Laserfiche WebLink
<br />SECTION 16721 <br /> <br />EXISTING FIRE ALARM AND DETECTION SYSTEM MODIFICATIONS <br /> <br />PART -1 GENERAL <br /> <br />1.01 WORK INCLUDED <br /> <br />A. Fire detection system. <br /> <br />B. Fire alann system. <br /> <br />1.02 RELATED WORK <br /> <br />A. Section 16010: Electrical General Provisions <br /> <br />B. Section 16050: Basic Materials and Methods <br /> <br />C. Section 16190: Supporting Devices and Hangers <br /> <br />D. Section 16111: Conduit <br /> <br />E. Section 16120: Wire and Cable <br /> <br />1.03 SUBMITTALS <br /> <br />A. Submit product data for approval in accordance with Section 16010. <br /> <br />B. Submit a complete conduit and wiring layout drawn to scale on building floor plans <br />and a point-to-point wiring diagram for approval. Fire alann system will be rejected <br />(without further review) should diagrams be omitted from the submittal package. <br /> <br />1.04 SYSTEM OPERATION <br /> <br />A. Modify the existing fire alann control panel as required to actuate from the following <br />alann initiation devices: <br />1. Non-coded pull station <br />2. Heat detector <br />3. Ceiling smoke detector <br />4. Duct-mounted sm<!>ke detector <br /> <br />B. Upon activation fire al~rm panel to initiate the following: <br />1. Initiate a general alarm including flashing of visual signals and sounding of <br /> <br />July 12, 2000 <br />November 22, 2000 <br /> <br />16721 - 1 <br /> <br />99087.00 <br />Revision No.5 <br />