<br />THE DEDICATED POS POWER CIRCUIT REQUIRES AN ISOLATED GROUND IN ADDITION TO
<br />THE NORMAL COMMON BUILDING GROUND. THE ISOLATED GROUND WIRE SERVES TWO
<br />PURPOSES:
<br />* AS A SAFETY PATH TO GROUND.
<br />* AS A ZERO REFERENCE POINT FOR ALL POS DIGITAL LOGIC.
<br />THE GROUND MUST EXHIBIT THE LOWEST POSSIBLE IMPEDANCE TO MINIMIZE VOLTAGE
<br />TRANSIENTS AND NOISE.
<br />NOTES:
<br />1. USE AN INSULATED GREEN WITH YELLOW STRIPE CONDUCTOR FOR THE ISOLATED
<br />GROUND WIRE.
<br />2. RUN THE ISOLATED GROUND WIRE THROUGH THE SAME CONDUIT AS THE HOT AND
<br />NEUTRAL WIRES.
<br />3. INSTALL ONLY ISOLATED GROUND (IG) TYPE RECEPTACLES.
<br />4. CONNECT THE ISOLATED GROUND WIRE TO BUILDING GROUND ONLY AT THE MAIN
<br />SERVICE PANEL
<br />DO MU CONNECT THE ISOLATED GROUND WIRE TO THE CONDUIT, JUNCTION BOXES, THE
<br />FRAME ON A SUBPANEL, OR ANY OTHER METAL SURFACE.
<br />DEDICATED CIRCUITS: DEDICATED CIRCUITS REQUIRE A DEDICATED HOT AND A NEUTRAL
<br />THAT ARE NOT SHARED WITH ANY OTHER CIRCUITS.
<br />SELECT THE CORRECT DETAIL THAT APPLIES TO THE PROJECT:
<br />none imn
<br />�1��1LM�1��1iL�
<br />�ATdbTdbTdbTdbTsTdbwal r►
<br />G
<br />"K3K3
<br />PANEL
<br />UTILITY NEUTRAL
<br />EARTH GROUND
<br />ISOLATED GROUND SYSTEM
<br />N.T.S.
<br />ISOLATED GROUND IG
<br />EQUIPMENT GROUND
<br />EQUIPMENT GROUND
<br />IG RECEPTACLE
<br />DEDICATED HOT
<br />F
<br />SUBPANEL
<br />(OR EQUIPMENT SERVICE
<br />PANEL)
<br />ISOLATED GROUND SYSTEM
<br />N.T.S.
<br />CONNECTIONS ARE ACCURATE TO THE BEST OF OUR KNOWLEDGE AND SHALL BE
<br />VERIFIED WITH THE EQUIPMENT SUPPLIER, OWNER AND/OR THE EQUIPMENT ROUGH —IN
<br />DRAWINGS. IN SOME INSTANCES, THE OWNER OR SUPPLIER MAY MAKE SUBSTITUTIONS
<br />OR THE EQUIPMENT ITEM MAY VARY FROM WHAT IS SHOWN ON THE PLAN. THEREFORE
<br />THE ARCHITECT/ENGINEER SHALL BE IMMEDIATELY NOTIFIED, PRIOR TO CONSTRUCTION
<br />OF ANY DEVIATIONS FROM WHAT IS SHOWN OR IMPLIED ON THESE DRAWINGS. FAILURE
<br />OF THE APPROPRIATE CONTRACTOR TO VERIFY ROUGH —INS OR THEIR LOCATIONS SHALL
<br />PLACE THE RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION AND/OR ADDITIONAL
<br />ROUGH —INS DIRECTLY UPON THE CONTRACTOR.
<br />!�j
<br />MAIN SERVICE PANEL
<br />SUBPANEL)
<br />UTILITY NEUTRAL
<br />EARTH GROUND
<br />POLE WITH OL DEVICE SHALL
<br />BE CONNECTED TO 120V
<br />POWER FOR EX FAN MOTOR. -
<br />PANEL
<br />20 AMP
<br />2 POLE -
<br />CIRCUIT -
<br />BREAKER
<br />a �70
<br />.
<br />7 ,
<br />0
<br />.
<br />r 1 - -• 71
<br />r
<br />SQUARE D
<br />RE4 SERIES
<br />CAT# RE4RM11BU
<br />r R
<br />L---J I ,
<br />FACTORY PROVIDED
<br />JUNCTION BOX, LOCATED
<br />ON PLAN (EXISTING)
<br />EF (TYPICAL)
<br />T
<br />SQUARE D
<br />CFSLA S 2510
<br />PROVIDE 20 AMP DOUBLE POLE
<br />MANUAL STARTER SWITCH, LOCATED
<br />NEXT TO HOOD. (DISCONNECTING MEANS
<br />NOTE: FOR HOOD)
<br />NEUTRAL AND GROUND WIRE NOT SHOWN.
<br />FACTORY PROVIDED
<br />GLOBE LIGHTS (EXISTING)
<br />-FRYER (CONTROL PANEL)
<br />RTU-2 EVAPORATOR
<br />FAN CONTROL SEE
<br />DETAIL 6 ON THIS SHEET
<br />RTU-1 EVAPORATOR
<br />FAN CONTROL SEE
<br />\ DETAIL 6 ON THIS SHEET
<br />`— MICRO SWITCH LOCATED
<br />IN HOOD FIRE SUPPRESSION
<br />SYSTEM CONTROL PANEL
<br />PROVIDE 20 AMP DOUBLE POLE SWITCH IN
<br />NEMA 3R ENCLOSURE, LOCATED ON ROOF.
<br />(DISCONNECTING MEANS FOR EF-1)
<br />EXHAUST FAN/FRYER CONTROL DIAGRAM
<br />N.T.S.
<br />��tl;Lt
<br />THERMOSTAT EXISTING
<br />sWUL ROOF TOP UNIT
<br />tm OFF EAT 1 VV1 HEAT 1
<br />EAT t2 YY2 HEAT 2
<br />(WHERE APPUCAE
<br />d FAN
<br />TO RTU
<br />INTERLOCK
<br />RELAY. DETAIL 2
<br />ON THIS SHEET
<br />COOL 1
<br />COOL 2
<br />(WHERE APPLICABLE
<br />24V CNTRL POWER
<br />LTO RTU
<br />INTERLOCK
<br />RELAY, DETAIL 2
<br />ON THIS SHEET
<br />RTU FAN INTERLOCK
<br />NTS
<br />GENERAL DEMOLITION NOTES:
<br />A. REMOVE EXISTING ELECTRICAL AND TELECOMMUNICATION SYSTEMS COMPLETE
<br />FROM BUILDING WHERE INDICATED. ELECTRICAL CONTRACTOR TO FIELD VERIFY
<br />EXACT REQUIREMENTS AT THE PRE -BID WALK THROUGH AS SPECIFIED.
<br />B. UNLESS NOTED OTHERWISE, REMOVE ALL EXISTING ELECTRICAL AND
<br />TELECOMMUNICATION EQUIPMENT COMPLETE FROM BUILDING WHERE INDICATED.
<br />DO NOT ABANDON CONDUIT, WIRE, OR ANY ELECTRICAL EQUIPMENT/DEVICE IN
<br />PLACE. REMOVE ALL CONDUIT, BOXES, DEVICES, WIRING, PANELS, CABINET,
<br />ETC, COMPLETE FROM PREMISES.
<br />C. MATERIALS AND EQUIPMENT TO BE SALVAGED, WILL BE TAGGED BY THE
<br />OWNER PRIOR TO THE PRE -BID WALK THROUGH. REMOVE AND DELIVER
<br />MATERIALS AND EQUIPMENT TO BE SALVAGED TO THE STORAGE LOCATION
<br />DESIGNATED BY THE OWNER.
<br />D. REPORT FINDING OF ANY MATERIAL CONTAINING ASBESTOS IMMEDIATELY TO
<br />THE OWNER'S CONSTRUCTION REPRESENTATIVE.
<br />E. MATERIALS AND EQUIPMENT INDICATED TO BE REMOVED AND NOT SALVAGED,
<br />SHALL BECOME THE PROPERTY OF THE CONTRACTOR. THE CONTRACTOR
<br />SHALL REMOVE, TRANSPORT, AND LEGALLY DISPOSE OF THE DEMOLISHED
<br />MATERIAL, EQUIPMENT DEBRIS, AND RUBBISH OFF THE SITE.
<br />F. THE CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE A MINIMUM
<br />OF (72) HOURS IN ADVANCE OF INTERRUPTING ANY UTILITIES OR BUILDING
<br />SERVICES, AND BEFORE SHUTTING DOWN ANY SYSTEMS OR EQUIPMENT.
<br />G. LIGHTING DEMOLITION - FLUORESCENT BALLAST AND LAMPS SHALL BE
<br />REMOVED AND DISPOSED OF SEPARATELY FROM CONSTRUCTION DEBRIS.
<br />PROPER PROTECTIVE EQUIPMENT MUST BE USED WHEN HANDLING LEAKING
<br />PCB BALLAST.
<br />CONTRACTOR SHALL PROVIDE STEEL DRUMS. CONTRACTOR SHALL SEPARATE
<br />PCB BALLASTS FROM NON PCB BALLASTS. AND PUT IN DRUMS. E.C. SHALL
<br />TAKE RESPONSIBILITY FOR PROPER DISPOSAL OF PCB CONTAINING BALLASTS.
<br />CLEAN LIGHT FIXTURE METAL OF ANY DEPOSITS LEAKED FROM BALLASTS,
<br />AND DISPOSE OF RAGS WITH BALLASTS. SPILLS MUST BE CLEANED UP IN
<br />ACCORDANCE WITH THE NATIONAL PCB CLEAN UP POLICY (52 FR 10688)
<br />FLUORESCENT LAMPS SHALL BE CONSIDERED HAZARDOUS WASTE CONTAINING
<br />MERCURY, LEAD, AND CADMIUM. CONTRACTOR SHALL OBTAIN SERVICES AND
<br />PROVIDE PROPER PACKAGING AND SHIPPING OF LAMPS FOR DISPOSAL
<br />DISPOSAL TO MEET ALL FEDERAL AND STATE REQUIREMENTS.
<br />ALL WASTE SHALL BE LABELED, STORED, HANDLED, TRANSPORTED, AND
<br />DISPOSED OF IN ACCORDANCE TO APPLICABLE STATE AND FEDERAL
<br />REGULATIONS.
<br />H. E.0 TO PROVIDE CONDUIT AND WIRE AS REQUIRED TO MAINTAIN ALL EXISTING
<br />BRANCH CIRCUITS AND DISTRIBUTION FEEDERS. THAT REQUIRE RELOCATION
<br />DUE TO WALL, FLOOR, OR CEILING DEMOLITION. E.C. TO REROUTE FEEDERS
<br />WHERE REQUIRED TO BYPASS ANY SUCH DEMOLITION. FIELD VERIFY EXACT
<br />REQUIREMENTS WITH ARCHITECTURAL AND ELECTRICAL DEMOLITION DRAWINGS
<br />PRIOR TO BID DATE.
<br />I. CONTRACTOR SHALL RELOCATE EXISTING LIGHTING FIXTURES AS NEEDED, DUE
<br />TO THE NEW FRYER HOOD LOCATION.
<br />GENERAL ELECTRICAL NOTES:
<br />A. THE WORK INCLUDES PROVIDING NEW MATERIALS, FIXTURES, DEVICES AND
<br />ACCESSORIES NECESSARY FOR A COMPLETE FUNCTIONING ELECTRICAL
<br />SYSTEM. ALL WORK SHALL BE IN ACCORDANCE WITH LOCAL CODES OR
<br />ORDINANCES AND SUBJECT TO INSPECTION.
<br />B. COMPLY WITH ALL LAWS APPLYING TO ELECTRICAL INSTALLATIONS IN EFFECT,
<br />AND WITH THE MOST RECENT EDITION OF THE NATIONAL ELECTRICAL CODE,
<br />ADA, APPLICABLE SECTIONS OF OTHER NFPA, OSHA, LIFE SAFETY CODES AND
<br />RECOMMENDATIONS, AND THE INTERIM AMENDMENTS IN EFFECT AT THE TIME
<br />OF THE PROPOSAL ALL MATERIALS USED SHALL BE NEW AND SHALL
<br />CONFORM TO THE STANDARDS ESTABLISHED BY THE UNDERWRITERS
<br />LABORATORIES INCORPORATED.
<br />C. THE INTENT OF THE DRAWINGS IS TO INDICATE THE GENERAL EXTENT OF
<br />WORK REQUIRED FOR THE PROJECT. THE DRAWINGS FOR ELECTRICAL WORK
<br />ARE DIAGRAMMATIC. SHOWING THE LOCATION, TYPE, DEVICES AND EQUIPMENT
<br />REQUIRED. THE DRAWINGS SHALL NOT BE SCALED FOR EXACT
<br />MEASUREMENTS. PROVIDE ALL FIXTURES, DEVICES, ACCESSORIES, OFFSETS,
<br />AND MATERIALS NECESSARY TO FACILITATE THE SYSTEM'S FUNCTIONING AS
<br />INDICATED BY THE DESIGN AND THE EQUIPMENT FURNISHED BY OTHERS.
<br />D. EXISTING CONDITIONS ARE BASED ON "AS -BUILT" DRAWINGS PROVIDED BY
<br />THE OWNER AND LIMITED FIELD VERIFICATION. CONTRACTOR SHALL ADJUST TO
<br />ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE OWNER.
<br />CONTRACTOR IS TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO BIDDING.
<br />E. ELECTRICAL CONTRACTOR TO FIELD VERIFY ALL EXISTING UNDERGROUND
<br />UTILITIES. ANY ITEM DAMAGED BY THIS CONTRACTOR SHALL BE REPAIRED
<br />IMMEDIATELY AND AT NO COST TO THE OWNER.
<br />F. CONTRACTOR TO VERIFY PLACEMENT OF ALL DEVICES SHOWN ON THE
<br />ELECTRICAL CONSTRUCTION DOCUMENTS WITH ARCHITECTURAL, MECHANICAL,
<br />PLUMBING, & KITCHEN DRAWINGS PRIOR TO FINAL PLACEMENT.
<br />G. ROOF PENETRATIONS SHALL COMPLY WITH "SMACNA7 AND 'NRCA" STANDARDS.
<br />AND WITH THE REQUIREMENTS OF THE EXISTING ROOFING WARRANTY. ALL
<br />PENETRATIONS SHALL BE COORDINATED WITH THE ROOFING CONTRACTOR.
<br />H. ELECTRICAL DESIGN HAS BEEN BASED ON THE INSTALLATION OF 75'C
<br />CONDUCTORS CONNECTED TO TERMINAL LUGS AND EQUIPMENT, U.L. LISTED
<br />FOR A MINIMUM 75'C. CONDUCTORS TERMINATED ON EQUIPMENT OR DEVICES
<br />WITH A LOWER RATING (60'C) OR NO RATING SHOWN, SHALL HAVE
<br />CONDUCTOR SIZE INCREASED TO CONFORM TO NEC TABLE 310-16 AND U.L
<br />NO. 489 REQUIREMENTS.
<br />I, CONDUIT SHALL BE SIZED TO COMPLY WITH NEC FOR NUMBER AND SIZE OF
<br />CONDUCTORS INSTALLED, MINIMUM 240 BELOW GRADE. PROVIDE SCHEDULE
<br />40 PVC PLASTIC OR RIGID STEEL CONDUIT BELOW GRADE, MINIMUM 3/4-.
<br />PROVIDE ELECTRICAL METAL TUBING (EMT) MEETING FS W-0563, OR
<br />FLEXIBLE CONDUIT (IN LENGTHS 6' OR LESS) FOR INTERIOR LOCATIONS. EMT
<br />CONNECTORS AND COUPLING SHALL BE SET -SCREW TYPE. CLAMP CONDUIT
<br />TO BOXES WITH BUSHING INSIDE AND LOCKNUT OUTSIDE.
<br />J. ALL CONDUIT AND RACEWAY SYSTEMS SHALL BE INSTALLED WITH SEPARATE
<br />GROUND CONDUCTOR. CONDUIT SYSTEM IS NOT TO BE USED AS THE SOLE
<br />GROUNDING MEANS.
<br />K. CONTRACTOR MAY COMBINE CIRCUIT IN RACEWAYS, BUT IF MORE THAN (3)
<br />CURRENT CARRYING CONDUCTORS ARE INSTALLED THEN CONTRACTOR TO
<br />DERATE CONDUCTORS IN ACCORDANCE WITH N.E.0 TABLE 310-15(bX2)(a).
<br />L E.C. SHALL PROVIDE AND INSTALL ELECTRICAL DEVICES AND WIRING TO
<br />COMPLY WITH N.F.PA. 96.7-3.1.3 FOR POWER SHUTOFF ON HOOD FAN AND
<br />ALL ELECTRICAL EQUIPMENT UNDER OVEN HOOD WHERE REQUIRED BY LOCAL
<br />CODE. VERIFY INSTALLATION AND OPERATION REQUIREMENTS WITH
<br />EXTINGUISHING SYSTEM SUPPLIER WHEN PRESENT.
<br />M. FOR EQUIPMENT FURNISHED BY OWNER OR OTHER CONTRACTORS;
<br />ELECTRICAL CONTRACTOR SHALL VERIFY EXACT LOAD, TYPE OF CONNECTION
<br />AND MOUNTING HEIGHT FOR EACH BOX OR EQUIPMENT ITEM TO BE
<br />INSTALLED. ALL HARD -WIRED CONNECTIONS TO EQUIPMENT SHALL BE MADE
<br />WITH FLEXIBLE LIQUID -TIGHT METAL CONDUIT WITH GREEN GROUND
<br />CONDUCTOR INSTALLED INSIDE RACEWAY. GROUND CONDUCTOR SHALL BE
<br />BONDED AT BOTH ENDS.
<br />N. PULL AND JUNCTION BOXES SHALL BE 16 GAUGE, OR HEAVIER, STEEL, WITH
<br />REMOVABLE KNOCKOUTS. BOXES SHALL BE AS MANUFACTURED BY APPLETON,
<br />STEEL CITY OR RACO. SIZE BOXES AS REQUIRED FOR THE INTENDED DUTY,
<br />MINIMUM SIZE AS REQUIRED BY THE NATIONAL ELECTRICAL CODE.
<br />0. RECEPTACLES SHALL BE LOCATED AS SHOWN ON THE DRAWINGS AND AT THE
<br />HEIGHTS SPECIFIED OR INDICATED. RECEPTACLE AND POWER OUTLETS SHALL
<br />BE SPECIFICATION GRADE, 20 AMP, GROUNDING TYPE AS MANUFACTURED BY
<br />HUBBELL, GENERAL ELECTRIC, PASS & SEYMOUR, EAGLE, OR LEVITON.
<br />RECEPTACLES SHALL BE WHITE. COLOR OF DEDICATED RECEPTACLES SHALL
<br />BE RED.
<br />P. ALL RECEPTACLES AND DATA/TELEPHONE OUTLETS SHALL BE MOUNTED AT
<br />+170 TO CENTER OF BOX UNLESS OTHERWISE NOTED.
<br />Q. REFER TO ARCHITECTURAL DRAWING FOR EQUIPMENT SCHEDULE. FIELD
<br />VERIFY ALL KITCHEN EQUIPMENT ELECTRICAL DATA WITH THE FOOD SERVICE
<br />CONTRACTOR. VERIFY EXACT LOADS, MOUNTING HEIGHTS AND NEMA
<br />CONFIGURATIONS PRIOR TO ROUGH -IN.
<br />R. SEE SHEET E-2 FOR LIGHT FIXTURE SCHEDULE.
<br />S. COORDINATE WITH THE SIGN CONTRACTOR AND ARCHITECT FOR NEW SIGN
<br />WATTAGE, VOLTAGE, AND EXACT LOCATION PRIOR TO J-BOX INSTALLATION.