Laserfiche WebLink
Section <br /># <br />Mechanical Rough -In Inspection <br />Complies? <br />Comments/Assumptions <br />& Req.ID <br />C402.2.6 <br />;Thermally ineffective panel surfaces of❑Complies <br />Exception: Requirement does not apply. <br />[ME41]3 =sensible <br />heating panels have <br />❑Does Not <br />i <br />insulation >= R-3.5. <br />❑Not Observable <br />❑Not Applicable <br />C402.5.5, <br />Stair and elevator shaft vents have <br />❑Complies <br />Exception: Requirement does not apply. <br />C403.2.4. <br />motorized dampers that automatically <br />❑Does Not <br />3 <br />[ME3]3❑Not <br />close. <br />Observable <br />❑Not Applicable <br />C403.2.12 <br />HVAC fan systems at design <br />❑Complies <br />Exception: Requirement does not apply. <br />.1 <br />conditions do not exceed allowable <br />❑Does Not <br />[ME65]3 <br />fan system motor nameplate hp or fan <br />❑Not Observable <br />See the Mechanical Systems list for values. <br />system bhp. <br />❑Not Applicable <br />C403.2.12 <br />Fans have efficiency grade (FEG) >= ;❑Complies <br />Exception: Fans integral to equipment listed under Section <br />.3 <br />67. The total efficiency of the fan at <br />❑Does Not <br />C403.2.3. <br />[ME117]2 <br />the design point of operation <= 15% <br />;RNot <br />Observable <br />of maximum total efficiency of the <br />'❑Not <br />Applicable <br />fan. <br />C403.2.9. <br />HVAC ducts and plenums insulated <br />❑Complies <br />Requirement will be met. <br />1.1 <br />and sealed according to Florida '!❑Does <br />Not <br />[ME60]2 <br />Section C403.2.9, Table C403.2.9. 1. <br />i❑Not <br />Observable <br />❑Not Applicable <br />C403.2.9. ;AII <br />ducts, air handlers, filter boxes, <br />❑Complies <br />Requirement will be met. <br />2 <br />building cavities, mechanical closets ;F <br />JDoes Not <br />[ME79]2 I <br />and enclosed support platforms that <br />❑Not Observable <br />form the primary air containment <br />❑Not Applicable <br />passageways for air distribution <br />systems are constructed and erected <br />in accordance with Table C403.2.9.2 <br />and with Chapter 6 of the Florida <br />Building Code, Mechanical. Ducts are <br />be constructed, braced, reinforced <br />and installed to provide structural <br />strength and durability. All transverse <br />,joints, <br />longitudinal seams and fitting <br />connections are securely fastened in <br />accordance with the applicable <br />standards of this section. <br />C403.2.9. ',Duct <br />insulation is protected from <br />❑Complies <br />Requirement will be met. <br />1.2 <br />damage but not limited to the <br />❑Does Not <br />[ME80]2 ;following: <br />1. Insulation exposed to <br />❑Not Observable <br />weather is suitable for outdoor <br />Applicable <br />'service. <br />Cellular foam insulation is❑Not <br />protected or painted with a coating <br />that is water retardant and provides <br />shielding from solar radiation. 2. <br />Insulation covering cooling ducts <br />located outside the conditioned space <br />is vapor retardant located outside the <br />insulation, all penetrations and joints <br />of which shall be sealed. <br />C403.2.9. ;Additional <br />insulation with vapor ❑Complies <br />Requirement will be met. <br />1.3 + <br />barrier is provided where the ❑Does Not <br />[ME81]2 ; <br />minimum duct insulation requirements <br />❑Not Observable <br />'determined <br />of Section C403.2.9.1.1 are <br />❑Not Applicable <br />to be insufficient to <br />prevent condensation. <br />111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3) <br />Project Title: BLOX - Zephyrhills Report date: 11/23/20 <br />Data filename: PACLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 21 of 37 <br />