A <br />u <br />17 <br />THE DEDICATED POS POWER CIRCUIT REQUIRES AN ISOLATED GROUND IN ADDITION TO <br />THE NORMAL COMMON BUILDING GROUND. THE ISOLATED GROUND WIRE SERVES TWO <br />PURPOSES: <br />* AS A SAFETY PATH TO GROUND. <br />* AS A ZERO REFERENCE POINT FOR ALL POS DIGITAL LOGIC. <br />THE GROUND MUST EXHIBIT THE LOWEST POSSIBLE IMPEDANCE TO MINIMIZE VOLTAGE <br />TRANSIENTS AND NOISE. <br />NOTES: <br />1. USE AN INSULATED GREEN WITH YELLOW STRIPE CONDUCTOR FOR THE ISOLATED <br />GROUND WIRE. <br />2. RUN THE ISOLATED GROUND WIRE THROUGH THE SAME CONDUIT AS THE HOT AND <br />NEUTRAL WIRES. <br />3. INSTALL ONLY ISOLATED GROUND (IG) TYPE RECEPTACLES. <br />4. CONNECT THE ISOLATED GROUND WIRE TO BUILDING GROUND ONLY AT THE MAIN <br />SERVICE PANEL <br />DO MU CONNECT THE ISOLATED GROUND WIRE TO THE CONDUIT, JUNCTION BOXES, THE <br />FRAME ON A SUBPANEL, OR ANY OTHER METAL SURFACE. <br />DEDICATED CIRCUITS: DEDICATED CIRCUITS REQUIRE A DEDICATED HOT AND A NEUTRAL <br />THAT ARE NOT SHARED WITH ANY OTHER CIRCUITS. <br />SELECT THE CORRECT DETAIL THAT APPLIES TO THE PROJECT: <br />none imn <br />�1��1LM�1��1iL� <br />�ATdbTdbTdbTdbTsTdbwal r► <br />G <br />"K3K3 <br />PANEL <br />UTILITY NEUTRAL <br />EARTH GROUND <br />ISOLATED GROUND SYSTEM <br />N.T.S. <br />ISOLATED GROUND IG <br />EQUIPMENT GROUND <br />EQUIPMENT GROUND <br />IG RECEPTACLE <br />DEDICATED HOT <br />F <br />SUBPANEL <br />(OR EQUIPMENT SERVICE <br />PANEL) <br />ISOLATED GROUND SYSTEM <br />N.T.S. <br />CONNECTIONS ARE ACCURATE TO THE BEST OF OUR KNOWLEDGE AND SHALL BE <br />VERIFIED WITH THE EQUIPMENT SUPPLIER, OWNER AND/OR THE EQUIPMENT ROUGH —IN <br />DRAWINGS. IN SOME INSTANCES, THE OWNER OR SUPPLIER MAY MAKE SUBSTITUTIONS <br />OR THE EQUIPMENT ITEM MAY VARY FROM WHAT IS SHOWN ON THE PLAN. THEREFORE <br />THE ARCHITECT/ENGINEER SHALL BE IMMEDIATELY NOTIFIED, PRIOR TO CONSTRUCTION <br />OF ANY DEVIATIONS FROM WHAT IS SHOWN OR IMPLIED ON THESE DRAWINGS. FAILURE <br />OF THE APPROPRIATE CONTRACTOR TO VERIFY ROUGH —INS OR THEIR LOCATIONS SHALL <br />PLACE THE RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION AND/OR ADDITIONAL <br />ROUGH —INS DIRECTLY UPON THE CONTRACTOR. <br />!�j <br />MAIN SERVICE PANEL <br />SUBPANEL) <br />UTILITY NEUTRAL <br />EARTH GROUND <br />POLE WITH OL DEVICE SHALL <br />BE CONNECTED TO 120V <br />POWER FOR EX FAN MOTOR. - <br />PANEL <br />20 AMP <br />2 POLE - <br />CIRCUIT - <br />BREAKER <br />a �70 <br />. <br />7 , <br />0 <br />. <br />r 1 - -• 71 <br />r <br />SQUARE D <br />RE4 SERIES <br />CAT# RE4RM11BU <br />r R <br />L---J I , <br />FACTORY PROVIDED <br />JUNCTION BOX, LOCATED <br />ON PLAN (EXISTING) <br />EF (TYPICAL) <br />T <br />SQUARE D <br />CFSLA S 2510 <br />PROVIDE 20 AMP DOUBLE POLE <br />MANUAL STARTER SWITCH, LOCATED <br />NEXT TO HOOD. (DISCONNECTING MEANS <br />NOTE: FOR HOOD) <br />NEUTRAL AND GROUND WIRE NOT SHOWN. <br />FACTORY PROVIDED <br />GLOBE LIGHTS (EXISTING) <br />-FRYER (CONTROL PANEL) <br />RTU-2 EVAPORATOR <br />FAN CONTROL SEE <br />DETAIL 6 ON THIS SHEET <br />RTU-1 EVAPORATOR <br />FAN CONTROL SEE <br />\ DETAIL 6 ON THIS SHEET <br />`— MICRO SWITCH LOCATED <br />IN HOOD FIRE SUPPRESSION <br />SYSTEM CONTROL PANEL <br />PROVIDE 20 AMP DOUBLE POLE SWITCH IN <br />NEMA 3R ENCLOSURE, LOCATED ON ROOF. <br />(DISCONNECTING MEANS FOR EF-1) <br />EXHAUST FAN/FRYER CONTROL DIAGRAM <br />N.T.S. <br />��tl;Lt <br />THERMOSTAT EXISTING <br />sWUL ROOF TOP UNIT <br />tm OFF EAT 1 VV1 HEAT 1 <br />EAT t2 YY2 HEAT 2 <br />(WHERE APPUCAE <br />d FAN <br />TO RTU <br />INTERLOCK <br />RELAY. DETAIL 2 <br />ON THIS SHEET <br />COOL 1 <br />COOL 2 <br />(WHERE APPLICABLE <br />24V CNTRL POWER <br />LTO RTU <br />INTERLOCK <br />RELAY, DETAIL 2 <br />ON THIS SHEET <br />RTU FAN INTERLOCK <br />NTS <br />GENERAL DEMOLITION NOTES: <br />A. REMOVE EXISTING ELECTRICAL AND TELECOMMUNICATION SYSTEMS COMPLETE <br />FROM BUILDING WHERE INDICATED. ELECTRICAL CONTRACTOR TO FIELD VERIFY <br />EXACT REQUIREMENTS AT THE PRE -BID WALK THROUGH AS SPECIFIED. <br />B. UNLESS NOTED OTHERWISE, REMOVE ALL EXISTING ELECTRICAL AND <br />TELECOMMUNICATION EQUIPMENT COMPLETE FROM BUILDING WHERE INDICATED. <br />DO NOT ABANDON CONDUIT, WIRE, OR ANY ELECTRICAL EQUIPMENT/DEVICE IN <br />PLACE. REMOVE ALL CONDUIT, BOXES, DEVICES, WIRING, PANELS, CABINET, <br />ETC, COMPLETE FROM PREMISES. <br />C. MATERIALS AND EQUIPMENT TO BE SALVAGED, WILL BE TAGGED BY THE <br />OWNER PRIOR TO THE PRE -BID WALK THROUGH. REMOVE AND DELIVER <br />MATERIALS AND EQUIPMENT TO BE SALVAGED TO THE STORAGE LOCATION <br />DESIGNATED BY THE OWNER. <br />D. REPORT FINDING OF ANY MATERIAL CONTAINING ASBESTOS IMMEDIATELY TO <br />THE OWNER'S CONSTRUCTION REPRESENTATIVE. <br />E. MATERIALS AND EQUIPMENT INDICATED TO BE REMOVED AND NOT SALVAGED, <br />SHALL BECOME THE PROPERTY OF THE CONTRACTOR. THE CONTRACTOR <br />SHALL REMOVE, TRANSPORT, AND LEGALLY DISPOSE OF THE DEMOLISHED <br />MATERIAL, EQUIPMENT DEBRIS, AND RUBBISH OFF THE SITE. <br />F. THE CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE A MINIMUM <br />OF (72) HOURS IN ADVANCE OF INTERRUPTING ANY UTILITIES OR BUILDING <br />SERVICES, AND BEFORE SHUTTING DOWN ANY SYSTEMS OR EQUIPMENT. <br />G. LIGHTING DEMOLITION - FLUORESCENT BALLAST AND LAMPS SHALL BE <br />REMOVED AND DISPOSED OF SEPARATELY FROM CONSTRUCTION DEBRIS. <br />PROPER PROTECTIVE EQUIPMENT MUST BE USED WHEN HANDLING LEAKING <br />PCB BALLAST. <br />CONTRACTOR SHALL PROVIDE STEEL DRUMS. CONTRACTOR SHALL SEPARATE <br />PCB BALLASTS FROM NON PCB BALLASTS. AND PUT IN DRUMS. E.C. SHALL <br />TAKE RESPONSIBILITY FOR PROPER DISPOSAL OF PCB CONTAINING BALLASTS. <br />CLEAN LIGHT FIXTURE METAL OF ANY DEPOSITS LEAKED FROM BALLASTS, <br />AND DISPOSE OF RAGS WITH BALLASTS. SPILLS MUST BE CLEANED UP IN <br />ACCORDANCE WITH THE NATIONAL PCB CLEAN UP POLICY (52 FR 10688) <br />FLUORESCENT LAMPS SHALL BE CONSIDERED HAZARDOUS WASTE CONTAINING <br />MERCURY, LEAD, AND CADMIUM. CONTRACTOR SHALL OBTAIN SERVICES AND <br />PROVIDE PROPER PACKAGING AND SHIPPING OF LAMPS FOR DISPOSAL <br />DISPOSAL TO MEET ALL FEDERAL AND STATE REQUIREMENTS. <br />ALL WASTE SHALL BE LABELED, STORED, HANDLED, TRANSPORTED, AND <br />DISPOSED OF IN ACCORDANCE TO APPLICABLE STATE AND FEDERAL <br />REGULATIONS. <br />H. E.0 TO PROVIDE CONDUIT AND WIRE AS REQUIRED TO MAINTAIN ALL EXISTING <br />BRANCH CIRCUITS AND DISTRIBUTION FEEDERS. THAT REQUIRE RELOCATION <br />DUE TO WALL, FLOOR, OR CEILING DEMOLITION. E.C. TO REROUTE FEEDERS <br />WHERE REQUIRED TO BYPASS ANY SUCH DEMOLITION. FIELD VERIFY EXACT <br />REQUIREMENTS WITH ARCHITECTURAL AND ELECTRICAL DEMOLITION DRAWINGS <br />PRIOR TO BID DATE. <br />I. CONTRACTOR SHALL RELOCATE EXISTING LIGHTING FIXTURES AS NEEDED, DUE <br />TO THE NEW FRYER HOOD LOCATION. <br />GENERAL ELECTRICAL NOTES: <br />A. THE WORK INCLUDES PROVIDING NEW MATERIALS, FIXTURES, DEVICES AND <br />ACCESSORIES NECESSARY FOR A COMPLETE FUNCTIONING ELECTRICAL <br />SYSTEM. ALL WORK SHALL BE IN ACCORDANCE WITH LOCAL CODES OR <br />ORDINANCES AND SUBJECT TO INSPECTION. <br />B. COMPLY WITH ALL LAWS APPLYING TO ELECTRICAL INSTALLATIONS IN EFFECT, <br />AND WITH THE MOST RECENT EDITION OF THE NATIONAL ELECTRICAL CODE, <br />ADA, APPLICABLE SECTIONS OF OTHER NFPA, OSHA, LIFE SAFETY CODES AND <br />RECOMMENDATIONS, AND THE INTERIM AMENDMENTS IN EFFECT AT THE TIME <br />OF THE PROPOSAL ALL MATERIALS USED SHALL BE NEW AND SHALL <br />CONFORM TO THE STANDARDS ESTABLISHED BY THE UNDERWRITERS <br />LABORATORIES INCORPORATED. <br />C. THE INTENT OF THE DRAWINGS IS TO INDICATE THE GENERAL EXTENT OF <br />WORK REQUIRED FOR THE PROJECT. THE DRAWINGS FOR ELECTRICAL WORK <br />ARE DIAGRAMMATIC. SHOWING THE LOCATION, TYPE, DEVICES AND EQUIPMENT <br />REQUIRED. THE DRAWINGS SHALL NOT BE SCALED FOR EXACT <br />MEASUREMENTS. PROVIDE ALL FIXTURES, DEVICES, ACCESSORIES, OFFSETS, <br />AND MATERIALS NECESSARY TO FACILITATE THE SYSTEM'S FUNCTIONING AS <br />INDICATED BY THE DESIGN AND THE EQUIPMENT FURNISHED BY OTHERS. <br />D. EXISTING CONDITIONS ARE BASED ON "AS -BUILT" DRAWINGS PROVIDED BY <br />THE OWNER AND LIMITED FIELD VERIFICATION. CONTRACTOR SHALL ADJUST TO <br />ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE OWNER. <br />CONTRACTOR IS TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO BIDDING. <br />E. ELECTRICAL CONTRACTOR TO FIELD VERIFY ALL EXISTING UNDERGROUND <br />UTILITIES. ANY ITEM DAMAGED BY THIS CONTRACTOR SHALL BE REPAIRED <br />IMMEDIATELY AND AT NO COST TO THE OWNER. <br />F. CONTRACTOR TO VERIFY PLACEMENT OF ALL DEVICES SHOWN ON THE <br />ELECTRICAL CONSTRUCTION DOCUMENTS WITH ARCHITECTURAL, MECHANICAL, <br />PLUMBING, & KITCHEN DRAWINGS PRIOR TO FINAL PLACEMENT. <br />G. ROOF PENETRATIONS SHALL COMPLY WITH "SMACNA7 AND 'NRCA" STANDARDS. <br />AND WITH THE REQUIREMENTS OF THE EXISTING ROOFING WARRANTY. ALL <br />PENETRATIONS SHALL BE COORDINATED WITH THE ROOFING CONTRACTOR. <br />H. ELECTRICAL DESIGN HAS BEEN BASED ON THE INSTALLATION OF 75'C <br />CONDUCTORS CONNECTED TO TERMINAL LUGS AND EQUIPMENT, U.L. LISTED <br />FOR A MINIMUM 75'C. CONDUCTORS TERMINATED ON EQUIPMENT OR DEVICES <br />WITH A LOWER RATING (60'C) OR NO RATING SHOWN, SHALL HAVE <br />CONDUCTOR SIZE INCREASED TO CONFORM TO NEC TABLE 310-16 AND U.L <br />NO. 489 REQUIREMENTS. <br />I, CONDUIT SHALL BE SIZED TO COMPLY WITH NEC FOR NUMBER AND SIZE OF <br />CONDUCTORS INSTALLED, MINIMUM 240 BELOW GRADE. PROVIDE SCHEDULE <br />40 PVC PLASTIC OR RIGID STEEL CONDUIT BELOW GRADE, MINIMUM 3/4-. <br />PROVIDE ELECTRICAL METAL TUBING (EMT) MEETING FS W-0563, OR <br />FLEXIBLE CONDUIT (IN LENGTHS 6' OR LESS) FOR INTERIOR LOCATIONS. EMT <br />CONNECTORS AND COUPLING SHALL BE SET -SCREW TYPE. CLAMP CONDUIT <br />TO BOXES WITH BUSHING INSIDE AND LOCKNUT OUTSIDE. <br />J. ALL CONDUIT AND RACEWAY SYSTEMS SHALL BE INSTALLED WITH SEPARATE <br />GROUND CONDUCTOR. CONDUIT SYSTEM IS NOT TO BE USED AS THE SOLE <br />GROUNDING MEANS. <br />K. CONTRACTOR MAY COMBINE CIRCUIT IN RACEWAYS, BUT IF MORE THAN (3) <br />CURRENT CARRYING CONDUCTORS ARE INSTALLED THEN CONTRACTOR TO <br />DERATE CONDUCTORS IN ACCORDANCE WITH N.E.0 TABLE 310-15(bX2)(a). <br />L E.C. SHALL PROVIDE AND INSTALL ELECTRICAL DEVICES AND WIRING TO <br />COMPLY WITH N.F.PA. 96.7-3.1.3 FOR POWER SHUTOFF ON HOOD FAN AND <br />ALL ELECTRICAL EQUIPMENT UNDER OVEN HOOD WHERE REQUIRED BY LOCAL <br />CODE. VERIFY INSTALLATION AND OPERATION REQUIREMENTS WITH <br />EXTINGUISHING SYSTEM SUPPLIER WHEN PRESENT. <br />M. FOR EQUIPMENT FURNISHED BY OWNER OR OTHER CONTRACTORS; <br />ELECTRICAL CONTRACTOR SHALL VERIFY EXACT LOAD, TYPE OF CONNECTION <br />AND MOUNTING HEIGHT FOR EACH BOX OR EQUIPMENT ITEM TO BE <br />INSTALLED. ALL HARD -WIRED CONNECTIONS TO EQUIPMENT SHALL BE MADE <br />WITH FLEXIBLE LIQUID -TIGHT METAL CONDUIT WITH GREEN GROUND <br />CONDUCTOR INSTALLED INSIDE RACEWAY. GROUND CONDUCTOR SHALL BE <br />BONDED AT BOTH ENDS. <br />N. PULL AND JUNCTION BOXES SHALL BE 16 GAUGE, OR HEAVIER, STEEL, WITH <br />REMOVABLE KNOCKOUTS. BOXES SHALL BE AS MANUFACTURED BY APPLETON, <br />STEEL CITY OR RACO. SIZE BOXES AS REQUIRED FOR THE INTENDED DUTY, <br />MINIMUM SIZE AS REQUIRED BY THE NATIONAL ELECTRICAL CODE. <br />0. RECEPTACLES SHALL BE LOCATED AS SHOWN ON THE DRAWINGS AND AT THE <br />HEIGHTS SPECIFIED OR INDICATED. RECEPTACLE AND POWER OUTLETS SHALL <br />BE SPECIFICATION GRADE, 20 AMP, GROUNDING TYPE AS MANUFACTURED BY <br />HUBBELL, GENERAL ELECTRIC, PASS & SEYMOUR, EAGLE, OR LEVITON. <br />RECEPTACLES SHALL BE WHITE. COLOR OF DEDICATED RECEPTACLES SHALL <br />BE RED. <br />P. ALL RECEPTACLES AND DATA/TELEPHONE OUTLETS SHALL BE MOUNTED AT <br />+170 TO CENTER OF BOX UNLESS OTHERWISE NOTED. <br />Q. REFER TO ARCHITECTURAL DRAWING FOR EQUIPMENT SCHEDULE. FIELD <br />VERIFY ALL KITCHEN EQUIPMENT ELECTRICAL DATA WITH THE FOOD SERVICE <br />CONTRACTOR. VERIFY EXACT LOADS, MOUNTING HEIGHTS AND NEMA <br />CONFIGURATIONS PRIOR TO ROUGH -IN. <br />R. SEE SHEET E-2 FOR LIGHT FIXTURE SCHEDULE. <br />S. COORDINATE WITH THE SIGN CONTRACTOR AND ARCHITECT FOR NEW SIGN <br />WATTAGE, VOLTAGE, AND EXACT LOCATION PRIOR TO J-BOX INSTALLATION. <br />Q 04.24.08 HAND SINK ADDITION <br />CONTRACT DATE: <br />03.21.08 <br />BUILDING TYPE: <br />?????? <br />STORE NUMBER: <br />95343 <br />ARCV NUMBER: <br />080406 <br />6548 GALL BLVD. <br />ZEPHYRHILLS, FL 33542 <br />El m0 <br />PLOT DATE: <br />02.19.08 <br />T, <br />