<br />609 Series Air Duct Smoke Detectors
<br />
<br />Table 4: Contents of Pre-packaged Duct Detector Models
<br />
<br />Pre-packaged Model Number
<br />609U01
<br />609U02
<br />609U01,11
<br />609U02-11
<br />----
<br />609U01-24
<br />
<br />609U02-24
<br />
<br />1---- 611 UD Photoelectronic
<br />
<br />G09U24 1
<br />609U24
<br />----
<br />
<br />611 UD Photoelectronic 609U31,
<br />--- -,...---,- u____ _ --- -, -'--_______, __.... ..___...__,...1
<br />
<br />Ji
<br />_=::::J
<br />
<br />609U01-31
<br />
<br />609U02-31
<br />
<br />612UD Ionization
<br />
<br />612UD Ionization
<br />
<br />609U31
<br />
<br />1_ For electrical specifications of function cards, see Tables on previous pages,
<br />
<br />Accessories
<br />
<br />All function cards provide for remote alarm indicator and/or remote
<br />test capability when used in conjunction with the ESL 606 Series
<br />accesories: Model 606U1 Remote Alarm Indicator or Model 606U2
<br />Remote Test and Alarm Indicator, All four-wire function cards
<br />include an extra terminal to facilitate connection of a local or remote
<br />detector alarm reset switch for use with the ESL Model 609URS
<br />Reset Switch or Model 606U3 Remote Alarm Indicator with Remote
<br />Test and Reset. See Table below for additional accessories,
<br />
<br />-- -
<br />
<br />Description
<br />
<br />Remote Indicator
<br />
<br />Remote Indicator with Keyed Remote Test
<br />
<br />Remote Indicator with Keyed Remote Test
<br />and Reset
<br />
<br />Inlet Sampling Tube Extension-2 ft.
<br />Inlet Sampling Tube Extension-4 ft.
<br />--
<br />Inlet Sampling Tube Extension-S ft.
<br />Test Tool
<br />
<br />Powel Supervision Unit 12 VDC systems
<br />Power Supervision Unit 220 V AC systems
<br />Local Reset Switch, N/C with 6" Leads
<br />
<br />Replacement Parts
<br />r __~~~el Number '-___ Descrlpt~on__,___J
<br />620010228 Foam Filter]
<br />~-------._------_.__._.__.- -----------------.-- .
<br />
<br />672200068 Round Duct Mounting Gasket
<br />
<br />66S090S4A
<br />
<br />Relay - 10 Amp
<br />
<br />Sentrol, Inc.
<br />Corporate Headquarters:
<br />12345 SW Leveton Drive
<br />Tualatin, OR 97062
<br />503-692-4052
<br />Technical Suppa"': 800-648,7424
<br />Bulletin 2269-8S6 December 1994 U.S. and Can..da: 800-547.2556
<br />Appearances and details subject to change without notice,
<br />
<br />t:5l:
<br />
<br />A Product of Sentrol, Inc.
<br />
<br />PRODUCT DATA
<br />Dimensions:
<br />Length: 16,5 in, (42 cm)
<br />Width: 5,5 in, (14 cm)
<br />Depth: 4,0 in, (10 cm)
<br />Integral sampling tubes extend the width by 5,5 inches and require two
<br />holes of 2 inches diameter for clearance
<br />Weight: ,"
<br />Maximum weight is 7S,75 oz, (2,23 kg,)
<br />Operating Temperature Range:
<br />0-50aC, 32-1200F
<br />Operating Duct Air Velocity Range:
<br />300-2000 fl./min, when the 612UD is installed within the duct hOllsing
<br />300-4000 ft./min, when the 611 UD is installed within the duct housing
<br />
<br />SPECIFICA TrONS
<br />This Air Duct Detector shall be either an ESL Model 609U01 Photoelec-
<br />tronic Detector, Enclosure assembly or an ESL Model609U02 Ionization
<br />Detector, Enclosure assembly,
<br />
<br />The base of the enclosure and the manifold shall be constructed of solid
<br />structural foam, and shall incorporate an air-tight smoke chamber in
<br />compliance with UL268A, Standard for Smoke Detectors for Duct Appli-
<br />cations, The detector enclosure shall be equipped with an integral
<br />mounting base capable of accomodating either a photelectronic or ioniza-
<br />tion detector head and shall be capable of local testing via a magnetic
<br />switch, The clear covers for the enclosure shall be constructed of Lexan,@
<br />
<br />The detector shall operate at air velocities of aDO feet per minute to 2000
<br />feet per minute utilizing a 612UD sensing head, and 300 - 4000 feet per.
<br />minute utilizing a 611 UD sensing head, The duct detector shall be
<br />capable of interfacing directly with ESL 606 Series Remote Stations.
<br />which shall provide for local alarm indication and test functions, Local or
<br />Remote Reset capability shall be provided for utilizing the Models
<br />609URS or 606U3 respectively,
<br />
<br />An integral filter system shall be included to reduce dust and residue
<br />accumulation which could cause adverse effects on the sensing head
<br />and the enclosure, A UNIOUE air flow monitor shall be included to
<br />indicate the presence of air flow through the detector, Air duct detector
<br />shall comply with the requirements of UL268A without the attachment of
<br />any sampling inlet or exhaust tube(s), Extension sampling tubes, where
<br />required, shall be easily installed after the housing is mounted to the duct
<br />by passing them through the duct detector enclosure,
<br />
<br />Distributed By:
<br />
|