EXTEND NEW 1-1/4" GAS PIPING TO EXISTING PIPING. J <br />CONTRACTOR SHALL ENSURE THAT POINT OF i l <br />CONNECTION IS AT LOCATION IN PIPE THAT WILL ACCEPT <br />AN ADDITIONAL 160 MBH LOAD. AFTER VERIFYING <br />EXISTING CAPACITY, IF EXISTING SYSTEM WILL NOT <br />ACCOMMODATE NEW LOAD, CONTRACTOR MUST <br />COORDINATE WITH LOCAL UTILITY FOR INCREASED <br />SERVICE CAPACITY. <br />ROUTE GAS PIPING <br />ON FACE OF WALL <br />WHEN ALLOWED <br />BY AHJ <br />DIRT LEG <br />GAS COCK <br />1-1/4" MECHANICAL <br />SOLENOID VALVE <br />BELOW CEILING <br />1-1/4" 160 MBH <br />INSTALL QUIK <br />DISCONNECT <br />TO FRYER <br />GAS COCK <br />(TYPICAL) - <br />GAS RISER PLAN N.T.S. I E <br />CONNECT TOBER <br />EXISTING PLUM��w <br />VERIFY LOCATI <br />I XIST. <br />I 1 /2"CW <br />1/2"CW I EXIST. <br />1/2"HW I 11/2"HW <br />I I <br />NEW HAND SINK <br />W/FOOT PEDAL <br />NEW HAND SINK <br />W/FOOT PEDAL <br />WATER RISER PLAN N.T.S. <br />I <br />EXIST. <br />1 1/2" <br />I VENT <br />NEW <br />I NEW <br />NEW <br />HAND <br />SINK <br />I HAND <br />-IjSINK <br />1 1/2" <br />SAN. <br />P.O.C. <br />EXIST. <br />54FIN. <br />1 1/2" <br />EXIST. <br />FLR. SAN. <br />2"SAN. <br />N EW`_- <br />3 <br />THE EQUIPMENT ROUGH -IN ITEMS AND THEIR DIMENSIONED LOCATIONS <br />FOR ALL CONNECTIONS ARE ACCURATE TO THE BEST OF OUR KNOWLEDGE <br />AND SHALL BE VERIFIED WITH THE EQUIPMENT SUPPLIER, OWNER AND/OR <br />THE EQUIPMENT ROUGH -IN DRAWINGS. IN SOME INSTANCES, THE OWNER <br />OR SUPPLIER MAY MAKE SUBSTITUTIONS OR THE EQUIPMENT ITEM MAY <br />VARY FROM WHAT IS SHOWN ON THE PLAN. THEREFORE, THE <br />ARCHITECT/ENGINEER SHALL BE IMMEDIATELY NOTIFIED, PRIOR TO <br />CONSTRUCTION OF ANY DEVIATIONS FROM WHAT IS SHOWN OR IMPLIED <br />ON THESE DRAWINGS. FAILURE OF THE APPROPRIATE CONTRACTOR TO <br />VERIFY ROUGH -INS OR THEIR LOCATIONS SHALL PACE THE <br />RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION AND/OR ADDITIONAL <br />ROUGH -INS DIRECTLY UPON THE CONTRACTOR. <br />A. ALL WORK SHALL BE IN ACCORDANCE WITH THE RULES AND <br />REGULATIONS OF CITY, AND/OR STATE. <br />B. ALL AUTHORITIES HAVING JURISDICTION SHALL BE NOTIFIED AT LEAST <br />THREE WORKING DAYS PRIOR TO COMMENCEMENT OF WORK. <br />C. ALL PIPING SHALL BE ROUTED IN THE SUSPENDED CEILING SPACE <br />UNLESS OTHERWISE INDICATED. ALL PIPING EXPOSED TO VIEW SHALL <br />BE ROUTED AS HIGH AS POSSIBLE AND TIGHT TO THE UNDERSIDE OF <br />THE STRUCTURAL STEEL. <br />D. EXPOSED PIPING IN FINISHED AREAS SHALL BE CHROME PLATED WITH <br />CHROME PLATED ESCUTCHEON AT PIPE ENTRY TO FINISHED AREA. <br />E. SLEEVE OR CORE -DRILL FLOOR SLABS, WALLS, ETC. AS REQUIRED FOR <br />PIPING AND FIRE -STOP OPENING AROUND PIPE VERIFY LOCATION OF <br />STRUCTURAL BEAMS, JOISTS, ETC. BEFORE DRILLING. <br />F. ALL OPENINGS IN DRAINAGE AND/OR VENT SYSTEMS AS A RESULT OF <br />INSTALLATION ROUGH -IN SHALL BE PROTECTED WITH A TEST PLUG THAT <br />IS SECURELY LOCKED IN PLACE UNTIL FINAL FINISHED CONNECTIONS <br />ARE INSTALLED. <br />G. ALL PIPING SHALL BE CONCEALED IN WALLS AND BEHIND FIXED <br />FURNISHINGS UNLESS OTHERWISE INDICATED. <br />H. WHEREVER FOUNDATION WALLS, OUTSIDE WALLS, ROOF, ETC. ARE <br />PENETRATED FOR INSTALLATION OF SYSTEMS, THEY SHALL BE PATCHED <br />TO MATCH EXISTING CONSTRUCTION AND SEALED WEATHER TIGHT. <br />WORK SHALL BE PERFORMED BY CRAFTSMEN SKILLED IN THEIR <br />RESPECTIVE TRADES. <br />F I. ALL PIPING SHALL BE RUN PARALLEL TO BUILDING LINES AND <br />SUPPORTED AND ANCHORED AS REQUIRED TO FACILITATE EXPANSION <br />AND CONTRACTION. ALL PIPING SHALL BE CONCEALED EXCEPT IN <br />UNFINISHED SPACES. INSTALL AS REQUIRED TO MEET ALL <br />CONSTRUCTION CONDITIONS AND TO ALLOW FOR INSTALLATION OF <br />OTHER WORK INCLUDING DUCTS AND ELECTRICAL CONDUIT. AT ALL <br />CONNECTIONS BETWEEN FERROUS PIPING AND NONFERROUS PIPING, <br />PROVIDE AN ISOLATING DIELECTRIC UNION. <br />J. PROVIDE ALL FITTINGS, ACCESSORIES, OFFSETS, AND MATERIALS <br />NECESSARY TO FACILITATE THE PLUMBING SYSTEM'S FUNCTIONING AS <br />INDICATED BY THE DESIGN AND THE EQUIPMENT INDICATED. <br />K. ALL DRAINAGE PIPING SHALL BE UNIFORMLY PITCHED, 1/4" PER FOOT <br />UNLESS OTHERWISE REQUIRED BY EXISTING CONDITIONS. <br />L. PROVIDE A COMPLETE SYSTEM OF COPPER, STEEL OR PLASTIC VENT <br />RISERS ABOVE FLOOR. ALL VENTS SHALL BE CARRIED THROUGH THE <br />ROOF WITH FLASHING. PLASTIC IS PREFERRED BY OWNER IF ALLOWED <br />BY AUTHORITIES. PLASTIC PIPING, IF PERMITTED, SHALL NOT BE FOAM <br />CORE P.V.C. <br />M. CONDENSATE AND INDIRECT DRAIN PIPING SHALL BE COPPER OR <br />PLASTIC TUBING. PLASTIC IS PREFERRED BY OWNER IF ALLOWED BY <br />AUTHORITIES. PLASTIC PIPING, IF PERMITTED, SHALL NOT BE FOAM <br />CORE P.V.C. <br />N. PROVIDE CLEAN -OUTS AT THE END OF EACH HORIZONTAL RUN, AND AT <br />THE BASE OF ALL VERTICAL WASTE AND DRAIN PIPES. CLEAN -OUTS <br />SHALL BE OF THE SAME SIZE AS THE PIPES THEY SERVE. <br />SANITARY RISER PLAN N.T.S. I G <br />17 � N <br />NEW <br />1-1 /4"GAS , <br />I € <br />E <br />14 4 5 ..`s, <br />11 <br />I <br />I <br />I <br />1 <br />I <br />I <br />I <br />1 <br />O. HOT AND COLD WATER PIPING SHALL BE TYPE "L" COPPER PIPE ABOVE <br />GRADE AND TYPE "K" COPPER PIPE BELOW GRADE, FITTINGS AS <br />REQUIRED BY LOCAL AUTHORITIES. PROVIDE WATER HAMMER <br />ARRESTORS WADE "SHOKSTOP" MODEL NO. W-5 THROUGH W-100, SIZE <br />AS INDICATED BY MANUFACTURER, WHERE SHOWN ON THE DRAWINGS. <br />INSTALL STOP VALVE IN AN ACCESSIBLE LOCATION IN EACH WATER <br />SUPPLY TO EACH FIXTURE. <br />P. INSULATE ALL HOT AND COLD WATER PIPING BOTH VERTICALLY AND <br />HORIZONTALLY, IN CEILING AND CONCEALED IN WALLS COMPLETELY. <br />PROVIDE 1" PREFORMED FIBERGLASS ASJ-VB, FLAME SPREAD 25, <br />SMOKE DEVELOPED 50, ASTM C-547. <br />Q. PIPING ROUTED IN EXTERIOR WALLS SHALL BE ROUTED ON THE <br />WINTER -WARM -SIDE OF THE BUILDING WALL INSULATION. <br />R. ACCESS PANELS SHALL BE PROVIDED WHERE CONCEALED CONTROL <br />DEVICES, VALVES, ETC. ARE CONCEALED WITHIN WALLS. WHERE <br />ACCESS FOR ADJUSTMENT AND MAINTENANCE IS POSSIBLE THROUGH <br />LAY -IN SUSPENDED CEILINGS, ACCESS PANELS ARE NOT REQUIRED. <br />�S. PROVIDE A COMPLETE NATURAL GAS PIPING SYSTEM AS NOTED ON THE <br />DRAWINGS. PIPE AND FITTINGS SHALL BE AS REQUIRED BY LOCAL <br />AUTHORITIES. PROV <br />IDE ALL UNIONS SHUT-OFF VALVES AND DIRT LEGS <br />REQUIRED BY NFPA-54 AND GOVERNING LOCAL CODES. PROVIDE ALL <br />TEST, METERS, INSPECTIONS, HANGERS AND EQUIPMENT CONNECTION <br />REQUIRED FOR A COMPLETE AND OPERATING SYSTEM. PAINT PIPING ON <br />ROOF WITH TWO COATS OF RUST RESISTANT OUTDOOR PAINT, <br />T. DRAINAGE PIPING UNDERGROUND SHALL BE CAST IRON OR PLASTIC <br />PIPE AND FITTINGS. PLASTIC IS PREFERRED BY OWNER IF ALLOWED BY <br />AUTHORITIES. PLASTIC PIPING IF PERMITTED, SHALL NOT BE FOAM CORE <br />P.V.C. <br />U. DRAINAGE PIPING INSIDE THE BUILDING SHALL BE CAST IRON OR <br />PLASTIC PIPE AND FITTINGS. PLASTIC IS PREFERRED BY OWNER IF <br />ALLOWED BY AUTHORITIES. PLASTIC PIPING, IF PERMITTED, SHALL NOT <br />BE FOAM CORE P.V.C. <br />V. EXISTING CONDITIONS ARE BASED ON "AS -BUILT" DRAWINGS PROVIDED <br />BY THE OWNER AND LIMITED FIELD VERIFICATION. CONTRACTOR SHALL <br />ADJUST TO ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO <br />THE OWNER. <br />W. CONTRACTOR SHALL VERIFY ALL SIZES, LOCATIONS, AND DEPTHS OF <br />EXISTING PLUMBING PRIOR TO CONSTRUCTION. <br />X. PVC SHALL BE USED FOR DRAIN, WASTE & VENT SYSTEMS WHENEVER <br />ALLOWED BY THE AUTHORITIES HAVING JURISDICTION (AHJ). <br />Y. PROVIDE AIR CHAMBERS WHEN WATER HAMMER ARRESTORS ARE NOT <br />ALLOWED (CHICAGO AREA). <br />Z. PROVIDE NEW CONDENSATE LINE FROM EVAPORATOR COIL IN COOLER/ <br />FREEZER TO APPROVED RECEPTACLE. INSTALL APPROVED <br />RECEPTACLE WHEN REQUIRED BY CODE. <br />,mim� GAS PIPING SHALL BE SCHEDULE 40 BLACK IRON STEEL. CONTRACTOR <br />SHALL PAINT GAS PIPING TO MATCH COLOR OF EXPOSED SURFACES. <br />BB. "OPTIONAL VEGGIE SINK": INSTALL AERO VEGGIE SINK WHEN REQUIRED <br />BY LOCAL AUTHORITIES HAVING JURISDICTION. INSTALL MODEL: N-909 <br />FOR APPLICATIONS WHERE DRAINBOARD IS LOCATED ON THE RIGHT. <br />INSTALL N-910 WHERE DRAINBOARD IS NEEDED ON LEFT SIDE. <br />GENERAL NOTES I D I <br />I <br />7 <br />6 9 10 <br />O <br />TI- ...5 <br />I <br />I I € <br />F <br />t <br />51 <br />11 <br />i <br />c <br />Q EXISTING GAS PIPING FROM EXISTING GAS METER. CONTRACTOR SHALL VERIFY IF <br />EXISTING GAS METER CAN HANDLE AN INCREASE OF 240.0 MBH. <br />O 1-1/4" GAS PIPING DOWN TO FRYER BELOW. DROP DOWN TO 12" AFF BEFORE <br />HORIZONTAL TRANSITION, <br />1" QUIK DISCONNECT FOR NEW FRYER AT 160.0 MBH TOTAL. REFER TO GAS RISER E/P1.0 <br />DETAIL D/P2.0 FOR INFORMATION. <br />® PROVIDE AND INSTALL NEW "HANDS FREE" KIT AT SITE OF EXISTING HANDSINK. <br />CONNECT TO EXISTING WATER SUPPLY LINES. REFER TO PLUMBING NOTES #4, #5, AND <br />DETAIL B/P2.0 FOR ADDITIONAL INFORMATION. <br />(aDEXISTING 3" HUB DRAIN SHOWN FOR REFERENCE. FIELD VERIFY EXACT LOCATION. <br />© NEW BEVERAGE DISPENSER TO REPLACE EXISTING BEVERAGE DISPENSER IN DINING <br />AREA. LOCATE AS SHOWN AFTER COMPLETION OF NEW DINING ROOM CONSTRUCTION <br />BY PEPSI SUPPLIER. PROVIDE NEW INDIRECT WASTE PIPING AND ROUTE TO EXISTING 3" <br />HUB DRAIN WITH CODE REQUIRED AIR GAP. <br />O NEW ICE MACHINE TO BE LOCATED ABOVE NEW BEVERAGE DISPENSER IN DINING AREA <br />AS SHOWN AFTER COMPLETION OF NEW DINING ROOM CONSTRUCTION. PROVIDE NEW <br />INDIRECT WASTE PIPING AND ROUTE TO EXISTING 3" HUB DRAIN WITH CODE REQUIRED <br />AIR GAP. PROVIDE NEW 1/2" FILTERED C.W. PIPING FROM SYRUP BUNDLE CONNECT TO <br />EXISTING FILTERED WATER LINE FOR ICE MACHINE. FIELD VERIFYLOCATION. <br />Q EXISTING BAG-N-BOX SHOWN FOR REFERENCE. <br />O NEW CARBONATOR TO BE LOCATED AS SHOWN AT DRINK DISPENSER. CONNECT TO <br />EXISTING FILTERED WATER PIPING FROM EXISTING SYRUP BUNDLE AS REQUIRED. <br />BACKFLOW PREVENTOR SHALL BE INSTALLED AT CARBONATOR WITH PIPING <br />DOWNSTREAM THEREFROM SHALL NOT BE AFFECTED BY CARBON DIOXIDE GAS. FIELD <br />VERIFY EXACT SIZE AND LOCATION. <br />10 CONTRACTOR SHALL PROVIDE AND INSTALL A DOUBLE CHECK VALVE BACKFLOW <br />PREVENTOR WITH ATMOSPHERIC VENT (WATTS SD-3 OR EQUAL) INSTALL UPSTREAM OF <br />CARBONATOR AS PER SECTION 608.16.1 OF THE 2004 FLORIDA PLUMBING CODE. <br />11 EXISTING GREASE INTERCEPTOR SHOWN FOR REFERENCE. FIELD VERIFY LOCATION. <br />12 EXISTING ICE MACHINE TO BE REMOVED. FIELD VERIFY EXACT LOCATION. DISPOSE OF <br />AS PER YUM CONSTRUCTION MANAGER'S DIRECTION. CAP EXISTING FILTERED WATER <br />LINES ABOVE CEILING OR AT WALL. <br />13 EXISTING 3" HUB DRAIN AT DEMO-6 ICE MACHINE. IF HUB DRAIN ONLY RECEIVES <br />INDIRECT WASTE FROM ICE MACHINE, CONTRACTOR SHALL REMOVE AND DISPOSE OF <br />AS YUM CONSTRUCTION MANAGER'S DIRECTION. REMOVE EXISTING WASTE PIPING BACK <br />TO POINT OF CONNECTION AND CAP. PATCH FLOOR BACK TO LIKE -NEW CONDITION. <br />VERIFY IN FIELD. <br />CD NEW "HANDS FREE" HANDSINK TO REPLACE EXISTING HANDSINK. CONNECT TO EXISTING <br />WATER SUPPLY, SANITARY AND VENT LINES. REFER TO PLUMBING NOTES #4, #5, AND <br />DETAIL B/P2.0 FOR ADDITIONAL INFORMATION. <br />15 NEW "HANDS FREE" HANDSINK. REFER TO PLUMBING NOTES #4, #5, AND DETAIL B/P2.0 <br />FOR ADDITIONAL INFORMATION. <br />(aD PROVIDE NEW 1/2" HOT & COLD WATER PIPING SUPPLY FOR NEW HAND SINK AND <br />CONNECT TO EXISTING. REFER TO WATER RISER F/P1.0 FOR INFORMATION. <br />17 PROVIDE 1-1/2" SANITARY FOR NEW HAND SINK AND CONNECT TO EXISTING. FIELD <br />VERIFY SIZE, LOCATION, AND DIRECTION OF FLOW. REFER TO SANITARY RISER G/P1.0 <br />FOR INFORMATION. <br />KEY NOTES I C <br />LEGEND <br />EX/ST/NG <br />NEW WORK <br />® NEW TO £X/S77NG CONNEC77ON <br />PLUMBING PLAN 1/4"=V-0" <br />CONNECT 1-1/4" GAS PIPING TO EXISTING GAS METER SUPPLYING AN ADDITIONAL 160 MBH <br />AT 8" WATER COLUMN WITH AN ALLOWABLE PRESSURE DROP OF 0.5" W.C. NEW GAS <br />METER BY LOCAL UTILITY COMPANY IF REQUIRED. CONTRACTOR SHALL VERIFY WITH <br />LOCAL GAS UTILITY COMPANY THAT THE GAS GAS METER AND SERVICE LINE IS CAPABLE <br />OF HANDLING THE ADDITIONAL LOAD. ONLY IN SEISMIC AREAS: INSTALL AN APPROVED <br />SEISMIC SHUT-OFF VALVE ON SERVICE IF EXISTING VALVE IS NOT PRESENT. <br />�2 EXISTING ELECTRICAL EQUIPMENT. NO PIPING SHALL CROSS THIS SPACE. <br />INSTALL 1-1/4" MECHANICAL SOLENOID VALVE SUPPLIED BY OWNER DROP GAS PIPING <br />THROUGH CEILING. LOCATE SOLENOID VALVE AND GAS COCK ADJACENT TO NEW GAS <br />HOOD. ROUTE GAS PIPING UP IN CEILING SPACE, THEN DOWN IN WALL. INSTALL QUICK <br />DISCONNECT AT FRYER. <br />® (REUSE EXISTING MIXING VALVE IF ONE IS PRESENT) PROVIDE THERMOSTATIC MIXING <br />VALVE, LEONARD MODEL: 210 MOUNTED BELOW FIXTURE. SET TEMPERATURE AS <br />REQUIRED BY AHJ. PIPE WATER FROM MIXING VALVE TO FOOT CONTROL (PROVIDED BY <br />OWNER) THEN BACK TO HANDSINK. FOLLOW MANUFACTURER'S INSTALLATION <br />INSTRUCTIONS. INSTALL NEW MIXING VALVE IF REQUIRED BY LOCAL AUTHORITIES. <br />50 INSTALL HAND FREE MODEL: FOOT CONTROL PEDALS (SUPPLIED BY OWNER). CONNECT <br />NEW 1/2 HOT AND COLD WATER TO EXISTTNG. VERIFY SIZES AND LOCATIONS OF EXISTING <br />PLUMBING PRIOR TO INSTALLATION. PROVIDE FLEXIBLE STAINLESS STEEL -BRAIDED <br />SUPPLY LINE TO FOOT CONTROL. SEE FOOT CONTROL DETAIL ON SHEET P-2. PROVIDE 0.5 <br />GPM FLOW CONTROL IN OUTLET OF FAUCET. REPLACE PLUMBING FOUND IN POOR <br />CONDITION. INSTALL PER MANUFACTURER'S REQUIREMENTS. <br />PLUMBING NOTES: I B <br />CONTRACT DATE: 03.21.08 <br />BUILDING TYPE: ?WM. <br />STORE NUMBER: 95343 <br />ARCV NUMBER: 080406 <br />6548 GALL BLVD. <br />ZEPHYRHILLS, FL 33542 <br />PLUMBING <br />PLAN <br />Pi so <br />PLOT DATE: <br />02.19.08 <br />