Laserfiche WebLink
ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to centered line of the box to be: 16" AFF <br />(general) <br />kitchen 44" AFF <br />bathroom 39" AFF <br />laundry room 36" AFF <br />exterior waterproof 12" AFF <br />garage general purpose 42" AFF <br />range 2" AFF <br />2. All trim plates & devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the <br />national electric code, latest edition, by a licensed electrical contractor who shall be responsible for the <br />installation & sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the <br />branch circuits in all dwelling units per NFPA 70 and the 2011 NEC. <br />7. Provide Tamper Resistant Receptacles as required by the 2011 NEC, 406.11 <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling <br />units in accordance with FBC R315 and NFPA 70. Such devices shall be listed by the appropriate <br />standard, either ANSI/UL 2034, standard for single and multiple station co alarms or UL 2075, gas and <br />vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and <br />labeled by a Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and <br />shall be equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffits <br />is not acceptable. <br />13. All doors and windows providing direct access from the home to the pool shall be equipped with an <br />exit alarm complying with UL 2017 that has a minimum sound pressure rating of 85 DBA at 10 feet, and <br />either hardwired or of the plug-in type. The exit alarm shall produce a continuous audible warning <br />when the door or window are opened.. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed <br />within 6' if the outside edge of a sink. This would include the receptacle installed for a washing <br />machine. Receptacles outlests shall not be required on a wall directly behind a range or sink to fulfill <br />the requirement for an outlet every 24". The width of the sink or range is not to be included in the <br />spacing of the outlets unless the distance from the sink or range is greater the 12" for straight counter <br />tops and 18" for sinks and ranges installed in corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />VIM <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />24 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN <br />TRACK LIGHT <br />FLOURESCENT LIGHT FIXTURE <br />O <br />EXHAUST FAN <br />Iwo <br />EXHAUST FAN/LIGHT COMBINATION <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />O <br />PUSHBUTTON SWITCH (OPTIONAL) <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />® <br />TELEVISION (OPTIONAL) <br />® 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />a <br />ELECTRIC PANEL <br />POWER CO. <br />INTERSYSTEM <br />BONDING <br />TERMINATION PER <br />NEC 08, 250.94 <br />200A INDOOR PANEL <br />CENTER <br />10 #14 copper to lights & outlets <br />NEMA 1 <br />200 AMP <br />00 #12 copper to 20 amp clos <br />10 #10.2 copper to WH <br />#10.3 copper to Dryer <br />METER <br />MAIN <br />O/0 <br />or <br />410 SER Alu <br />200 amp <br />150 amp <br />Bare Cu Ground <br />CLAMP PER 250.50 AND <br />250.52 OF THE 2011 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram (Updated 7-1-14) <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70 - 2011, LOCAL CODES AND THE LOCAL POWER CO. <br />r------------------------------------------------------ <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />1 <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />------------------------------------ ----------------- <br />--1 <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />DISCONNECT SWITCH <br />® SPEAKER (OPTIONAL) <br />�7 <br />ROUGH -IN FOR OPT. CEILING FAN <br />V J <br />C, CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR UPPER FLOOR ELECTRICAL PLAN <br />G J OPT. CEILING FAN <br />W (1) PHONE LINE, (1) DATA PORT SCALE: 4'=1'-0" <br />UI to <br />Z o <br />— o <br />Z <br />Z <br />Q <br />J <br />d <br />Z <br />Ln 0 <br />Q) C—n <br />—J W <br />W <br />O~ <br />� <br />O <br />In ~ <br />_O r- <br />m 01 <br />U <br />WC <br />~ <br />— 8 <br />a)M <br />W c) <br />;a 00 <br />O 2 C <br />Gj <br />U <br />s� <br />E � <br />oYl: <br />Ly Y <br />0. p <br />to o v <br />Q rn <br />�i<6 <br />AlN.C.a°° <br />B D. <br />o <br /><o N <br />_N <br />Ci N <br />to <br />V <br />to <br />9AZmrn p <br />O <br />_ o <br />5 t 1 —, 0 <br />W <br />�W. ILLo <br />Z0��W-� <br />a� <br />0 `m: �w <br />o <br />�tnWon° <br />HQ: <br />0 <br />mm <br />Z 9 9 <br />L04 L <br />a <br />W W < C\l <br />°U <br />0 <br />U <br />To the best of the Engineer's knowledge, information, and <br />belief, the structural plans and specifications contained <br />within these drawings comply with the Florida Building <br />Code 5th Edition (2014) Residential. Engineer's signature <br />and seal is only for the structural engineering portions of <br />the drawing pages bearing Engineer's signature and seal. <br />O <br />O <br />Z �► <br />O N� <br />> U.) <br />M <br />Q � O Ln <br />a. cn•�� <br />�LL� <br />CL .� <br />oC V p. V-4 <br />� <br />Q <br />Z M <br />J <br />W <br />tD <br />d' <br />z <br />�a <br />Z <br />Wap� <br />' � U <br />J <br />O� <br />Uf <br />ouj_�...s <br />U�W0 <br />L <br />MW <br />Z z <br />fz <br />N <br />Z <br />W <br />J <br />to 3 <br />L <br />W <br />O <br />0 <br />CC <br />V <br />X: <br />fu <br />O <br />w <br />o <br />0 <br />^ <br />L.L <br />LL <br />J <br />Z <br />�08n <br />k <br />N <br />G <br />Q <br />Q W 3 <br />8"Sg <br />Z <br />^ <br />a <br />a�oZ � <br />a <br />Z~Z <br />M <br />Ln <br />Z <br />Z <br />tj <br />SYZ <br />o <br />g <br />UJI <br />0 <br />Ul) <br />f <br />SCALE : AS NOTED <br />DATE : 2/24/2014 <br />TECH: MJAMES <br />VERSION NO. 10 <br />SHEET NO. <br />4.1 <br />