Laserfiche WebLink
<br />audible signals. <br />2. Light appropriate annunciator light(s) per zoning schedule. <br />3. Release magnetic door hold-open devices. <br />4. Close smoke dampers by means ofE.P. relay or control auxiliary relay as required <br />by Division 15. <br />5. Shut down supply and return air-handling fans per zoning schedule on drawings by <br />means of a control relay in control panel. <br />6. Send signal over telephone company leased lines to remote receiving unit located <br />at designated fire station. <br /> <br />C. In the event of either an operating power failure, an open circuit, or a ground in the <br />system, modify the trouble signal and trouble lamp to actuate until system is restored to <br />normal. Silence trouble signal with a switch mounted on: <br />1. Control panel door. <br />2. Remote annunciator. <br /> <br />D. Continue to flash trouble lamp until system is restored to normal. Upon restoration of <br />system to normal, trouble signal again to sound until switch is returned to normal <br />position. <br /> <br />E. Operate existing fire alarm system from 120 volt AlC power supply with (4-hour) <br />battery backup built into control panel. Where required battery back-up is not available <br />on existing systems, same shall be provided. <br /> <br />F. Provide each 120-volt, AC circuit feeding existing control panel power supply with an <br />(in-line) UL 1499 Listed transient voltage surge suppressor with connections to hot, <br />neutral, and ground conductors (Leviton #51020- WM). <br /> <br />G. Provide sufficient new motherboards, with applicable zone modules for separate and <br />distinct zones as described in the zoning schedule on drawings where extender cabinets <br />are necessary, provide as needed. <br /> <br />PART - 2 PRODUCTS <br /> <br />2.01 MATERIALS <br /> <br />A. Provide new components which match and are compatible with the existing Simplex <br />4100 Series system including but not limited to the Simplex catalog numbers shown. <br /> <br />B. Furnish control panel modifications consisting of, but not be limited to, the following <br />modules housed in a cqmmon cabinet bearing UL label visible behind a tempered glass <br />locked cabinet door: <br />1. Alarm control w/rbound and trouble control: 2001-1007 <br />I <br />, <br /> <br />July 12, 2000 <br />November 22,2000 <br /> <br />16721 - 2 <br /> <br />99087.00 <br />Revision No.5 <br />