Test Laboratory: Hurricane Test Laboratory, Inc. (Now known as Intertek Architectural <br />Testing, Inc.) <br />Test report numbers: 0049-1106-00, 0049-0406-01 & 0049-0202-05 <br />Note: All HVHZ test reports have been signed & sealed by a Florida PE. <br />General report notes & system limitations: <br />1. All size & installation conditions shown in this report, the referenced drawing No. 1789 <br />and/or Addendum "A" are based off the referenced test reports and/or engineering <br />analysis in accordance with the Florida Building Code. <br />2. Curtain wall shall be constructed in accordance with the descriptions in this report, and <br />the manufacturer's state approved quality assurance entity specifications. <br />3. This product is approved for use in & outside of the High Velocity Hurricane Zones <br />(HVHZ). <br />4. Job required design wind pressure shall be calculated in accordance with the Florida <br />Building Code Chapter 16 and ASCE 7 Minimum Design Loads for Buildings and Other <br />Structures (0.85 directionality factor may apply per the current ASCE 7 standard). <br />5. This curtain wall is large missile impact rated for use in wind zone 4 & missile level "D" <br />locations and need not be shuttered. <br />6. Dry glazing gaskets are in accordance with ASTM C864 <br />7. When applicable, all safety glass requirements must be met per FBC chapter 24. <br />Ouality Assurance Entity: (ATI) Architectural Testing, Inc. <br />APR 0 8 2016 <br />Warren . Schaefer, P.E. <br />Florid .E. #44135 <br />