ELECTRICAL SPECIFICATIONS: <br />PART 1- GENERAL <br />1.1. GENERAL REQUIREMENTS: <br />ALL WORK SHALL BE IN ACCORDANCE WITH THE ARRANGEMENT, DETAILS AND <br />LOCATION AS INDICATED ON THE CONTRACT DOCUMENTS, REFERENCE DRAWINGS AND <br />ANY SUPPLEMENTAL ADDENDA, BULLETINS OR DRAWINGS ISSUED BY THE <br />ARCHITECT/ENGINEER. LAYOUTS ARE DIAGRAMMATIC AND FINAL ARRANGEMENT OF <br />EQUIPMENT SHALL SUIT FIELD CONDITIONS. REFER TO ALL DRAWINGS AND <br />SPECIFICATIONS ASSOCIATED WITH THIS PROJECT FOR THE EXACT LOCATION OF ALL <br />EQUIPMENT AND REQUIRED MOUNTING HEIGHTS PRIOR TO THE START OF ANY <br />ROUGHING. THE RIGHT IS RESERVED TO MAKE ANY REASONABLE CHANGE IN LOCATION <br />TO OUTLETS AND EQUIPMENT PRIOR TO ROUGHING AT NO ADDITIONAL EXPENSE TO <br />THE OWNER. <br />1.2. SCOPE OF WORK: <br />THE SCOPE OF WORK CONSISTS OF THE INSTALLATION OF ALL MATERIALS TO BE <br />FURNISHED UNDER THIS SECTION, AND WITHOUT LIMITING THE GENERALITY THEREOF, <br />CONSISTS OF FURNISHING ALL LABOR, MATERIALS, EQUIPMENT, STORAGE, <br />TRANSPORTATION, RIGGING, STAGING, APPURTENANCES AND SERVICES NECESSARY <br />AND/OR INCIDENTAL TO PROPERLY COMPLETE ALL ELECTRICAL WORK SHOWN ON THE <br />DRAWINGS, AS DESCRIBED IN THE SPECIFICATIONS, OR AS REASONABLY INFERRED FROM <br />EITHER, IN THE OPINION OF THE ARCHITECT/ENGINEER AS BEING REQUIRED. <br />1.3. SITE VISIT: <br />BIDDERS ARE ADVISED TO VISIT THE SITE AND INFORM THEMSELVES AS THE TO <br />CONDITIONS UNDER WHICH THIS WORK WILL BE PERFORMED. FAILURE TO DO SO WILL, <br />IN NO WAY, RELIEVE THE SUCCESSFUL BIDDER FROM THE RESPONSIBILITY OF <br />FURNISHING ANY MATERIALS OR PERFORMING ANY WORK IN ACCORDANCE WITH THE <br />TRUE INTENT AND MEANING OF THE DRAWINGS AND SPECIFICATIONS. NO <br />COMPENSATION WILL BE GRANTED FOR ADDITIONAL WORK CAUSED BY UNFAMILIARITY <br />WITH SITE CONDITIONS THAT ARE VISIBLE OR READILY CONSTRUED BY AN EXPERIENCED <br />OBSERVER. FIELD VERIFY MEASUREMENTS AND CIRCUITING ARRANGEMENTS THAT ARE <br />SHOWN ON DRAWINGS. ARRANGEMENTS SHALL BE MADE WITH THE OWNER PRIOR TO <br />THE VISIT FOR INSPECTION F THE WORK <br />0 WO AREA(S). <br />1.4. RELATED WORK: <br />1. THE FOLLOWING RELATED WORK IS NOT INCLUDED UNDER THIS SECTION AND SHALL BE <br />PROVIDED UNDER OTHER SECTIONS. C COORDINATE WITH OOR ALL DIVISIONS TO ENSURE A <br />COMPLETE INSTALLATION: <br />A. CUTTING AND PATCHING. <br />B. ALLOWANCES. <br />C. ALTERNATIVES. <br />D. MAGNETIC DOOR RELEASE. <br />E. ACCESS PANELS. <br />F. MAGNETIC LOCK. <br />1.5. DEFINITIONS: <br />A. "CONCEALED" SHALL BE DEFINED AS AREAS WHERE CONDUIT AND WIRING IS <br />LOCATED IN CHASES, WALLS, PARTITIONS, SHAFTS, AND ABOVE FINISHED CEILINGS. <br />B. "EXPOSED" SHALL MEAN CONDUIT AND WIRING RUN ON THE SURFACE OF THE <br />BUILDING CONSTRUCTION. <br />C. "CONDUIT" SHALL MEAN IN ADDITION TO CONDUIT, ALL FITTINGS, HANGERS AND <br />OTHER ACCESSORIES RELATING TO SUCH CONDUIT SYSTEMS. <br />D. "WIRING" SHALL MEAN WIRE, RACEWAY, BOXES AND FITTINGS. <br />E. "PROVIDE" SHALL MEAN "PROVIDED COMPLETE IN PLACE" THAT IS, "FURNISHED <br />AND INSTALLED." <br />1.6. CODES, REGULATIONS, AND PERMITS: <br />ALL WORK UNDER THIS SECTION SHALL CONFORM TO THE LATEST EDITIONS OF THE <br />LOCAL STATE BUILDING CODE, THE STATE ELECTRICAL CODE, NFPA, ANSI/NECA <br />INSTALLATION STANDARDS, AND ALL OTHER LOCAL GOVERNING CODES. GIVE NOTICES, <br />FILE PLANS, OBTAIN AND PAY FOR PERMITS AND LICENSES AND OBTAIN NECESSARY <br />APPROVALS FROM AUTHORITIES HAVING JURISDICTION. PERMITS SHALL BE SECURED <br />THROUGH THE CITY. DELIVER CERTIFICATES OF INSPECTIONS TO ARCHITECT/ENGINEER. <br />NO WORK SHALL BE COVERED BEFORE EXAMINATION AND APPR <br />OVAL ROVAL BY <br />ARCHITECT ENGINEER AND THE AUTHORITIES HA <br />VING JURISDICTION. IMPERFECT OR <br />CONDEMNED WORK SHALL B REPLACED WITH E PLACE WORKING CONFORMING TO <br />REQUIREMENTS AT NO ADDITIONAL COST TO THE OWNER, SUBJECT TO APPROVAL OF <br />THE ARCHITECT/ENGINEER. IF WORK IS COVERED BEFORE DUE INSPECTION AND <br />APPROVAL THE ELECTRICAL CONTRACTOR SHALL PAY COSTS OF UNCOVERING THE <br />INSTALLED WORK, WHETHER IT MEETS CONTRACT REQUIREMENTS OR NOT. <br />1.7. MATERIAL <br />S: <br />ALL MATERIALS AND EQUIPMENT FURNISHED UNDER THIS SECTION SHALL BE NEW AND <br />OF THE BEST GRADE FOR THE SERVICE INTENDED. IT IS NOT INTENDED THAT THESE <br />SPECIFICATIONS OR DRAWINGS SHOW EVERY CONDUIT, FITTING, AND APPURTENANCE. <br />ALL SUCH PARTS NECESSARY FOR THE COMPLETE EXECUTION OF THE WORK, IN <br />ACCORDANCE WITH THE BEST PRACTICES OF THE TRADE AND TO THE SATISFACTION OF <br />THE ARCHITECT/ENGINEER SHALL BE PROVIDED WHETHER THESE PARTS MAY HAVE <br />SPECIFICALLY MENTIONED OR NOT, OR INDICATED ON THE DRAWINGS. <br />1.8. SHOP DRAWINGS: <br />WHERE THE DRAWINGS OR SPECIFICATIONS LIST SPECIFIC BRANDS OR CATALOG <br />NUMBERS, ONLY THESE PRODUCTS MAY BE USED UNLESS THE WORDS: "OR APPROVED <br />EQUAL" OR "BUT ARE NOT LIMITED TO" ARE INCLUDED, THE ENGINEER'S REVIEW IS FOR <br />GENERAL CONFORMANCE WITH THE DESIGN INTENT. MARKINGS OR COMMENTS SHALL <br />NOT BE CONSTRUED AS RELIEVING THE ELECTRICAL CONTRACTOR FROM COMPLIANCE <br />WITH DRAWINGS AND SPECIFICATIONS, NOR DEPARTURES THEREOF. THE ELECTRICAL <br />CONTRACTOR REMAINS RESPONSIBLE FOR DETAILS AND ACCURACY, FOR CONFORMING <br />AND CORRECTNESS OF ALL QUANTITIES AND DIMENSIONS, FOR SELECTING FABRICATING <br />PROCESSES, FOR TECHNIQUES OR ASSEMBLY, AND FOR PERFORMING THEIR WORK IN A <br />SAFE MANNER. DEVIATIONS TO SPECIFIED MATERIALS SHALL BE AT THE SOLE RISK OF <br />THE ELECTRICAL CONTRACTOR, WHO SHALL BE RESPONSIBLE FOR ALL ASSOCIATED <br />CHANGES TO THIS AND OTHER TRADES. WITHIN THIRTY (30) DAYS AFTER THE DATE OF <br />NOTICE TO PROCEED, AND BEFORE THE PROCUREMENT OF ANY MATERIALS AND <br />EQUIPMENT, SUBMIT FOR APPROVAL A COMPLETE ITEMIZED LIST OF ALL THE <br />MATERIALS AND SHOP <br />EQUIPMENT INCORPORATED UNDER THIS SECTION. A Q 0 LS <br />DRAWING SUBMITTALS SHALL BE COMPLETE AND INCLUDE ALL PART 2 PRODUCTS AND <br />VFDS OF THIS SPECIFICATION AND BE CLEARLY IDENTIFIED. NO CONSIDERATION WILL BE <br />GIVEN TOP PARTIAL SUBMITTALS EXCEPT WITH PRIOR APPROVAL. AR X 0 AL. <br />1.9. OPERATIONS AND MAINTENANCE MANUALS: <br />1. AT LEAST TWO (2) WEEKS PRIOR TO THE TIME OF TURNINGOVER HIS CONTR <br />ACT TO THE <br />OWNER FOR USE AND OCCUPANCY OR SUBSTANTIAL COMPLETION, SECURE AND <br />DELIVER TO THE ARCHITECT/ENGINEER THREE (3) COMPLETE INDEXED BOUND FILES <br />CONTAINING APPROVED OPERATING AND MAINTENANCE MANUALS, SHOP DRAWINGS, <br />AND OTHER DATA AS FOLLOWS: <br />A. OPERATION DESCRIPTION OF ALL SYSTEMS. <br />B. COMPLETE SHOP DRAWINGS OF ALL EQUIPMENT. <br />C. PREVENTIVE MAINTENANCE INSTRUCTIONS FOR ALL SYSTEMS. <br />D. SPARE PARTS LISTS OF ALL SYSTEM COMPONENTS. <br />E. NAMES, ADDRESS AND TELEPHONE NUMBERS OF ALL SUPPLIERS OF THE SYSTEMS. <br />2. NON -AVAILABILITY OF OPERATING AND MAINTENANCE MANUALS OR INACCURACIES <br />THEREIN MAY BE GROUNDS FOR CANCELLATION AND POSTPONEMENT OF ANY <br />SCHEDULED FINAL INSPECTION BY THE OWNER UNTIL SUCH TIME AS THE DISCREPANCY <br />HAS BEEN CORRECTED AND/OR RETAINAGE OF SUFFICIENT MONIES TO PREPARE SAME. <br />1.10. RECORD DRAWINGS: <br />OWNER'S RECORD DRAWINGS SHALL BE UPDATED AS THE PROJECT PROGRESSES. <br />MAINTAIN DOCUMENTS IN SAFE, DRY LOCATION. INDICATE CLEARLY AND ACCURATELY <br />ANY CHANGES NECESSITATED BY FIELD CONDITIONS AND DIMENSION ALL CONCEALED <br />RACEWAYS. THE ELECTRICAL CONTRACTOR SHALL DELIVER THE COMPLETED <br />REPRODUCIBLE RECORD DRAWINGS AND CAD DISKS PROPERLY TITLED AND DATED TO <br />ARCHITECT/ENGINEER. THESE RECORD DRAWINGS SHALL BECOME THE PROPERTY OF <br />THE OWNER. <br />1.11. CHANGE ORDERS/PROPOSAL REQUEST: <br />A. DURING THE COURSE OF CONSTRUCTION, CHANGES IN THE WORK MAY OCCUR. <br />WHEN A SIGNIFICANT CHANGE IS TO BE MADE, A PROPOSAL REQUEST WILL BE <br />ISSUED. <br />B, PROVIDE A COMPLETE COST BREAKDOWN WHEN RESPONDING TO EACH <br />PROPOSAL REQUEST. <br />C. EACH ITEM OF WORK TO BE PRICED SEPARATELY. <br />D. EACH LINE ITEM TO BE BROKEN DOWN INCLUDING QUANTITIES AND LISTING <br />SEPARATELY LABOR AND MATERIAL. <br />0 <br />E. BOTH CREDITS AND EXTRAS SHALL BE SEPARATELY AND CLEARLY QUANTIFIED. <br />F. ALLOWANCES FOR OVERHEAD AND PROFIT SHALL BE AS LISTED IN THE <br />SUPPLEMENTARY CONDITIONS. <br />G. IF YOU BECOME AWARE OF A FIELD CONDITION, CODE REQUIREMENT, ERROR, OR <br />OMISSION THAT YOU FEEL SHOULD RESULT IN A CHANGE TO THE WORK, PLEASE <br />CONTACT THE ENGINEER FOR DISCUSSION. THE ENGINEER MAY BE ABLE TO <br />CLARIFY THE SITUATION AND AVOID UNNECESSARY PAPERWORK. <br />H. IT IS RECOGNIZED THAT THE OWNER BENEFITS WHEN THE CONSTRUCTION <br />PROCESS IS A COOPERATIVE EFFORT INSTEAD OF AN ADVERSARIAL RELATIONSHIP. <br />REASONABLE GIVE-AND-TAKE ALLOWS THE CONSTRUCTION PROCESS TO MOVE <br />SMOOTHLY. YOUR EFFORTS IN THIS REGARD WILL BE APPRECIATED BY ALL PARTIES. <br />1.12. GUARANTEE AND SERVICE: <br />THE ELECTRICAL CONTRACTOR SHALL GUARANTEE THE PERFORMANCE OF THE <br />INSTALLATION AND ALL EQUIPMENT INCLUDED IN THIS SECTION IN WRITING FOR ONE <br />(1) YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE ENGINEER. SHOULD ANY <br />DEFECTS IN MATERIALS OR WORKMANSHIP APPEAR DURING THIS PERIOD, THEY SHALL <br />BE CORRECTED OR REPLACED BY THE ELECTRICAL CONTRACTOR TO THE SATISFACTION <br />OF THE ARCHITECT/ENGINEER, AT NO ADDITIONAL COST TO THE OWNER. <br />1.13, COORDINATE WITH OTHER TRADES: <br />CONFER WITH OTHER TRADES AND FURNISH IN WRITING TO THE ARCHITECT/ENGINEER <br />ANY INFORMATION D NECESSARY TO PERMIT THE WORK OF ALL TRADES TO BE INSTALLE <br />D <br />E <br />SATISFACTORILY AND WITH THE LEAST POSSIBLE INTERFERENCE OR DELAY. WORK <br />INSTALLED THAT CREATED INTERFERENCE OR RESTRICTS ACCESS REQUIRED BY CODE OR <br />TO CONDUCT MAINTENANCE AND/OR ADJUSTMENTS SHALL BE MODIFIED AT NO <br />ADDITIONAL COST TO THE OWNER. FURNISH TO OTHER TRADES ANY INFORMATION <br />REQUIRED FOR THE PURPOSE OF COORDINATING ADJACENT WORK. <br />1.14. CUTTING AND PATCHING: <br />: <br />I <br />INCLUDE ALL CORING, CUTTING, PATCHING AND FIREPROOFING NECESSARY FOR THE <br />EXECUTION OF THIS SECTION. STRUCTURAL ELEMENTS SHALL NOT BE CUT WITHOUT <br />WRITTEN APPROVAL OF THE ARCHITECT ENGINEER. REPAIR AND P E PATCH AROUND T / A H <br />WORK SPECIFIED HEREIN TO MATCH THE EXISTING ADJACENT SURFACES TO THE <br />SATISFACTION OF THE ARCHITECT/ENGINEER. FILL AND PATCH ALL OPENINGS OR HOLES <br />LEFT IN THE EXISTING STRUCTURES BYTHE REMOVAL OF EXISTING EQUIPMENT THAT IS <br />PART OF THIS SECTION OF THE SPECIFICATIONS. APPLY FIRESTOPPING TO CABLE AND <br />RACEWAY SLEEVES AND OTHER PENETRATIONS OF FIRE -RATED FLOOR AND WALL <br />ASSEMBLIES TO RESTORE ORIGINAL UNDISTURBED FIRE -RESISTANCE RATINGS OF <br />ASSEMBLIES. <br />1.15. HOISTING, SCAFFOLDING AND PLANKING: <br />INCLUDE THE FURNISHING, SETUP -UP AND MAINTENANCE OF ALL HOISTING <br />MACHINERY, CRANES, SCAFFOLDS, STAGING AND PLANKING AS REQUIRED FOR THE <br />EXECUTION OF WORK FOR THIS SECTION. <br />1.16. SAFETY REQUIREMENTS: <br />LIFE SAFETY AND ACCIDENT PREVENTION SHALL BE A PRIMARY CONSIDERATION. <br />COMPLY WITH ALL SAFETY REQUIREMENTS OF THE OWNER AND OSHA THROUGHOUT <br />THE ENTIRE CONSTRUCTION PERIOD OF THE PROJECT. FURNISH, PLACE AND MAINTAIN <br />PROPER GUARDS AND ANY OTHER NECESSARY CONSTRUCTION REQUIRED TO SECURE <br />SAFETY OF LIFE AND PROPERTY. <br />1.17. ACCESSIBILITY: <br />ALL WORK PROVIDED UNDER THIS SECTION SHALL BE PROVIDED SO THAT PARTS <br />REQUIRING PERIODIC INSPECTION, MAINTENANCE AND REPAIR ARE READILY <br />ACCESSIBLE, WORK OF THIS TRADE SHALL NOT INFRINGE UPON THE CLEARANCES OF <br />OTHER TRADES. <br />1.18. PROTECTION OF WORK AND PROPERTY: <br />THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE CARE AND THE <br />PROTECTION OF ALL WORK INCLUDED UNDER THIS SECTION UNTILTHE COMPLETION <br />AND FINAL ACCEPTANCE OF THIS PROJECT. PROTECT ALL EQUIPMENT AND MATERIALS <br />FROM DAMAGE FROM ALL CAUSES INCLUDING, BUT NOT LIMITED TO, FIRE, VANDALISM, <br />AND THEFT. ALL MATERIALS AND EQUIPMENT DAMAGED OR STOLEN SHALL BE <br />REPAIRED OR REPLACED WITH EQUAL MATERIAL OR EQUIPMENT AT NO ADDITIONAL <br />COSTTO THE OWNER. PROTECT ALL EQUIPMENT, OUTLETS AND OPENINGS, AND ROOF <br />PENETRATIONS WITH TEMPORARY PLUGS, CAPS AND COVERS. PROTECT WORK AND <br />MATERIALS OF OTHER TRADES FROM DAMAGE THAT MIGHT BE CAUSED BY WORK OR <br />WORKMEN UNDER THIS SECTION AND MAKE GOOD ON DAMAGE THUS CAUSED. <br />DAMAGED MATERIALS SHALL BE REMOVED FROM THE SITE; DAMAGE CAUSED BY THE <br />ELECTRICAL CONTRACTOR DURING INSTALLATION SHALL BE REPAIRED AND/OR <br />REPLACED AT THIS CONTRACTOR'S EXPENSE TO THE COMPLETE SATISFACTION OF THE <br />BUILDING OWNER. <br />1.19. SEISMIC RESTRAINT REQUIREMENTS: <br />PROVIDE SEISMIC RESTRAINTS AS REQUIRED IN ACCORDANCE WITH THE STATE <br />BUILDING CODE. A REGISTERED PROFESSIONAL STRUCTURAL ENGINEER, LICENSED IN <br />THE APPLICABLE STATE FOR THE PROJECT LOCATION, SHALL PREPARE THE SEISMIC <br />RESTRAINT DESIGN AND CERTIFY THAT THE DESIGN IS IN COMPLIANCE WITH THE STATE <br />BUILDING CODE REQUIREMENTS. <br />1.20. PROJECT CLOSEOUT: <br />A CERTIFICATE OF COMPLETION SHALL BE ISSUED BY THE ELECTRICAL CONTRACTOR <br />INDICATING THAT THE INSTALLATION IS IN CONFORMANCE WITH THE CONSTRUCTION <br />DOCUMENTS AND ALL APPLICABLE LOCAL, STATE AND FEDERAL STATUTES AND CODES. <br />FINAL INSPECTION BY THE ENGINEER SHALL BE CONDUCTED AFTER RECEIPT OF THE <br />CERTIFICATE OF COMPLETION. NO LIFE SAFETY DEFICIENCIES IN THE EGRESS OR EXIT <br />LIGHTING SYSTEMS, FIRE ALARM SYSTEM, OR THE EMERGENCY POWER SYSTEM SHALL <br />BE PRESENT WHEN REQUESTING FINAL INSPECTION. PREMATURE REQUESTS FOR FINAL <br />INSPECTIONSTHAT REQUIRE REINSPECTION OF DEFICIENT ITEMS WILL RESULT IN BACK <br />CHARGES OF THE COSTS ASSOCIATED WITH THE REINSPECTION. <br />1.21. TEMPORARY POWER AND LIGHTING: <br />1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE AND PAY FOR CAPACITY FROM THE <br />LOCAL UTILITY COMPANY POWER LINES, MAKE ARRANGEMENTS WITH THE LOCATION <br />UTILITY COMPANY FOR TEMPORARY SERVICE AS REQUIRED. <br />2. PROVIDE ADEQUATE DISTRIBUTION EQUIPMENT, WIRING, AND OUTLETS FOR POWER <br />AND LIGHTING. <br />3. PROVIDE POWER OUTLETS FOR CONSTRUCTION OPERATIONS, WITH BRANCH WIRING <br />AND DISTRIBUTION BOXES LOCATED AS REQUIRED. <br />4. PROVIDE 20 AMPERE DUPLEX OUTLETS, SINGLE PHASE CIRCUITS FOR POWER TOOLS IN <br />THE ACTIVE WORK AREA AS REQUIRED. PERMANENT CONVENIENCE RECEPTACLES MAY <br />BE UTILIZED DURING THE PROCESS. CONSTRUCTION THE GENERAL CONTRACTOR SHALL PRO L <br />PAY ALL UTILITY COMPANY USAGE BILLINGS. <br />5. PROVIDE GFCI PROTECTED POWER OUTLETS FOR CONSTRUCTION OPERATIONS, WITH <br />BRANCH WIRING AND DISTRIBUTION BOXES LOCATED AS REQUIRED. <br />6. THE ELECTRICAL CONTRACTOR SHALL PROVIDE FOR TEMPORARY LIGHTING, PROVIDING <br />AND MAINTAINING OSHA REQUIRED LIGHTING LEVELS FOR CONSTRUCTION <br />OPERATIONS. <br />7. PROVIDE BRANCH WIRING FROM POWER SOURCE TO DISTRIBUTION BOXES WITH <br />LIGHTING CONDUCTORS, PIGTAILS, AND LAMPS AS REQUIRED. <br />8. THE ELECTRICAL CONTRACTOR SHALL MAINTAIN LIGHTING AND PROVIDE ROUTINE <br />REPAIRS AS REQUIRED. PERMANENT BUILDING LIGHTING MAY BE UTILIZED DURING <br />CONSTRUCTION. POWER SHALL BE DERIVED FROM THE EXISTING BUILDING AND KWH <br />USAGE PAID BY THE OWNER. <br />1.22. DRAWINGS AND SPECIFICATIONS: <br />THE DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY EACH TO THE OTHER, AND <br />ANY LABOR OR MATERIAL CALLED FOR BY EITHER, WHETHER OR NOT BY BOTH, OR <br />NECESSARY FOR THE SUCCESSFUL OPERATION OF ANY COMPONENTS SHALL BE <br />PROVIDED. BEFORE INSTALLING ANY WORK, VERIFY THAT IT DOES NOT INTERFERE WITH <br />THE CLEARANCES REQUIRED FOR OTHER WORK. INSTALLED WORK WHICH INTERFERES <br />WITH EXISTING NECESSARY SERVICES SHALL BE MODIFIED AS DIRECTED BY THE <br />ARCHITECT, AT NO ADDITIONAL COST TO THE OWNER. BE FAMILIAR WITH THE <br />DRAWINGS AND SPECIFICATIONS OF ALL OTHER TRADES TO PREVENT INTERFERENCES <br />AND ASSURE COMPLETE COORDINATION. IF THERE ARE ANY DISCREPANCIES BETWEEN <br />THE ELECTRICAL DRAWINGS AND SPECIFICATIONS REQUEST CLARIFICATION FROM THE <br />ARCHITECT/ENGINEER PRIOR TO START AND OR CONTINUATION OF ANY WORK OR THE <br />PROCUREMENT OF ANY MATERIALS AND EQUIPMENT. <br />PART 2 - PRODUCTS <br />2.1. FIRE ALARM SYSTEM: <br />1. GENERAL: PROVIDE AN ADDITION AND MODIFICATION TO THE EXISTING AUTOMATIC <br />AND MANUAL, AUXILIARY CONNECTED FIRE ALARM SYSTEM, ACCORDING TO THE <br />FOLLOWING SPECIFICATIONS TO BE WIRED, CONNECTED, TESTED AND LEFT IN FIRST <br />CLASS OPERATING CONDITION. ALL EQUIPMENT SHALL BE UNDERWRITERS' <br />LABORATORIES APPROVED FOR THE INTENDED USE AND SHALL MEET WITH THE <br />APPROVAL OF THE LOCAL AUTHORITY. THE COMPLETE SYSTEM SHALL BE AS <br />MANUFACTURED BY SIEMENS. THE COMPLETE SYSTEM SHALL BE INSTALLED IN <br />ACCORDANCE WITH APPLICABLE SECTIONS OF NFPA STANDARDS, SECTION 72, <br />101 LIFE SAFETY, THE STATE OF MASSACHUSETTS BUILDING CODES, THE STATE OF <br />MASSACHUSETTS SAFETY CODES AND ALL LOCAL CODES AND REQUIREMENTS, ALL <br />MODIFICATIONS TO CONTROL EQUIPMENT MUST BE WITH THE SAME BRAND OF <br />EQUIPMENT AS THE EXISTING. <br />2. ALL DEVICES MUST BE U.L. LISTED AS COMPATIBLE WITH THE CONTROL EQUIPMENT. <br />SUBMIT PROOF OF COMPATIBILITY WITH SHOP DRAWING SUBMITTAL. <br />3. REPLACE ANY EXISTING EQUIPMENT AND WIRING THAT IS NOT COMPATIBLE WITH THE <br />EQUIPMENT THAT YOU PROVIDE OR THE MODIFICATIONS THAT YOU MAKE, WITHOUT <br />ADDITIONAL COMPENSATION. <br />4. DEVICES PROVIDE ADDITIONAL FIRE ALARM ES AS SHOWN ON THE DRAWINGS. NEW <br />C <br />DEVICES SHALL MATCH AND BE FULLY COMPATIBLE WITH EXISTING EQUIPMENT; <br />PROVIDE IN WHITE FINISH UNLESS OTHERWISE NOTED_ THE MANUFACTURE OF THE <br />NEW EQUIPMENT SHALL MATCH EXISTING. EXTENSION OF EXISTING FIRE ALARM <br />SYSTEM SHALL INCLUDE INFRASTRUCTURE UPGRADES INCLUDING EXISTING FIRE ALARM <br />CONTROL PANEL, ADDITIONAL POWER SUPPLIES, AMPLIFIERS, BATTERIES, SOFTWARE <br />AND ALL OTHER ADDITIONAL COMPONENTS AS REQUIRED TO PROVIDE AND FULLY <br />FUNCTIONAL FIRE ALARM SYSTEM. PRIOR TO SUBMITTING SHOP DRAWINGS THE <br />ELECTRICAL CONTRACTOR AND/OR THEIR FIRE ALARM VENDOR SHALL FIELD VERIFY <br />THATTHE EXISTING FIRE ALARM CONTROL PANEL IS EXPANDABLE AND IS NOT LIMITED <br />TO SOFTWARE COMPATIBILITY, HARDWARE, AVAILABILITY OF PARTS, ETC. IF IT IS FOUND <br />THAT THE EXISTING FIRE ALARM CONTROL PANEL CANNOT BE USED IN THE NEW DESIGN <br />PER THE CONSTRUCTION DOCUMENTS, THEN THE ELECTRICAL CONTRACTOR SHALL <br />PROVIDE SEPARATE PRICING FOR REPLACING THE CONTROL PANEL WITH A FULLY <br />COMPATIBLE TYPE AND RE -PROGRAMING OF ALL EXISTING DEVICES AS REQUIRED. <br />5. AS IT IS NOT PRACTICAL TO ENUMERATE IN THESE SPECIFICATIONS ALL DETAILS OF <br />FITTINGS AND ACCESSORY EQUIPMENT REQUIRED FOR PROPER OPERATION OF THE <br />SYSTEM HEREIN DESCRIBED, IT IS UNDERSTOOD THAT THEY WILL BE SUPPLIED BY THE <br />CONTRACTOR WITHOUT EXTRA COMPENSATION. PROVIDE ALL FITTINGS, <br />TERMINATIONS, ETC., NEEDED FOR THE BEST PERFORMANCE POSSIBLE AT THE PRESENT <br />STATE-OF-THE-ART. <br />6. WIRING: THE ELECTRICAL SUBCONTRACTOR SHALL PROVIDE IN ACCORDANCE WITH <br />MANUFACTURER'S INSTRUCTIONS, ALL WIRING, CONDUIT AND OUTLET BOXES <br />REQUIRED FOR INSTALLATION OF A COMPLETE SYSTEM AS DESCRIBED HEREIN AND AS <br />SHOWN ON THE PLANS. PROVIDE ALL WIRING IN METALLIC RACEWAY. PROVIDE NO. 14 <br />GAUGE, THWN, SOLID CONDUCTORS AND COLOR CODE AS REQUIRED. <br />7. TAG ALL WIRES AT ALL JUNCTION POINTS AND TEST FREE FROM GROUNDS OR CROSSES <br />BETWEEN CONDUCTORS. CARRY THE WIRING SYSTEM THROUGH ALL EQUIPMENT. <br />PROVIDE RED PAINTED TERMINAL CABINETS WITH HINGED LOCKABLE COVERS AT ALL <br />JUNCTION POINTS. MAKE ALL CONDUCTOR SPLICES ON SCREW TYPE TERMINAL BLOCKS; <br />WIRE NUTS SHALL NOT BE USED. PROPERLY LABEL ALL TERMINALS WITHIN TERMINAL <br />CABINETS. MAKE FINAL CONNECTIONS BETWEEN CONTROL EQUIPMENT AND THE <br />WIRING SYSTEM UNDER DIRECT SUPERVISION OF A REPRESENTATIVE OF THE <br />MANUFACTURER. <br />8. SUBMIT COMPLETE DOCUMENTATION FOR THE FIRE ALARM/LIFE SAFETY SYSTEM <br />SHOWING THE MODEL NUMBER, TYPE, RATING, SIZE, STYLE, MANUFACTURER'S NAMES, <br />AND MANUFACTURER'S CATALOG DATA SHEETS FOR ALL ITEMS TO ENSURE <br />COMPLIANCE WITH THESE SPECIFICATIONS. <br />9. UPON CONTRACT BID APPROVAL, AND PRIOR TO START OF SYSTEM INSTALLATION, <br />SUBMIT SHOP DRAWINGS TO AND OBTAIN WRITTEN APPROVAL FROM THE FIRE <br />DEPARTMENT, PRIOR TO ORDERING FIRE ALARM EQUIPMENT, GENERAL REQUIREMENTS <br />ARE AS FOLLOWS: <br />A. SYSTEM OPERATION DESCRIPTION: DETAILED DESCRIPTION FOR THIS PROJECT, <br />INCLUDING METHOD OF OPERATION AND SUPERVISION OF EACH TYPE OF CIRCUIT <br />AND SEQUENCE OF OPERATIONS FOR MANUALLY AND AUTOMATICALLY INITIATED <br />SYSTEM INPUTS AND OUTPUTS. MANUFACTURER'S STANDARD DESCRIPTIONS FOR <br />GENERIC SYSTEMS ARE NOT ACCEPTABLE. <br />B. DEVICE ADDRESS LIST: COORDINATE WITH FINAL SYSTEM PROGRAMMING. <br />C. SYSTEM RISER DIAGRAM WITH DEVICE ADDRESSES, CONDUIT SIZES, AND CABLE <br />AND WIRE TYPES AND SIZES. <br />D. WIRING DIAGRAMS: POWER, SIGNAL, AND CONTROL WIRING. INCLUDE DIAGRAMS <br />FOR EQUIPMENT AND FOR SYSTEM WITH ALL TERMINALSAND INTERCONNECTIONS <br />IDENTIFIED. SHOW WIRING COLOR CODE. <br />E. BATTERIES: SIZE CALCULATIONS. <br />10. SUBMIT SHOP DRAWINGS TO AND OBTAIN WRITTEN APPROVAL FROM THE <br />AUTHORITIES HAVING JURISDICTION, PRIOR TO ROUGHING. RESUBMIT IF REQUIRED TO <br />MAKE CLARIFICATIONS OR REVISIONS TO OBTAIN APPROVAL. ON RECEIPT OF <br />COMMENTS FROM AUTHORITIES HAVING JURISDICTION, SUBMIT THEM TO ENGINEER <br />FOR REVIEW. <br />11. GUARANTEE AND FINAL TEST: GUARANTEE ALL NEW EQUIPMENT AND WIRING TO BE <br />FREE FROM INHERENT MECHANICAL AND ELECTRICAL DEFECTS FOR A PERIOD OF ONE <br />YEAR FROM THE DATE OF FINAL ACCEPTANCE. THE ELECTRICAL CONTRACTOR SHALL <br />PROVIDE THE SERVICES OF THE BUILDING FIRE ALARM MAINTENANCE CONTRACTOR <br />FOR TIE-IN OF NEW FIRE ALARM CIRCUITRY. <br />12. BEFORE THIS INSTALLATION SHALL BE CONSIDERED COMPLETE AND ACCEPTABLE TO <br />THE AWARDING AUTHORITIES, A COMPLETE TEST ON THE SYSTEM SHALL BE <br />PERFORMED AS FOLLOWS: THE ELECTRICAL CONTRACTOR'S JOB FOREMAN, IN THE <br />PRESENCE OF A REPRESENTATIVE OF THE FIRE ALARM MAINTENANCE CONTRACTOR, <br />FIRE ALARM MANUFACTURER AND A REPRESENTATIVE OF THE LOCAL FIRE <br />DEPARTMENT, SHALL OPERATE EACH ALARM INITIATING DEVICE AND VERIFY ZONE <br />ANNUNCIATION, AUDIBLE AND VISUAL SIGNALING AND PROPER OPERATION OF THE <br />MASTER BOX. EACH CIRCUIT SHALL BE OPENED AT ITS MOST REMOTE POINTTO CHECK <br />FORTH E CORRECTNESS OF THE SUPERVISORY CIRCUITRY. WHEN THE ABOVE TEST HAS <br />BEEN COMPLETED TO THE SATISFACTION OF THE MANUFACTURER'S REPRESENTATIVE, <br />THE ELECTRICAL SUBCONTRACTOR'S JOB FOREMAN, AND THE LOCAL FIRE DEPARTMENT, <br />A LETTER WITNESSED AND CO -SIGNED BY ALL ATTESTING TO THE COMPLETION OF THIS <br />TESTING SHALL BE FORWARDED TO THE ENGINEER. TEST TO INCLUDE BOTH NEW AND <br />EXISTING WIRING AND EQUIPMENT. <br />13. DURING THE GUARANTEE PERIOD, 24 HOUR SERVICE (365 DAYS/YEAR) IS REQUIRED OF <br />THE CONTRACTOR AND EQUIPMENT SUPPLIER. <br />14. QUARTERLY TESTING, AS REQUIRED BY THE MASSACHUSETTS FIRE SAFETY CODE IS NOT <br />PART OF THIS CONTRACT. <br />15. SERVICE CALLS RESULTING FROM ACTS OF VANDALISM, ACTS OF NATURE, OR ACTS <br />WHICH ARE BEYOND THE CONTROL OF THE EQUIPMENT MANUFACTURER ARE <br />EXCLUDED UNDER THE GUARANTEE AND SHALL BE CONSIDERED A BILLABLE CALL. <br />2.2. WIRE AND CABLE: <br />WIRING SHALL BE TYPE THHN/THWN OR XHHW, MINIMUM OF #12 AWG SOLID COPPER <br />WITH CONDUCTIVITY OF NOT LESS THAN 98% OF THE ANSI STANDARD FOR ANNEALED <br />COPPER, UL LISTED FOR BUILDING WIRE 90 DEGREES CELSIUS. WET OR DRY LOCATIONS <br />RATED FOR 600V SERVICE. MC AND FAMC CABLING CAN BE USED WHERE CONCEALED. <br />CONDUCTORS LARGER THAN #10 SHALL BE STRANDED. COLOR CODING SHALL BE <br />CONSISTENT THROUGHOUT. <br />2.3. CONDUIT: <br />ELECTRIC METALLIC TUBING SHALL BE ELECTRO-GALVANIZED SHERARDIZED STEEL. <br />WHERE EXPOSED, ALL WIRING SHALL BE INSTALLED IN CONDUIT. ALL ROUTING OF <br />CONDUIT SHALL BE RUN PERPENDICULAR TO BUILDING WALLS. ALL ELECTRIC METALLIC <br />TUBING SHALL BE UTILIZED WITH STEEL SET SCREW TYPE FITTINGS. CONDUIT SHALL BE <br />TUBING SHALL BE UTILIZED WITH STEEL SET SCREW TYPE FITTINGS, CONDUIT SHALL BE <br />SUPPORTED FROM BUILDING STRUCTURE; AND SHALL BE INDEPENDENT OF DUCTS, <br />PIPES, CEILING AND THEIR SUPPORTING MEMBERS. CONTRACTOR SHALL PATCH AND <br />REPAIR EXISTING FIRESTOPPING TO RESTORE ORIGINAL FIRE -RESISTANCE RATING OF <br />BUILDING STRUCTURE FOLLOWING INSTALLATION. ALL FIRESTOPPING SHOULD BE BY <br />G.C.. <br />2.4. WIRING DEVICES: <br />1. LIGHTSWITCHES: <br />A. REFER TO DRAWINGS. <br />B. COLOR OF SWITCHES SHALL BE AS SELECTED BY ARCHITECT. <br />2. OCCUPANCY SENSORS: <br />A. REFER TO DRAWINGS. <br />3. RECEPTACLES: <br />A. DUPLEX RECEPTACLES SHALL BE SPECIFICATION GRADE GROUNDING TYPE, RATED <br />20 AMPERES, 125 VOLTS. RECEPTACLES SHALL BE BACK AND SIDE WIRED WITH <br />SCREW TYPE TERMINALS HAVING SUITABLE CONDUCTOR RELEASE ARRANGEMENT <br />GFCI RECEPTACLES SHALL BE SPECIFICATION GRADE 20 AMPERES, 125 VOLTS. <br />B, COLOR OF RECEPTACLES SHALL BE AS SELECTED BY ARCHITECT. <br />2.S. LIGHTING FIXTURES: <br />A. FURNISH ALL LABOR, MATERIALS AND EQUIPMENT REQUIRED FOR A COMPLETE <br />INSTALLATION OF THE LIGHTING EQUIPMENT SPECIFIED ON THE LIGHTING FIXTURE <br />SCHEDULE. <br />B. INTERIOR LIGHTING FIXTURES SHALL BE 3500°K UNLESS NOTED OTHERWISE. <br />C. LIGHTING FIXTURES SHALL BE SUPPORTED ABOVE CEILING FROM STRUCTURAL <br />FLOOR ABOVE VIA #12 JACK CHAIN AND "Y" HANGERS FROM TWO OPPOSITE <br />CORNERS. <br />D. EXIT SIGNS SHALL BE TYPICALLY MOUNTED ON CEILING WHERE VISIBLE OR ON <br />WALL WHERE CEILING MOUNTING IS NOT PRACTICAL. PRIOR TO ROUGHING <br />COORDINATE WITH ARCHITECTURAL DRAWINGS/ELEVATIONS FOR SPECIFIC <br />MOUNTING DIRECTION AND FOR LOCATION. <br />E. WHERE LIGHTING FIXTURES OTHER THAN THE SPECIFIED PRODUCTS ARE <br />PROVIDED, THE CONTRACTOR SHALL PROVIDE LIGHT LEVEL CALCULATIONS IN <br />ACCORDANCE WITH IESNA STANDARDS TO JUSTIFY THAT SUBSTITUTED FIXTURES <br />ARE OR EQUAL PERFORMANCE TO THE SPECIFIED PRODUCTS (APPLIES TO ALL <br />LIGHTING FIXTURES IN ALL SPACES). <br />F. WHERE SUBMITTING TO ENGINEER FOR REVIEW THE LIGHTING FIXTURE <br />SUBMITTALS SHALL CONSIST OF THE FOLLOWING: LIGHTING FIXTURE CUT SHEET, <br />LIGHTING FIXTURE BALLAST/DRIVER CUT SHEET, AND LIGHTING FIXTURE LAMP/LED <br />CUT SHEET FOR EACH FIXTURE. GROUPED CUT SHEETS WILL NOT BE ALLOWED. <br />WHEN SUBMITTING ON LED PRODUCTS PROVIDE LIGHTING FACTS, LM-79 AND <br />LM-80 TEST REPORTS FOR REVIEW. <br />2.6. OUTLET BOXES: <br />PROVIDE OUTLET BOXES AS REQUIRED FOR ALL ELECTRICAL DEVICES AND EQUIPMENT. <br />MINIMUM SIZE OF BOXES SHALL BE 4", 1-1/4" DEEP. ALL OUTLET BOXES SHALL BE <br />GALVANIZED STEEL. <br />2.7. PULL BOXES, JUNCTION BOXES AND WIREWAYS: <br />A. PULL BOXES SHALL BE OF CODE GAUGE GALVANIZED STEEL WITH SCREW COVERS <br />TO MATCH. PULL BOXES AND WIREWAYS SHALL BE AS SHOWN ON CONTRACT <br />DRAWINGS AND/OR AS REQUIRED BY THE NATIONAL ELECTRICAL CODE AND/OR <br />JOB CONDITIONS, WITH STEEL BARRIERS SEPARATING SYSTEMS. <br />B. WIREWAYS SHALL BE OF CODE GAUGE STEEL, BAKED ENAMEL MANUFACTURED <br />STANDARD SECTIONS AND STEEL FITTINGS, WITH COMBINATION HINGED AND <br />SCREW COVERS. <br />C. CONDUCTORS PASSING THROUGH PULL BOXES AND WIREWAYS SHALL BE <br />IDENTIFIED TO INDICATE THEIR ORIGIN AND TERMINATION. PROVIDE NAMEPLATES <br />FOR ALL PULL BOXES. <br />2.8. THERMAL SWITCHES: <br />A. THERMAL SWITCHES SHALL BE NEMA TYPE 1 TOGGLE SWITCH FOR NORMAL DUTY <br />WITH THERMAL OVERLOAD RELAY. <br />B. SWITCH ENCLOSURES SHALL BE OF A TYPE APPROVED FOR THE LOCATION AND <br />ATMOSPHERE IN WHICH IT IS MOUNTED. <br />C. THERMAL SWITCHES SHALL BE INSTALLED WHERE CALLED FOR OR WHERE <br />REQUIRED BY CODE. <br />D. THERMALSWITCHES SHALL BE PROVIDED WITH PILOT WHERE CALLED FOR ON THE <br />DRAWINGS. <br />2.9. CIRCUIT BREAKERS FOR EXISTING PANELBOARDS: <br />A. CIRCUIT BREAKERS SHALL BE EQUAL TO THE EXISTING CIRCUIT BREAKERS AND OF <br />THE SAME MANUFACTURER AS THE EXISTING PANELBOARDS IN WHICH THEY ARE <br />TO BE INSTALLED. <br />B. PROVIDE UPDATED TYPEWRITTEN CIRCUIT DIRECTORY CARDS INDICATING AREAS <br />AND DEVICES SERVED BY EACH CIRCUIT IN ALL EXISTING PANELBOARDS PANELS <br />AFFECTED BY THE WORK OF THIS PROJECT. <br />2.10. PANELBOARDS: <br />A. AT EACH LOCATION INDICATED ON THE PLANS, FURNISH AND INSTALL AN <br />APPROPRIATE PANEL OF THE AMPACITY AND VOLTAGE RATING SHOWN ON THE <br />DRAWINGS. <br />B. ALL PANELS SHALL BE OF THE SAFETY DEAD FRONT CIRCUIT BREAKER TYPE FOR <br />SERVICE ON THREE PHASES, FOUR WIRE MAINS UNLESS OTHERWISE SPECIFIED. <br />C. ALL PANELS SHALL BE OF CODE GAUGE STEEL. <br />D. PANELS SHALL BE SURFACE OR FLUSH MOUNTED, AS INDICATED ON THE PLANS, <br />AND INSTALLED SO THAT THE TOP CIRCUIT BREAKER IS NO MORE THAN 6-0"ABOVE <br />THE FINISHED FLOOR. <br />E. THE PANELBOARDS SHALL BEAR THE UNDERWRITERS' LABORATORIES LABEL. <br />F. ALL BUSES SHALL BE COPPER. <br />G. ALL PANELBOARDS SHALL HAVE A CIRCUIT DIRECTORY CARD MOUNTED IN A FRAME <br />WITH PLASTIC COVER INSTALLED ON THE INSIDE OF THE DOOR. <br />H. ALL DIRECTORY CARDS SHALL BE PROPERLY FILLED IN, USING A TYPEWRITER, AND <br />INDICATING AREAS AND DEVICES SERVED BY EACH CIRCUIT. <br />I. ALL CIRCUIT BREAKERS SHALL BE OF QUICK -MAKE AND QUICK -BREAK TYPE ON <br />MANUAL OPERATION, TRIP -FREE, AND WITH INVERSE TIME CHARACTERISTICS AND <br />SHALL HAVE BOLTED BUS CONNECTIONS; PLUG-IN CIRCUIT BREAKERS WILL NOT BE <br />ALLOWED. <br />J. PANELBOARD TRIMS SHALL BE DOOR -IN -DOOR DESIGN. <br />K. TRIMS AND DOORS SHALL BE MADE OF CODE GAUGE, FULL FINISH SHEET STEEL. <br />L. THE TRIM AND DOORS SHALL BE FACTORY FINISHED ON BOTH SIDES. <br />M. ALL PANELBOARDS SHALL BE KEYED ALIKE. <br />N. PANELBOARDS SHALL CONTAIN CIRCUIT BREAKERS INDICATED ON PANELBOARD <br />SCHEDULE ON THE DRAWINGS. <br />0. TWO AND THREE POLE BREAKERS SHALL BE COMMON TRIP TYPE. <br />P. ALL PANELBOARDS SHALL BE EQUIPPED WITH A NEUTRAL BAR HAVING ONE <br />SOLDERLESS CONNECTOR FOR EACH CIRCUIT AS INDICATED AND WITH ALL <br />REQUIRED KNOCKOUTS. <br />Q. NEW PANELBOARDS SHALL BE MANUFACTURED BY GENERAL ELECTRIC. <br />2.11. DRY TYPE TRANSFORMER: <br />A. DRY TYPE TRANSFORMER SHALL MEET NEMA PREMIUM <br />EFFICIENCY LEVELS, U.L. LISTED. <br />B. NOISE LEVEL SHALL BE A MAXIMUM OF 50 DB AVERAGE <br />MEASURED AT DISTANCE OF 1" FROM CASE PER NEMA <br />PUBLICATION #TR-1-1960 PER LARGE REVISION THEREOF. <br />C. PROVIDE SUPPLEMENTAL STEEL AS REQUIRED TO DISTRIBUTE <br />LOADING. <br />D. SEE TRANSFORMER SCHEDULE FOR ADDITIONAL INFORMATION. <br />E. MANUFACTURER SHALL BE GENERAL ELECTRIC. <br />2.12. DISCONNECT SWITCHES: <br />A. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL DISCONNECTING <br />MEANS AS REQUIRED BY THE NATIONAL ELECTRICAL CODE FOR ALL MOTORS, <br />B. MANUAL MOTOR STARTERS SHALL HAVE QUICK MAKE, QUICK BREAK TOGGLE <br />MECHANISMS WITH ALLOWANCE FOR UP TO 10% FIELD ADJUSTMENTTO <br />NOMINAL OVERLOAD HEATER VALUES. <br />C. DISCONNECT SWITCHES SHALL BE FUSED OR UNFUSED AS SHOWN ON THE <br />DRAWINGS, OR AS REQUIRED, NEMA TYPE HD SAFETY SWITCHES FOR HEAVY DUTY, <br />WITH INTERLOCKING COVER, SIDE OPERATED WITH PROVISIONS FOR PADLOCKING <br />THE SWITCH HANDLE IN THE OFF POSITION. <br />D. ALL MOTOR ISOLATING SWITCHES INDICATED ON THE DRAWINGS SHALL BE RATED <br />IN HORSEPOWER, AND SHALL BE RATED FOR THE VOLTAGE OF THE MOTOR AND <br />SHALL BE FURNISHED AND INSTALLED AT THE MOTOR LOCATION WHETHER OR <br />NOT THE MOTOR IS WITHIN SIGHT OF THE MOTOR FEEDER DISCONNECTING <br />MEANS. <br />E. DISCONNECT SWITCH ENCLOSURES SHALL BE OF THE PROPER NEMA TYPE FOR THE <br />INTENDED LOCATION AS DEFINED BY NEMA AND SHALL BE PHOSPHATE COATED OR <br />EQUIVALENT CODE GAUGE GALVANIZED SHEET STEEL WITH USAF[ NO. 24 DARK <br />GRAY BAKED ENAMEL FINISH. <br />F. FUSES E HALL BE CLASS RK-1 SIZE PER DRAWING AND NAMEPLATE <br />S D <br />REQUIREMENTS. <br />G. INSTALL REJECTION CLIPS TO PROHIBIT INSTALLATION OF OTHER THAN CURRENT <br />LIMITING FUSES. <br />H. DISCONNECT SWITCHES SHALL BEAR THE UNDERWRITERS' LABORATORIES LABEL <br />AND BE MANUFACTURED BY SQUARE D COMPANY. <br />PART 3 - EXECUTION <br />3.1. GENERAL: <br />A. ALL INTERRUPTIONS AND SHUTDOWNS OF EXISTING ELECTRICAL SYSTEMS AND <br />SERVICES SHALL BE AS SHORT AS POSSIBLE AND AT TIME AND DURATION <br />APPROVED BY THE OWNER AND THE ENGINEER. THE ELECTRICAL CONTRACTOR <br />SHALL INCLUDE ALL PREMIUM TIME ASSOCIATED WITH THE SYSTEM AND SERVICE <br />INTERRUPTIONS AND SHUTDOWNS. <br />3.2. CLEANING, ADJUSTING, AND TESTING: <br />A. AT THE COMPLETION OF THE WORK, ALL PARTS OF THE INSTALLATION SHALL BE <br />THOROUGHLY CLEANED. ALL DEVICES, EQUIPMENT, CONDUITS, AND FITTINGS <br />SHALL BE COMPLETELY CLEANED OF GREASE, METAL CUTTINGS, DIRT WHICH MAY <br />HAVE ACCUMULATED DURING CONSTRUCTION, AND PROTECTION COVERS. <br />B. ANY DISCOLORATION OR DAMAGE TO PARTS OF THE BUILDING, ITS FINISH OR <br />FURNISHINGS DUE TO FAILING TO PROPERLY CLEAN THE ELECTRICAL SYSTEM SHALL <br />BE REPAIRED BY THE ELECTRICAL CONTRACTOR WITHOUT COST TO THE OWNER. <br />C. THE ELECTRICAL CONTRACTOR SHALL TEST ALL WORK AND EQUIPMENT AS <br />DIRECTED BY THE ARCHITECT AND AS REQUIRED BY AUTHORITIES HAVING <br />JURISDICTION, FURNISH ALL EQUIPMENT, NECESSARY PERSONNEL AND THE <br />ELECTRICAL POWER. <br />D. THE ENTIRE INSTALLATION SHALL BE TESTED FOR SHORTS, GROUNDS AND OPEN <br />CIRCUITS AND ALL DEFECTS SHALL BE CORRECTED BEFORE ACCEPTANCE OF WORK. <br />E. ALL WORK SHALL BE DEMONSTRATED TO BE IN PROPER OPERATING CONDITION TO <br />THE COMPLETE SATISFACTION OF THE ARCHITECT, TENANT, AND BUILDING <br />OWNER. <br />3.3. EQUIPMENT CONNECTIONS: <br />THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONNECTIONS TO ALL EQUIPMENT <br />REQUIRING ELECTRICAL SERVICE, INCLUDING POWER CABLES, BRANCH CIRCUIT <br />EXTENSIONS, FIRE ALARM CABLES, MOTORS, CONTROLLERS, LIGHTING FIXTURES AND ALL <br />OTHER EQUIPMENT AND SYSTEMS SPECIFIED OR SHOWN ON THE DRAWINGS. <br />3.4. GROUNDING AND BONDING: <br />PROVIDE GROUNDING AND BONDING METHODS IN ACCORDANCE WITH NEC CODE <br />ARTICLE 250 AND LOCAL UTILITY COMPANY REGULATIONS, <br />3.5. CONDUIT WORK: <br />1. BRANCH CIRCUIT WIRING IN HUNG CEILINGS, FURRED SPACES OR EXPOSED AND NOT <br />SUBJECT TO PHYSICAL DAMAGE MAY BE INSTALLED IN ELECTRICAL METALLIC TUBING. <br />2. TYPE MC CABLE MAY BE USED WHERE REQUIRED FOR "FISHING" INTO EXISTING WALL <br />AND CEILING CAVITIES. <br />3. CONDUIT EXTENSIONS IN METAL PARTITIONS MAY BE MADE WITH FLEXIBLE METAL <br />CONDUIT, WITH GROUNDING CONDUCTOR. <br />4. CONNECTIONS TO PORTABLE AND PERMANENTLY MOUNTED MOTORIZED EQUIPMENT <br />AND MOTORS, AS WELL AS THE EQUIPMENT HOUSING, SHALL BE MADE WITH <br />APPROVED LIQUID TIGHT FLEXIBLE METAL CONDUIT. <br />5. FLEXIBLE CONNECTIONS SHALL BE A MAXIMUM OF 18" LONG AND WITH GROUNDING <br />CONDUCTOR. <br />6. FLEXIBLE CONNECTIONS SHALL BE USED PRIOR TO ATTACHMENT TO EQUIPMENT <br />HOUSINGS. <br />7. CONDUIT ENDS SHALL BE CUT SQUARE, THREADED AND REAMED TO REMOVE BURRS <br />AND SHARP EDGES. <br />8. FIELD THREADS SHALL BE OF THE SAME TYPE AND HAVE THE SAME EFFECTIVE LENGTH <br />AS FACTORY CUT THREADS. <br />9. EXCESSIVE EXPOSED THREADS WILL NOT BE ALLOWED. <br />10. TURNS, WHEREVER REQUIRED IN EXPOSED CONDUIT RUNS SHALL BE MADE BY THE USE <br />OF FACTORY -MADE BENDS, OR FIELD MADE BENDS. <br />11. CONDULETS, OR IN THE EVENT OF A MULTIPLICITY OF CONDUITS MAKING THE SAME <br />TURN, A STEEL JUNCTION BOX WITH A REMOVABLE STEEL COVER MAY BE USED. <br />12. OFFSETS AND BENDS FOR CHANGES IN ELEVATION OF EXPOSED CONDUIT RUNS SHALL <br />BE MADE AT WALLS OR BEAMS AND NOT IN OPEN SPACES BETWEEN WALLS OR BEAMS. <br />13. CONDUITS SHALL BE ROUTED SO AS NOT TO INTERFERE WITH THE OPERATION OF <br />MAINTENANCE OF ANY EQUIPMENT. <br />14. THE ENTIRE JOB SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER. <br />15. ALL CONDUIT WORK SHALL BE CAREFULLY CLEANED AND DRIED INSIDE BEFORE THE <br />INSTALLATION OF CONDUCTORS. <br />16. PLUG CONDUIT ENDS TO EXCLUDE DUST, MOISTURE, PLASTER OR SIMILAR WHILE <br />TENANT FIT -OUT IS UNDER CONSTRUCTION. <br />17. NO LUBRICANTS OR CLEANING AGENTS WHICH MIGHT HAVE A DELETERIOUS EFFECTS <br />ON CONDUCTOR COVERINGS SHALL BE USED FOR DRAWING CONDUCTORS INTO <br />RACEWAYS. <br />1 DRAWINGS, IN RE T TO ROUTING OF CONDUITS ARE DIAGRAMMATIC. <br />8. RELATION I M <br />19. THE NUMBER AND SIZE OF CONDUITS AND WIRE SHALL BE FURNISHED AND INSTALLED <br />AS INDICATED BY THE DRAWINGS. <br />20. CONDUITS SHALL BE ROUTED IN THE FIELD SO AS TO BE COORDINATED WITH THE <br />BUILDING STRUCTURE AND ALL OTHER TRADES. <br />21. CONCEALED CONDUIT SHALL BE AS SHORT AND DIRECT AS POSSIBLE. <br />22. EXPOSED CONDUIT SHALL BE RUN IN STRAIGHT LINES PARALLEL TO WALLS, BEAMS AND <br />COLUMNS AND WITH RIGHT ANGLE BENDS AND STEEL THREADED CONDUIT FITTINGS. <br />23. CONDUITS PASSING THROUGH FLOORS, WALLS AND BEAMS SHALL BE OF SUCH SIZE, <br />NUMBER AND IN SUCH LOCATIONS SO AS NOT TO IMPAIR THE STRENGTH OF THE <br />EXISTING CONSTRUCTION. <br />24. PARTICULAR ATTENTION SHALL BE GIVEN TO THE INSTALLATION OF CONDUITS AT <br />GROUPED AREAS, SUCH AS PANELBOARD, CABINET AND PULL BOX ENTRANCES. <br />25. RACEWAYS IN CEILING SPACES SHALL BE ROUTED IN SUCH AN APPROVED MANNER AS <br />TO ELIMINATE OR MINIMIZE THE NUMBER OF JUNCTION BOXES REQUIRED, BUT ALSO <br />SHALL BE ROUTED IN AN ORDERLY AND ORGANIZED MANNER. <br />26. SUPPORT RODS AND CLAMPS SHALL BE FURNISHED AND INSTALLED AS REQUIRED FOR <br />COMPLETE INSTALLATION. <br />27. SUPPORT OF CONDUITS BY USE OF WIRE IS STRICTLY PROHIBITED. <br />28. CONDUITS SHALL BE SUPPORTED AND SECURED BY CONDUIT SUPPORT DEVICES. <br />29. WHERE RIGID METAL CONDUIT IS THREADED IN THE FIELD, A STANDARD CONDUIT <br />CUTTING DIE PROVIDING 3/4" TAPER PER FOOT SHALL BE EMPLOYED. <br />30. THREADLESS COUPLING SHALL NOT BE USED ON RIGID METAL CONDUIT EXCEPT WHERE <br />SPECIFICALLY ALLOWED BY THE ARCHITECT. <br />31. RUNNING THREADS SHALL NOT BE USED ON RIGID METAL CONDUIT. <br />32. CONDUIT WORK SHALL BE INSTALLED IN SUCH A MANNER TO KEEP EXPOSED THREADS <br />TO AN ABSOLUTE MINIMUM, AND IN NO CASE SHALL MORE THAN THREE THREADS BE <br />LEFT EXPOSED AFTER THE CONDUIT WORK IS MADE UP TIGHT. <br />33. THIS REQUIREMENT APPLIES TO ALL CONDUIT WORK. <br />34. MINIMUM SIZE CONDUIT SHALL BE 1/2" NOMINAL TRADE SIZE. <br />35. A MINIMUM 3/16" DIAMETER TWISTED NYLON PLASTIC TYPE FISH CORD SHALL BE <br />FURNISHED AND INSTALLED IN ALL EMPTY RACEWAYS. <br />36. PROVIDE A TAG ON EACH END OF FISH CORD INDICATING THE LOCATION OF THE OTHER <br />END. <br />ii <br />3.6. FIRE STOPPING: <br />1. ELECTRICAL INSTALLATIONS IN HOLLOW SPACES, VERTICAL SHAFTS AND VENTILATION <br />OR AIR HANDLING DUCTS SHALL BE SO MADE THAT THE POSSIBLE SPREAD OF FIRE OR <br />PRODUCTS OF COMBUSTION WILL NOT BE SUBSTANTIALLY INCREASED. <br />2. OPENINGS AROUND ELECTRICAL PENETRATIONS THROUGH FIRE -RESISTANCE RATED <br />WALLS, PARTITIONS, FLOORS OR CEILINGS SHALL BE FIRESTOPPED USING APPROVED <br />METHODS TO MAINTAIN THE FIRE -RESISTANCE RATING. <br />3.7. IDENTIFICATION: <br />1. NAMEPLATES SHALL BE FURNISHED AND INSTALLED ON THE METER <br />CENTERS/SWITCHBOARD AND METER CENTERS/SWITCHBOARD CIRCUIT BREAKERS, <br />PANELBOARDS, TRANSFORMERS, JUNCTION BOXES, CABINETS FOR ALL SPECIAL <br />PURPOSE SWITCHES, MOTOR DISCONNECT SWITCHES, STARTERS AND OTHER CONTROLS <br />FURNISHED UNDER THIS CONTRACT, TO DESIGNATE THE EQUIPMENT CONTROLLED AND <br />FUNCTION. <br />2. NAMEPLATES SHALL BE LAMINATED WHITE BAKELITE WITH 1/4" HIGH BLACK RECESSED <br />LETTERS. <br />3. NAMEPLATES SHALL BE SECURELY ATTACHED TO THE EQUIPMENT WITH GALVANIZED <br />SCREWS OR RIVETS. <br />4. ADHESIVES OR CEMENTS WILL NOT BE PERMITTED. <br />5. ALL PULL BOXES AND JUNCTION BOXES SHALL BE IDENTIFIED AS TO SYSTEM AND <br />FUNCTION BY MEANS OF BLACK FIBRE PEN. <br />00 <br />O <br />O <br />N <br />(V <br />04 <br />U <br />0 <br />PROJfCT: <br />PINCHASERS EAST PASCO <br />ANTHONY PERRONE <br />6816 GALL BOULEVARD <br />ZEPHYRHILLS, FL 33542 <br />PROJECT NUMBER: 21 161 <br />I ( J N :E"' O <br />o <br />N U <br />oU <br />uj QU <br />t <br />3 2 = <br />D< <br />u <br />OV <br />I ine 0 <br />uj m -]�: <br />x 3 <br />O O <br />�__ _ 10 <br />u M ,O <br />C) -ITN v <br />w 1� <br />i_ Ln <br />�v <br />V) = V) <br />0 <br />w . <br />wu- <br />z U <br />N <br />N N <br />z< (. <br />Z v <br />ujZN <br />U 00 <br />N in <br />Q . <br />a <br />.i <br />'h, <br />-'4 <br />..4 O <br />¢, . <br />aj 9 <br />O .� <br />0 n 0 O 00 N <br />4-+ <br />M <br />• '� (� M <br />�w O U O,, p <br />N %ar.knIn 0 <br />rn M .r4 <br />3 <br />GPM* kf) kn <br />. <br />,c 00 p <br />O O <br />= <br />rA U U <br />ct 0 in ­4U <br />-4--a`* N <br />, <br />1�1 -0= <br />.40�b N <br />O% <br />, <br />p�/%�? M <br />00 <br />STAMP: <br />�i��+►u�r�o•st fr.r <br />- `- <br />,14 <br />r { lfw/� <br />la � <br />1CTle <br />� yV ,k. <br />` 1.4 <br />i . i O.r i, <br />1 •: N <br />N <br />;. <br />' l <br />I rI J I' F -<, -ter <br />i <br />*r�. �,-_ I(l�i : `4 - <br />ISSUE: <br />DATE: <br />ISSUED FOR PERMIT <br />01 /25/2023 <br />DRAWING SCALE: NOTED <br />DRAWN BY: SB <br />CHECKED BY: MD <br />DRAWING TITLE: <br />ELECTRICAL - SPECIFICATIONS <br />DRAWING NUMBER: <br />