Laserfiche WebLink
<br />AIR SYSTEM SIZING SUMMARY <br />Air System~: A~EA D 10-01-95 <br />Weathcer" . . . .: Zephyr hi Ils, F lor ida HAP v3..02 <br />Prepared By: PHILLIP ALVAREZ Page 1 of 1 <br />************************************************************************* <br /> <br />AIR SYSTEM INFORMATION <br /> <br />System Type.............: (SZ CAV) <br />Number of Zones.........: 1 <br />Floor Area..............: 1385 sqft <br /> <br />COOLING COIL SIZING DATA <br /> <br />Total coil load (Tons)...: <br />Sensible coil load (Tons): <br />Coil CFM at Jul 1500.....: <br />Max coil airflow (CFM)...: <br />Design supply temp (F)...: <br />sqft/T ons . . . . . . . . . . . . . . . . : <br />BTU/hr/sqft..............: <br />Water gpm @ 10F rise. ....: <br /> <br />CENTRAL HEATING COIL SIZING DATA <br /> <br />Max coil load (BTU/hr)...: <br />Coil airflow (CFM).......: <br />Design supply temp (F)...: <br /> <br />SUPPLY FAN SIZING DATA <br /> <br />Actual airflow (CFM).....: <br />Standard airflow (CFM)...: <br /> <br />VENTILATION AIR DATA <br /> <br />Airflow (CFM).. ........ ..: <br />CFM/sqft . . . . . . . . . . . . . . . . . : <br /> <br />2.9 <br />2.3 <br />1222 <br />1222 <br />55.0 <br />483.4 <br />24.8 <br />6.88 <br /> <br />20106 <br />1222 <br />80.5 <br /> <br />1222 <br />1222 <br /> <br />120 <br />0.09 <br /> <br />Load occurs at. ..: <br />OA DB/RH (F/%). ..: <br />Entering Db/Wb. ..: <br />Leaving Db/Wb....: <br />Coil ADP.........: <br />Bypass factor....: <br />Resulting RH.....: <br /> <br />Jul 1500 <br />92.0/ 51.2 <br />76.7/ 63.8 F <br />55.3/ 54.1 F <br />52.9 F <br />0.100 <br />48 % <br /> <br />BTU/hr/sqft........ .: <br />Water gpm @ 20F drop: <br /> <br />14.5 <br />2.01 <br /> <br />CFM/person...........: 15.00 <br />