EQUIPMENT WIRING SCHEDULE <br />AMPACITY <br />WIRE AND CONDUIT SIZE <br />15,20 <br />1 <br />2#12 + 1#12 GROUND IN 3/4" CONDUIT <br />15,20 <br />3 <br />3#12 + 1#12 GROUND IN 3/4" CONDUIT <br />25,30 <br />1 <br />2#10 + 1#10 GROUND IN 3/4" CONDUIT <br />25,30 <br />3 <br />3#10 + 1#10 GROUND IN 3/4" CONDUIT <br />35,40 <br />1 <br />2#8 + 1#10 GROUND IN 3/4" CONDUIT <br />35,40 <br />3 <br />3#8+ 1#10 GROUND IN 3/4" CONDUIT <br />45,50,55 <br />1 <br />2#6 + 1#10 GROUND IN 3/4" CONDUIT <br />45,50,55 <br />3 <br />3#6 + 1#10 GROUND IN 3/4" CONDUIT <br />60 <br />1 <br />2#4 + 1#10 GROUND IN 1" CONDUIT <br />60 <br />3 <br />3#4 + 1#10 GROUND IN 1" CONDUIT <br />70 <br />3 <br />3#4 + 1#8 GROUND IN 1" CONDUIT <br />80 <br />3 <br />3#3 + 1#8 GROUND IN 1-1/4" CONDUIT <br />90 <br />3 <br />3#2 + 1#8 GROUND IN 1-1/4" CONDUIT <br />100,110 <br />3 <br />3#1 + 1#6 GROUND IN 1-1/4" CONDUIT <br />125,150 <br />3 <br />3#1/0 + 1#6 GROUND IN 1-1/2" CONDUIT <br />175 <br />3 <br />3#2/0 + 1#6 GROUND IN 2" CONDUIT <br />200 <br />3 <br />3#3/0 + 1#4 GROUND IN 2" CONDUIT <br />NOTE: <br />1. THE AMPERAGE AND PHASE OF THE WIRING ON THIS SCHEDULE <br />CORRESPONDS TO THE CIRCUIT BREAKER SIZE IN THE ELECTRICAL <br />CONNECTION SCHEDULE FOR MECHANICAL EQUIPMENT. <br />PROVIDE WIRING AS INDICATED UNLESS OTHERWISE SPECIFIED. <br />2, WIRE SIZE IS BASED ON THE USE OF COPPER CONDUCTORS. <br />FIRE STOPPING NOTES <br />LIGHT FIXTURE SCHEDULE <br />TYPE <br />FIXTURE DESCRIPTION <br />MANUFACTURER <br />CATALOG NO. <br />MOUNTING <br />LAMPING <br />VOLTAGE <br />DESCRIPTION/REMARKS <br />TYPE <br />WATTAGE <br />A <br />6" DOWNLIGHT <br />(TO BE SELECTED) <br />- <br />RECESSED <br />LED <br />- <br />120 <br />6" RECESSED LED DOWNLIGHT <br />B <br />6" PENDANT <br />(TO BE SELECTED) <br />- <br />PENDANT <br />LED <br />- <br />120 <br />6" DECORATIVE PENDANT LIGHT <br />C <br />8' LED STRIP <br />(TO BE SELECTED) <br />- <br />RECESSED <br />LED <br />- <br />120 <br />8' LED STRIP LIGHT <br />D <br />2'x4' LIGHT FIXTURE <br />(TO BE SELECTED) <br />- <br />RECESSED <br />LED <br />- <br />120 <br />2'x4' RECESSED LED LIGHT <br />E <br />ACCENT LIGHT <br />(TO BE SELECTED) <br />- <br />WALL <br />LED <br />- <br />120 <br />3ECORATIVE WALL MOUNTED PENDANT ACCENT LIGHT <br />F <br />PENDANT FIXTURE <br />(TO BE SELECTED) <br />- <br />PENDANT <br />LED <br />- <br />120 <br />LARGE DECORATIVE PENDANT LIGHT <br />G <br />DIRECTIONAL DOWNLIGHT <br />(TO BE SELECTED) <br />- <br />RECESSED <br />LED <br />- <br />120 <br />6" RECESSED LED DIRECTIONAL DOWNLIGHT <br />NOTES: <br />1. PROVIDE ACCESSORIES AND MOUNTING HARDWARE AS REQUIRED FOR ALL LIGHT FIXTURES. <br />2. FIXTURE/ACCESSORY COLORS NOT INDICATED ON THE DRAWINGS SHALL BE SELECTED BY ARCHITECT. <br />3. PROVIDE LAMPING FOR ALL FIXTURES UNLESS LAMPING IS INCLUDED WITH FIXTURE. <br />4. PROVIDE TYPICAL MOCK-UP FOR LIGHT FIXTURE HANGING HEIGHTS AND EXPOSED ELECTRICAL CONDUIT LAYOUT TO BE REVIEWED BY ARCHITECT. <br />5. ALL LIGHT FIXTURES WITH INCANDESCENT OR FLOURESCENT LAMPING SHALL BE PROVIDED WITH A COMPATIBLE LED LAMP. <br />6. COLOR AND FIN ISH OF ALL LIGHT FIXTURES SHALL BE APPROVED BY OWNER/ARCHITECT PRIOR TO THE SUBMITTAL OF SHOP DRAWINGS. <br />1. GENERAL: FIRE STOPPING SHALL BE PROVIDED BY THIS CONTRACTOR FOR ALL <br />FLOOR, CEILING AND FIRE RATED WALL PENETRATIONS FOR CONDUIT, SLEEVES <br />AND/OR CABLING AS REQUIRED BY JOB CONDITIONS. <br />2. THE CONTRACTOR SHALL PROVIDE A FIRE STOP SYSTEM IN ACCORDANCE WITH THE <br />FOLLOWING: <br />2.1. THE SYSTEM SHALL CONSIST OF A WATER BASED SEALANT AND SUITABLE <br />DAMMING MATERIALS (WHERE REQUIRED) AND BE INSTALLED PER <br />MANUFACTURER'S REQUIREMENTS. <br />2.2. THE SEALANT SUPPLIED SHALL BE A TWO STAGED INTUMESCENT AND CAPABLE <br />OF EXPANDING UP TO 8 TIMES ITS ORIGINAL VOLUME. <br />2.3. THE SEALANT SUPPLIED SHALL CONTAIN NO ASBESTOS, NO FIBERGLASS, AND <br />NO SOLVENTS NOT CORROSIVE MINERAL SALTS OF ANY KIND. <br />2.4. THE SEALANT SHALL FORM A SURFACE CAPABLE OF BEING SANDED AND <br />PAINTED TO MATCH SURROUNDING SURFACES AND SHALL BE IMPERVIOUS TO <br />WATER WHEN DRY. <br />2.5. THE FIRE STOP SYSTEM SHALL BE TESTED TO THE TIME/TEMPERATURE <br />REQUIREMENTS OF ASTM E119 AND SHALL BE UL1479 (ASTM E814) AND <br />CLASSIFIED FOR UP TO 3 HOURS. <br />2.6. THE FIRE STOP SEALANT SHALL BE SPECSEAL SEALANT AS MANUFACTURED BY <br />SPECIFIED TECHNOLOGIES, INC. OR APPROVED EQUAL. <br />2.7. SPECIAL CARE SHALL BE TAKEN WITH ELECTRICAL SYSTEMS NOT TO <br />COMPROMISE ANY OF THE BUILDING FIRE PARTITIONS, FLOORS, WALLS OR <br />MEMBRANES. PROVIDE ALL FIRESTOPPING REQUIRED TO COMPLY WITH THE <br />BUILDING CODE, THE ELECTRICAL CODE AND THE UL LISTING OF EACH <br />ASSEMBLY. COORDINATE LOCATIONS AND TYPES OF MEMBRANES WITH <br />ARCHITECT. <br />SEISMIC RESTRAINT NOTES <br />1, GENERAL: IT IS THE INTENT OF THIS SEISMIC SPECIFICATION TO KEEP ALL ELECTRICAL <br />BUILDING SYSTEM COMPONENTS IN PLACE DURING A SEISMIC EVENT. ALL <br />ELECTRICAL SYSTEMS MUST BE INSTALLED IN STRICT ACCORDANCE WITH SEISMIC <br />CODES, COMPONENT MANUFACTURER'S AND BUILDING CONSTRUCTION <br />STANDARDS. WHENEVER A CONFLICT OCCURS BETWEEN THE MANUFACTURER'S OR <br />CONSTRUCTION STANDARDS, THE MOST STRINGENT SHALL APPLY. <br />2. THIS CONTRACTOR SHALL ENGAGE A PROFESSIONAL STRUCTURAL ENGINEER <br />REGISTERED IN THE JURISDICTION OF THIS PROJECT TO REVIEW THE ENTIRE <br />INSTALLATION TO DETERMINE ALL SEISMIC RESTRAINT REQUIREMENTS AND <br />METHODS. CONTRACTOR SHALL SUBMIT A REPORT OUTLINING THE STRUCTURAL <br />ENGINEER'S REVIEW AS WELL AS SEISMIC RESTRAINT SHOP DRAWINGS AND <br />SUPPORTING CALCULATIONS PREPARED BY THE PROFESSIONAL STRUCTURAL <br />ENGINEER FOR REVIEW BY THE ARCHITECT. <br />3. SEISMIC RESTRAINTS SHALL BE DESIGNED IN ACCORDANCE WITH SEISMIC FORCE <br />LEVELS AS DETAILED IN THE APPLICABLE BUILDING CODE. <br />3.1. ALL EQUIPMENT, CONDUITAND PULL BOXES SHALL BE ADEQUATELY <br />RESTRAINED TO RESIST SEISMIC FORCES. RESTRAINT DEVICES SHALL BE <br />DESIGNED AND SELECTED TO MEET SEISMIC REQUIREMENTS AS DEFINED IN <br />THE LATEST ISSUE OF THE BOCA NATIONAL BUILDING CODE IN ACCORDANCE <br />WITH THE APPLICABLE SEISMIC ZONE. <br />3.2. ANCHOR BOLT CALCULATORS, SIGNED AND STAMPED BY A REGISTERED <br />PROFESSIONAL ENGINEER, SHALL BE SUBMITTED SHOWING ADEQUACY OF THE <br />BOLT SIZING AND TYPE, STAMPED CALCULATIONS SHALL ALSO BE FURNISHED <br />FOR ANCHORS ON RESTRAINT DEVICES, CABLES, ISOLATORS AND RIGIDLY <br />MOUNTED EQUIPMENT. <br />INSTALLED EVERY 25 DEVICES <br />PANELBOARD: LP1 <br />AI C : 100, 000 <br />BUS RATING: 1225A I <br />225 A, 208Y1120 V, 3 PH, 4 W, 60 HZ <br />MAIN LUG ONLY <br />MAIN CIRCUIT BREAKER X <br />FLUSH MOUNTEDB <br />SURFACE MOUNTED X <br />NOTES: <br />LC = <br />VIA LIGHTING CONTROL PANEL <br />G = <br />GFCI - 5mA TRIP <br />P = <br />GFPE - 30 mA TRIP <br />S = <br />SHUNT TRIP <br />L = <br />PROVIDE LOCK ON CB <br />SHUNT TRIP MAIN <br />200% RATED NEUTRAL <br />ISOLATED GROUND <br />FEED THRU LUGS <br />100% RATED MAIN BREAKER <br />GROUND FAULT MAIN C.B. <br />CKT <br />No. <br />LOAD <br />Note <br />WIRE <br />SIZE <br />CIRCUIT BREAKERS <br />CKT <br />No. <br />LOAD <br />Note <br />WIRE <br />SIZE <br />CIRCUIT BREAKERS <br />o <br />N <br />Q <br />m <br />m <br />U <br />U <br />o <br />p <br />w <br />W <br />U-(9 <br />U- <br />(� <br />o <br />N <br />m <br />m <br />m <br />U <br />v <br />0 <br />p <br />p <br />p <br />w <br />w <br />w <br />U- <br />LL <br />u— <br />C9 <br />(� <br />1 <br />LIGHTING <br />1 <br />2 <br />LIGHTING <br />1 <br />3 <br />LIGHTING <br />1 <br />4 <br />LIGHTING <br />1 <br />5 <br />LIGHTING <br />1 <br />6 <br />LIGHTING <br />1 <br />7 <br />LIGHTING <br />1 <br />8 <br />LIGHTING <br />1 <br />9 <br />LIGHTING <br />1 <br />10 <br />RECEPTACLES <br />1 <br />11 <br />RECEPTACLES <br />1 <br />12 <br />ARCADE <br />1 <br />13 <br />ARCADE <br />1 <br />14 <br />ARCADE <br />1 <br />15 <br />ARCADE <br />1 <br />16 <br />ARCADE <br />1 <br />17 <br />ARCADE <br />1 <br />18 <br />DESK <br />1 <br />19 <br />RECEPTACLES <br />1 <br />20 <br />SPARE <br />21 <br />SPARE <br />22 <br />SPARE <br />23 <br />SPARE <br />24 <br />SPARE <br />25 <br />SPARE <br />26 <br />SPARE <br />27 <br />SPARE <br />28 <br />SPARE <br />29 <br />SPARE <br />30 <br />SPARE <br />31 <br />SPARE <br />32 <br />SPARE <br />33 <br />SPARE <br />34 <br />SPARE <br />35 <br />SPARE <br />36 <br />SPARE <br />37 <br />SPARE <br />38 <br />SPARE <br />F39 <br />SPARE <br />40 <br />SPARE <br />41 <br />SPARE <br />42 <br />SPARE <br />Im <br />F �T L kSD CM CM SD D Sp D <br />kSD kSD RTS RTS ( — _ <br />24V WIRING I 2 � TO ADDITIONAL <br />�? DEVICES <br />IM CM IM I F F F F �B <br />EXISTING 177cd 177cd 75cd 75cd <br />— ( 1 FIRE ALARM <br />POWER <br />SUPPLY ( 1 <br />EXISTING I �' AP7S] (TYP.) <br />ADDRESSABLE — <br />MAI N L 20AJ1 P <br />FIRE ALARM � �120V <br />CONTROL PANEL. I � � 3 <br />CAC �► iti <br />20A/1P _ <br />120-V/ <br />i <br />O1 ALL STROBES SHALL BE SYNCHRONIZED. EXACT METHOD FOR SYNCHRONIZATION SHALL BE <br />SPECIFIC TO EACH FIRE ALARM MANUFACTURER. PROVIDE EVIDENCE OF SYNCHRONIZATION IN <br />FIRE ALARM SUBMITTAL. <br />20 PROVIDE ISOLATION MODULES AT EITHER SIDE OF FIRE ALARM MODULES FOR BOOSTER PANELS <br />AND MASTER BOX, TYPICAL, <br />OPARTIAL FIRE ALARM RISER DIAGRAM <br />SCALE: N.T.S. <br />FIRE ALARM SYSTEM GENERAL NOTES: <br />1. ALL WIRING SHALL BE PER MANUFACTURER'S SPECIFICATIONS. <br />2. THIS SCHEMATIC IS TYPICAL. WIRE TO ALL DEVICES ON ALL LOOPS AND CIRCUITS. SEE PLAN VIEWS FOR TYPES AND QUANTITIES <br />OF DEVICES. <br />3. ALL FIRE ALARM WIRING SHALL BE RUN CONTINUOUS FROM DEVICE TO DEVICE. (SEE RIUFC). <br />4. OUTGOING AND RETURN CONDUCTORS MUST BE RUN IN SEPARATE RACEWAYS. PROVIDE MINIMUM SEPARATION OF 1 FOOT <br />WHERE THE CABLE IS RUN VERTICALLY AND A 4 FEET SEPARATION WHERE THE CABLE IS RUN HORIZONTALLY. (SEE RIUFC AND NFPA). <br />5. PROVIDE ANY ADDITIONAL REMOTE POWER SUPPLIES AS NECESSARY, PROVIDE ADDITIONAL SMOKE DETECTORS AS NECESSARY <br />PER NFPA. <br />6. PROVIDE INTERMEDIATE RELAYS AS NEEDED. <br />7. SYNCHRONIZE ALL STROBE LIGHTS. <br />8. VERIFY WIRING TYPE FOR INITIATING LOOP. <br />9. VERIFY ADDITIONAL WIRING (e.g. 24V POWER FOR MODULES) WITH SPECIFIED MANUFACTURER. <br />10. PROVIDE NEW FIRE ALARM POWER SUPPLIES, DEVICES, WIRING, ETC, AS REQUIRED TO SERVE NEW FIRE ALARM NOTIFICATION <br />DEVICES SHOWN ON THE DRAWINGS. <br />11. PROVIDE ISOLATION MODULES AS REQUIRED IN ACCORDANCE WITH THE RHODE ISLAND FIRE SAFETY CODE. PROVIDE <br />AN ISOLATION MODULE FOR EVERY 25 INITIATING DEVICES. <br />12. PROVIDE 25% SPARE CAPACITY ON INITIATIONS AND NOTIFICATIONS LOOPS. <br />13. ALL FIRE ALARM EQUIPMENT INCLUDING AND NOT LIMITED TO FIRE ALARM PANELS, CABINETS, ANNUNCIATOR, PULL STATIONS, <br />ETC. SHALL BE LOCKABLE TYPE. PROVIDE KEY ALIKE LOCKABLE EQUIPMENT AS REQUIRED. <br />PROJECT: <br />PINCHASERS EAST PASCO <br />ANTHONY PERRONE <br />6816 GALL BOULEVARD <br />ZEPHYRHILLS, FL 33542 <br />PROJECT NUMBER: 21 161 <br />Ln 0 <br />M O <br />O <br />cv U <br />_.J o U <br />WQLU <br />�Q <br />_J 06 <br />ck� D <br />Lu m 3: <br />O10 <br />x0 � <br />O d <br />u 10M 10 <br />w L. <br />F- � <br />v = �C) <br />r /J � �0; <br />0 <br />■� ,n <br />�� <br />z w. <br />(v) me <br />� <br />N <br />z <br />er <br />Z N <br />w <br />U CO <br />Q o <br />C'4 L0 <br />co <br />rL. <br />a� <br />c� <br />N <br />OMO 4 i <br />O <br />• F* M <br />M <br />U p 00 00 <br />N <br />O <br />oo <br />�VM <br />STAMP: <br />x,v. <br />y L i <br />�c <br />r� <br />rro4,�. <br />ISSUE: <br />DATE: <br />ISSUED FOR PERMIT <br />01 /25/2023 <br />DRAWING SCALE: NOTED <br />DRAWN BY: SB <br />CHECKED BY: MD <br />DRAWING TITLE: <br />ELECTRICAL - SCHEDULES <br />DRAWING NUMBER: <br />E260 <br />