Laserfiche WebLink
<br />..250-102. Equipment Bonding Jumpers <br /> <br />(a) Material. Equipment bonding jumpers shall be of copper or other corrosion-resistant material. A bonding <br />jumper shall be a wire, bus, screw, or similar suitable conductor. <br /> <br />(b) Attachment. Equipment bonding jumpers shall be attached in the manner specified by the applicable <br />provisions of Section 250-8 for circuits and equipment and by Section 250-70 for grounding electrodes. <br /> <br />(c) Size - Equipment Bonding Jumper on Supply Side of Service. The bonding jumper shall not be smaller <br />than the sizes shown in Table 250-66 for grounding electrode conductors. Where the service-entrance phase <br />conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the bonding jumper shall have an area <br />not less than 12 ~ percent of the area of the largest phase conductor except that, where the phase conductors and <br />the bonding jumper are of different materials (copper or aluminum), the minimum size of the bonding jumper <br />shall be based on the assumed use of phase conductors of the same material as the bonding jumper and with an <br />ampacity equivalent to that of the installed phase conductors. Where the service-entrance conductors are <br />paralleled in two or more raceways or cables, the equipment bonding jumper, where routed with the raceways or <br />cables, shall be run in parallel. The size of the bonding jumper for each raceway or cable shall be based on the <br />size of the service-entrance conductors in each raceway or cable. <br /> <br />The bonding jumper for a grounding electrode conductor raceway or cable armor as covered in Section <br />250-64( d) shall be the same size or larger than the required enclosed grounding electrode conductor. <br /> <br />(d) Size - Equipment Bonding Jumper on Load Side of Service. The equipment bonding jumper on the <br />load side of the service overcurrent devices shall be sized, as a minimum, in accordance with the sizes listed in <br />Table 250-122, but not required to be larger than the circuit conductors supplying the equipment, and not <br />smaller than No. 14. <br /> <br />A single common continuous equipment bonding jumper shall be permitted to bond two or more raceways or <br />cables where the bonding jumper is sized in accordance with Table 250-122 for the largest overcurrent device <br />supplying circuits therein. <br /> <br />( e) Installation. The equipment bonding jumper shall be permitted to be installed inside or outside of a raceway <br />or enclosure. Where installed on the outside, the length of the equipment bonding jumper shall not exceed 6 ft <br />(1.83 m) and shall be routed with the raceway or enclosure. Where installed inside of a raceway, the equipment <br />bondmg jumper shall comply with the requirements of Sections 250-119 and 250-148'f?;;t~il <br /> <br />. . 250-104. Bonding of Piping Systems and Exposed Structural Steel <br /> <br />( a) Metal Water Piping. The interior metal water piping system shall be bonded as required in (1), (2), (3), or <br />(4) of this section. The bonding jumper shall be installed in accordance with Section 250-64(a), (b), and (e). The <br />points of attachment of the bondingjumper(s) shall be accessible. <br /> <br />(1) General. The interior metal water piping system shall be bonded to the service equipment enclosure, the <br />grounded conductor at the service, the grounding electrode conductor where of sufficient size, or to the one or <br />more grounding electrodes used. The bonding jumper shall be sized in accordance with Table 250-66 except as <br />permitted in (2) and (3). ;rc~~;ii <br /> <br />(2) Buildings of Multiple Occupancy. In buildings of multiple occupancy, where the interior metal water <br />piping system for the individual occupancies is metallically isolated from all other occupancies by use of <br />