N <br />QUICK DISCONNECT GAS SHUTOFF VALVE, <br />(2) 90' STREET ELBOWS, GAS HOSE, <br />SWIVEL CONNECTIONS AND RESTRAINING <br />DEVICES SHALL BE FURNISHED BY OWNER <br />AND INSTALLED BY CONTRACTOR <br />IF SWIVEL CONNECTION IS NOT RECEIVED WITH <br />REST OF EQUIPMENT — ADVISE YUM CONSTRUCTION MANAGER. <br />PLUMBING CONTRACTOR SHALL INSTALL GAS <br />PIPING AS CLOSE AS POSSIBLE TO THE WALL. <br />FRYERS SHALL BE INSTALLED FLUSH TO THE BACK <br />OF HOOD, SPACE SHOWN IS FOR DRAWING CLARITY. <br />IF WING FLOW/EQUIPMENT IS OPPOSITE AS THE PLANS IJ <br />SHOWS, THE GAS LINE & ANSUL BOX SHALL SWITCH SIDES. <br />3' FLEX HOSE W/ SWIVEL <br />& QUICK DISCONNECT <br />DORMONT /16100BPOSR.36 <br />PROVIDED BY OWNER <br />GAS MANIFOLD <br />SEE PLANS FOR <br />SIZE <br />900 STREET ELBOW <br />PIPE FITTING <br />—TYPICAL — ONE STUB <br />PER APPLANCE <br />GAS UNE DOWN ON <br />WHEN ALLOWED BY AW, <br />IF NOT ALLOWED, PIPE GAS <br />IN WALL AND LOCATE <br />APPROVED VALVE OUTSIDE <br />OF WALL <br />- APPROVED VALVE <br />IN RISE <br />STREET ELBOW <br />PIPE FITTING <br />6" DIRT LEG <br />WALL <br />TERMIM7E SLEEVE FLUSH WITH <br />FINISHED WALL SURFACES <br />SEAL OR CAULK SLEEVES <br />THRU FIRE WALLS IN SMOKE <br />TIGHT MANNER AND TO MEET <br />FIRE RATING OF WALL (REFER <br />TO ASTW E-814)-----_ <br />PIPE AND INSULATION TO BE <br />CENTERED IN SLEEVE — DO <br />SUPPORT PIPE FROM SLEEVE <br />MECHANICAL GAS <br />SHUT—OFF VALVE <br />LINKED TO ANSUL <br />SYSTEM ----n <br />ANSUL SYSTEM <br />ME (7) 1 <br />ROUTE GAS UNE <br />ON FACE OF WALL <br />WHEN ALLOWED <br />BY LOCAL CODE — <br />GAS <br />6" DIRT LEG <br />TYPICAL <br />TO GAS MAIN SEE <br />PLANS FOR kZE <br />LJ <br />FRYER 1111 / _o_ i <br />SEE PLANS <br />FOR SIZES <br />QUIK DISCONNECT <br />FOR FLEXIBLE HOSE <br />CONNECTION (TYPICAL). <br />FRYER GAS CONNECTION DETAILS N.T.S. <br />D <br />STANDARD WEIGHT STEEL PIPE <br />h <br />SLEEVE OF SIZE TO PASS PIPE <br />AND INSULATION. PLUS GAP AS <br />REQUIRED BY LOCAL CODES. <br />ALSO25 GACCEPTABSPLITL� SLEEVE <br />FINISHED ESCUTCHEON PLATE FLUSH <br />AGAINST WALL AND OF SIZE TO <br />COMPLETELY COVER OPENING <br />RN/SHED WALL SURFACE <br />I <br />CONCEALED PIPING PIPING EXPOSED TO VIEW <br />NOTE PROVIDE FOR ALL <br />MASONRY WALLS AND <br />FIRE RATED WALLS <br />PIPE SLEEVE INTERIOR WALLS N.T.S. I F <br />THE EQUIPMENT ROUGH —IN ITEMS AND THEIR DIMENSIONED LOCATIONS FOR ALL <br />CONNECTIONS ARE ACCURATE TO THE BEST OF OUR KNOWLEDGE AND SHALL BE <br />VERIFIED WITH THE EQUIPMENT SUPPLIER, OWNER AND/OR TH£ EQUIPMENT <br />ROUGH —IN DRAWINGS IN SOME INSTANCES, THE OWNER OR SUPPLIER MAY MAKE <br />SUBSTITUTIONS OR THE EQUIPMENT ITEM MAY VARY FROM WHAT IS SHOWN ON THE <br />PLAN. THEREFORE, THE ARCHITECT/ENGINEER SHALL BE IMMEDIATEL Y NOTIFIED, PRIOR <br />TO CONSTRUCTION OF ANY DEVIATIONS FROM WHAT IS SHOWN OR IMPLIED ON THESE <br />DRAWINGS. FAILURE OF THE APPROPRLATE CONTRACTOR TO VERIFY ROUGH —INS OR <br />THEIR LOCATIONS SHALL PLACE THE RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION <br />AND/OR ADDITIONAL ROUGH —INS DIRECTLY UPON THE CONTRACTOR. <br />SYMBOL-S <br />P L U M B I N G <br />SYMBOL <br />DESCRIPTION <br />SYMBOL <br />DESCRIPTION <br />SYMBOL <br />DESCRIPTION <br />SANITARY DRAIN ABOVEGROUND <br />4— <br />GAS COCK <br />DO WC <br />WATER CLOSET (TAW TYPE) <br />�-- <br />SANITARY DRAIN BELOWGROUND <br />oi­ <br />GLOBE VALVE <br />VC <br />WATER CLOSET (FLUSH VALVE) <br />VENT LINE <br />—IV— <br />CHECK VALVE <br />S <br />STORM DRAIN ABOVEGROUND <br />PRESSURE RELIEF VALVE <br />UR <br />URINAL <br />=S= <br />STORM BRAIN BELOWGROUND <br />—pro-- <br />STOP AND WASTE VALVE <br />LAV <br />LAVATORY <br />-- <br />COLD WATER (CV) <br />STOP AND WASTE VALVE (IN RISE) <br />---- <br />HOT WATER (HW) <br />—y« <br />MIXING VALVE <br />® KS <br />KITCHEN SINK <br />---- <br />HOT WATER CIRCULATING (HWC) <br />PRESSURE REGULATING VALVE (PRV) <br />SS <br />SERVICE SINK <br />G <br />GAS LINE <br />UNION <br />Ih HE <br />H13SE BIBB <br />DF <br />DRINKING FOUNTAIN <br />—- <br />STRAINER <br />HWH <br />WALL HYDRANT <br />EVC <br />ELECTRIC WATER COOLER <br />BALANCING COCK <br />Iq FH <br />FIRE HYDRANT <br />- Ef—�— <br />RUNNING TRAP <br />O NH <br />MANHOLE <br />COLUMN NUMBER <br />CLEAN OUT <br />+® <br />VALVE IN RISE <br />a <br />O- <br />PLUMBING RISER NUMBER <br />—O <br />GRADE CLEAN OUT <br />QD -1 <br />DRAIN AND MARK <br />N.LTZ. <br />NOT IN THIS CONTRACT <br />ORD <br />RAF DRAIN <br />VTR <br />VENT THROUGH ROOF <br />ODS <br />DOWN SPOUT <br />VACUUM BREAKER <br />V.C.P. <br />VITRIFIED CLAY PIPE <br />—�� <br />BALL VALVE <br />C.I. <br />CAST IRON <br />I.E. <br />INVERT ELEVATION <br />PROWL <br />VALVE <br />SET TE <br />LOCAL <br />CONCE <br />COVER <br />1/2' <br />STEE <br />FUFA <br />DUAL <br />PED <br />HANDSINK <br />1/2 <br />ROLL VAL VE <br />1/2 <br />12 <br />(7YPICUL <br />) <br />E MIXING <br />WHEN REQUIRED <br />1/2 <br />UPERATURE PER <br />® <br />REQUIREMENTS <br />4L IN PEDESTAL <br />1/2 <br />1/2 <br />STAINLESS <br />t—BRAIDED <br />PEG <br />ISLE LINES <br />FOOT <br />L <br />ao <br />,—WALL <br />HANDSINK <br />TEMPERED <br />,R TO HAND <br />SYMBOLS LEGEND I A <br />HW & C Tj W —PROVIDE MIXING <br />VALVE WHEN <br />' CW REQUIRED <br />ESTAL COVER —STROP LINES TO WALL, <br />FLEXIBLE LINES SHALL NOT <br />TOUCH FLOOR. <br />90 DEGREE <br />DUAL FOOT PEDAL <br />1 /4" X 3- TAPCON HEX HEAD <br />SCREW <br />TYPICAL. FOOT CONTROL DETAIL N.T.S. I B <br />MAXIMUM SPACING FOR <br />GAS PIPE SUPPORTS <br />STUL PIPE <br />SEE (NPS) <br />SPA= N FEET YN. ROD SEE — INICHM <br />(HORIZONTAL.) <br />1/2' <br />5' 3/8' <br />3/4' TO 1 1/4' <br />6' 3/8' <br />1 1/2' TO 3' <br />10, 1/2' <br />(VMI-) <br />3 1/2- TO 5' <br />EVERY FLOOR <br />NOTE <br />PAINT BLOCK & PLATE SAME AS SPECIFIED FOR <br />OTHER SUPPORTS & PIPE ON ROOF. <br />SPACING SAME AS SPEC/PIED FOR PIPE HANGERS. <br />PIPE <br />ROLLER TYPE PIPE PROVIDE 114 " PLATED LAG SCREWS <br />SUPPORT 4" X 4" X 24" 7R6A7E9 <br />ATTACH TO ROOF AS DIRECTED WOOD BLOCK <br />BY THE ROOFING CONTRACTOR%F 1--ROOF <br />-- /NSULAT/ON <br />04.24.08 HAND SINK ADDITION <br />CONTRACT DATE: 03.21.08 <br />BUILDING TYPE: ?????? <br />STORE NUMBER: 95343 <br />ARCV NUMBER: 080406 <br />6548 GALL BLVD. <br />ZEPHYRHILLS, FL 33542 <br />P200 <br />ROOFTOP PIPING SUPPORT N.T.S. C PLOT DATE: 02A9.08 <br />p <br />2 <br />