Laserfiche WebLink
<br />nonmetallic water piping, the interior metal water piping system for each occupancy shall be permitted t~ be <br />bonded to the equipment grounding terminal of the panelboard or switchboard enclosure (other than service <br />equipment) supplying that occupancy. The bonding jumper shall be sized in accordance with Table 250-122. <br />:c~~t~~i'~ <br /> <br />(3) Multiple Buildings or Structures Supplied from a Common Service. The interior metal water piping <br />system shall be bonded to the building or structure disconnecting means enclosure where located at the building <br />or structure, or to the equipment grounding conductor run with the supply conductors, or to the one or more <br />grounding electrodes used. The bonding jumper shall be sized in accordance with Section 250-122 based on the <br />rating or setting of the largest overcUITent device protecting the feeder(s) or branch circuit(s) that supply the <br />building. <br /> <br />(4) Separately Derived Systems. The grounded conductor of the separately derived system shall be bonded to <br />the nearest available point of the interior metal water piping system in the area served by the separately derived <br />system. This connection shall be made at the same point on the separately derived system where the grounding <br />electrode conductor is connected. The bonding jumper shall be sized in accordance with Table 250-66. <br />'rc~e::hiJ <br /> <br />X(b) Metal Gas Piping. Each aboveground portion ofa gas piping system upstream from the equipment shutoff <br />valve shall be electrically continuous and bonded to the grounding electrode system. <br /> <br />(c) Other Metal Piping. Interior metal piping that may become energized shall be bonded to the service <br />equipment enclosure, the grounded conductor at the service, the grounding electrode conductor where of <br />sufficient size, or to the one or more grounding electrodes used. The bonding jumper shall be sized in <br />accordance with Table 250-122 using the rating of the circuit that may energize the piping. <br /> <br />The equipment grounding conductor for the circuit that may energize the piping shall be permitted to serve as <br />the bonding means. <br /> <br />FPN: Bonding all piping and metal air ducts within the premises will provide additional safety. <br /> <br />(d) Structural Steel. Exposed interior structural steel that is interconnected to form a steel building frame and is <br />not intentionally grounded and may become energized shall be bonded to the service equipment enclosure, the <br />grounded conductor at the service, the grounding electrode conductor where of sufficient size, or to the one or <br />more,grounding electrodes used. The bonding jumper shall be sized in accordance with Table 250-66 and <br />installed in accordance with Sections 250-64(a), (b), and (e). The points of attachment of the bonding jumpers <br />shall be accessible. f.ic..'~. ''"';;,,1 <br />~":'rl .. . . .. .. <br /> <br />. . 250-106. Lightning Protection Systems <br /> <br />The lightning protection system ground terminals shall be bonded to the building or structure grounding <br /> <br />electrode system. J~-.:t~a <br /> <br />FPN No.1: See Section 250-60 for use of air terminals. For further information, see Standard for the Installation of Lightning <br />Protection Systems, NFPA 780-1997, which contains detailed information on grounding, bonding, and spacing from lightning <br />protection systems. <br /> <br />FPN No.2: Metal mceways, enclosures, frames, and other noncurrent-carrying metal parts of electric equipment installed on a <br />building equipped with a lightning protection system may require bonding or spacing from the lightning protection conductors in <br />accordance with Standardfor the Installation of Lightning Protection Systems, NFPA 780-1997. Separation from lightning <br />protection conductors is typically 6 ft (1.83 m) through air or 3 ft (0.92 m) through dense materials such as concrete, brick, or <br />