Laserfiche WebLink
Building Type Type II-B, Fully Sprinklered <br />Occ. Group A-3 <br />Occupant <br />Load <br />Load Calculation <br />SF <br />Factor <br />Occupants <br />Fitness Area <br />13,272 <br />1 50 <br />266 <br />Storage <br />884 <br />1 300 <br />3 <br />Locker Rooms/Showers <br />2,677 <br />1 50 <br />54 <br />Tanning/Massage <br />1,553 <br />1 Per Room/Bed <br />11 <br />Total Square Feet <br />18,389 <br />334 <br />Allowable Area per FBC 507 <br />31,836 <br />(Type II-8, Fully Sprinklered) <br />Required Exit Width (.20 x Total <br />Occupants) <br />66.8" <br />Provided Exit Width <br />136" <br />Required Number of Exits <br />2 <br />Provided Number of Exits <br />3 <br />EXIT 3 <br />DESIGN OCC. LOAD = 83 <br />REQ'D WIDTH = 17" <br />PROVIDED WIDTH = 34" <br />V <br />(D- <br />NOTE: <br />MINIMUM CLEARANCE BETWEEN ALL <br />EQUIPMENT ON EXIT ACCESS ROUTES TO <br />BE MINIMUM 44" CLEAR, TYP. <br />a — <br />TO EXIT 3=103'-8" <br />TO EXIT 1=175'-1" <br />TO EXIT 2=193'-2" <br />NOTE: <br />ABRUPT CHANGES IN ELEVATION OF <br />WALKING SURFACES WITHIN THE MEANS <br />OF EGRESS NOT TO EXCEED 1/4". <br />CHANGES IN ELEVATION EXCEEDING 1/4" <br />BUT LESS THAN 1/2" SHALL BE BEVELED <br />WITH A SLOPE OF 1:2. <br />NOTE: <br />MEANS OF EGRESS SHALL BE MARKED IN <br />ACCORDANCE WITH FFPC 7.10, INCLUDING <br />TACTILE SIGNAGE WHERE REQ'D BY FFPC <br />7.10.1.3. <br />WORKOUT <br />10� <br />CIRCUIT TRAINING <br />102 <br />TO EXIT 3=108'-8" <br />TO EXIT 2=139'-6" <br />TO EXIT 1=203'-11 <br />ELECTRICAL PF 360 <br />112E 1#103B <br />ABS & STRETCHING <br />103A <br />11 <br />EXIT 2 <br />DESIGN OCC. LOAD = 83 <br />REQ'D WIDTH = 17" <br />PROVIDED WIDTH = 34" <br />/1,// <br />TRAVEL = 58'-9" ° <br />iom;� — �t — y". � t <br />s d <br />R <br />& <br />EX EX EX 0 <br />co EXIT 1 ► AV IT HYDROMASSAGE <br />DESIGN OCC. LOAD = 167 i 112A 115B <br />RECEPTION REQ'D WIDTH = 34" <br />116 PROVIDED WIDTH = 68" _ _ _ I NOTE: <br />—'------— — — — — — — — — — — <br />PER CODE, THE MAXIMUM TRAVEL <br />O 0 0 O U I I DISTANCE TO AN EXIT IS 250'-0" <br />NOTE: <br />SEE A3.0 FOR DOOR SCHEDULE <br />2 3 <br />118 <br />rill <br />MEN'S LOCKER <br />109 <br />TO EXIT 2=139'-10" <br />TO EXIT 3=156'-O" <br />I TO EXIT 1=175'-0" <br />EN'S BATH <br />108 <br />WOMEN'S BATH <br />105 <br />TO EXIT 1=132'-11" <br />TO EXIT 2=181'-11" <br />TO EXIT 3=198'-l" <br />WOMEN'S LOCKER <br />104 <br />#111B <br />TANNING <br />111A <br />TANNING <br />1C <br />TANNING <br />111D <br />TO EXIT 1=108'-4" <br />TO EXIT 2=218'-8" <br />TO EXIT 3=234'-10" <br />Planet Fitness <br />4 Liberty Lane West <br />Hampton, New Hampshire 03842 <br />Issue Sets <br />No. I Issue Set <br />By I Date IAppr.I <br />ARCHITECT <br />Daniel K. Mullin, Architect, NCARB <br />517 S Main St. <br />Moscow, ID 83843 <br />P. (208) 892-8433 <br />F. (208) 892-8533 <br />MEP ENGINEERS <br />:::E <br />Dave M. Saarem, P. E. <br />2188 Alfred Way <br />Carson City, NV 89703 <br />P. (775) 772-9846 <br />STRUCTURAL ENGINEERS <br />Richard M. Welcher, P.E. <br />Tatum Smith Welcher Engineers, Inc. <br />3100 S Market St, Suite 202 <br />Rogers, AR 72758 <br />P. (479) 621-6128 <br />COPYRIGHT <br />These plans are an instrument of service and are <br />the property of DKMullin Architects, and may not be <br />duplicated, disclosed, or reproduced without the <br />written consent of DKMullin Architects. Copyright <br />and infringement will be enforced and prosecuted. <br />Project Manager Approval <br />Architect/Engineer of Record <br />a�. <br />Location <br />7910 GALL BLVD <br />ZEPHYRHILLS, FL 33541 <br />Project/Space No. <br />Planet Fitness Tenant Improvement <br />Sheet Title <br />EGRESS PLAN <br />EGRESS PLAN <br />1/8" = 1'-0" <br />Scale: As Shown <br />Drawn By: C.W. <br />Chk'd By: T.G. <br />Issue Date: <br />APRIL 15, 2020 <br />Project No. <br />191205 <br />Sheet <br />EG 1.0 <br />