVIDE AN ACCESS DOOR, MINIMUM 10"00", ADJACENT TO THE FUSIBLE
<br />LINK OF EACH DAMPER. DOOR SHALL BE FACTORY FABRICATED, WITH 24 GA
<br />FRAME & DOOR, FIBERGLASS INSULATION, NEOPRENE GASKETING, & CAM -LOCK
<br />FASTENERS.
<br />6. LOCATION OF FIRE DAMPERS SHALL BE AS SHOWN ON THE PLAN, WITH THE
<br />STANDARD SYMBOL 1- POINTING TO THE LOCATION OF A TYPE "A" FIRE
<br />DAMPER, AND THE STANDARD SYMBOL (B)IO POINTING TO THE LOCATION
<br />OF A TYPE "B" FIRE DAMPER.
<br />BIRDSCREEN
<br />FACTORY CURB:
<br />SEE DETAIL
<br />ROOF
<br />COORDINATE WITH OTHER
<br />TRADES TO AVOID PIPING
<br />& CONDUIT INTERFERENCES
<br />WITH ROOF INTAKE DUCTWORK
<br />ROOF INTAKE DETAIL
<br />REMOVABLE TOP:
<br />SPUN ALUMINUM
<br />ROOF INTAKE DUCTWORK:
<br />NO INSULATION, MASTIC
<br />SEAL
<br />�- REFRIGERATION PIPING
<br />PIPE CLAMPS:
<br />"HYDRO ZORB" OR
<br />"SUPER -STRUT",
<br />WITH SIZE TO MATCH
<br />ELECTRICAL CONDUIT.
<br />SUPPORT CHANNEL:
<br />"HYDRO ZORB" OR
<br />"SUPER -STRUT"
<br />REFRIGERANT PIPING DETAIL
<br />1. ALL REFRIGERANT PIPING SHALL BE HARD COPPER, ACR TYPE "L",
<br />WITH LONG RADIUS ELBOWS AND WROUGHT FITTINGS.
<br />2. TRAPS SHALL BE SINGLE PIECE, WROUGHT COPPER.
<br />3. INSULATE SUCTION LINES FULL LENGTH WITH "ARMAFLEX"
<br />INSULATION. THICKNESS SHALL BE 1/2" UP THROUGH 7/8" SUCTION
<br />LINE SIZE, WITH 3/4" THICKNESS FOR 1-1/8" SUCTION LINES & ABOVE
<br />ALL INSULATION SHALL BE ASTM E84 APPROVED (FLAME SPREAD OF 25,
<br />SMOKE DENSITY OF 50).
<br />4. INSULATION SHALL NOT BE SPLIT DURING INSTALLATION.
<br />5. ROUTING OF ALL REFRIGERANT PIPING SHALL BE "SQUARE WITH"
<br />BUILDING LINES. HORIZONTAL PIPING SHALL BE SLOPED AT THE
<br />RATE OF (1) INCH FOR EACH (10) FEET, TOWARD THE COMPRESSOR.
<br />6. SUPPORT OF THE REFRIGERANT PIPING AT THE COMPRESSORS,
<br />CONDENSERS, AND AIR HANDLING UNITS SHALL BE AS SHOWN ABOVE.
<br />7. SUPPORT OF THE REFRIGERANT PIPING, IN CEILING PLENUMS, SHALL
<br />BE WITH STRAP HANGERS, SHEET METAL "SADDLES", WITH 3/4"
<br />INSULATION TO ELIMINATE ANY METAL -TO -METAL CONTACT.
<br />8. BRAZE ALL REFRIGERANT PIPING WITH A FLOW OF DRY NITROGEN
<br />DURING THE BRAZING OPERATIONS.
<br />9. SOLDER SHALL BE 15% SILVER "SIL-FOS" OR EQUAL.
<br />10. CHANGE FILTER -DRIER CORES AFTER 30 DAYS OF OPERATION. SAVE
<br />CORES FOR INSPECTION BY TEST & BALNCE, OR BY OWNERS
<br />REPRESENTATIVE INSPECTION.
<br />SEEDS Engineering, Inc.
<br />27730 Santa Anita Blvd. p: (813) 902-2515
<br />Wesley Chapel, FL 33544 f: (813) 902-2516
<br />jmakar@seedseng.com
<br />Florida Certificate of Authorization No. 28278
<br />Wiedrick
<br />Architecture, I nc.
<br />WIEDRICK ARCHITECTURE INC.
<br />AA26001799
<br />2020 HEIDELBERG AVE.
<br />DUNEDIN, FLORIDA, 34698
<br />727.736.8627
<br />51 A I E OF I-LUKIUA
<br />REGISTERED ARCHITECT:
<br />MATTHEW WIEDRICK
<br />AR94577
<br />No.54827
<br />r STATE OF
<br />o,� '�<oRioP •�w� o:
<br />F• � e
<br />ALENG
<br />t'KVJt_u I HUUKtJJ:
<br />38444 5TH AVE.
<br />ZEPHYRHILLS, FL 33542
<br />CLIENT:
<br />FLORIDA PHARMACY
<br />SOLUTIONS, INC.
<br />13933 17TH ST. SUITE 300
<br />DADE CITY, FL 33525
<br />MECHANICAL NOTES AND DETAILS