PXERT1Nt; 5,P t Dv <br />RISER KEY NOTES: OX <br />10. EXISTING (4) # 3/0 & (1) # 1/0 G, IN EXISTING 2" CONDUIT <br />0 NEW (4) # 3/0 & (1) # 6 G, IN EXISTING 2" CONDUIT. <br />0 EXISTING 4" TO 2" REDUCER. <br />® NEW (4) # 3/0 & (1) # 6 G, IN EXISTING 4" CONDUIT. <br />Q NEW 4" TO 2" REDUCER AT THE TOP OF THE EXISTING <br />CONDUIT STUB IN. <br />EXISTING GROUND — <br />©NEW (4) # 3/0 & (1) # 6 GROUND IN NEW 2" CONDUIT. <br />QNEW 7-DAY, 4 CIRCUIT PROGRAMMABLE TIME CLOCK <br />ALL WIRING SHALL BE COPPER ONLY. <br />CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR <br />TO SUBMITTING BIDS (INCLUDING ALL WIRE AND CONDUIT TYPE, <br />SIZE, NUMBER, AND LOCATION). IF EXISTING CONDITIONS ARE <br />NOT AS SPECIFIED, CONTRACTOR SHALL UPGRADE THE EXISTING <br />CONDITIONS TO MATCH WHAT IS SHOWN ON THESE DRAWINGS. <br />EXISTING 12' X 12" WP WIREWAY WITH KEY TAPS <br />Building Power Riser Diagram <br />SCALE: NTS <br />MANUFACTURER: SQUARE Q 'NQ' <br />MAIN BREAKER: <br />MAIN LUGS: 225A <br />K.AJ.C.: 42 <br />MOUNTED; SURFACE <br />NAME: PANEL 'B1' <br />3 PHASE <br />4 WIRE PROJECT NAME: ZEPHYR COMMONS <br />120/208 VOLTS PROJECT NUMBER: 206319 <br />FED FROM: EXISTING WIREWAY <br />EXTERIOR i INTERIOR <br />f <br />NEW <br />200 AMP <br />TENANT <br />PANEL <br />(B1) <br />J T.C. <br />NEW <br />200 AMP <br />TENANT 7O <br />PANEL <br />(B2) <br />IN <br />C <br />C <br />O <br />CKT <br />O <br />LOAD/PHASE (KVA) <br />CIRCUIT BREAKER <br />LOAD,'PHASE <br />(KVA) <br />0 <br />CKT <br />IDENTIFICATION <br />WIREICOND <br />WIRE/COND <br />IDENTIFICATION <br />ENO. <br />D <br />D <br />NO. <br />E <br />E <br />E <br />S <br />S <br />A <br />B <br />C <br />TRIP <br />P <br />P <br />TRIP <br />A <br />B <br />C <br />4 <br />1 <br />EXIT EMER NITS LGT <br />2#12 1#12G, 3'4"G <br />L <br />0.22 <br />= - <br />20 <br />1 <br />1 <br />20 <br />1.25 <br />'" — <br />_ - <br />L <br />2#12, 1#12G, 3,,4"C <br />TENANT SIGNAGE <br />2 <br />' <br />3 <br />3 <br />RR LIGHT 8 EF. <br />2#12, 1#12G, 3:4 C <br />L <br />- _ _ <br />1 14�a# <br />;�! <br />20 <br />1 <br />1 <br />20 <br />I; <br />1.25 <br />L <br />2#12, 1#12G, 3I4 C <br />TENANT SIGNAGE <br />4 <br />3 <br />5 <br />SPARE <br />- <br />20 <br />1 <br />1 <br />20 <br />4'' <br />A <br />= <br />1.25 <br />L <br />2#12, 1#12G, 314"C <br />TENANT SIGNAGE <br />6 <br />3 <br />= <br />7 <br />SPARE <br />-_ <br />—� <br />= <br />20 <br />111 <br />20 <br />1.27 <br />R <br />2#12, 1#12G 314"C <br />SHOW WINDOW RECE <br />8 <br />ei <br />9 <br />SPARE <br />- <br />20 <br />1 <br />1 <br />20 <br />1.27 <br />R <br />2#12, 1*12G, 314"C <br />SHOW WINDOW RECE <br />10 <br />11 <br />SPACE ONLY <br />- <br />1 <br />20 <br />1.27 <br />R <br />2#12, 1#12G, 3/4"C <br />SHOW WINDOW RECE <br />12 <br />13 <br />SPACE ONLY <br />_ = <br />-_ <br />1 <br />20 <br />1.27 <br />R <br />2#12, 1#12G, 314"C <br />SHOW WINDOW RECE <br />14 <br />- <br />15 <br />SPACE ONLY <br />- <br />- - <br />1 <br />20 <br />1 <br />0.72 <br />R <br />2#12, 1#12G, 3i'4"C <br />RECEPTACLES <br />16 <br />___ _ <br />= <br />17 <br />SPACE ONLY <br />1 <br />20 <br />"! <br />SPARE <br />18 <br />- <br />19 <br />SPACE ONLY <br />1 <br />20 <br />y <br />SPARE <br />20 <br />21 <br />SPACE ONLY <br />1 <br />20ti <br />SPARE <br />22 <br />23 <br />SPACE ONLY <br />SPACE ONLY <br />24 <br />-- =" <br />_ _ <br />25 <br />SPACE ONLY <br />- <br />-- <br />SPACE ONLY <br />26 <br />27 <br />SPACE ONLY <br />= <br />_ <br />SPACE ONLY <br />28 <br />_ = <br />29 <br />SPACE ONLY <br />SPACE ONLY <br />30 <br />31 <br />SPACE ONLY <br />- <br />33 <br />SPACE ONLY <br />--� <br />- <br />'''r <br />. - <br />SPACE ONLY <br />34 <br />F'';;'_' <br />35 <br />SPACE ONLY <br />li,i, <br />'li:' <br />ll,rkRUP <br />- <br />SPACE ONLY <br />36 <br />-_ <br />--- <br />F <br />37 <br />SPACE ONLY <br />- <br />= <br />_ — <br />3 <br />3.02°' <br />— <br />C <br />38 <br />39 <br />SPACE ONLY <br />3 <br />35 <br />`i <br />-- <br />3,02 <br />� _- <br />C <br />3#8, 1#10G, 3d'4"C <br />4 TUN RTU <br />4p <br />2 <br />U W$ , <br />41 <br />SPACE ONLY <br />—= <br />3 <br />� <br />3.02 <br />C <br />42 <br />0-2 <br />1 1 <br />0.0 <br />6.8 <br />6.3 <br />5.5 <br />TOTAL KVA PHASE A: 7-03 <br />TOTAL KVA PHASE B. 7.40 <br />TOTAL KVA PHASE C: 5,54 <br />LIGHTING (L) <br />RECEPTACLES (R) <br />A1C HEATING (H) <br />A/C COOLING (C) <br />KITCHEN EQUIPENT (K) <br />LARGEST MOTOR (M) <br />OTHER (0) <br />D LOAD'. � <br />i <br />TOTAL CONNECTED KVA: 19.97 <br />TOTAL CONNECTED AMPS: 55,43 <br />TOTAL DEMAND KVA: 21.25 <br />TOTAL DEMAND AMPS: 58.98 <br />GENERAL <br />SQUARE FOOT: LIGHTING LOAD: <br />** LIGHTING DEMAND LOAD IS BASED ON THE LARGER OF THE TWO <br />** (CONNECTED VS. TABLE 220.3a, NEC 2002.) <br />"LARGER A/C LOAD: 9,06 KVA <br />(TL) LENGTH 0 KVA <br />NOTES: 1) PROVIDE LOCKED CIRCUIT BREAKER 2) PROVIDE HACR RATED CIRCUIT BREAKER 3) VIA TENANT TIME CLOCK 4) NFPA 70-05 240.83 (D) COMPLIANT <br />VA/SF <br />Electrical Legend <br />NOTES: 1. MOUNTING HEIGHTS SHOWN ARE MAX. / MIN. HANDICAP ACCESSIBILITY 2. NOT ALL DEVICES SHOWN IN LEGEND ARE REQUIRED. RE: PLANS <br />STANDARDS - THEY SHALL NOT BE ALTERED W / 0 WRITTEN AUTHORIZATION. & DETAILS FOR ITEMS WHICH APPLY TO THIS PROJECT. <br />A®a A®a <br />FLUORESCENT LIGHT FIXTURE, LETTER INDICATES TYPE. SEE FIXTURE <br />A_1 3 <br />CONDUIT RUN CONCEALED IN WALLS BELOW SLAB, OR CEILING SPACES. <br />oa <br />SCHEDULE. LOWER CASE LETTER INDICATES SWITCH (IF USED) <br />ARROWS INDICATE HOMERUN. SMALL HASHMARKS INDICATE NUMBER OF <br />FLUORESCENT STRIP LIGHT, LETTER INDICATES TYPE. SEE FIXTURE <br />HOT CONDUCTORS, AND LARGE HASHMARK INDICATES NEUTRAL.SUBSCRIPT <br />INDICATES PANEL AND CIRCUIT NUMBERS. GROUND <br />SCHEDULE. LOWER CASE LETTER INDICATES SWITCH (IF USED) <br />CONDUCTOR REQUIRED IN ALL CONDUITS BUT NOT INDICATED. <br />OR I= <br />SURFACE MOUNTED LIGHT, LETTER INDICATES TYPE. SEE FIXTURE <br />SCHEDULE. LOWER CASE LETTER INDICATES SWITCH (IF USED) <br />A-37:39:41 <br />SUBSCRIPT INDICATES PANEL -AND NUMBERS WITH COLONS <br />A <br />O B oa Y B <br />INCANDESCENT OR HID LIGHT FIXTURE, LETTER INDICATES TYPE <br />INDICATE 2 OR 3 POLE CIRCUITS. <br />SEE LIGHT FIXTURE SCHEDULE TO CONFIRM TYPE AND MOUNTING. <br />Q C as Q C <br />WALL BRACKET LIGHT FIXTURE, LETTER INDICATES TYPE SEE <br />Lo <br />DISCONNECT SWITCH <br />LIGHT FIXTURE SCHEDULE TO CONFIRM TYPE AND MOUNTING. <br />100/3160 <br />DISCONNECT DESIGNATION (SIZE/POLES/FUSE) "NF" INDICATES <br />NL <br />NIGHT LIGHT FIXTURE (NL) <br />NON -FUSED; "DE" INDICATES DUAL ELEMENT FUSES. <br />® X <br />EXIT LIGHT (SHADE AREA INDICATES DIRECTION) LETTER INDICATES TYPE <br />EF <br />MOTOR PERMANENTLY CONNECTED WITH FLEXIBLE CONDUIT <br />SEE LIGHT FIXTURE SCHEDULE TO CONFIRM TYPE AND MOUNTING. <br />(HORSEPOWER OR EQUIPMENT INDICATED) <br />BATTERY POWERED EMERGENCY LIGHT <br />THERMOSTAT. PROVIDE SINGLE GANG BOX WITH 1/2" C. STUBBED <br />O <br />INTO CEILING SPACE, MOUNT 60" A.F.F. U.O.N. (COORDINATE WITH <br />TRACK LIGHTING AND TRACK. FOR INFORMATION ON TRACK SEE <br />MECHANICAL DRAWINGS PRIOR TO ROUGH -IN) <br />LIGHT FIXTURE SCHEDULE TO CONFIRM TYPE AND MOUNTING. <br />TELEPHONE WALL OUTLET, PROVIDE SINGLE GANG BOX WITH 314" <br />WALL WASHER FIXTURE. (SHADE AREA INDICATES DIRECTION) SEE <br />v <br />CONDUIT WITH PULL WIRE AND INSULATING BUSHING STUBBED INTO <br />LIGHT FIXTURE SCHEDULE TO CONFIRM TYPE AND MOUNTING. <br />CEILING SPACE. MOUNT BOX 18" A.F.F. U.O.N. <br />SINGLE POLE SWITCH, LOWER CASE LETTER INDICATES LIGHTS <br />CONTROLLED. LETTER NOT SHOWN IF SELF EVIDENT. MOUNT <br />a <br />48" A.F.F. U.O.N. <br />F <br />SINGLE POLE SWITCH. FAN CONTROLLER, MOUNT 48" A.F.F. U.O.N. <br />3 <br />3-WAY SWITCH, FOR CONTROLLING LIGHTS FROM TWO DIFFERENT POINTS. <br />® <br />TWO GANG FLOOR OUTLET BOX. ONE QUADPLEX ISOLATED GROUND <br />RECEPTACLE AND ONE COMPUTER OUTLET. <br />FA--A--ffl <br />WIREMOLD-WALKER INFLOOR SYSTEMS. RC4 FLUSH QUAD POKE <br />THRU SERIES WITH FOUR MULTIMEDIA COMMUNICATION LOCATIONS <br />QAdb <br />WIREMOLD WALLSOURCE MULTIPLE SERVICE BOX. <br />Q QUADPLEX FLOOR RECEPTACLE OUTLET. <br />QUADPLEX RECEPTACLE OUTLET. <br />QUADPLEX RECEPTACLE OUTLET MOUNTED ABOVE COUNTER TOP U.O.N. <br />OO DUPLEX FLOOR RECEPTACLE OUTLET. <br />DUPLEX RECEPTACLE, MOUNT 18" AFF UON <br />& DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER HEIGHT U.O.N. <br />�GFI GROUND FAULT INTERRUPTER RECEPTACLE, LEVITON #6898-I, MOUNT <br />ABOVE COUNTER HEIGHT U.O.N. <br />I.G. DUPLEX RECEPTACLE, ISOLATED GROUND TYPE, LEVITON #5362-IGI <br />& MOUNTED ABOVE COUNTER HEIGHT. U.O.N. <br />I.G. <br />DUPLEX RECEPTACLE, ISOLATED GROUND TYPE, LEVITON #5362-IGI <br />MOUNT AT 18" AFF UON <br />DUPLEX RECEPTACLE, MOUNTED ABOVE STOREFRONT WINDOWS <br />SINGLE RECEPTACLE, MOUNTED AT HEIGHT NOTED ON PLANS <br />® <br />SPECIAL PURPOSE RECEPTACLE OUTLET <br />O <br />JUNCTION BOX (FLUSH MOUNT IN FINISHED AREAS U.O.N.) <br />LIGHTING, POWER, FACP PANELBOARD OR TELE. TERM. CABINET. <br />MSB/MDP <br />MAIN SWITCHBOARD OR MAIN DISTRIBUTION PANEL <br />CONDUIT CONCEALED IN WALL, BELOW SLAB, OR ABOVE CEILING. <br />CONDUIT EXPOSED ON WALL OR CEILING. <br />FLEXIBLE CONDUIT NOT TO EXCEED 6 FEET IN LENGTH <br />MANUFACTURER: SQUARE Q 'NQ' <br />MAIN BREAKER: <br />MAIN LUGS: 225A <br />K,A,I.C,: 42 <br />MOUNTED: SURFACE <br />Q COMPUTER OUTLET. MOUNT BOX @ 18" A.F.F. U.O.N. <br />O <br />O <br />0 <br />MF <br />HORN/STROBE: EDWARDS #692-8A-HSW <br />OSMOKE <br />DETECTOR: EDWARDS #ISIGA-PS <br />OHEAT <br />DETECTOR: EDWARDS #SIGA-HRS <br />CEILING SPEAKERS MTD. AND WIRED PER AEI MUSIC NETWORK, <br />INC. (800-274-9298) <br />CEILING MTD. SENSOR DEVICE <br />FIRE ALARM PULL STATION: EDWARDS #SIGA-270 <br />FACP PANEL: SIEMEN CYRBURUS MODEL #PXL <br />EF BATH ROOM FAN LIGHT (BROAN S150L) <br />ABBREVIATIONS <br />ACC-CU <br />CONDENSING UNIT <br />LB <br />LOCK BREAKER <br />AFF <br />ABOVE FINISH FLOOR <br />NF <br />NON -FUSED <br />AFG <br />ABOVE FINISH GRADE <br />NIC <br />NOT IN CONTRACT <br />A/H-AHU <br />AIR HANDLING UNIT <br />NL <br />NIGHT LIGHT <br />C/T <br />CURRENT TRANSFORMER <br />NTS <br />NOT TO SCALE <br />DE <br />DUAL ELEMENT FUSE <br />OS <br />OCCUPANCY SENSORS <br />EC <br />EMPTY CONDUIT <br />PC <br />PULL CHAIN <br />E/F-EF <br />EXHAUST FAN <br />RTU <br />ROOF TOP UNIT <br />EG <br />EQUIPMENT GROUND <br />TTB <br />TELEPHONE TERMINAL BOARD <br />EM <br />EMERGENCY LIGHT <br />TTC <br />TELEPHONE TERMINAL CABINET <br />EWC <br />ELECTRIC WATER COOLER <br />TYP <br />TYPICAL <br />EWH <br />ELECTRIC WATER HEATER <br />UON <br />UNLESS OTHERWISE NOTED <br />EX <br />EXISTING DEVICE TO REMAIN <br />VTC <br />VIA TIME CLOCK <br />FACP <br />FIRE ALARM CONTROL PANEL <br />WP <br />WEATHERPROOF <br />GFI <br />GROUND FAULT INTERRUPTER <br />X <br />EXIT LIGHT <br />IG <br />ISOLATED GROUND <br />NOTE: MOUNTING <br />HEIGHTS NOTED ARE TO BOTTOM OF DEVICE SHOWN <br />UON <br />NAME: PANEL 'B2* <br />3 PHASE <br />4 WIRE PROJECT NAME: ZEPHYR COMMONS <br />120/208 VOLTS PROJECT NUMBER: 206319 <br />FED FROM: EXISTING WIREWAY <br />C <br />C <br />€ <br />O <br />O <br />O <br />LOADIPHASE <br />(KVA) I <br />CIRCUIT BREAKER <br />LOAD/PHASE <br />(KVA) <br />O <br />I <br />CKT <br />TCKT <br />IDENTIFICATION <br />WIRE�COND <br />I <br />WIREtCOND <br />IDENTIFICATION ENO. <br />T <br />NO <br />D <br />D <br />E <br />E <br />S <br />E <br />E <br />S <br />A <br />B <br />C <br />TRIP <br />P <br />P <br />TRIP <br />A <br />B <br />C <br />4 <br />1 <br />EXIT, EMER, NOTE LGT <br />2#12, 1#12G, 3/4"C <br />L <br />0.22 <br />20 <br />1 <br />1 <br />20 <br />1.25 <br />_ <br />L <br />2*12, 1#12G, 3/4"C <br />TENANT SIGNAGE <br />2 <br />3 <br />�] <br />aY <br />EXTR. REAR GT <br />� L -. <br />2#12 1#12G 3/4"C <br />i y C <br />L <br />(� <br />Qe � � <br />20 <br />1 <br />1 <br />� 0 <br />u�,!r <br />�Idyi�i <br />r4k' <br />1.25 <br />_ <br />., � +.,,` <br />L <br />2*12 1#12G 3/4"C <br />i <br />TENANT SIGNAGE a <br />4 <br />3 <br />5 <br />RR LIGHT & EF <br />2#12, 1#12G, 3/4"C <br />L <br />_ <br />1.14 <br />20 <br />1 <br />1 <br />20 <br />i qrf <br />'I <br />1.27 <br />R <br />2#12 1#12G, 3/4"C <br />SHOW WINDOW RECE <br />6 <br />7 <br />SPARE <br />20 <br />1 <br />1 <br />20 <br />1.27 <br />R <br />2#12. 1#12G, 3/4"C <br />SHOW WINDOW RECE <br />8 <br />s <br />_ <br />9 <br />SPARE <br />_ <br />20 <br />1 <br />1 <br />20 <br />1.27 <br />R <br />2#12. 1#12G, 3/4"C <br />SHOW WINDOW RECE <br />10 <br />11 <br />SPARE <br />20 <br />1 <br />1 <br />20 <br />1.27 <br />R <br />2#12, 1#12G, 3/4"C <br />SHOW WINDOW RECE <br />12 <br />13 <br />SPACE ONLY <br />20 <br />.72 <br />#12G, 3/4" C <br />RECEPTACLES <br />14 <br />15 <br />SPACE ONLY <br />-- <br />�- <br />1 <br />20 <br />---- <br />SPARE _ <br />16 <br />17 <br />SPACE ONLY <br />1 <br />20 <br />, � , <br />SPARE <br />18 <br />19 <br />SPACE ONLY <br />° °ikl <br />- <br />1 <br />20 <br />- _ <br />SPARE <br />20 <br />21 <br />SPACE ONLY <br />y, <br />g:'!I'"IIr <br />''` <br />SPACE ONLY <br />22 <br />23 <br />SPACE ONLY <br />- -" <br />� <br />', ��, "� <br />SPACE ONLY <br />24 <br />g <br />= - <br />25 <br />SPACE ONLY <br />27 <br />SPACE ONLY <br />= - _ <br />- <br />-- <br />SPACE ONLY <br />28 <br />_ _ <br />29 <br />SPACE ONLY <br />SPACE ONLY <br />30 <br />31 <br />SPACE ONLY <br />- <br />SPACE ONLY <br />g2 <br />- � : <br />_ <br />_-- <br />33 <br />SPACE ONLY <br />I� <br />SPACE ONLY <br />35 <br />SPACE ONLY <br />u!E <br />s <br />=_ <br />SPACE ONLY <br />36 <br />37 <br />SPACE ONLY <br />= _ — <br />3 <br />3.02 <br />� - <br />C <br />38 <br />39 <br />SPACE ONLY <br />3 <br />35 <br />3.02 <br />C <br />3#8, 1#10G, 3/4"C <br />4 TON RTU <br />40 <br />2 <br />_ _ <br />41 <br />SPACE ONLY <br />3 <br />3.02 <br />C <br />42 <br />� <br />— <br />__-- <br />0.2 <br />0.1 <br />1.1 E <br />6.3 <br />5.5 <br />5.6 <br />TOTAL KVA PHASE A: 6.48 <br />TOTAL KVA PHASE B: 5.64 <br />TOTAL KVA PHASE C: 6.70 <br />TOTAL CONNECTED KVA: <br />18.82 <br />TOTAL CONNECTED AMPS: <br />52.24 <br />TOTAL DEMAND KVA: <br />19-81 <br />TOTAL DEMAND AMPS: <br />54.99 <br />GENERAL <br />* SQUARE FOOT: LIGHTING LOAD: VAISF <br />** * LIGHTING DEMAND LOAD IS BASED ON THE LARGER OF THE TWO <br />(CONNECTED VS_ TABLE 220.3a, NEC 2002.) <br />**LARGER A/C LOAD: 9.06 KVA <br />(TL) LENGTH 0 KVA <br />I <br />NOTES: 1) PROVIDE LOCKED CIRCUIT BREAKER 2) PROVIDE HACR RATED CIRCUIT BREAKER 3) VIA TENANT TIME CLOCK 4) NFPA 70-05 240.83 (D) COMPLIANT <br />LIGHTING (L) <br />RECEPTACLES (R) <br />A/C HEATING (H) <br />A`C COOLING (C) <br />KITCHEN EQUIPENT (K) <br />LARGEST MOTOR (M) <br />OTHER (0) <br />DENAND <br />LOAD <br />(KVY <br />C7 <br />x <br />a <br />0 <br />U <br />Qm <br />Y <br />m Q <br />m <br />Q� J <br />Um <br />J J <br />� <br />/Qn <br />V <br />lqj- J <br />�W <br />p w <br />z� <br />W -J <br />WCL <br />w <br />W <br />W <br />N <br />J <br />W <br />Q'LU <br />z <br />U <br />O <br />c�D <br />N <br />� <br />O <br />o <br />N <br />Z <br />� <br />¢ <br />0 <br />w <br />w <br />z <br />� <br />U <br />o Lj L <br />E301 <br />