REFRIGERANT PIPING: <br />NEOPRENE HANGER <br />ISOLATORS <br />II <br />I I 1 II <br />I I I II <br />I I 1 II <br />RETURN I I II <br />A I R DUCT I I �� 1L_ <br />Li I <br />FLOAT SWITCH: LOCATED AT LOW SPOT <br />IN DRAIN PAN, TO SHUT DOWN UNIT <br />IF WATER GETS INTO THE DRAIN PAN. <br />CONDENSATE DRAIN AND P-TRAP: <br />1" COPPER, 1/2" ARMAFLEX INSULATION <br />DISCONNECT OR CIRCUIT <br />BREAKER LOCATION: BY <br />ELECTRICAL CONTRACTOR. <br />SINGLE POINT SERVICE. <br />I I- <br />z LIJ I <br />UNIT SHALL BE EQUIPPED WITH: <br />ANTI -SHORT CYCLE TIMER <br />CRANKCASE HEATER <br />10 YEAR COMPRESSOR/COIL WARRANTY <br />HIGH PRESSURE SWITCH <br />LOW PRESSURE SWITCH <br />LIQUID LINE FILTER/DRIER <br />SUPPLY <br />AIR <br />DUCT <br />SECURE TO PAD WITH \ <br />16 GAGE STRAP AND <br />SCREWS. (2) PER SIDE <br />AUXILLARY DRAIN PAN: <br />22 GAUGE SHEET METAL <br />SOLDERED WATER -TIGHT. <br />2" DEEP & 3" LARGER <br />THAN UNIT. SUPPORT <br />FROM DUCTWORK ONLY. <br />AIR HANDLER <br />MARK <br />--- <br />AHU-1 <br />AHU-2,3 <br />AHU-4 <br />MANUFACTURER <br />--- <br />TRANE <br />TRANE <br />TRANE <br />MODEL <br />--- <br />GAM5BOA60 <br />GAM5BOA36 <br />GAM513OA48 <br />CAPACITY <br />TONS <br />5.0 <br />3.0 <br />4.0 <br />TOTAL COOLING <br />MBH <br />60 <br />36 <br />48 <br />SENSIBLE COOLING <br />MBH <br />45 <br />27 <br />36 <br />SUPPLY AIR <br />CFM <br />1800 <br />1200 <br />1600 <br />OUTSIDE AIR <br />CFM <br />200 <br />140 <br />225 <br />EXTERNAL STATIC PRESSURE <br />IN H2O <br />0.6 <br />0.6 <br />0.6 <br />FAN MOTOR <br />HP/FLA <br />1 /7.6 <br />1 /2/4. 1 <br />3/4/6 <br />ELECTRIC HEAT <br />KW/VOLTS <br />7.68 <br />7.68 <br />7.68 <br />FILTER TYPE <br />--- <br />- <br />- <br />- <br />ELECTRICAL DATA <br />V/PH/HZ <br />240/1 <br />240/1 <br />240/1 <br />MCA <br />AMPS <br />50 <br />45 <br />48 <br />MOCP <br />AMPS <br />50 <br />45 <br />50 <br />LOCATION <br />--- <br />SEE PLAN <br />SEE PLAN <br />SEE PLAN <br />WEIGHT <br />LBS <br />170 <br />142 <br />166 <br />HANGER SUPPORTS: ROUND 'SNAPLOCK" SHEET <br />8' O.C. = 0-35" DUCTS METAL FOR RUN -OUTS <br />6' O.C. = 36-59" DUCTS GREATER THAN 25', WITH <br />( 1", 22 GAUGE - TYPICAL) 2" WRAP INSULATION. AN <br />APPROVED EQUAL IS <br />"SPIRO-PIPE" <br />SPIN -IN FITTING: <br />WITH SCOOP AND <br />DAMPER, EXCEPT IN <br />GYP. BOARD CEILINGS, <br />DAMPER IN NECK <br />----------- <br />S S S N� <br />AR EEC 1 TAPE AND MASTIC <br />I I OUTER JACKET <br />R �� \ I J (TYPICAL) <br />- - <br />I <br />MINIMUM RADIUS EQUAL TO <br />SADDLE: 22 GAUGE THE FLEX DUCT DIAMETER <br />FLEXIBLE DUCT: <br />MAXIMUM 25 FEET, <br />DO NOT SAG OR <br />KINK <br />FIBERGLASS TAPE <br />SUPPORTS TO <br />PREVENT SAGS AND <br />KINKS IN FLEX <br />BAND CLAMP AND <br />THREE SHEET METAL <br />SCREWS THROUGH <br />HELIX OF FLEXIBLE <br />DUCT LINER <br />(TYPICAL) <br />24" MAXIMUM <br />VERTICAL DUCT RUN <br />REINFORCEMENT: WRAP INSULATION ABOVE CEILING DIFFUSER: SET <br />0-24" = NOT REQUIRED THE CEILING DIFFUSERS THROW AS SHOWN ON PLANS <br />25"+ = REQUIRED AT <br />24" O.C. <br />FIBERGLASS DUCT DETAIL <br />1. FIBERGLASS DUCTS SHALL BE FABRICATED & INSTALLED PER THE LATEST <br />EDITION OF SMACNA AND THE 2010 FLORIDA ENERGY CODE WITH LOCAL AMENDMENTS. <br />MATERIAL SHALL BE 1-1/2" 800 El BOARD, WITH A MINIMUM 6.0 "R" VALUE <br />AND BE NFPA 90A APPROVED. <br />2. FABRICATION SHALL BE MACHINE CUT V-GROOVE OR SHIPLAP: BUTT JOINTS <br />ARE NOT ACCEPTABLE. DUCT CLOSURE METHOD SHALL BE WITH GLASS FABRIC <br />AND MASTIC USING "EPOLUX CADOPRENE 725", PRESSURE SENSITIVE TAPE, OR <br />HEAT SEALABLE TAPE. ALL CLOSURE METHODS SHALL BE PER MANUFACTURERS <br />INSTALLATION INSTRUCTIONS AND SHALL MEET THE REQUIREMENTS OF UL 181 <br />FOR A CLASS 1 AIR DUCT SYSTEM. <br />3. SHEET METAL SLEEVES SHALL BE PROVIDED FOR; VOLUME DAMPERS, BRANCH <br />TAKE -OFFS, REGISTER & GRILLE CONNECTIONS, RECTANGULAR DUCT <br />CONNECTIONS, FIRE DAMPERS & DUCT HEATERS. <br />4. REINFORCEMENT CHANNELS, OR TEES, SHALL BE PROVIDED AS NOTED ABOVE <br />& AT ALL ELBOWS OR AT ALL BRANCH CONNECTIONS, PER FIGURE 4.1. <br />5. HANGER SUPPORTS SHALL BE AS NOTED ABOVE (PER FIGURE 5-1D) FOR DUCTS <br />UP TO 24", AND WITH TRAPEZE HANGERS (PER FIGURE 5-1B OR 5-1C) FOR <br />DUCTS 25" AND ABOVE. <br />6. ELBOWS SHALL BE SQUARE NECK (SAME IN OUT DIMENSION) WITH 2" DOUBLE <br />THICKNESS TURNING VANES. <br />7. OFFSETS SHALL NOT EXCEED 30' ANGLE, AND SHALL NOT REDUCE THE FREE <br />AREA OF THE DUCT. <br />8. TRANSITIONS SHALL NOT EXCEED 1:3 RATIO (4" TRANSITION PER FOOT <br />SINGLE SIDED TRANSITION, AND 8" PER FOOT DOUBLE SIDED TRANSITION). <br />9. RECTANGULAR BRANCH CONNECTIONS SHALL BE 45' ENTRY TYPE, WITH METAL <br />SLEEVE & CLINCH LOCK CONNECTION. ENTRY LENGTH SHALL BE 25% OF BRANCH <br />DUCT WIDTH. <br />10. ROUND DUCT CONNECTIONS SHALL BE WITH "METAL MANUFACTURING COMPANY" <br />TL-FD-6 SPIN -IN FITTINGS, WITH SCOOP, DAMPER AND HANDLE. <br />11. FLEXIBLE ROUND DUCT SHALL INCLUDE: AN INNER POLYTHYLENE LINER, A <br />SPRING HELIX, A 1-1/2" BLANKET INSULATION WITH MINIMUM 6.0 "R" VALUE <br />AND AN ALUMINUM FOIL OUTER VAPOR BARRIER, AND BE UL-181 APPROVED. <br />EQUIPMENT PAD B'. <br />GENERAL CONTRACTOR <br />DISCONNECT OR CIRCUIT <br />BREAKER LOCATION: BY <br />I ELECTRICAL CONTRACTOR. <br />4 <br />rah' DO NOT MOUNT ON UNIT. <br />ONTROL WIRING: APPROVED <br />HIRE -TIES" <br />EFRIGERANT PIPING: <br />ERVICE VALVES: EXTERNAL <br />D UNIT <br />RATION ISOLATION PADS: <br />3/8" THICK, RIBBED, NEOPRENE <br />CONDENSER UNIT <br />MARK <br />--- <br />CU-1 <br />CU-2,3 <br />CU-4 <br />MANUFACTURER <br />--- <br />TRANE <br />TRANE <br />TRANE <br />MODEL <br />--- <br />4TT8306OD1 <br />4TTB3036E1 <br />4TTB3048D1 <br />CAPACITY <br />TONS <br />5.0 <br />3.0 <br />4.0 <br />CIRCUITS <br />NO. <br />1 <br />1 <br />1 <br />EFFICIENCY <br />SEER/EER <br />13 <br />13 <br />13 <br />COMPRESSOR <br />NO/RLA <br />1/26.8 <br />1/15.3 <br />1/21.8 <br />CONDENSING FAN <br />NO/FLA <br />1 /0.93 <br />1 /0.74 <br />1 /1 .2 <br />ELECTRICAL DATA <br />V/PH/HZ <br />240/1 <br />240/1 <br />240/1 <br />MCA <br />AMPS <br />35 <br />20 <br />28 <br />MOCP <br />AMPS <br />60 <br />35 <br />50 <br />LOCATION <br />--- <br />SEE PLAN <br />SEE PLAN <br />SEE PLAN <br />WEIGHT <br />LBS <br />226 <br />159 <br />203 <br />NOTES <br />--- <br />- <br />- <br />- <br />HANGER SUPPORTS: 1/4" <br />THREADED ROD & NEOPRENE <br />ISOLATORS, DO NOT <br />SUPPORT FROM CEILING <br />DISCONNECT SWITCH: <br />FURNISHED BY THE { <br />MECHANICAL <br />SUBCONTRACTOR <br />i <br />i <br />VARIABLE SPEED i <br />CONTROLLER L a 1 <br />CEILING <br />11 <br />Z� <br />SEAL ALL SHEET METAL <br />DUCT WITH MASTIC <br />ONLY (NO TAPE) <br />- BACKDRAFT DAMPER: <br />CLEAR OF SCREWS <br />EXHAUST GRILLE: BY <br />FAN MANUFACTURER <br />CEILING FAN DETAIL <br />MARK <br />- <br />TEF-1,2 <br />MANUFACTURER <br />- <br />GREENHECK <br />MODEL <br />- <br />SP-B70 <br />SERVICE <br />- <br />SEE PLAN <br />AIR QUANTITY <br />CFM <br />50 <br />EXTERNAL STATIC PRESSURE <br />IN H2O <br />0.3 <br />FAN TYPE <br />- <br />CENTRIFUGAL <br />MAXIMUM FAN SPEED <br />RPM <br />643 <br />DRIVE <br />- <br />DIRECT <br />MOTOR <br />HP(W) <br />45 W <br />ELECTRICAL <br />V/PH/HZ <br />115/1 <br />CONTROLS <br />- <br />WITH LIGHTS <br />SONES <br />- <br />2.0 <br />WEIGHT <br />LBS. <br />9 <br />NOTES <br />- <br />- <br />MOUNTING ANGLES: <br />1-1/2" x 1-1/2" <br />WRAP INSULATION Al <br />x 16 GA, FASTENED <br />TO SLEEVE (ONLY) <br />• <br />WITH #10 SHEET <br />BREAKAWAY CONNECTION: ° <br />METAL SCREWS ON <br />PER FIGURE, SMACNA r <br />8" CENTERS. <br />"FIRE DAMPER & HEAT <br />DO NOT FASTEN <br />STOP GUIDE" 1981 TO <br />AT CORNERS. <br />EITHER SLEEVE (TYPE <br />A) OR TO DAMPER I <br />MAX 1/2" <br />(FOR TYPE B) I <br />CLEARANCE <br />FIRE DAMPER. <br />CLOSURE <br />SIZE EQUAL TO I <br />SPRING <br />1/4" LESS THAN <br />DUCT SIZE & <br />FASTENED TO I I <br />SLEEVE WITH <br />DUCT: SIZE <br />#8 SHEET METAL <br />PER PLAN <br />SCREWS ON 8" <br />CENTERS .•. <br />SLEEVE: SIZE & ;. <br />FIRE -RATED LID: <br />GAUGE TO MATCH <br />OPENING BY GENERAL <br />DUCT. <br />CONTRACTOR. OPENING SIZE <br />0-12" DUCT = 26 GA <br />EQUAL TO DUCT SIZE PLUS <br />13-30" DUCT = 24 GA MAX 6" � <br />1/4" PER FOOT OF DUCT <br />31-54" DUCT = 22 GA SLEEVE <br />SIZE, TO ALLOW CLEARANCE <br />55-84" DUCT = 20 GA EXTENSION <br />OF OF 1/8" PER FOOT OF DUCT <br />SIZE. <br />HORIZONTAL FIRE DAMPER DETAIL <br />1. ALL FIRE DAMPERS SHALL BE UL 555 APPROVED. <br />2. FIRE DAMPERS WITH INTEGRAL SLEEVE AND FACTORY MOUNTING ANGLES ARE <br />ACCEPTABLE (RUSKIN OR EQUAL). <br />3. INSTALLATION SHALL COMPLY WITH UL APPROVED INSTALLATION INSTRUCTIONS. <br />4. HORIZONTAL DAMPERS SHALL HAVE A STAINLESS STEEL CLOSURE SPRING <br />FOR OPERATION OF THE DAMPER. <br />5. PROVIDE AN ACCESS DOOR, MINIMUM 10"00", ADJACENT TO THE FUSIBLE <br />LINK OF EACH DAMPER. DOOR SHALL BE FACTORY FABRICATED, WITH 24 GA <br />FRAME & DOOR, FIBERGLASS INSULATION, NEOPRENE GASKETING, & CAM -LOCK <br />FASTENERS. <br />6. LOCATION OF FIRE DAMPERS SHALL BE AS SHOWN ON THE PLAN, WITH THE <br />STANDARD SYMBOL 1- POINTING TO THE LOCATION OF A TYPE "A" FIRE <br />DAMPER, AND THE STANDARD SYMBOL (B)IO POINTING TO THE LOCATION <br />OF A TYPE "B" FIRE DAMPER. <br />BIRDSCREEN <br />FACTORY CURB: <br />SEE DETAIL <br />ROOF <br />COORDINATE WITH OTHER <br />TRADES TO AVOID PIPING <br />& CONDUIT INTERFERENCES <br />WITH ROOF INTAKE DUCTWORK <br />ROOF INTAKE DETAIL <br />REMOVABLE TOP: <br />SPUN ALUMINUM <br />ROOF INTAKE DUCTWORK: <br />NO INSULATION, MASTIC <br />SEAL <br />�- REFRIGERATION PIPING <br />PIPE CLAMPS: <br />"HYDRO ZORB" OR <br />"SUPER -STRUT", <br />WITH SIZE TO MATCH <br />ELECTRICAL CONDUIT. <br />SUPPORT CHANNEL: <br />"HYDRO ZORB" OR <br />"SUPER -STRUT" <br />REFRIGERANT PIPING DETAIL <br />1. ALL REFRIGERANT PIPING SHALL BE HARD COPPER, ACR TYPE "L", <br />WITH LONG RADIUS ELBOWS AND WROUGHT FITTINGS. <br />2. TRAPS SHALL BE SINGLE PIECE, WROUGHT COPPER. <br />3. INSULATE SUCTION LINES FULL LENGTH WITH "ARMAFLEX" <br />INSULATION. THICKNESS SHALL BE 1/2" UP THROUGH 7/8" SUCTION <br />LINE SIZE, WITH 3/4" THICKNESS FOR 1-1/8" SUCTION LINES & ABOVE <br />ALL INSULATION SHALL BE ASTM E84 APPROVED (FLAME SPREAD OF 25, <br />SMOKE DENSITY OF 50). <br />4. INSULATION SHALL NOT BE SPLIT DURING INSTALLATION. <br />5. ROUTING OF ALL REFRIGERANT PIPING SHALL BE "SQUARE WITH" <br />BUILDING LINES. HORIZONTAL PIPING SHALL BE SLOPED AT THE <br />RATE OF (1) INCH FOR EACH (10) FEET, TOWARD THE COMPRESSOR. <br />6. SUPPORT OF THE REFRIGERANT PIPING AT THE COMPRESSORS, <br />CONDENSERS, AND AIR HANDLING UNITS SHALL BE AS SHOWN ABOVE. <br />7. SUPPORT OF THE REFRIGERANT PIPING, IN CEILING PLENUMS, SHALL <br />BE WITH STRAP HANGERS, SHEET METAL "SADDLES", WITH 3/4" <br />INSULATION TO ELIMINATE ANY METAL -TO -METAL CONTACT. <br />8. BRAZE ALL REFRIGERANT PIPING WITH A FLOW OF DRY NITROGEN <br />DURING THE BRAZING OPERATIONS. <br />9. SOLDER SHALL BE 15% SILVER "SIL-FOS" OR EQUAL. <br />10. CHANGE FILTER -DRIER CORES AFTER 30 DAYS OF OPERATION. SAVE <br />CORES FOR INSPECTION BY TEST & BALNCE, OR BY OWNERS <br />REPRESENTATIVE INSPECTION. <br />SEEDS Engineering, Inc. <br />27730 Santa Anita Blvd. p: (813) 902-2515 <br />Wesley Chapel, FL 33544 f: (813) 902-2516 <br />jmakar@seedseng.com <br />Florida Certificate of Authorization No. 28278 <br />Wiedrick <br />Architecture, I nc. <br />WIEDRICK ARCHITECTURE INC. <br />AA26001799 <br />2020 HEIDELBERG AVE. <br />DUNEDIN, FLORIDA, 34698 <br />727.736.8627 <br />51 A I E OF I-LUKIUA <br />REGISTERED ARCHITECT: <br />MATTHEW WIEDRICK <br />AR94577 <br />No.54827 <br />r STATE OF <br />o,� '�<oRioP •�w� o: <br />F• � e <br />ALENG <br />t'KVJt_u I HUUKtJJ: <br />38444 5TH AVE. <br />ZEPHYRHILLS, FL 33542 <br />CLIENT: <br />FLORIDA PHARMACY <br />SOLUTIONS, INC. <br />13933 17TH ST. SUITE 300 <br />DADE CITY, FL 33525 <br />MECHANICAL NOTES AND DETAILS <br />PROJECT #: 14022 <br />