<br />M. Provide circuit numbers using black permanent marker on covers of outlet boxes <br />located above dropped ceilings (or exposed in area without ceilings)indicating all <br />circuits being routed within said boxes. <br /> <br />3.02 JUNCTION BOX INSTALLATION <br /> <br />A. Size junction boxes according to number of conductors in box or type of service to be <br />provided. Minimum junction box size is 4-11/16" square and 2-1/8" deep. Provide <br />screw covers for junction boxes. <br /> <br />B. Use code gauge steel with screw covers for pull boxes, paint with prime coat and <br />provide with screw cover. Size pull boxes according to NEC. <br /> <br />C. Provide pull box every 100 feet of conduit run or where excessive number of bends, <br />never to exceed 360 degrees, necessitates a box for ease of wire installation. <br /> <br />D. Color-code essential electrical system boxes in accordance with NEC and General <br />Electrical Notes on drawings. <br /> <br />E. Provide circuit numbers using black permanent marker on covers of junction boxes <br />indicating all circuits being routed within said boxes. <br /> <br />END OF SECTION <br /> <br />July 12, 2000 <br />November 22, 2000 <br /> <br />16130 - 3 <br /> <br />99087.00 <br />Revision No.5 <br />