Job
<br />Truss
<br />Truss Type
<br />Qty
<br />Ply
<br />T30850243
<br />TTH27-33
<br />T04A
<br />Hip
<br />1
<br />1
<br />Job Reference (optional)
<br />Builders FirstSource (Tampa, FL), Tampa, FL - 33%4, 8.630 s Nov 19 2022 MiTek Industries, Inc. Mon Jun 19 12,29:36 2023 Page 1
<br />I D: tP uYCeVfQTfYt3OC?ZvfnpzlG U H-RfC?P sB7OH g3NSgPgn L8w3u ITXbGKWrC Doi7J4zJC?f
<br />-�1-0-Q 7-0-5 13-0-13 18-9-10 24-2-6 29-7-3 35-11-11 43-0-0
<br />-0. 7-0-5 ' 6-4-8 5-4-13 5-4-13 5-4-13 6-4-8 7-0-5
<br />5x6 =
<br />c nnf
<br />3x4 =
<br />19 5 20
<br />3x4 =
<br />3x6 =
<br />6 7
<br />54 =
<br />8
<br />Scale = 1:73.8
<br />3x8 = 17 16 10 Z2 Za 14 24 20 la 12 11 3x8 =
<br />2x4 11 3x8 = 46 =
<br />3x4 =
<br />4x6 = 3x8 =
<br />2x4 II
<br />LOADING (psf)
<br />TCLL 20.0
<br />TCDL 7.0
<br />BCLL 0.0
<br />BCDL 10.0
<br />SPACING- 2-0-0
<br />Plate Grip DOL 1.25
<br />Lumber DOL 1.25
<br />Rep Stress Incr YES
<br />Code FBC2020/TPI2014
<br />CSI.
<br />TIC0.85
<br />BC 0.80
<br />WB 0.77
<br />Matrix-SH
<br />DEFL. in (loc) I/deft Ud
<br />Vert(LL) -0.41 12-14 >999 240
<br />Vert(CT) -0.71 12-14 >723 180
<br />Horz(CT) 0.21 10 n/a n/a
<br />PLATES GRIP
<br />MT20 244/190
<br />Weight: 217 lb FT = 20%
<br />LUMBER- BRACING -
<br />TOP CHORD 2x4 SP No.2 TOP CHORD
<br />Structural wood sheathing directly applied or 2-2-0 oc purlins.
<br />BOT CHORD 2x4 SP No.1 BOT CHORD
<br />Rigid ceiling directly applied or 4-4-7 oc bracing.
<br />WEBS 2x4 SP No.3
<br />REACTIONS. (size) 10=0-3-8, 2=0-3-8
<br />Max Horz 2=190(LC 11)
<br />Max Uplift 10=857(LC 12), 2=944(LC 12)
<br />Max Grav 10=1807(LC 18), 2=1861(LC 17)
<br />FORCES. (lb) -Max. Comp./Max. Ten. -All forces 250 (lb) or less except when shown.
<br />TOP CHORD 2-3=-396412102, 3-4=-3217/1790, 4-5=2948/1731, 5-7=-3390/1945, 7-8=2951/1723,
<br />8-9=-322011794, 9-1 0=-3964/21 00
<br />BOT CHORD 2-17=-1855/3714, 16-17=-1855/3714, 14-16=-1622/3358, 12-14=-1637/3305,
<br />11-12=-1846/3592, 10-11=-1846/3592
<br />WEBS 3-17=0/276, 3-16=-784/507, 4-16=-405/964, 5-16=-655/358, 5-14=0/255, 7-14=0/253,
<br />7-12=-654/357, 8-12=-416/965, 9-12=793/515, 9-11=0/277
<br />NOTES- (8)
<br />1) Unbalanced roof live loads have been considered for this design.
<br />2) Wind: ASCE 7-16; Vu@=150mph (3-second gust) Vasd=116mph; TCDL=4.2psf; BCDL=3.Opsf; h=25ft; B=45ft; L=43ft; eave=5ft; Cat.
<br />II; Exp C; Encl., GCpi=0.18; MWFRS (directional) and C-C Exterior(2E) -1-0-0 to 3-3-10, Interior(1) 3-3-10 to 13-4-13, Exterior(2R)
<br />13-4-13 to 19-5-12, Interior(1) 19-5-12 to 29-7-3, Exterior(2R) 29-7-3 to 35-11-11, Interior(1) 35-11-11 to 42-10-4 zone; cantilever left
<br />and right exposed ; end vertical left and right exposed;C-C for members and forces & MWFRS for reactions shown; Lumber
<br />DOL=1.60 plate grip DOL=1.60
<br />This item has been
<br />3) Building Designer / Project engineer responsible for verifying applied roof live load shown covers rain loading requirements specific
<br />electronically signed and
<br />to the use of this truss component.
<br />sealed by Velez, Joaquin, PE
<br />4) Provide adequate drainage to prevent water ponding.
<br />using a Digital Signature.
<br />5) This truss has been designed for a 10.0 psf bottom chord live load nonconcurrent with any other live loads.
<br />6) ' This truss has been designed for a live load of 20.Opsf on the bottom chord in all areas where a rectangle 3-6-0 tall by 2-0-0 wide
<br />Printed copies of this
<br />will fit between the bottom chord and any other members, with BCDL = 10.Opsf.
<br />document are not Considered
<br />7) Provide mechanical connection (by others) of truss to bearing plate capable of withstanding 100 lb uplift at joint(s) except Qt=lb)
<br />signed and sealed and the
<br />10=857, 2=944.
<br />8) 'This manufactured product is designed as an individual building component. The suitability and use of this component for any
<br />signature must be verified
<br />particular building is the responsibility of the building designer per ANSI TPI 1 as referenced by the building code."
<br />on any electronic copies.
<br />Joagaia V.1- PE No.68182
<br />MiTek lac. DDA 4DTek USA FL Cert 6634
<br />16023 Swinglcy Ridge Rd.
<br />Chesterfield, MO 63017
<br />Dare:
<br />June 20,2023
<br />A WARNING - Verify design parameters and READ NOTES ON THIS AND INCLUDED MITEK REFERENCE PAGE 10II-7473 rev. 5/19/2020 BEFORE USE.
<br />Design valid for use only with MiTek® connectors. This design is based only upon parameters shown, and is for an individual building component, not
<br />a truss system. Before use, the building designer must verify the applicability of design parameters and properly incorporate this design into the overall
<br />building design. Bracing indicated is to prevent buckling of individual truss web and/or chord members only. Additional temporary and permanent bracing MiTG k"
<br />is always required for stability and to prevent collapse with possible personal injury and property damage. For general guidance regarding the
<br />fabrication, storage, delivery, erection and bracing of trusses and truss systems, see ANSf/TPIi Quality Criteria, DSB-89 and SCSI Building Component 16023 Swingley Ridge Rd
<br />Safety Information available from Truss Plate Institute, 2670 Crain Highway, Suite 203 Waldorf, MD 20601 Chesterfield, MO 63017